2014-184 sfir TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5902 (518) 761-8201
Community Development - Building & Codes (518) 761-8256
CERTIFICATE OF OCCUPANCY
Permit Number: P20140184 Date Issued: Thursday, August 07, 2014
This is to certify that work requested to be done as shown by Permit Number P20140184
has been completed.
Location: 1415 STATE ROUTE 9
Tax Map Number: 523400-288-000-0001-053-000-0000
Owner: NORTHWAY OUTLETS, LLC
Applicant: ADIDAS
This structure may be occupied as a:
Commercial Alteration
By Order of Town Board
TOWN OF QUEENSBURY
Issuance of this Certificate of Occupancy DOES NOT relieve the property I34J9 4 >E�
owner of the responsibility for compliance with Site Plan, Variance, or
other issues and conditions as a result of approvals by the Planning Board Director of Building&Code Enforcement
or Zoning Board of Appeals.
TOWN OF QUEENSBURY
FON
742 Bay Road,Queensbury,NY 12804-5902 (518)761-8201
Community Development-Building& Codes (518) 761-8256
BUILDING PERMIT
Permit Number: P20140184 Application Number. A20140184
Tax Map No: 523400-288-000-0001-053-000-0000
Permission is hereby granted to: NORTHWAY OUTLETS. LLC
For property located at: 1415 STATE ROUTE 9
in the Town of Queensbury,to construct or place
at the above location in accordance with application together with plot plans and other information hereto filed
and approved and in compliance with the NYS Uniform Building Codes and the Queensbury Zoning
Ordinance. Type of Construction Value
Owner Address: NORTHWAY OUTLETS, LLC Commercial Alteration $152,000.00
2700 WESTCHESTER Ave Suite 407 Total Value $I52,000.00
PURCHASE NY 10577-0000
Contractor or Builder's Name /Address Electrical Inspection Agency
Plans &Specifications
2014-184 ADDIDAS suite#150
Comm. Alterations 5,432 sq ft
$1,086.40 PERMIT FEE PAID-THIS PERMIT EXPIRES: Wednesday,June 03, 2015
(If a longer period is required,an application for an extension must be made to the code Enforcement Officer
of the Town of Queensbury before the expiration date.)
Dated at the Town Quee bury ire ue y un 03,2014
SIGNED BY �,Yf for the Town of Queensbury.
Director of Building&Code Enforcement
eEu � �
Town of Queensbury Building & Codes
i ed:
PRINCIPAL STRUCTURE APPLICATION Taxap IDgAY 2 I 1 �,
Pe it No.:
A permit must be obtained before beginning construction {{ tt
9 9 P�ermi Eee:N OF$QU r� �( !_
f3U1LDUJD
Please read: `TB resolution 86-2013(1.28-2013): $850 recreation fee for new dwelling 'Rei te:,.----^$ A
units, including single-family dwellings,duplexes or two-family dwellings, multiple family Site Plan No.:
dwellings, apartments, condominiums, townhouses, and/or manufactured and modular Subdivision No.:
homes,but not including mobile homes. This is in addition to the permit fee.
Date 5-16- 14 Applicant (-'LAW l(,L(As rets,
Tax Map ID Address (t t b.)- kilts k. h?4t.
