CC-000191-2015 TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5904 (518)761-8201
Community Development-Building& Codes (518)761-8256
CERTIFICATE OF OCCUPANCY
Permit Number: CC-000191-2015 Date Issued: Friday, December 1, 2017
This is to certify that work requested to be done as shown by Permit Number CC-000191-2015
has been completed.
Tax Map Number: 296.15-1-2
Location: 28 Gentry Hill North
Owner: Schermerhorn Properties
Applicant: Schermerhorn Properties
This structure may be occupied as a: Cottage Hill Project,Bldg.22
6-unit apartment building w/FPs By Order of Town Board
see SP 59-2012 TOWN OF QUEENSBURY
Issuance of this Certificate of Occupancy DOES NOT relieve the
property owner of the responsibility for compliance with Site Plan,
Variance,or other issues and conditions as a result of approvals by the
Director of Building&Code Enforcement
Planning Board or Zoning Board of Appeals.
- TOWN OF QUEENSBURY
1 742 Bay Road,Queensbury,NY 12804-5904 (518)761-8201
Community Development- Building& Codes (518) 761-8256
BUILDING PERMIT
Permit Number: CC-000191-2015
Tax Map No: 296.58-1-10
Permission is hereby granted to: Schermerhom Properties
For property located at: 28 Gentry Hill North
In the Town of Queensbury,to construct or place at the above location in accordance with application together
with plot plans and other information hereto filed and approved and in compliance with the NYS Uniform
Building Codes and the Queensbury Zoning Ordinance
Type of Construction
Owner Name: Schermerhom Properties Multi-Family-New $140,000.00
Owner Address: 536 BAY RD Total Value $140,000.00
Queensbury,NY 12804
Contractor or Builder's Name/Address Electrical Inspection Agency
Schermerhom Properties
RENEWED
Plans&Specifications
Cottage Hill Project,Bldg.22
$ 50.00 PERMIT FEE PAID -THIS PERMIT EXPIRES: Tuesday, May 9,2017
(If a longer period is required,an application for an extension must be made to the code Enforcement Officer
of the Town of Queensbury before the expiration date.)
Dated at the Town o�aee bury; rid H 8,2015
SIGNED BY: AI for the Town of Queensbury.
Director of Building&Code Enforcement
TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5902 (518)761-8201
Virg
Community Development- Building& Codes (518) 761-8256
BUILDING PERMIT
Permit Number: P20150115 Application Number: A20150115
Tax Map No: 523400-296-015-0001-002-000-0000
Permission is hereby granted to: SCH COTTAGE HILL, LLC
For property located at: Gentry Ln
in the Town of Queensbury, to construct or place
at the above location in accordance with application together with plot plans and other information hereto filed
and approved and in compliance with the NYS Uniform Building Codes and the Queensbury Zoning
Ordinance. Type of Construction Value
Owner Address: SCH COTTAGE HILL, LLC
536 BAY Rd Suite 2 Apartments $140,000.00
QUEENSBURY NY 12804-0000 Fireplace
Garage Attached
Total Value $140,000.00
Contractor or Builder's Name /Address Electrical Inspection Agency
Plans&Specifications
2015-115 Cottage Hill Project bldg. #22 28 Gentry Hill North
Apartment Building with 6-units
see SP 59-2012
$2,051.70 PERMIT FEE PAID-THIS PERMIT EXPIRES: Sunday,May 08,2016
(If a longer period is required,an application for an extension must be made to the code Enforcement Officer
of the Town of Queensbury before the expiration date.)
Dated at the Town of Queensbury; Friday,May 08, 2015
SIGNED BY for the Town of Queensbury.
Director of Building&Code Enforcement
(0
• . f
FILE COPY
OFFICE USE ONLY
f
• TAX MAP NO. PERMIT NO. 2N. - 11 f
•
FEES: PERMIT RECREATION ENGINEERING
f f
(If applicable.) f
PRINCIPAL STRUCTURE: APPLICATION FOR ZONING APPROVAL & BUILDING
PERMIT
A PERMIT MUST BE OBTAINED BEFORE BEGINNING CONSTRUCTION. APPLICATION IS SUBJECT TO REVIEW
BEFORE ISSUANCE OF A VALID PERMIT FOR CONSTRUCTION.
APPLICANT/BUILDER: ' 4rIterVilierclIFettPAROWNER: 6 i*-
ADDRESS: S E5tri grip tt.tAig 2 ADDRESS:
PHONE NOS. I e ''eeL-ag_1 PHONE NOS.faie�
CONTACT PERSON FOR BUILDING&CODES COMPLIANCE:01,4104 ua0 P E: aoXo-ii/$o-L
gy� Nom'
LOCATION OF PROPERTY: I,�iWO At.; 1 .;4- fn.._r: 111,-
.64.1e..
