CC-000358-2016 �^ TOWN OF QUEENSBURY
a
y
� 742 Bay Road,Queensbury,NY 12804-5904 (518)761-8201
--__ Community Development - Building & Codes (518) 761-8256
CERTIFICATE OF OCCUPANCY
Permit Number: CC-000358-2016 Date Issued: Friday, June 14, 2019
This is to certify that work requested to be done as shown by Permit Number CC-000358-2016
has been completed.
Tax Map Number: 309.13-1-47
Location: 10 CONNECTICUT AVE
Owner: Scott Tynon
Applicant: Queensbury Seamless Gutters
This structure may be occupied as a: 800 sq. ft. roof repairs due to fire damage
Business Office / Cold Storage of Queensbury Seamless Gutters By order of Town Board
Building Permit Renewed Sept. 4th, 2018 TOWN OF QUEENSBURY
Issuance of this Certificate of Occupancy DOES NOT relieve theproperty owner owner of the responsibility for compliance with Site Plan,
Variance, or other issues and conditions as a result of approvals by the Director of Building&Code Enforcement
Planning Board or Zoning Board of Appeals.
f - TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5904 (518)761-8201
Community Development - Building& Codes (518) 761-8256
BUILDING PERMIT
Permit Number: CC-0003 5 8-2016
Tax Map No: 309.13-1-47
Permission is hereby granted to: Queensbury Seamless Gutters
For property located at: 10 CONNECTICUT AVE
In the Town of Queensbury,to construct or place at the above location in accordance with application together
with plot plans and other information hereto filed and approved and in compliance with the NYS Uniform
Building Codes and the Queensbury Zoning Ordinance
Type of Construction
Owner Name: Scott Tynon Business Office-Alteration $17,500.00
Owner Address: 10 Connecticut AVE Total Value $17,500.00
Queensbury,NY 12804
Contractor or Builder's Name/Address Electrical Inspection Agency
Plans& Specifications
800 sq.ft.roof repairs due to fire damage
Business Office/Cold Storage of Queensbury Seamless Gutters
$ 160.00 PERMIT FEE PAID -THIS PERMIT EXPIRES: Thursday,June 15, 2017
(If a longer period is required,an application for an extension must be made to the code Enforcement Officer
of the Town of Queensbury before the expiration date.)
Dated at the Town of ee urj-y 15, 2016
SIGNED BY: �, I for the Town of Queensbury.
Director of Building&Code Enforcement
- I--- i-- Mi--vv- --- -wI- . J. -t A X 1 I V11WU uhz V111Y
Date: , --/D-- L ( f
- � Permit No.
Tax Map ID �S O`�• — q : Permit Fee
Zone Historic? _YesN Rec Fee
Subdivision Name Lot# Site Plan#
Subdivision #
Project Location
TOWN BD.RESOLUTION 86-2013: $850 recreation fee for new dwelling units—single family,duplexes/two-family, multiple family,
apartments,condominiums,townhouses,and/or manufactured&modular homes,but not mobile homes. This is in addition to the
permit fee(s). {
Primary Owner(s) C opt
Address 156 vie
►n wvet__ r r�moi'
Phone/Email
Applicant
Address
Phone/Email
Contractor
Address
Phone/Ernail
Contact Person for Building & Codes Compliance: Phone
TYPE OF CONSTRUCTION
,/Check-all that apply New Addition Alteratio 1 "floor sf 2"d floor sf Total sf Height
Single Family _T
Two-Family
Multi-Family
(#of units
Townhouse
B mess Office
Retail-Mercantile 5�
Factory-Industrial
Attached Garage
(1, 2, 3, 4+)
Other
Town of Queens urtAuilding i Codes Princip Structure Application revised January 2016
Tf commercial or industrial please indicate name of business
Proposed use of building or addition a1A I !