Zoning CiH c&-coo (e oe .2_
Phone/E-mail In--7-9(o."I
W�r+�urb"a.� 1Lun-n ,amna-Koni tide. Com
Property Owner L0D SofW4-ioh/ L Lc Contractor/Agent ' E-TFSD
Address 350 LA,NQI Cec&. # Address
W�CKoPF N�' 0114 SI
Phone/E-mail 2ot-4 85 — $1-402 Phone/E-mail
Aobin.C7Cnevese, LOO Cora }iohs. town
Contact Person for Building&Code Compliance: E.R4 AJ 6LAck.ee RtA Day Phone: Co6-Cg3-S6o3
Building Street Address: 1415 Statc, A0.-ke• `� SuiFC it ISO Queu.. "nj M 12-b°11-
Subdivision Name: Lot#: Historic Site: Yes ), No
Estimated cost of construction: $ 1(11 coo
Type of Construction:
Check all that apply Please indicate measurements as required below:
c o l
0
a d 1st Floor 2nd Floor Other Total Height
F Q a
Single Family
Two-Family
Multi-Family(#of
units )
Townhouse
Business Office
Retail-Mercantile 1/ /r—
Factory-Industrial
Attached Garages(# )
Other
Town of Queensbury Building&Codes Principal Structure Packet 518-761-8256
•
If commercial or industrial indicate name of business a a ( ol A. 5
Proposed use of building or addition e r-Ga-ti*i be
Source of heat(circle one) teras Oil Propane Solar Other
Fireplace-complete a separate application for"Fuel Buming Appliances&Chimneys" Yes t✓ No
Are there structures not shown on plot plan?
uts-
Are their easements on the property? NI
Site Information
a. Dimensions or acreage of lot
•
b. Is this a corner lot?
c. Will the grade be changed as a result of construction: Yes ✓No
d. Public water or Private well p l is
e. Sewer or Private Septic System Se€'J ce-
Value of all work to be performed(labor and materials) $ I y Zr Coo
Declaration: I acknowledge no construction activities shall be commenced prior to issuance of a valid permit and will be completed
within a 12 month period. If work is not complete by the 1 year expiration date the permit may be renewed, subject to fees and
department approval. I certify that the application, plans,and supporting materials are a true and complete statement/description of the
work proposed,that all work will be performed in accordance with the NY State Building Codes,local building laws and ordinances,and
in conformance with local zoning regulations. I acknowledge that prior to occupying the facilities proposed, I or my agents will obtain a •
certificate of occupancy. I also understand that I/we are required to provide an as-built survey by.a licensed land surveyor of all newly
constructed facilities prior to issuance of a certificate of occupancy.
I have read and agree to the above.
Print Name: P-'ta kdAIJ Co. we.rot
Signature: ) Date: c- I te- Hi
FOR OFFICE USE ONLY:
Operating Permit Issued: _Yes _No
Occupancy Type:
Construction Classification:
Assembly Occupancy Limit:
Special Conditions:
Town of Queensbury Building&Codes Principal Structure Packet 518-761-8256
No Fat- x- pa+Xt.
Town of Queensbury Fire Marshal Office Use Only
Received:
ESTABLISHMENT OF A NEW BUSINESS Tax Map ID:
CERTIFICATE OF OCCUPANCY PERMIT APPLICATION Permit No.: /y-1 g�0
*Note: This application is for occupancy( only,with no work requiring a building permit. Permit Fee:
Name of Business Aa.. c1115 (*men C0. , Inc_
Address 14 l 5 ,i -fa � w c. q7 Su-"rf-e. ISO
Type of Business Rel-a-)1 S-Fort : F-fru r I -50.1ts c-F 4¢{-t(
MaPerson in chargenager S}tv-e.- et- �G tu' Ar f rare/
MaJ
Business Phone No. 5p3 -333 -75340
Property Owner SC oft Rsh4X
Address N 21 st-a-(re.. Rout 1 , Lan Gepr5c ()y 1.2J39-5-
Phone
22'}sPhone +_518 - 1'13 -381C
✓Provide an accurate layout of your store showing all walls, exits,stockrooms, rest rooms,counters, and fixture layout on a
separate sheet of paper.
Print Name: Er'cendt) Qt. 1C-g-
Signature: ,�� 4itt At horizedAg�
Date: L: 2014
Notes/Comments:
IMPORTANT: The business owner is responsible for keeping exits clear and maintaining exit signs and emergency lights. Fire
extinguishers, fire sprinkler systems, and fire alarm systems require annual inspections by an outside contractor and the corresponding
documentation must be provided to the Fire Marshal's office. Fire extinguishing systems found in kitchens and gas stations require
semi-annual inspections. Anv violations noted during an inspection, require immediate corrective action.