HAS THERE BEEN A SITE PLAN REVIEW;VARIANCE OR SUBDIVISION APPROVAL? EYES 0 NO
IF SO, INDICATE APPLICATION NO.AND DATE OF APPROVAL:
PLEASE INDICATE MEASUREMENTS AS REQUIRED BELOW:
CHECK ALL THAT pO F.
APPLY TO YOUR I z p Ci I w U-
PROJECT O i- 0 t- pc -J O = _
CT)iii 0 LII � � o LI- Ill
= r Ooz
Z < < r0) NCO Ou - U- 0_ = o5
SINGLE FAMILY
1 TWO-FAMILY
I
,I MULTI-FAMILY //_ ,/ q(� /) 1 ,Q s�j
(NO.of UNITS U/ ) `� l I IWI� �t A) 91 jl4+ i/ I li
t
TOWNHOUSE
BUSINESS OFFICE
RETAIL- I
MERCANTILEI
i
I FACTORY OR
INDUSTRIAL
ATTACHED f 1441112
II14�
GARAGE(1,2,3)
1 1 ,
I OTHER
Town of Queensbury* Community Development Office*742 Bay Road, Queensbury NY 12804
Revised 4/14/2010
IF COMMERCIAL OR INDUSTRIAL-NAME OF BUSINESS: C.brritIkete VOL, IDOARDUSeS
ESTIMATED CONSTRUCTION COSTA 140 oco FUEL TYPE OAT thW
S.
HEAT TYPE: .! *HOW MANY FIREPLACE(S):,4) AND/OR WOODSTOVES(S): t•VA
ZONING CATEGORY: ARE THERE WETLANDS ON THIS SITE? sliej
IS THIS A HISTORIC SITE? 140
PROPOSED USE OF BUILDING OR ADDITION: ' ( u 41--(1Z- /4,111eArinbiNtr
ARE THERE STRUCTURES NOT SHOWN ON PLOT PLAN? 140
ARE THERE EASEMENTS ON PROPERTY? E-.V014
I acknowledge no construction activities shall be commenced prior to issuance of a valid
permit. I certify that the application, plans, and supporting materials are a true and
complete statement/description of the work proposed, that all work will be performed in
accordance with the NY State Building Codes, local building laws and ordinances, and in
conformance with local zoning regulations. I acknowledge that prior to occupying the
facilities proposed, I or my agents will obtain a certificate of occupancy. i also understand
that I/we are required to provide an as-built survey by a licensed land surveyor of all newly
constructed facilities prior to issuance of a certificate of occupancy,
I have read and agree t• h. above.
Signed
'
Director of Buildinn & Codes: 761-8258 (for questionsregarding Building Permits,
e_mias, cvnsi
ruction codes
or septic systems)
Zoning Administrator: 761-8218 (for questions regarding required permits, the permit process,
application requirements or to schedule an appointment)
Town of Queensbury* Community Development Office* 742 Bay Road, Queensbury NY 12804
Revised 4/14/2010
Permission is hereby granted to the above This application / proposed action described
Applicant to erect or alter the building herein is found to be in accordance with the
described herein in accordance with said zoning Laws of the Town of Queensbury.
Application:
f I
r t F
f 9
iff:4
f { J
I / I
BUILD i' : CODES AP" VAL ZONING APPROVAL
J p J
/I1,/z7/,ç1 Y d
DATE
` ; DATE
(
k $
J I J
s s a s r s s s s+s s s s s s r n r e I J 3
µQUE8TIONS? CALL 761-8256 OR EMAIL -�
Ours- i:€t�ntli V.:96
Office Use Only \, VISIT OUR WEBSITE FOR MORE INFORMATION 1
Operating Permit Issued: Yes No d��
Occupancy Type: Construction Classification:
Assembly Occupancy Limit: Special Conditions:
Town of Queensbury k Community Development Office*742 Bay Road, Queensbury NY 12804
Office Use Only
Town of Queensbury Building & Codes Received:
Tax Map ID:
FUEL BURNING APPLIANCE & CHIMNEY APPLICATION Permit No.:
Permit Fee: $
Application is hereby made to the Building & Codes Office for the issuance of a Building & Use Permit pursuant to the NYS Fire Prevention &
Building Code. The applicant or owner agrees to comply with all applicable laws,ordinances,regulations,and all conditions that are part of these
requirements and also will allow all inspectors to enter premises to perform required inspections.
Important Note To Applicant: Rough-In and Final Inspections Are Required:
Date 4J ACkit-
Owner installer/Builder ±
Address Air VW Address
Oi"
PhonePhone
Location of proposed construction and for installation: 774IL.t. 4 a, #2z
Contact Person for Building&Codes Compliance: 1 4-4Ea— gt1180644"4 g
Subdivision Name: 4trrilsr45faa 441
Fuel Burning Appliance Information Wood Coal Pellet Gas Oil
Stove
VFireplace Insert
Fireplace,factory built* t
Fireplace,Masonry
Furnace,(Garage Only)
*If Factory Built, Please Provide: Manufacturer Name: Model No. ta/- —
Listed By: Number.