Source of Heat(circle one) Gas Oil PropAne Solar Other
Fireplace: Complete a separate application for Fuel Burning
Appliances & Chimneys
Are there structures not shown on plot plan? �/�f 0
Are there easements on the property? I(ID
Site Information:
a. Dimensions or acreage of lot
b. Is this a comer lot? Yes No
c. Will the grade be changed as a result of construction Yes No
d. Public water or Private well (circle one) Publi Private
e. Sewer or Private Septic System(circle one) Sewer Pnvate
Value of all work to be performed (labor or materials) $
DECLARA TION:
✓ 1. I acknowledge no construction shall be commenced prior to issuance of a valid permit and will be
completed within a 12 month period.
1/ 2. If work is not complete by the 1 year expiration date the permit may be renewed, subject to fees and
department approval.
/- 3. I certify that the application, plans and supporting materials are a true and complete statement /
description of the work proposed, that all work will be performed in accordance with the NYS
Building Codes, local building laws and ordinances,and in conformance with local zoning regulations
`f4. I acknowledge that prior to occupying the facilities proposed, I or my agents will obtain a certificate
of occupancy.
/5. I also understand that I /we are required to provide an as-built survey by a licensed land surveyor of
all newly constructed facilities prior to issuance of a certificate of occupancy.
I have read and agree to the above:
PRINT NAME: DATE:
SIGNATURE: DATE:
For office use only
Operating Permit Issued: Yes No
Occupancy Type
Construction Classification
Assembly Occupancy Limit
Special Conditions
Town of Queensbury Building&Codes Principal Structure Application Revised January 2016
INSPECTION WORKSHEET (BINS-008588-2018)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
CC-000358-2016Permit
Case Number:Case Module:
Fri Dec 14, 2018Failed
Inspection Date:Inspection Status:
John O'BrienCommercial Final Inspection
Inspector:Inspection Type:
10 CONNECTICUT AVE309.13-1-47
Job Address:Parcel Number:
Queensbury, NY 12804
Contact TypeCompany NameName
Granted PermissionQueensbury Seamless Gutters
Primary OwnerTynon, Scott
ApplicantQueensbury Seamless Gutters
Checklist ItemPassedComments
Plumbing Vent Through Roof/Roof completeYES
Ext Finish /Grade Complete/6 in 10ft orYES
Equivalent
Stockroom /Storage/Receiving/Shipping RoomNO-Install 1 hour fire separation wall with 45 min. Fire door with
self closing hinges and rear exit door from existing storage
and attic area as per conversations with Dave Hatin and
John O'Brien.
H/C Bathroom Grab Bars /Sinks/Toilets/MirrorsNO- Reposition 24" grab bar and use as 18" vertical grab bar.
- Add 42" grab bar on side wall.
Public Toilet Room Handicapped AccessibleNO
Final Electrical / Flex Gas Piping BondedNOFinal Electrical Inspection
Dec 14, 2018Page (1)
INSPECTION WORKSHEET (BINS-008588-2018)
Checklist ItemPassedComments
OK to Issue Temporary C/ONO
Dec 14, 2018Page (2)
INSPECTION WORKSHEET (BINS-008588-2018)
Checklist ItemPassedComments
OK to Issue C/ONO5/31/17 Final Inspection Not Approved
1) Complete handicapped bathroom
-Install permanent floor so toilet sits properly.
-Flush handle for toilet must be on the open side change out
tank.
-Install handicapped sink no cabinet sink needs to be open
underneath and is to close to the toilet.
-Install mirror over sink. Bottom of mirror should not be more
than 40" off finished floor.
-Install Trap Protector on sink Trap.
-Install grab bars as shown on permit drawings.
-Complete sheetrock on side wall and create access to water
meter.
-Install bathroom door with lever handle hardware.
-Install unisex handicapped bathroom sign on wall next to
door latch. Center sign needs to be 60" from finish Floor.
The sign must have Braille lettering at bottom.
-Complete electric in bathroom including bathroom fan
vented to exterior.
2) Complete Office
- Door entry threshold must be ada compliant or ramped on
both sides
- Install permanent floor.
- Complete Electrical Work.