CONTACT NUMBERS:
Director, Building and Codes-761-8253 Zoning Administrator-761-8218 Zoning-761-8238
Fire Marshal-761-8206 Planning-761-8220
Town of Queensbury Fire Marshal—New Business Permit 518-761-8206
EMERGENCY CONTACT UPDATE
TO: Warren County Sheriff's Department
1. This form is used to assist Emergency Service personnel who may be called to your business after hours. Please
be sure that the persons listed on this form will be willing and available to respond during off-hours to assist Police
and/or Fire personnel in gaining entry to your building.
2. Please be advised that failure to respond to assist emergency service personnel may result in damage to your
building to facilitate entry by police and/or fire personnel.
PLEASE PRINT
JUL 0 2 2014
DATE:
BUSINESS NAME: AoUctas 4ier=rca f$'tc
BUSINESS ADDRESS: 11-41 S 51a,l-e. {Q01t Q sir 150
Lake 6-ee,-9e ,Ny . 12gYS
BUSINESS PHONE: 503 - 3s3- 78 3(0
eve, Earner CONTACT 1: Stg HOME PHONE � -333 - 783
ADDRESS: 14 t S 5-ftt .3c +e- /SD
CONTACT 2: n Z HOME PHONE 1 - 6cgo - t f g`I 7-
ADDRESS: 1 L1 t 5 stt j2a.c-ba qScta-iQ. /so.
Town of Queensbury Fire Marshal—New Business Permit 518-761-8206
Town of Queensbury Building&Code Enforcement
Office No. (518)761-8256
Commercial Final Inspection Report
Inspection request received:
Name: -olAc{d,c Inspected on: %-11-N14
Location: )'-Ii 5 R41 Arrive: . Adr . / ,.m.
Permit No.: I 7-f Sy Inspector's Initials: pia
COMMENTS
Y N NA
Chimney/"B"Vent/Direct Vent Location
Plumbing Vent Through Roof 6"/Roof Complete
Exterior Finish/Grade Complete 6"in 10'or Equivalent
Interior/Exterior Guardrails 42 inch Platform/Decks
Interior/Exterior Balusters 4 inch Spacing Platform/Decks
Stair Handrail 34 inch-38 inch/Step Risers 7"/Treads 11"
Vestibules For Exit doors>3000 sq.ft.
All Doors 36 inch w/Lever Handles/Panic Hardware, if required
Exits At Grade Or Platform 36"(w)x 44"(0/Canopy or Equiv.
Gas Valve Shut-off Exposed&Regulator(18")Above Grade
Floor Bathroom Watertight/Other Floors Okay
Relief Valve, Heat Trap 1 Water Temperature 110 Degrees Maximum
Boiler/Furnace Enclosure 1 hour or Fire Extinguishing System
Fresh Air Supply for Occupancy/Ventilation Combustion
Low Water Shut Off For Boilers
Gas Fumace Shut Off Within 30 ft.or Within Line Of Site
Oil Furnace Shut Off at Entrance to Furnace Area
Stockroom/Storage/Receiving/Shipping Room(2 hr.), 1 1/2 doors > 10%> 1000 sq.ft.
%Hour Corridor Doors&Closers
Firewalls/Fire Separation,2 Hour,3 Hour Complete/Fire Dampers/Fire Doors
Ceiling Fire Stopping,3,000 sq.ft.Wood Frame
Attic Access 30"x 20"x 30"(h),Crawl Space Access 18"x 24"
Smoke Vents Or Fan, if required
Elevator Operation and Signage/Shaft Sealed
Handicapped Bathroom Grab Bars/Sinks/Toilets/Mirrors
Handicapped Bath/Parking Lot Signage
Public Toilet Room Handicapped Accessible
Handicapped Service Counters,34 inch,Checkout 36 inch
Handicapped Ramp/Handrails Continuous/12 inch Beyond[Both sides]
Active Listening System and Signage Assembly Space
Final Electrical/Flex Gas Piping Bonded
Site Plan/Variance required
Final Survey,New Structure/Flood Plain certification,if req.