Chimney Information
Masonry'* check one _Block _Brick _Stone
Flue (check one Tile /Steel Size in Inches
Material "'check one _Double Wall Triple Wall InsulatedDirect Vent _Chimney Liner
**If Non-Masonry,please provide: Manufacturer Name: Model No.
Signatures:
Print Name: ` 1ifte 114167'
Signature: 400,
Date: Mae ,e2/<J
ADDITIONAL NOTE: CONSTRUCTION/INSTALLATION MUST CONFORM TO NYS FIRE PREVENTION&BUILDING CODE
AND/OR MANUFACTURER REQUIREMENTS. CONSULT AVAILABLE TOWN OF QUEENSBURY HANDOUTS REGARDING
REQUIRED INSPECTIONS.
.sue
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: CC-0001 91-201 5 Case Module: Permit
Inspection Date: 12/01/2017 Inspection Status: Passed
Inspector: Gary Stillman Inspection Type: OCC-Inspections
Job Address: 28 Gentry Hill North Parcel Number: 296.15-1-2
Queensbury,NY 12804
Contact Type Company Name Name
Granted Permission [Schermerhorn Properties]
Primary Owner [Schermerhorn Properties]
Contractor [Schermerhorn Properties]
Applicant [Schermerhorn Properties]
Checklist Item Passed Comments
Fire Marshal YES Chris
Exit Access FC1014&FC1029 YES
Exit Discharge FC1024&FC1029 YES
Truss ID Signage FC505.3 YES
Clearance to Electrical FC 605.3 YES
Electrical Wiring Enclosed/Labeled FC605.3.1 YES
Combustibles in Equipment Rooms FC 315.2.3 YES
F.D.Signage-FC510 YES
Interior Finishes FC803-804 YES
Smoke Detectors FC907 YES Ok
CO Detectors FC610 YES Ok
Clearance to Sprinkler/Ceiling FC315.2.1 18"/24" YES
Sprinkler System Annual YES RECIEVED NFPA13 LETTER FROM FIRETEK DATED 11/28/17
Sprinkler FDC YES
Knox Box:installed/checked FC506 YES Verified
Occupancy Cycle YES R
Stillman,Gary(Inspector)
Page(t)
Dec 01,2017
s
iip Ft
T rY \,' " 1 .
,- ,
LA
_
j SPRINKLER SYSTEMS LLC
58 Hudson River Rd. • Waterford, NY 12188
Phone: (518)244-3772 Fax: (518)238-2608
11/28/17
Mr. Mike Palmer
Fire Marshall
Town of Queensbury
742 Bay Rd.
Queensbury,NY 12804
RE: Cottage Hill Apts.
28 Gentry Hill North
Queensbury,NY
Mike,
The installation of the fire sprinkler system, at the above address, has been completed. The system is on and
operational. To the best of my knowledge the installation conforms to NFPA 13R. Should you require anything
further,please give me a call.
Sincerely,
TAX
Bob Wood
Vice President
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: CC-000191-2015 Case Module: Permit
Inspection Date: 12/01/2017 Inspection Status: Passed
Inspector: Gary Stillman Inspection Type: Gas Fireplace/Stove
Job Address: 28 Gentry Hill North Parcel Number: 296.15-1-2
Queensbury,NY 12804
Contact Type Company Name Name
Granted Permission [Schermerhom Properties]
Primary Owner [Schermerhorn Properties]
Contractor [Schermerhom Properties]
Applicant 61\VV?All [Schermerhom Properties]
Checklist Item Passed Comments
Fire Marshal Notes YES Superior DRT 2000
S/N.A-A17F285036
B-A17F285035
C-Al 7F285031
D-Al 7F285030
E_Al 7F285029
F-Al 7F285040
Floor Protection YES
Clearances to Combustibles(all sides) YES
Firestop(s)-Wall Penetration YES
Vent Clearance to Combustibles YES
Vent Chimney Termination YES
Gas Shut-off Valve YES
Combustion Air YES
Mantel-height above fp opening YES
Witness Operation YES Return
12/1/17 ok
CO Detection YES Return to verify function
12/1/17 verified
CSST Bonding YES
Stillman,Gary(Inspector)
a. s,
Dec Ot,2017
Page(1)
�,:I(dam
r �I ,� 0;; e ,,, I a a '" t v e wr I N ""4 r orb e Jd
ac $a+� y - S -
Town
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: CC-000191-2015 Case Module: Permit
Inspection Date: 09/26/2017 Inspection Status: Partial Pass
Inspector. Mike Palmer Inspection Type: Gas Fireplace/Stove
Job Address: 28 Gentry Hill North Parcel Number: 296.15-1-2
Queensbury,NY 12804
Contact Type Company Name Name
Primary Owner [Schermerhorn Properties]
Applicant [Schermerhorn Properties]
Granted Permission [Schermerhorn Properties]
Contractor [Schermerhorn Properties]
Checklist Item Passed Comments
Fire Marshal Notes YES Superior DRT 2000
S/N.A-A17F285036
B-A17F285035
C-A17F285031
D-Al7F285030
E_A17F285029
F-A17F285040
Floor Protection YES
Clearances to Combustibles (all sides) YES
Firestop(s)-Wall Penetratio 1 YES
Vent Clearance to Combust oles YES
Vent Chimney Termination YES
Gas Shut-off Valve YES
Combustion Air YES
Mantel-height above fp opening YES
Witness Operation NO Return
CO Detection NO Return to verify function
CSST Bonding YES
Palmer,Mike(Inspector)
Sep 26,2017 Page(1)
Innovative Hearth Products 900004 0 Installation 04/2015
Superior"'DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Table 7:Horizontal vent termination clearances for buildings with combustible and noncumbustible exteriors
Inside Corner Uulside Corner Recessed Lacaiien
S, , ee Table-6 / �N// P Q�ii/,
IT im /.
