2012-424 TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5902 (518)761-8201
Community Development - Building & Codes (518) 761-8256
CERTIFICATE OF OCCUPANCY
Permit Number: P20120424 Date Issued: Monday, January 07, 2013
This is to certify that work requested to be done as shown by Permit Number P20120424
has been completed.
Location: 78 TUTHILL Rd
Tax Map Number: 523400-307-000-0001-015-000-0000
Owner: WALTER & HELEN LINGG
Applicant: WALTER & HELEN LINGG
This structure may be occupied as a:
Residential Addition By Order of Town Board
TOWN OF QUEENSBURY
Issuance of this Certificate of Occupancy DOES NOT relieve the property rcIDowner of the responsibility for compliance with Site Plan, Variance, or YY
other issues and conditions as a result of approvals by the Planning Board Director of Building& Code Enforcement
or Zoning Board of Appeals.
0.4 TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5902 (518)761-8201
7
Community Development-Building&Codes (518) 761-8256
BUILDING PERMIT
Permit Number: P20120424 Application Number: A20120424
Tax Map No: 523400-307-000-0001-015-000-0000
Permission is hereby granted to: WALTER&HELEN LINGG
For property located at: 78 TUTHILL Rd
in the Town of Queensbury,to construct or place
at the above location in accordance with application together with plot plans and other information hereto filed
and approved and in compliance with the NYS Uniform Building Codes and the Queensbury Zoning
Ordinance. Type of Construction Value
Owner Address: WALTER& HELEN LINGG Residential Addition $80,000.00
78 TUTHILL Rd Total Value
QUEENSBURY,NY 12804-0000 $80,000.00
Contractor or Builder's Name/Address Electrical Inspection Agency
GREG RACZKOWSKI
NY 12804-0000
Plans&Specifications
BP 2012-424
Residential Addition of 1,284 sq. ft.; adding second story to existing SFD; height to peak 28 ft.
$256.80 PERMIT FEE PAID-THIS PERMIT EXPIRES: Wednesday, September 11,2013
(If a longer period is required,an application for an extension must be made to the code Enforcement Officer
of the Town of Queensbury before the expiration date.)
Dated at the Town of ueen ury; hues u , 1•ptember 11, 2012
for the Town of Queensbury.
BY Q ury.
Director of Building&Code Enforcement
, OFFICE USE ONLY c)b )
TAX MAP NO)7'°° -1-IS 1�- Da�
PERMIT NO. „-..,,.,z ,„,
FEES: PERMIT - 5 "- RECREATION ENGINEERING
Stamp
(If applicable)
PRINCIPAL STRUCTURE:
APPLICATION FOR ZONING APPROVAL & BUILDING PERMIT
A PERMIT MUST BE OBTAINED BEFORE BEGINNING CONSTRUCTION. APPLICATION IS SUBJECT TO REVIEW
BEFORE ISSUANCE OF/�AVALID PERMIT FOR CONSTRUCTION.
APPLICANT/BUILDER: &Fel R.C((,ZkC0 7\K; OWNER: Hae..,-, (
QSckic,tt`'&--
`1 i*L + l 061-,S vADDRESS: a kGtlie fVcsk 1� /, ADDRESS:
PHONE NOS. s.1 -
C33� PHONE NOS. 19 K - Ca/6CD
CONTACT PERSON FOR BUILDING & CODES COMPLIANCE: (. r-ec' PHONE: -2,(1 ci3n-
LOCATION OF PROPERTY: 8 Tv-i-[.,, Lj 12-d 62A.)-ea, _S Luiti ,U1 12-foti
HAS THERE E'"FN A SITE PLAN REVIEW; VARIANCE OR SUBDIVISION APPROVAL? 0 YES giNO
IF SO, INDICATE APPLICATION NO. AND DATE OF APPROVAL:
PLEASE INDICATE MEASUREMENTS AS REQUIRED BELOW:
CHECK ALL THAT Z
APPLY TO YOUR z < 0 C1 C1 0
PROJECT � Q p U. w
E -ori W < O = =
D = Q Q. — U
0 Z
-� F- La
-J
z C�
Z Q Q Nfn OE PE rt _
ed
SINGLE FAMILY 3�t 5 LlaZA di-
r :`,T-7-7Le)
9 , -
TWO-FAMILY
MULTI-FAMILYb C/Fe- / ► • /
(NO.of UNITS ) "di
TOWNHOUSE
BUSINESS OFFICE
RETAIL-
MERCANTILE
FACTORY OR
INDUSTRIAL
ATTACHED
GARAGE(1,2,3)
OTHER
IF COMMERCIAL OR INDUSTRIAL_NAME OF BUSINESS: —
ESTIMATED CONSTRUCTION COST: 'frCSO FUEL TYPE:
HEAT TYPE: G *HOW MANY FIREPLACE(S): PO/4---AND/OR WOODSTOVES(S):
ZONING CATEGORY: ARE THERE WETLANDS ON THIS SITE?