As-built Septic System Layout Required or On File
Building Number or Tenant Address on Building or Driveway 4" � J ,
YhSJ�
Water Fountain or Cooler O , •-"Cp
Building Access All Sides by 20'/Drivable Surface 20'wide V `
Special Inspections/Engineer or Architect Approval (p -
Okay To Issue Temporary or Permanent 0/0
Okay To Issue C/C
Commercial Final Inspection_11 2712 THE (-6t)1 G 6 tkE L�
143pc A ' E tk) Cc
0
Townof Queensbury Building &Code Enforcement g6�Q�!a-
3o
.j .. Office No. (518)761-8256 b
Commercial Final Inspection Report
Inspection request received:
Name: �c� Act__3 Inspected •on: � ,�_
�f
Location: %�//,`j 6+9 ��-�/SO Arrive: �M/*p.m.
Permit No.: / —f gy Inspector's Initials: Win
• K 'j i e 2&b _gO8 - 816)41 f COMMENTS
Y /N NA
Chimney/"B"Vent/Direct Vent Location
Plumbing Vent Through Roof 6"/Roof Complete
Exterior Finish/Grade Complete 6"in 10'or Equivalent
Interior/Exterior Guardrails 42 inch Plafform/Decks
Interior/Exterior Balusters 4 inch Spacing Platform/Decks
Stair Handrail 34 inch—38 inch/Step Risers 7"/Treads 11"
Vestibules For Exit doors>3000 sq.ft.
All Doors 36 inch w/Lever Handles/Panic Hardware, if required �
Exits At Grade Or Platform 36"(w)x 44"(I)/Canopy or Equiv. V
Gas Valve Shut-off Exposed&Regulator(18")Above Grade
Floor Bathroom Watertight/Other Floors Okay
Relief Valve,Heat Trap I Water Temperature 110 Degrees Maximum
Boiler/Furnace Enclosure 1 hour or Fire Extinguishing System
Fresh Air Supply for Occupancy I Ventilation Combustion
Low Water Shut Off For Boilers
Gas Furnace Shut Off Within 30 ft.or Within Line Of Site
Oil Furnace Shut Off at Entrance to Furnace Area
Stockroom/Storage/Receiving/Shipping Room(2 hr.), 1 'A doors >10%u>1000 sq.ft. .._kOOtjj R-t)
%Hour Corridor Doors&Closers � /
Firewalls/Fire Separation,2 Hour,3 Hour Complete/Fire Dampers/Fire Doors Y F>,1J(m_ \Scarey.a.
Ceiling Fire Stopping,3,000 sq.ft.Wood Frame ��
Attic Access 30"x 20"x 30"(h),Crawl Space Access 18"x 24" � lsJ� r� 'PtzA
Smoke Vents Or Fan, if required 1E Gce.)
Elevator Operation and Signage/Shaft Sealed / Q�
Handicapped Bathroom Grab Bars/Sinks/Toilets/Mirrors V p
Handicapped Bath/Parking Lot Signage
Public Toilet Room Handicapped Accessible
Handicapped Service Counters,34 inch,Checkout 36 inch
Handicapped Ramp/H. or.' _••:• : • e• < • • .•;'.]
Active Listening System and Signage Assembly Space
Final Electrical/Flex Gas Piping Bonded
Site Plan/Variance required
Final Survey, New Structure/Flood Plain certification,if req.