ki
i \ , HF —
Fined II B �V —I II
Balcony with No SI&Wall Balcony with Perpendicular Sid.Wall
Close9 I] Operable Fixed
n Closetl 0 ( y
\Openable
S
I e 1—K—0Y M(__
11
0
❑y TERMINATION CAP OX AIR SUPPLY INLET m GAS METER 0 RESTRICTED AREA
(TERMINATION PROHIBITED)
U.S.Installation** Canadian Installation*
A Clearance above grade,veranda,porch,desk,or balcony 12"(300 mm)** 12"(300 mm)*
B Clearance to window or door that may be opened 6"(150 mm) 6"(150 mm)
for fireplaces<10,000 Btu/h(3 kW), for fireplaces<10,000 Btu/h(3 kW),
12"(300 mm)
for fireplaces>10,000 Btu/h(3 kW),and<50,000 Btu/h for fireplaces>10,000 Btu/h(3 kW)
(15 kW),
12"(300 mm)
for fireplaces>50,000 Btu/h(15 kW)**
C Clearance to permanently closed window 9"(229 mm) 12"(305 mm)
recommended to prevent window condensation recommended to prevent
window condensation
D Vertical clearance to ventilated soffit located above the 18"(458 mm) 18"(458 mm)
termination within a horizontal distance of 18"(458 mm)
E Clearance to unventilated soffit 12"(305 mm) 12"(305 mm)
F Clearance to outside corner 5"(127 mm) 5"(127 mm)
minimum minimum
G Clearance to inside corner 6"(152 mm)minimum 6"(152 mm)minimum
H Clearance to each inside of center line extended above 36"(910 mm) 36"(910 mm)
meter/regulator assembly within a height of 15 ft above the meter/regulator assembly* within a height of 15 ft above the meter/
regulator assembly*
I Clearance to service regulator vent outlet 36"(910 mm)** 36"(910 mm)*
J Clearance to nonmechanical air supply inlet to building or 6"(150 mm) 6"(150 mm)
the combustion air inlet to any other fireplace for fireplaces<10,000 Btu/h(3 kW), for fireplaces<10,000 Btu/h(3 kW),
9"(230 mm) 12"(300 mm)
for fireplaces>10,000 Btu/h(3 kW)and<50,000 Btu/h(15 kW), for fireplaces>10,000 Btu/h(3 kW)
12"(300 mm)
for fireplaces>50,000 Btu/h(15 kW)**
K Clearance to a mechanical air supply inlet 36"(910 mm)above if within 10 ft(3 m)horizontally** 72"(1830 mm)*
L Clearance above paved sidewalk or paved diveway located 84"(2130 mm)$ 84"(2130 mm)$
on public property
M Clearance under veranda,porch,deck or balcony 12"(300 mm)*$ 12"(300 mm)*$
`
N Depth of alcove(maximum)
72"(1830 mm)** 72"(1830 mm)*
0 Clearance to termination(alcove) 6"(15.2 mm)** 6"(15.2 mm)*
P Width of alcove(minimum) 36"(910 mm)** 36"(910 mm)*
Q Clearance to combustible above(alcove) 18"(457 mm)** 18"(457 mm)*
' In accordance with the current CSA-B149.1 National Gas And Propane Installation Code
** In accordance with the curent ANSI Z223.1/NFPA 54 National Fuel Gas Codes
$ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
*# Only permitted if veranda,porch,deck,or balcony is fully-open on a minimum two sides beneath the floor
13
Innovative Hearth Products Installation
Superiorr"'DRT2000 and DRC2000 Direct-Vent Gas Fireplaces 900004-00,04/2015
MINIMUM CLEARANCES TO COMBUSTIBLES
Fireplace And Vent Clearances
The fireplace is approved with zero clearance to combustible materials on all sides (Table 8),with the following
exception:The unit may not be recessed (allowance made for mantel legs/side trim in Figure 6).When the unit is
installed with one side flush with a wall,the wall on the other side of the unit must not extend beyond the front edge
of the unit(Figure 6).