IS THIS A HISTORIC SITE?
PROPOSED USE OF BUILDING OR ADDITION:
*Please complete a separate Application for"Fuel Burning Appliances&Chimneys"available in our office
2 3-LGL I 1-f
ARE THERE STRUCTURES NOT SHOWN ON PLOT PLAN? Ib
ARE THERE EASEMENTS ON PROPERTY? /3 U
I acknowledge no construction activities shall be commenced prior to issuance of a valid
permit. I certify that the application, plans, and supporting materials are a true and
complete statement/description of the work proposed, that all work will be performed in
accordance with the NY State Building Codes, local building laws and ordinances, and in
conformance with local zoning regulations. I acknowledge that prior to occupying the
facilities proposed, I or my agents will obtain a certificate of occupancy. I also understand
that I/we are required to provide an as-built survey by a licensed land surveyor of all newly
constructed facilities prior to issuance of a certificate of occupancy.
/1/have read and agree to the above.
• Signed -416"'
(--
Director
Director of Building & Codes: 761-8256 (for questions regarding Building Permits, construction codes
or septic systems)
Zoning Administrator: 761-8218 (for questions regarding required permits, the permit process,
application requirements or to schedule an appointment)
•
Permission is hereby granted to the above This application / proposed action described
Applicant to erect or alter the building herein is found to be in accordance with the
described herein in accordance with said zoning Laws of the Town of Queensbury.
Application:
BUILDING & CODES APPROVAL ZONING APPROVAL
DATE DATE
J
J
QUESTIONS? CALL 761.8256 OR EMAIL
codesaqueensburv.net
Office Use Only
VISIT OUR WEBSITE FOR MORE INFORMATION
Operating Permit Issued: Yes No www•queensburv.net
Occupancy Type: Construction Classification:
Assembly Occupancy Limit: Special Conditions:
•
►=J��t's£ (. /() I,)
Queensbury Building & Code Enforcement - Residential Final Inspection
Office No. (518)761-8256 Arrive: am/pm De art: \3�m/pm
Date Inspection request received: Inspector's Initials:
NAME: 2, 1 n`y9 / 1 . e ���� < PERMIT#: - �< 7
LOCATION: 7 �.Li' Koi DATE: - - •
TYPE OF STRUCTURE: 7-4c1J
Comments:
Yes No N/A
4" Building Number Address visible from road /` ,),� , _ ��
Chimney Height/"B"Vent/Direct Vent Location C - 4 �` ''``"
Fresh Air Intake (Ar."-y\
mak. t
in
3 inch Plumbing Vent through roof minimum 18 inches
Roof Complete/Exterior Finish Complete3 l --�
25
Platform at all exterior doors 07-
Handrail 4 or more risersitif21/4"tect ,
Guards at stairs,decks,patios more than 30 inches above grade Guard at stairwell at 34 inches or more
Guard at deck, porches 36 inches or more
Handrail Termination at Newell Post or Wall
Interior/Exterior Railings 34 inches to 38 inches
Deck Bracing/Handicapped Ramp Compliant
Grade away from foundation 6 inches with 10 feet
6 inch clearance to sill plate
Gas Valve shut-off exposed/regulator 18 inches above grade
Interior privacy/trim/doors/main entrance 36 inches
Bathroom/Kitchen watertight
Safety glazing/Window in stairwells safety glazing
Interior Smoke Detectors I Carbon Monoxide Detectors
Every level: Every Bedroom:
Outside every bedroom area:
Inter Connected: Battery backup:
Attic access 30 inches x 22 inches x 30 inches(height)in accessible area
Crawl Spaces 18 inch x 24 inch access, 1 sq.ft.-150 sq.ft.vents
Bathroom Fans, if no window
Plumbing fixtures
Foundation insulation to floor/Sticker on Panel
Duct work sealed properly/Blower Door Test Certification
Floor truss,draft stopping finished basement 1,000 sq.ft.