As-built Septic System Layout Required or On File /,
Building Number or Tenant Address on Building or Driveway 4" �//
Water Fountain or Cooler
Building Access All Sides by 20'/Drivable Surface 20'wide
Special Inspections/Engineer or Architect Approval
Okay To Issue Temporary or Permanent C/O
Okay To Issue C/C
Commercial Final Inspection_11 2712
.4
CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
Lti\JIL I
Date: 8/1/14 ; '
"1111
i lit 1.n h!.11... N1
PROJECT: ADIDAS AMERCA - OUTLETS
ADDRESS: LAKE GEORGE, NEW YORK
ENGINEER:
ARCHITECT: BKA ARCHITECTS, INC.
HVAC CONTRACTOR: GRIMALDI' S HEATING & SHEETMETAL
808 THIRD AVE.
UTICA, NEW YORK 13051
reeChnolo ier s
NEBB TAB CONTRACTOR: NEW YORK TECHNOLOGIES CORP. ��_
180 FOREST HILL DRIVE TERRY p1NTER.P.E.
CERTIFlCATION
SYRACUSE, NY 13206 2770
Exp.3/dvu e
PHONE: (315) 432-1917
.i • a: t;
FAX: (315) 432-5627
� �
National Environmental Balancing Bureau
Report Not Valid Unless Cover Sheet Stamped With
NEBB Certification Seal
TAB 2005
Copyright, NESE 2005 8.11
` New York Technologies Corporation
180 Forest Hill Drive
Syracuse,New York 13206
Phone: 315-432-1917
FAX: 315-432-5627
E-Mail: TDNYTECH@MSN.com
New York
Technologies
PROJECT: ADIDAS AMERICA—OUTLETS AT LAKE GEORGE,NEW YORK
TABLE OF CONTENTS
Air Outlet Test Report 2 pages
Notes:
The data presented in this report is a record of system measurements and
final adjustments that have been obtained in accordance with the current
edition of the NEBB Procedural Standards for Testing,Adjusting, and
Balancing of Environmental Systems. Any variances from design quantities,
which exceed NEBB tolerances,are noted in the Test-Adjust-Balance Report.
•
__ AIR OUTLET
1 TEST REPORT
► % •.
.
PROJECT: ADIDAS AMERICA-OUTLETS AT LAKE GEORGE, NEW YORK SYSTEM. VAVS 1 -4
OUTLET MANUFACTURER: — TEST APPARATUS: FLOW HOOD/HOT WIRE
AREAIRM# OUTLET DESIGN _ PRELIMINARY FINAL REMARKS
SERVED NO. TYPE SIZE AK VEL CFM CFM CFM CFM CFM CFM CFM
DISPLAY AREA 1 SA LINEAR — 200 295 220 VAV-1
2 _ 278 205
3 r 270 198
4 - , _ _ 284 210 I
ENTRY 5 12x12 279 200
STORE AREA 6 18"RND 400 512 415
STORE AREA 7 18"RND 400 465 404
DISPLAY AREA 1 SA LINEAR — 200 152 202 VAV-2
2 _ 160 210
3 156 207
4149 196
5 164 215
STORE AREA 6 18"RND 400 320 404
STORE AREA 7 18"RND 400 345 398
STORE AREA 1 SA 18"RND — 400 182 425 VAV-3
2 570 409
, g 3498 405
4 553 420
•
STOCK ROOM 1 SA 18"RND — 300 410 304 VAV-4
STOCK ROOM 2 SA 18"RND — 300 456 322 VAV-4
REMARKS:
TEST DATE: 7/29, 7/31 2014 READINGS BY: AARON JACKSON,ADAM JACKSON
National Environmental Balancing Bureau
TAB 2005 Report Not Veld Unless Cover Sneed Stamped Mk
C Copyright.NEBB ams NEBB Cenmratan Seal Page 1 of 2
- AIR OUTLET
t % { TEST REPORT
A k ( .