Table 8:Minimum Clearances *
1"(26mm)to wrapper for 45"model,all
Back others 1/2"(13mm)to wrapper
0"(0 mm)to Spacers
Sides 1/2"(13 mm)to wrapper
0"(0 mm)to Spacers**
Top Standoffs 0"(0 mm)to top standoffs
Floor 0"(0 mm)
From Bottom of Unit to Ceiling 64"(1626 mm)
Vent 3"(76 mm)—Top****
1"(25.4 mm)—Sides and Bottom
Front Service Clearance— 36"(914 mm)
clearance immediately in front of viewing area(s)
*3"(76 mm)above any horizontal/inclined vent component.
**See Page 19 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it.
***Top vent clearance can be reduced to 2"on horizontal runs when first elbow is located at least 6 ft above the fireplace.
The fireplace must be mounted on a fully supported base extending the full width and depth of the unit.The fireplace
may be located on or near conventional construction materials. However, if installed on combustible materials, such
as carpeting,vinyl tile or other combustible material other than wood flooring,the appliance shall be installed on a
metal or wood panel extending the full width and depth of the appliance.
Hearth Extension
A hearth extension is not required with this fireplace. If a hearth extension is used, do not block the lower control
compartment door.Any hearth extension used is for appearance only and does not have to conform to standard
hearth extension installation requirements.
Shelf Height
To provide for the lowest possible shelf surface, use the rear vent model. For top vent models,the venting attached
to the top vent should be routed in a way to minimize obstructions to the space above the fireplace. Do not insulate
the space between the fireplace and the area above it(Table 9and Table 10).The minimum height from the base
of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in
Table 9 and Table 10.
Table 9:Combustible Shell Height—Top Vent
Top Vent with one 90°Elbow
Model
Secure Vent® Secure Flex®(flex elbow)
DRC2033/DRT2033 44"(1118 mm) 46"(1168 mm)
DRC2035/DRT2035 47"(1194 mm) 49"(1245 mm)
DRC2040/DRT2040 52" 54" ' o1
(1321 mm
) (1372 mm) j No combustibles
or insulation
Shelf Height in the shaded
DRC2045/DRT2045 50"(1270 mm) 52"(1321 mm) (see table) area between
the appliance
and the shelf
above it.
14
Innovative Hearth Products Installation
Superior^'DRT2000 and DRC2000 Direct-Vent Gas Fireplaces 900004-00,04/2015
Table 10:Combustible Shelf Height—Rear Vent
Rear Vent with two 90°Elbows
Model >_3"clearance from shelf to
Secure Vent® Secure Flex®(flex elbow) top of fireplace and/or vent
DRC2033/DRT2033 34"(864 mm) 34"(864 mm) pipe,whichever is higher
oir
DRC2035/DRT2035 351/2"(902 mm) 35 1/2"(902 mm) i I 0llllllll1
DRC2040/DRT2040 40 1/2"(1029 mm) 401/2"(1029 mm) , ,Nombustibles
Shelf Height or insulation
DRC2045/DRT2045 451/2"(1156 mm) 451/2"(1156 mm) (see table) in the shaded
ri area between
the appliance
/ and the shelf
/'"`' above it.
Figure 6:Combustible Side Clearances Figure 7:Mantel Height
At 6"minimum
side wall
clearance,a --Mantel depth
combustible Top View of \ 18(457)
wall can project / Fireplace \
to any length. // 16(406)
Combustible materials 14(356) ,
3 1/2" allowed in shaded area
Il _ I (89 mm) "Safe Zone". 12(305)
Combustible walls 10(254)
shown in dark gray (�
h
1- 18(203) ,
-- - — Combustible mantel
legs may project 12 g q
beyond either side of
the fireplace opening (305)�10(203) a-6 2(102) — Hood
as long as they are kept in.(mm) (254) (152) (51) ^r
- -' within the shaded area
L
illustrated here. Fireplace
6"
(152 mm)
Wall Finishes/Surrounds/Mantels
NOTE: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined
by the fireplace front face (black sheet metal). Never allow combustible materials to be positioned in front of or
overlapping the fireplace face (Figure 41).