3) Garage
-Complete installing 5/8" type x fire code sheetrock on
garage side ceiling, common wall to garage and up Final
truss to the roof deck at rear of building before two story
section. Seal sheetrock at roof deck with 1 hour fire caulk no
fire foam.
- Clean and seal charred floor joists for loft area.
- Complete Electrical Work
4) Obtain Final Electrical Inspection
5) Fire Marshal's Final Inspection(Cancelled today no where
near ready).
9/22/17 Status Inspection Not Approved- Scott your permit
has expired and we need to verify that the items listed below
have been completed. Please address the items listed below
so a Final Inspection can be completed by myself and Mike
Palmer the Fire Marshal. If you have not completed the items
we need to know what your time frame for completing the
work and pay the renewal fee which is $50.00
1) Complete handicapped bathroom
-Install permanent floor so toilet sits properly.
Dec 14, 2018Page (3)
INSPECTION WORKSHEET (BINS-008588-2018)
Checklist ItemPassedComments
-Flush handle for toilet must be on the open side change out
tank.
-Install handicapped sink, no cabinet. The sink needs to be
open underneath and right now it is to close to the toilet.
Refer to bathroom floor plan view that is with permit.
-Install mirror over sink. Bottom of mirror should not be more
than 40" off finished floor.
-Install Trap Protector on sink Trap.
-Install grab bars as shown on permit drawings.
-Complete sheetrock on side wall and create access to water
meter.
-Install bathroom door with lever handle hardware.
-Install unisex handicapped bathroom sign on wall next to
door latch. Center sign needs to be 60" from finish Floor.
The sign must have Braille lettering at bottom.
-Complete electric in bathroom including bathroom fan
vented to exterior.
2) Complete Office
- Exit Door entry threshold must be ada compliant or ramped
on both sides
- Install permanent floor.
- Complete Electrical Work.
3) Garage
-Complete installing 5/8" type x fire code sheetrock on
garage side ceiling, common wall to garage and up Final
truss to the roof deck at rear of building before two story
section. Seal sheetrock at roof deck with 1 hour fire caulk no
fire foam.
- Clean and seal charred floor joists for loft area.
- Complete Electrical Work
4) Obtain Final Electrical Inspection
5) Fire Marshal's Final Inspection(Cancelled today no where
near ready).
6/27/18 submit revised plan and renew permit
12/14/18 Final Inspection Not Approve
Remaining Items:
-Install 1 hour fire separation wall with 45 min. Fire doorm
with self closing hinges and rear exit door from existing
storage and attic area as per conversations with Dave Hatin
and John O'Brien.
- Reposition 24" grab bar and use as 18" vertical grab bar.
- Add 42" grab bar on side wall.
- Final Electrical Inspection
Dec 14, 2018Page (4)
INSPECTION WORKSHEET (BINS-008588-2018)
Checklist ItemPassedComments
- Install mirror over sink. Bottom of mirror must 40" max off
floor.
- Install CO Detector in office. Battery operated is fine.
- Install ABC Fire Extinguisher In Office at end wall as
discussed
O'Brien, John (Inspector)
Dec 14, 2018Page (5)
INSPECTION WORKSHEET (BINS-003140-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000358-2016 Case Module:Permit
Inspection Date:Tue Jun 4, 2019 Inspection Status:Failed
Inspector:John O'Brien Inspection Type:Commercial Final Inspection
Job Address:Parcel Number:10 CONNECTICUT AVE
Queensbury, NY 12804
309.13-1-47
Contact Type Company Name Name
Granted Permission Queensbury Seamless Gutters
Applicant Queensbury Seamless Gutters
Primary Owner Tynon, Scott
Checklist Item Passed Comments
Plumbing Vent Through Roof/Roof complete YES
Ext Finish /Grade Complete/6 in 10ft or
Equivalent
YES
Stockroom /Storage/Receiving/Shipping Room NO -Install 1 hour fire separation wall with 45 min. Fire door with
self closing hinges and rear exit door from existing storage
and attic area as per conversations with Dave Hatin and
John O'Brien.