PROJECT: ADIDAS AMERICA-OUTLETS AT LAKE GEORGE, NEW YORK SYSTEM: VAV-5&TEV-3
OUTLET MANUFACTURER — TEST APPARATUS: FLOW HOOD/HOT WIRE
AREAIRM# OUTLET DESIGN PRELIMINARY FINAL REMARKS
SERVED NO. TYPE SIZE AK VEL CFM CFM CFM CFM CFM CFM CFM
OFFICE — SA 12x12 — 100 183 101 VAV-5
TOILET 1 EA 24x24 — 75 5 6 TEV-3 (1)
_ CHANGING ROOM 2 EA 6x6 — 50 3 4 II
REMARKS: (1)There is no actual exhaust fan installed as part of the existing "exhaust" system.
TEST DATE: 7/29, 7/31 2014 READINGS BY: AARON JACKSON,ADAM JACKSON
National Environmental Balancing Bureau
TAB 2005 Report Not vara Unless Cover Sheet stamped WO
@Copyright NEea 2C05 NEou Centrraron Seat Page 2 of 2
i uw sac9
Inspection Forms.
r3v
Town of Queensbury Fire Marshal 0 Periodic Inspection Date: /S)/ ty/ Time: pi
742 Bay Road,Queensbury NY 12804 o Re-Inspection G/ rb/w�
518 761 8206/518 761 8205 e'CO Inspection Permit#: / /—I
F e Marshals Representative
MJ Palmer Business Name: 4--et 0.S
Location: i yt i 9 C9{-,c316 b
_)(GK Stillman Contact: K31 etc573 (4
tin
Type of Inspection N/A Yes No O' sog - b
EXITS. Exit Access FC 1014&FC1029 NOTES
Exit Enclosure FC 1020&FC1029
Exit Discharge FC 1024&FC1029
Locks and latches FC1008& FC1029.2 /
Sign. Normal FC 1011 &FC1029
Sign backup FC 1011.5.3&FC1029.7.5
AISLES:
Main Aisle Width FC 1024/1025&FC1029.11
Secondary Aisle Width FC 1025&FC1029.11
FIRE EXTINGUISHER: Hung FC 906 ./'
Inspection of extinguisher FC 906 /
EVAC Plan FC 404.2
TRUSS ID SIGNAGE FC 505.3
EMERGENCY LIGHTING:
Intenor FC 1006.3&FC1029.8
Extenor FC 1006.3
Clearance Electrical /
Electric Wiring Enclosed/Labeled
d FC 605.3.1 Milk
Combustibles in Equipment Rooms FC315.2.3
F.D.Signage- FC 510
No Smoking Signs FC 310.3 / Ern
Storage FC 315.2
Compressed Gas FC 3003 / . '
Vehicle Impact Protection FC 312.1 l _ —
Interior Finishes FC 803-804
Smoke Detectors FC 907 .----- ,
CO detectors FC 610
Clearance to Sprinkler/Ceiling FC 315.2.1 /
18" / 24"
EVAC SIGNS IN Rooms FC 404.6(R1 &R2)
Fuel Pump Warning Signs FC2205.6
Fuel Station Emer Procedures FC2204.3.5 ----"--
Exterior
Exterior Building FC 315.3 REINSPECTION DUE APPROXIMATELY
Vacant Buildings FC 311 /—
Emergency Disconnect FC 2203.2 / 21 DAYS
SYSTEMS: FC 901.6 Insp OK NC
DATE: OK NC
Date
Generator Annual DATE: OK NC
Hood Installation
Elevator Semi Annual c''
FIRE ALARM Annual '7 Y t DATE: OK NC
HVAC Shutdown /t
Sprinkler System Annual Sprinkler FDC
Kitchen Suppression Semi AnnualFuel Hood Cea Suppression S-6-A n ual ���i�/I'Y/ K92C14(
iCi
Knod Cleanina 3-6-AnnualI 6'
Knox Box:installed/checked FC506
Operating Permit, if required will be issued after
Completion of Inspection
H.411r
n of Queensbury Building & Code Enforcement 'vnoc -3
Office No. (518)761-8256 _
Commercial Final Inspection Report
Inspection request received:r/�ty
Name: ckdt acitS Inspected on: —az
Location: 1 4-ti 6 R+'? Arrive: o : S.m. IS
Permit No.: t y -( VI _ Inspector's Initials: 41.2
r.