Non-combustible materials,such as surrounds and other fireplace trim,may be installed on the fireplace face,but they
must not cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (Figure 7). Mantels
constructed of non-combustible materials may be installed at any height above the fireplace opening. However, do
not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves,window sills, mantels, etc. above
the fireplace.
NOTE:To avoid heat-related finish damage,use finish materials rated 175°F,or higher,on the underside of the mantel.
INSTALLATION PREPARATION
The fireplace is shipped with all gas controls and components installed and pre-wired. Before installing the fireplace,
follow these steps:
1. Remove the shipping carton, and retain the front of the carton (used to protect the fireplace during construction).
2. Remove the shipping pad, exposing the front glass door.
3. Remove the glass door(Page 57).
NOTE: Place the glass door on the shipping carton to protect its surface.
15
f
Or
C [ b C''' 1 ......- 3
Foundation Inspection Report
levill-
Office No. (518) 761-8256 Date Inspection r:. -:113r
. S
Queensbury Building&Code Enforcement Arrive:\" ; - p Depart: VAjarfpm
742 Bay Rd., Queensbury,NY 12804 Inspector's Inti.. _
f.
j I
NAME: SC, — r)--T pH k 11 p r ' IT#: 9--
---- S
LOCATION: 2A( G k k- /JJ 1 1 Al D. SPECT ON: •
Mil
TYPE OF STRUCTURE: 11-51 G . Zz
.... Comments
Irr•
�� +l , '
Y N N/A
iiiFootings \� 0
Piers
a olithic Slab
\\,//
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this purpose on site.
Foundation/Wallpour
Reinforcement in Place
Footing Dowels or Keyway in place
Foundation Dampproofing
Foundation Waterproofing
Footing Drain Daylight or Sump
iF ng Drain Stone:
2 inch width
6 inches above footing
6 mil poly for wet areas under slab / ,
Backfill Approval
/Plumbing Under Slab
PVC/Cast/Copper
4) Fo - ,. xterior
R- \co ` � i
Rough Grade. inch drop within 10 ft.
L:\Building &Codes Forms\Building &Codes\Inspection Forms\Foundation Inspection Report.doc
Last printed 12/9/2014
Foundation Inspection Report
Office No. (518) 761-8256 Date Inspection reque tt -,:
Queensbury Building&Code Enforcement Arrive: 3:00a (j. Depart: J-/o am/�
742 Bay Rd., Queensbury,NY 12804 Inspector's Initials:,
NAME: C(-la PP'lLPJ) : RMIT#: ICC— I L6---
LOCATION: BLDG,#ZZ.—Li cQ.T 1-4►0_ N INSPECT ON: ii ''' IQ-15-
TYPE OF STRUCTURE:
�, Comments
' � 4' 4' 4
YN N/A
Footings
Piers
Monolithic Slab
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this purpose on site.
Foundation/Walipour
Reinforcement in Place
Footing Dowels or Keyway in place
Foundation Dampproofing
Foundation Waterproofing
Footing Drain Daylight or Sump
Footing Drain Stone:
12 inch width
si6 inches above footing
6 mil poly for wet areas under slab
Plumbing Under Slab '
PVC/Cast/Copper
-P- Foundation Tnsulatio; Interio ' xterior
R- Vt "` . '`" b
Rough Grade 6 inch drop within 10 ft.
L:\Building &Codes Forms\Building &Codes\Inspection Forms\Foundation Inspection Report.doc
Last printed 12/9/2014
/1/6,10h, Q�1D—yON
Foundation Inspection Report L
1 i
Office No. (518) 761-8256 Date Inspection re• - • ed: 41 ' i 5
Queensbury Building&Code Enforcement Arrive: AD .� • j� i epart: 'I p
742 Bay Rd.,Queensbury,NY 12804 Inspector's Initial~�./`
NAME: 67jerivte-14161- -- •• IT#: / S
LOCATION: bi–d5INSPECT ON: �.
TYPE OF STRUCTURE: °2g" Ui
Comments
Y N N/A
Footings
Piers
Monolithic Slab
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this u�pr ose on site. Z
Croupelallpour
Reinforcement in Place
Footing Dowels or Keyway in place
Foundation Dampproofing
Foundation Waterproofing
Footing Drain Daylight or Sump
Footing Drain Stone:
12 inch width
6 inches above footing
6 mil poly for wet areas under slab
Backfill Approval
Plumbing Under Slab
PVC/Cast/Copper
Foundation Insulation Interior/Exterior
R-
Rough Grade 6 inch drop within 10 ft.
L:\Building &Codes Forms\Building &Codes\Inspection Forms\Foundation Inspection Report.doc
Last printed 12/9/2014
LAIVuZ) iVir Ur (;HCHYL LLC HLINL
BRIAN A. CUSTER TRUST 1489/194
3823/72
%PF
LANDS N/F OF
EL S. & KATHERINE M. DIER 25.5
4903/261
,x
ISLAND
LANDS N/F OF x
PAUL & MARIA KRUGER
3401/147 POND
4"
C.M.