6/4/19
- Install 22"x30" 45 minute fire rated access panel on
backroom side as discussed.
- Fire caulk joint at sheetrock where it terminates at wood
beam in back room.
- Install beveled wood transition pieces at fire door and back
door eliminating tripping hazard as discussed.
Attic Access 30 x 20 x 30 (h)NO - Install 22"x30" 45 minute fire rated access panel on
backroom side as discussed.
Jun 04, 2019 Page (1)
INSPECTION WORKSHEET (BINS-003140-2019)
Checklist Item Passed Comments
H/C Bathroom Grab Bars /Sinks/Toilets/Mirrors YES - Reposition 24" grab bar and use as 18" vertical grab bar.
- Add 42" grab bar on side wall.
Final Electrical / Flex Gas Piping Bonded YES Final Electrical Inspection
Jun 04, 2019 Page (2)
INSPECTION WORKSHEET (BINS-003140-2019)
Checklist Item Passed Comments
OK to Issue C/O NO 5/31/17 Final Inspection Not Approved
1) Complete handicapped bathroom
-Install permanent floor so toilet sits properly.
-Flush handle for toilet must be on the open side change out
tank.
-Install handicapped sink no cabinet sink needs to be open
underneath and is to close to the toilet.
-Install mirror over sink. Bottom of mirror should not be more
than 40" off finished floor.
-Install Trap Protector on sink Trap.
-Install grab bars as shown on permit drawings.
-Complete sheetrock on side wall and create access to water
meter.
-Install bathroom door with lever handle hardware.
-Install unisex handicapped bathroom sign on wall next to
door latch. Center sign needs to be 60" from finish Floor.
The sign must have Braille lettering at bottom.
-Complete electric in bathroom including bathroom fan
vented to exterior.
2) Complete Office
- Door entry threshold must be ada compliant or ramped on
both sides
- Install permanent floor.
- Complete Electrical Work.
3) Garage
-Complete installing 5/8" type x fire code sheetrock on
garage side ceiling, common wall to garage and up Final
truss to the roof deck at rear of building before two story
section. Seal sheetrock at roof deck with 1 hour fire caulk no
fire foam.
- Clean and seal charred floor joists for loft area.
- Complete Electrical Work
4) Obtain Final Electrical Inspection
5) Fire Marshal's Final Inspection(Cancelled today no where
near ready).
9/22/17 Status Inspection Not Approved- Scott your permit
has expired and we need to verify that the items listed below
have been completed. Please address the items listed below
so a Final Inspection can be completed by myself and Mike
Palmer the Fire Marshal. If you have not completed the items
we need to know what your time frame for completing the
work and pay the renewal fee which is $50.00
1) Complete handicapped bathroom
-Install permanent floor so toilet sits properly.
Jun 04, 2019 Page (3)
INSPECTION WORKSHEET (BINS-003140-2019)
Checklist Item Passed Comments
-Flush handle for toilet must be on the open side change out
tank.
-Install handicapped sink, no cabinet. The sink needs to be
open underneath and right now it is to close to the toilet.
Refer to bathroom floor plan view that is with permit.
-Install mirror over sink. Bottom of mirror should not be more
than 40" off finished floor.
-Install Trap Protector on sink Trap.
-Install grab bars as shown on permit drawings.
-Complete sheetrock on side wall and create access to water
meter.
-Install bathroom door with lever handle hardware.
-Install unisex handicapped bathroom sign on wall next to
door latch. Center sign needs to be 60" from finish Floor.
The sign must have Braille lettering at bottom.
-Complete electric in bathroom including bathroom fan
vented to exterior.
2) Complete Office
- Exit Door entry threshold must be ada compliant or ramped
on both sides
- Install permanent floor.
- Complete Electrical Work.
3) Garage
-Complete installing 5/8" type x fire code sheetrock on
garage side ceiling, common wall to garage and up Final
truss to the roof deck at rear of building before two story
section. Seal sheetrock at roof deck with 1 hour fire caulk no
fire foam.