Emergency egress below grade
Gas Furnace shut-off within 30 feet or within line of site
Oil Furnace shut-off at entrance to furnace area
Furnace/Hot Water Heater operating
Low water shut-off boiler
Relief Valve(s)installed/Heat Trap/Water Temp 110
Enclosed Stairs Sheetrock Underside minimum/2"Gypsum
Basement stairs closed rise>4 inches
Garage Floor Pitched
Garage fireproofing/'/,hour fire door/door closer {
Gas Logs in Sealed or Glass Enclosure
Final Electrical; Energy Saving Light Bulbs 50%
c
L � ;
Final Survey Plot Plan
Arc Fault Breaker Habitable Spaces/Tamper Proof Receptacles
Flex Gas Pipe Bonding
As Built Septic System/Sewer Dept. Inspection Sticker
Site Plan /Variance required /(
Flood Plain Certification, if required
Okay to issue C/C or C/0[Temporary/Permanent]
L:1Building&Codes Forms\Building&Codesllnspection Forms\Residential Final Inspection Form_revised_100405.doc;Revised
January 7,2008; Revised 6/26/08;Revised 12/22/10, Revised 04/13/11
L3 c /6 -/
Queensbury Building & Code Enforcement - Residential Final Inspection
Office No. (518) 761-8256 Arrive: am/p De art:L I 0 a cn/pm
Date Inspection request received: Inspector's Initials:
NAME: ) 1 rme. PERMIT#: !--) -t/A V
LOCATION: 7 ,?.-ii/ft>r l i 0,-,v° DATE: i / a-/c*--/,4
TYPE OF STRUCTURE: R P 3 ; c{.
Comments: _
Yes No NIA
4" Building Number Address visible from road f
Chimney Height/"B"Vent/Direct Vent Location LA)rd---40. t.
Fresh Air Intake
3 inch Plumbing Vent through roof minimum 18 inches f
Roof Complete/Exterior Finish Complete
Platform at all exterior doors
Handrail 4 or more risers
Guards at stairs,decks, patios more than 30 inches above grade r
Guard at stairwell at 34 inches or more
Guard at deck,porches 36 inches or more \,
Handrail Termination at Newell Post or Wall
Interior/Exterior Railings 34 inches to 38 inches
Deck Bracing/Handicapped Ramp Compliant
Grade away from foundation 6 inches with 10 feet \A�-- 7 --�C
6 inch clearance to sill plate
Gas Valve shut-off exposed/regulator 18 inches above grade NA-IP't E1 —
Interior privacy/trim I doors I main entrance 36 inches
Bathroom/Kitchen watertight _, p-S '? R_.... 19 ► —
Safety glazing/Wind• in stairwells safety gl. ng
Interior Smoke Det:«ors/Carbon Moxid- Detectors -+
Every level: :ve Bedro :
Outside every bedrooa a: �t �
Inter Connected: Battery backup:
Attic access 30 inches x 22 inches x 30 inches eight)in accessible area / 7-t
Crawl Spaces 18 inch x 24 inch access, 1 sq.ft.-150 sq.ft.vents
Bathroom Fans,if no window --1
•`
Plumbing fixtures --- r-1-0-Q----
Foundation insulation to floor/Sticker on Panel
Duct work sealed properly/Blower Door Test Certification � __
Floor truss,draft stopping finished basement 1,000 sq.ft.