LANDS N/F OF
ROBERT M. PURDY
PATRICIA A. PURDY
428/361
PF
LANDS N/F OF
STEVEN W. PINCHOOK
1430/45
r/
o
IJ tL6n- U�U
M'i2302015
lu�}ul6
B B!11LDING & CODES 0
Schermerhorn Res Prop BP 2015-115
28 Gentry Hill North
TOWNHOUSE bldg. #22
LANE
D�
LAS',
BY.
F I
A
HOME
D)
BY
BOUNDAR
WITH ADJOINING W
LAST
BY., VAN DUSj
d LANDS N/F OF
96.g Q QUEENSBURY BAYBRIDGE HOA
1216/235
PHASE TWO - PARCEL "A"
UTiuTILS
o�DgIV
R ��BgI� GE
RAJNY Consulting, LLC
69 Hayden Point Loop
Diamond Point, NY 12824
518 221-3240
11/30/2017
Mr. Rich Schermerhorn
Schermerhorn Real Estate Holdings
536 Bay Road Ste. 2
Queensbury,NY 12804
Inspection Address: 28A Gentry Hill North, Queensbury, NY 12804
Report Number: 1130171
Dear Rich:
The Blower Door Test to verify infiltration rate of the subject property, as per
requirements of the NYS 2010 Energy Conservation Construction Code was performed
on 11/30/2017. GRAJNY Consulting, LLC is pleased to submit the following report.
The following data was provided:
- Square Footage of the apartment, including 1St and 2nd floor= 1,408 SF
- Volume of the apartment, including 1St and 2nd floor= 11,876 CF
Based on above,the following test data was collected:
- Infiltration Rate of the apartment at 50 Pascal= 984 CFM
- ACH50,Actual Changes per Hour at 50 Pascal=984X60/11,876=4.9< 7
The Instruments used for test were provided by the Energy Conservatory Digital Gauge
DG-3 rated accuracy=+/- I%, calibrated minimum once per year.
Thank you for selecting our company.We appreciate the opportunity to be of service.
Please call this office if there are any questions.
Sincerely,
Sta,w C,ra j"
Stan Grajny, PE
RESNET HERS Energy Rater 5609922
NYS PE 065406-1
RAJNY Consulting, LLC
69 Hayden Point Loop
Diamond Point, NY 12824
518 221-3240
11/30/2017
Mr. Rich Schermerhorn
Schermerhorn Real Estate Holdings
536 Bay Road Ste. 2
Queensbury,NY 12804
Inspection Address: 28B Gentry Hill North, Queensbury, NY 12804
Report Number: 1130172
Dear Rich:
The Blower Door Test to verify infiltration rate of the subject property, as per
requirements of the NYS 2010 Energy Conservation Construction Code was performed
on 11/30/2017. GRAJNY Consulting, LLC is pleased to submit the following report.
The following data was provided:
- Square Footage of the apartment, including 1St and 2nd floor= 1,408 SF
- Volume of the apartment, including 1St and 2nd floor= 11,876 CF
Based on above,the following test data was collected:
- Infiltration Rate of the apartment at 50 Pascal= 1,073 CFM
- ACH50,Actual Changes per Hour at 50 Pascal= 1,073X60/11,876=5.4< 7
The Instruments used for test were provided by the Energy Conservatory Digital Gauge
DG-3 rated accuracy=+/- I%, calibrated minimum once per year.
Thank you for selecting our company.We appreciate the opportunity to be of service.
Please call this office if there are any questions.
Sincerely,
Sta,w C,ra j"
Stan Grajny, PE
RESNET HERS Energy Rater 5609922
NYS PE 065406-1
RAJNY Consulting, LLC
69 Hayden Point Loop
Diamond Point, NY 12824
518 221-3240
11/30/2017
Mr. Rich Schermerhorn
Schermerhorn Real Estate Holdings
536 Bay Road Ste. 2
Queensbury,NY 12804
Inspection Address: 28C Gentry Hill North, Queensbury, NY 12804
Report Number: 1130173
Dear Rich:
The Blower Door Test to verify infiltration rate of the subject property, as per
requirements of the NYS 2010 Energy Conservation Construction Code was performed
on 11/30/2017. GRAJNY Consulting, LLC is pleased to submit the following report.
The following data was provided:
- Square Footage of the apartment, including 1St and 2nd floor= 1,408 SF
- Volume of the apartment, including 1St and 2nd floor= 11,876 CF
Based on above,the following test data was collected:
- Infiltration Rate of the apartment at 50 Pascal= 1,147 CFM
- ACH50,Actual Changes per Hour at 50 Pascal= 1,147X60/11,876=5.8 < 7
The Instruments used for test were provided by the Energy Conservatory Digital Gauge
DG-3 rated accuracy=+/- I%, calibrated minimum once per year.