- Clean and seal charred floor joists for loft area.
- Complete Electrical Work
4) Obtain Final Electrical Inspection
5) Fire Marshal's Final Inspection(Cancelled today no where
near ready).
6/27/18 submit revised plan and renew permit
12/14/18 Final Inspection Not Approve
Remaining Items:
-Install 1 hour fire separation wall with 45 min. Fire doorm
with self closing hinges and rear exit door from existing
storage and attic area as per conversations with Dave Hatin
and John O'Brien.
- Reposition 24" grab bar and use as 18" vertical grab bar.
- Add 42" grab bar on side wall.
- Final Electrical Inspection
Jun 04, 2019 Page (4)
INSPECTION WORKSHEET (BINS-003140-2019)
Checklist Item Passed Comments
- Install mirror over sink. Bottom of mirror must 40" max off
floor.
- Install CO Detector in office. Battery operated is fine.
- Install ABC Fire Extinguisher In Office at end wall as
discussed
6/4/19 Final Inspection Not Approved
- Install 22"x30" 45 minute fire rated access panel on
backroom side as discussed.
- Fire caulk joint at sheetrock where it terminates at wood
beam in back room.
- Install beveled wood transition pieces at fire door and back
door eliminating tripping hazard as discussed.
- Bathroom fan needs to be vented to the exterior on a gable
end or in the soffit with approved soffit kit.
- General note property needs to cleaned up of debris and
scrap metal. Owner to be cleaning up property this coming
weekend.
Jun 04, 2019 Page (5)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-003578-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000358-2016 Case Module:Permit
Inspection Date:Fri Jun 14, 2019 Inspection Status:Passed
Inspector:John O'Brien Inspection Type:Commercial Final Inspection
Job Address:Parcel Number:10 CONNECTICUT AVE
Queensbury, NY 12804
309.13-1-47
Contact Type Company Name Name
Granted Permission Queensbury Seamless Gutters
Primary Owner Tynon, Scott
Applicant Queensbury Seamless Gutters
Checklist Item Passed Comments
Plumbing Vent Through Roof/Roof complete YES
Ext Finish /Grade Complete/6 in 10ft or
Equivalent
YES
Stockroom /Storage/Receiving/Shipping Room YES -Install 1 hour fire separation wall with 45 min. Fire door with
self closing hinges and rear exit door from existing storage
and attic area as per conversations with Dave Hatin and
John O'Brien.
6/4/19
- Install 22"x30" 45 minute fire rated access panel on
backroom side as discussed.
- Fire caulk joint at sheetrock where it terminates at wood
beam in back room.
- Install beveled wood transition pieces at fire door and back
door eliminating tripping hazard as discussed.
Attic Access 30 x 20 x 30 (h)YES - Install 22"x30" 45 minute fire rated access panel on
backroom side as discussed.
Jun 14, 2019 Page (1)
INSPECTION WORKSHEET (BINS-003578-2019)
Checklist Item Passed Comments
H/C Bathroom Grab Bars /Sinks/Toilets/Mirrors YES - Reposition 24" grab bar and use as 18" vertical grab bar.
- Add 42" grab bar on side wall.
Final Electrical / Flex Gas Piping Bonded YES Final Electrical Inspection
Jun 14, 2019 Page (2)
INSPECTION WORKSHEET (BINS-003578-2019)
Checklist Item Passed Comments
OK to Issue C/O YES 5/31/17 Final Inspection Not Approved
1) Complete handicapped bathroom
-Install permanent floor so toilet sits properly.
-Flush handle for toilet must be on the open side change out
tank.
-Install handicapped sink no cabinet sink needs to be open
underneath and is to close to the toilet.
-Install mirror over sink. Bottom of mirror should not be more
than 40" off finished floor.
-Install Trap Protector on sink Trap.
-Install grab bars as shown on permit drawings.
-Complete sheetrock on side wall and create access to water
meter.
-Install bathroom door with lever handle hardware.