COMMENTS
Y N NA Marl(
Chimney/"B"Vent/Direct Vent Location
�e I �
�a
Plumbing Vent Through Roof 6"/Roof Complete V/ D Lob--
Exterior Finish/Grade Complete 6"in 10'or Equivalent
Interior/Exterior Guardrails 42 inch Platform/Decks
Interior/Exterior Balusters 4 inch Spacing Platform/Decks
Stair Handrail 34 inch-38 inch I Step Risers 7"/Treads 11"
Vestibules For Exit doors>3000 sq.ft. /
All Doors 36 inch w/Lever Handles/Panic Hardware, if required J
Exits At Grade Or Platform 36"(w)x 44"(I)/Canopy or Equiv.
Gas Valve Shut-off Exposed&Regulator(18")Above Grade
Floor Bathroom Watertight I Other Floors Okay
Relief Valve,Heat Trap I Water Temperature 110 Degrees Maximum
Boiler/Furnace Enclosure 1 hour or Fire Extinguishing System
Fresh Air Supply for Occupancy/Ventilation Combustion
Low Water Shut Off For Boilers /
Gas Furnace Shut Off Within 30 ft.or Within Line Of Site V/ —
Oil Furnace Shut Off at Entrance to Furnace Area
Stockroom/Storage/Receiving/Shipping Room(2 hr.), 1 %doors > 10%> 1000 sq.ft. — Ft?E Ai!Q-` ARLt,;
V.Hour Corridor Doors&Closers r�t-1S
Firewalls/Fire Separation,2 Hour, 3 Hour Complete/Fire Dampers/Fire Doors
Ceiling Fire Stopping,3,000 sq.ft.Wood Frame
Attic Access 30"x 20"x 30"(h),Crawl Space Access 18"x 24"
Smoke Vents Or Fan, if required
levator Operation and Signage I Shaft Sealed
Handicapped Bathroom Grab Bars/Sinks/Toilets/Mirrors /
K- B
Handicapped Bath/Parking Lot Signage � n_ t LLE HFt
Public Toilet Room Handicapped Accessible H tCNSS�
andicapped Service Counters,34 inch,Checkout 36 inch 6 Fpm OW:66tt
' Handicappe• Ram Handrails Continuous/12 inch Beyond [Both sides] `t �-A
Active Listening System and Signage Assembly Space /
Final Electrical/Flex Gas Piping Bonded J
Site Plan/Variance required
Final Survey, New Structure/Flood Plain certification, if req. /
As-built Septic System Layout Required or On File t///
Building Number or Tenant Address on Building or Driveway 4" } 6 V tsc),
Water Fountain or Cooler /
Building Access All Sides by 20'/Drivable Surface 20'wide
Special Inspections I Engineer or Architect Approval
ry /
Okay To Issue Temporary or Permanent CIO '
Okay To Issue C/C
Commercial Final Inspection_11 27 12
//At 1- 3 ,
Inspection Form
Town of Queensbury Fire Marshal 0 Periodic Inspection Date:_-7�/L 4Ane: /3D7l
742 Bay Road,Queensbury NY 12804 o Re-Inspection �'�r/// /�,
518 761 8206/518 761 8205 CO r Permit#: /7/7T/L/�
Fire Marshals Representative
MJ Palmer Business Name:
Location: ��� `- �J$
Ale - f ) St: /9)
GK Stillman Contact: 47,91,
Type of Inspection N/A Yes No
EXITS Exit Access FC 1014&FC1029
-
Exit Enclosure FC 1020&FC1029 NOTES
Exit Discharge FC 1024&FC1029
Locks and latches FC1008& FC1029.2 /
Sign Normal FC 1011 & FC1 kar_�
Sign backup FC 1011.5.33&&FC1029.7.5 r / �j j
AISLES: �S v Tecicl
Main Aisle Width FC 1024/1025&FC1029.11
Secondary Aisle Wdth FC 1025&FC1029.11
FIRE EXTINGUISHER: Hung FC 906
Inspection of extinguisher FC 906 f� S `���,
EVAC Plan FC 404.2 �J(-'-�Lj /40----
EVAC
TRUSS ID SIGNAGE FC 505.3 I " I k(Gfc.-i Mir-
EMERGENCY LIGHTING: f e L„ 1
Interior FC 1006.3&FC1029.8 �j�'
Extenor FC 1006.3 ���//-/P�r,,
Clearance to Electrical FC 605.3 .‘- j„ 1. /a.,C'n /'�_e , _4'02.