Thank you for selecting our company.We appreciate the opportunity to be of service.
Please call this office if there are any questions.
Sincerely,
Sta,w C,ra j"
Stan Grajny, PE
RESNET HERS Energy Rater 5609922
NYS PE 065406-1
RAJNY Consulting, LLC
69 Hayden Point Loop
Diamond Point, NY 12824
518 221-3240
11/30/2017
Mr. Rich Schermerhorn
Schermerhorn Real Estate Holdings
536 Bay Road Ste. 2
Queensbury,NY 12804
Inspection Address: 28D Gentry Hill North, Queensbury, NY 12804
Report Number: 1130174
Dear Rich:
The Blower Door Test to verify infiltration rate of the subject property, as per
requirements of the NYS 2010 Energy Conservation Construction Code was performed
on 11/30/2017. GRAJNY Consulting, LLC is pleased to submit the following report.
The following data was provided:
- Square Footage of the apartment, including 1St and 2nd floor= 1,408 SF
- Volume of the apartment, including 1St and 2nd floor= 11,876 CF
Based on above,the following test data was collected:
- Infiltration Rate of the apartment at 50 Pascal= 1,160 CFM
- ACH50,Actual Changes per Hour at 50 Pascal= 1,160X60/11,876=5.9< 7
The Instruments used for test were provided by the Energy Conservatory Digital Gauge
DG-3 rated accuracy=+/- I%, calibrated minimum once per year.
Thank you for selecting our company.We appreciate the opportunity to be of service.
Please call this office if there are any questions.
Sincerely,
Sta,w C,ra j"
Stan Grajny, PE
RESNET HERS Energy Rater 5609922
NYS PE 065406-1
RAJNY Consulting, LLC
69 Hayden Point Loop
Diamond Point, NY 12824
518 221-3240
11/30/2017
Mr. Rich Schermerhorn
Schermerhorn Real Estate Holdings
536 Bay Road Ste. 2
Queensbury,NY 12804
Inspection Address: 28E Gentry Hill North, Queensbury, NY 12804
Report Number: 1130175
Dear Rich:
The Blower Door Test to verify infiltration rate of the subject property, as per
requirements of the NYS 2010 Energy Conservation Construction Code was performed
on 11/30/2017. GRAJNY Consulting, LLC is pleased to submit the following report.
The following data was provided:
- Square Footage of the apartment, including 1St and 2nd floor= 1,408 SF
- Volume of the apartment, including 1St and 2nd floor= 11,876 CF
Based on above,the following test data was collected:
- Infiltration Rate of the apartment at 50 Pascal= 1,175 CFM
- ACH50,Actual Changes per Hour at 50 Pascal= 1,175X60/11,876=5.9< 7
The Instruments used for test were provided by the Energy Conservatory Digital Gauge
DG-3 rated accuracy=+/- I%, calibrated minimum once per year.
Thank you for selecting our company.We appreciate the opportunity to be of service.
Please call this office if there are any questions.
Sincerely,
Sta,w C,ra j"
Stan Grajny, PE
RESNET HERS Energy Rater 5609922
NYS PE 065406-1
RAJNY Consulting, LLC
69 Hayden Point Loop
Diamond Point, NY 12824
518 221-3240
11/30/2017
Mr. Rich Schermerhorn
Schermerhorn Real Estate Holdings
536 Bay Road Ste. 2
Queensbury,NY 12804
Inspection Address: 28F Gentry Hill North, Queensbury, NY 12804
Report Number: 1130176
Dear Rich:
The Blower Door Test to verify infiltration rate of the subject property, as per
requirements of the NYS 2010 Energy Conservation Construction Code was performed
on 11/30/2017. GRAJNY Consulting, LLC is pleased to submit the following report.
The following data was provided:
- Square Footage of the apartment, including 1St and 2nd floor= 1,408 SF
- Volume of the apartment, including 1St and 2nd floor= 11,876 CF
Based on above,the following test data was collected:
- Infiltration Rate of the apartment at 50 Pascal= 1,042 CFM
- ACH50,Actual Changes per Hour at 50 Pascal= 1,042X60/11,876=5.3 < 7
The Instruments used for test were provided by the Energy Conservatory Digital Gauge
DG-3 rated accuracy=+/- I%, calibrated minimum once per year.
Thank you for selecting our company.We appreciate the opportunity to be of service.
Please call this office if there are any questions.
Sincerely,
Sta,w C,ra j"
Stan Grajny, PE
RESNET HERS Energy Rater 5609922
NYS PE 065406-1