-Install unisex handicapped bathroom sign on wall next to
door latch. Center sign needs to be 60" from finish Floor.
The sign must have Braille lettering at bottom.
-Complete electric in bathroom including bathroom fan
vented to exterior.
2) Complete Office
- Door entry threshold must be ada compliant or ramped on
both sides
- Install permanent floor.
- Complete Electrical Work.
3) Garage
-Complete installing 5/8" type x fire code sheetrock on
garage side ceiling, common wall to garage and up Final
truss to the roof deck at rear of building before two story
section. Seal sheetrock at roof deck with 1 hour fire caulk no
fire foam.
- Clean and seal charred floor joists for loft area.
- Complete Electrical Work
4) Obtain Final Electrical Inspection
5) Fire Marshal's Final Inspection(Cancelled today no where
near ready).
9/22/17 Status Inspection Not Approved- Scott your permit
has expired and we need to verify that the items listed below
have been completed. Please address the items listed below
so a Final Inspection can be completed by myself and Mike
Palmer the Fire Marshal. If you have not completed the items
we need to know what your time frame for completing the
work and pay the renewal fee which is $50.00
1) Complete handicapped bathroom
-Install permanent floor so toilet sits properly.
Jun 14, 2019 Page (3)
INSPECTION WORKSHEET (BINS-003578-2019)
Checklist Item Passed Comments
-Flush handle for toilet must be on the open side change out
tank.
-Install handicapped sink, no cabinet. The sink needs to be
open underneath and right now it is to close to the toilet.
Refer to bathroom floor plan view that is with permit.
-Install mirror over sink. Bottom of mirror should not be more
than 40" off finished floor.
-Install Trap Protector on sink Trap.
-Install grab bars as shown on permit drawings.
-Complete sheetrock on side wall and create access to water
meter.
-Install bathroom door with lever handle hardware.
-Install unisex handicapped bathroom sign on wall next to
door latch. Center sign needs to be 60" from finish Floor.
The sign must have Braille lettering at bottom.
-Complete electric in bathroom including bathroom fan
vented to exterior.
2) Complete Office
- Exit Door entry threshold must be ada compliant or ramped
on both sides
- Install permanent floor.
- Complete Electrical Work.
3) Garage
-Complete installing 5/8" type x fire code sheetrock on
garage side ceiling, common wall to garage and up Final
truss to the roof deck at rear of building before two story
section. Seal sheetrock at roof deck with 1 hour fire caulk no
fire foam.
- Clean and seal charred floor joists for loft area.
- Complete Electrical Work
4) Obtain Final Electrical Inspection
5) Fire Marshal's Final Inspection(Cancelled today no where
near ready).
6/27/18 submit revised plan and renew permit
12/14/18 Final Inspection Not Approve
Remaining Items:
-Install 1 hour fire separation wall with 45 min. Fire doorm
with self closing hinges and rear exit door from existing
storage and attic area as per conversations with Dave Hatin
and John O'Brien.
- Reposition 24" grab bar and use as 18" vertical grab bar.
- Add 42" grab bar on side wall.
- Final Electrical Inspection
Jun 14, 2019 Page (4)
INSPECTION WORKSHEET (BINS-003578-2019)
Checklist Item Passed Comments
- Install mirror over sink. Bottom of mirror must 40" max off
floor.
- Install CO Detector in office. Battery operated is fine.
- Install ABC Fire Extinguisher In Office at end wall as
discussed
6/4/19 Final Inspection Not Approved
- Install 22"x30" 45 minute fire rated access panel on
backroom side as discussed.
- Fire caulk joint at sheetrock where it terminates at wood
beam in back room.
- Install beveled wood transition pieces at fire door and back
door eliminating tripping hazard as discussed.
- Bathroom fan needs to be vented to the exterior on a gable
end or in the soffit with approved soffit kit.
- General note property needs to cleaned up of debris and
scrap metal. Owner to be cleaning up property this coming
weekend.
6/14/19 Final Inspection Approved - Ok to Issue CO!
Jun 14, 2019 Page (5)