Electric Wiring Enclosed/Labeled FC 605.3.1 Me/44 ct [iv(lf'
Combustibles in Equipment Rooms 1C315.2.3
F.D.Smakingnage i FC 510 '242-4
� � ,��
No Smoking Signs FC 310.3 J
li
Stora.e FC 315.2
Com.ressed Gas FC 3003 �_�
Vehicle Im•act Protection FC 312.1 �� r
Interior Finishes FC 803 -804 _IM1_
Smoke Detectors FC 907 MIME_ j q LIC
r
CO detectors FC 610 t Qnl f; f_�X-
Clearance to Sprinkler/Ceiling FC 315.2.1
18" / 24"
EVAC SIGNS IN Rooms FC 404.6(R1 &R2)
Fuel Pump Warning Signs FC2205.6
Fuel Station Emer Procedures FC2204.3.5
Exterior Storage FC 315.3 REINSPECTION DUE APPROXIMATELY
Vacant Buildings FC 311
Emergency Disconnect FC 2203.2 / 21 DAYS
SYSTEMS: FC 901.6 lnsp OK NC DATE: OK NC
Date
Generator Annual DATE: OK NC
Hood Installation
Elevator Semi Annual
FIRE ALARM Annual -OJ }( DATE: OK NC
HVAC Shutdown
Sprinkler System Annual
KSitchen upp 3(;,_ //I ,�.,rlK /9�� // ' / s/2‘
Kitchen Suppression Semi Annual / r (�.,'/'N VY7 (9 '/�+�—b
Fuel Island Suppression Semi Annual
Hood Cleaning 3-6-Annual
Knox Box:installed/checked FC506
Operating Permit, if required will be issued after
Completion of Inspection
Town of Queensbury Building &Code Enforcement I(,( a S 1-3
Office No. (518) 761-8256
Framing I Firestopping Inspection Report
Inspection request received:
Name: 74-c Jt (jest S Inspected on: /
Location: / 4115 R+9 Arrive: �,
Permit No.: /- I g cf Inspector's Initials: ��
TYPE OF STRUCTURE: Ct,5—rn-AcyN
Y N N/A COMMENTS:
Framing
Attic Access 22"x 30°minimum
Jack Studs(Headers
Truss Specification Provided J/
Bracing I Bridging
Joist hangers
Jack Posts!Main Beams
Exterior sheeting nailed properly
12"O.C.
Headroom 6 ft.8 in.
Stairwells 36 in.or more
Exterior Deck Bracing
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate •
1 Y=(w)16 gauge(8) 16D nails each side
Draft stopping 1,000 sq.ft.floor trusses
Anchor Bolts 6 ft.or less on center
Ice and water shield 24 inches from wall
Fire separation 1,2,3 hour
Fire wall 2,3,4 hour
Firestopping
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side''%inch or 518 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space!Bedrooms
24 in.(H)
20 in. (W)
5.7 sf above/below grade
5.0 sf grade
Design Professional Sign-off,if required
Framing/ Firestopping Inspection Report