Emergency egress below grade
Gas Furnace shut-off within 30 feet or within line of site
Oil Furnace shut-off at entrance to furnace area
Furnace/Hot Water Heater operating
Low water shut-off boiler
Relief Valve(s)installed/Heat Trap/Water Temp 110
Enclosed Stairs Sheetrock Underside minimum%z"Gypsum
Basement stairs closed rise>4 inches
Garage Floor Pitched
Garage fireproofing/%hour fire door/door closer
0
Gas Logs in Sealed or Glass Enclosure . 1r �
Final Electrical;Energy Saving Light Bulbs 50% 1
Final Survey Plot Plan �J 5-g3
Arc Fault Breaker Habitable Spaces/Tamper Proof Receptacles - [
Flex Gas Pipe Bonding
As Built Septic System/Sewer Dept. Inspection Sticker
Site Plan /Variance required
Flood Plain Certification, if required
AIOkay to issue C/C or C I 0[Temporary/Permanent]
L:1Building&Codes Forms\Building&Codesllnspection Fomis\Residential Final Inspection Form_revised_100405.doc; Revised
January 7,2008; Revised 6/26/08; Revised 12/22/10, Revised 04/13/11
ffc
Rough Plumbing I Insulation Inspection Report
Office No. (518) 761-8256 Date Inspection request received:
Queensbury Building &Code Enforcement Arrive: am/pm Depart: r- c am/pm
742 Bay Road, Queensbury, NY 12804 Inspector's Initials: •lig
NAME: h �' _ PERMIT #: 0-j<10
LOCATION: • .� I ( INSPECT ON: /J--i3- -0 ?
TYPE OF STRUCTURE: _ S
c
Y N N/A (j) ) y
Rou•h Plumbin• /Nail Plates
Plumbing Vent/Vents in Place
1 % inch minimum Drain Size
Washing Machine Drain 2 inch minimum
Cleanout every 100 feet I change of direction
Pressure Test
Drain /Vent
Air/Head
5 P.S.I. or 10 ft. above highest connection for 15 minutes
Pressure Test
Water Supply Piping
Air/Head
50 P.S.I for 15 minutes
Insulation / Residential Check I Commercial Check
Tyvek or Similar Exterior Sealant
Proper Vent, Attic Vent
Door/Window Sealed (No Insulation)
Duct/ Hot Water Piping Insulation
If required unheated spaces
Combustion Air Supply for Furnace
Duct work sealed properly/No duct tape • /,V �,. ,r' Lam'
COMMENTS: " V
Rough Plumbing Insulation Report.revised Nov 17 2003, revised February 15,2005, revised January 7,2008
Rough Plumbing / Insulation Inspection Report oC-ot '
Office No. (518) 761-8256 Date Inspection request received: /1 /1/40/.)_
Queensbury
1 /1/40f.)-
Queensbury Building & Code Enforcement Arrive: am/pm De art: ; c am/pm
742 Bay Road, Queensbury, NY 12804 Inspectors Initials: __ / r
3 377
NAME:
re e zkcws kPERMIT #: - Yo`/
LOCATION: `7 1 t,� l� ( � INSPECT ON: 11 Q2,I i
TYPE OF STRUCTURE: (2'? S �
Y N NJA
Rough Plumbing/Nail Plates
Plumbing Vent J Vents in Place
1 '/Y inch minimum Drain Size
Washing Machine Drain 2 inch minimum
Cleanout every 100 feet I change of direction
Pressure Test
Drain/Vent
Air/ Head
5 P.S.I. or 10 ft. above highest connection for 15 minutes
Pressure Test
Water Supply Piping
Air/Head
. or 15 minutes
nsul ' Residential Check/ Commercial Check
Tyvek or Similar Exterior Sealant
Proper Vent, Attic Vent
Door/Window Sealed (No Insulation)
Duct t Hot Water Piping Insulation
If required unheated spaces
Combustion Air Supply for Furnace
Duct work sealed properly/No duct tape
COMMENTS:
Rough Plumbing Insulation Report.revised Nov 17 2003, revised February 15,2005, revised January 7,2008
cJ(i )
Rough Plumbing 1 Insulation Inspection eport
Office No. (51 .) 761-8256 Date Inspection request received: 1�
Queensbury B ' •' • z ode Enforcement Arrive: am/pm art:/t am/pm
742 Bay Road, Queensbury, NY 12804 Inspector's Initials: `
NAME: _ PERMIT #: 0 Z �-`
LOCATION: 'Z " L INSPECT ON: Iona
TYPE OF STRUCTURE: I�rC? -'
Y N/A
Rou•h Plumbin, /Nail Plates r
Plumbin• Vent/Vents in Place ME
1 '/2 inch minimum Drain Size
Washing Machine Drain 2 inch minimum
Clea_•� ijaa40 feet/chane a of direction
-ure Test
Drain /Vent
Air/Head
5 P.S.I. • + ft. above hi hest connection for 15 minutes
Pressure Test
Water Supply Piping
Air/Head ecv,ts
50 P.S.I for 15 minutes
Insulation / Residential Check I Commercial Check
T ek or Similar Exterior Sealant
Proper Vent, Attic Vent
Door/Window Sealed No Insulation
Duct/ Hot Water Piping Insulation
If required unheated spaces
Combustion Air Su• • for Furnace
Duct work sealed •ro•er1 / No duct to•e
COMMENTS:
Rough Plumbing Insulation Reportrevised Nov 17 2003, revised February 15,2005, revised January 7,2008
/cD ,3D
Rough Plumbing I Insulation Inspection Report
Office No. (518) 761-8256 Date Inspection request received:
Queensbury Building & Code Enforcement Arrive: am/pm Depart:1 am/pm
742 Bay Road, Queensbury, NY 12804 Inspector's Initials: '�(�
NAME: 1-,A-k) PERMIT #: Z. j 2. 424-
LOCATION: ---tcA INSPECT ON: e&I191 t z
TYPE OF STRUCTURE: �Z
Y N N/A
Rough Plumbing /Nail Plates
Plumbing Vent/Vents in Place
1 % inch minimum Drain Size
Washing Machine Drain 2 inch minimum
Cleanout every 100 feet 1 change of direction
Pressure Test
Drain /Vent
Air/Head
5 P.S.I. or 10 ft. above highest connection for 15 minutes
Pressure Test
Water Supply Piping
Air/Head
50 P.S.I for 15 minutes
Insulation /Residential Check/Commercial Check
Tyvek or Similar Exterior Sealant
Proper Vent, Attic Vent
Door/Window Sealed (No Insulation)
Duct I Hot Water Piping Insulation
If r- •uired unheated s•aces
Combustion Air Supply for Furnace
Duct work sealed properly/ No duct tape
crL 0-ik9
COMMENTS: tAi V
'
(211
Rough Plumbing Insulation Report.revised Nov 17 2003, revised February 15, 2005, revised January 7, 2008
f-- ectD g1,30
ion Rough Plumbing / insulation inspect o Report p )
Office No. (518) 761-8256 Date Inspection request received:
Queensbury Building & Code Enforcement Arrive: am/pm Depart• o am/pm
742 Bay Road, Queensbury, NY 12804 Inspector's Initials:
OLf)
NAME: L v PERMIT #:
LOCATION: ' *h I I cif INSPECT ON: /
TYPE OF STRUCTURE:
Y N/A
Rough Plumbing / Nail Plates
Plumbing Vent I Vents in Place
1 '/Z inch minimum Drain Size
Washing Machine Drain 2 inch minimum
Cleanout every 100 feet I change of direction
Pressure Test
Drain /Vent
Air/Head
5 P.S.I. or 10 ft. above highest connection for 15 minutes
Pressure Test
Water Supply Piping Co
Air l Head �--
50 P.S.I for 15 minutes
Insulation / Residential Check/Commercial Check
Tyvek or Similar Exterior Sealant
Proper Vent, Attic Vent
Door/Window Sealed (No Insulation)
Duct/ Hot Water Piping Insulation
If required unheated spaces
Combustion Air Supply for Furnace
Duct work sealed properly/ No duct tape
t� c -o t
V)vv
COMMENTS: at .;/
c
Rough Plumbing Insulation Report.revised Nov 17 2003, revised February 15,2005, revised January 7,2008
-1' hullo 1-3
Foundation Inspection Report
Office No.(518)761-8256 Date Inspection request received:
Queensbury Building&Code Enforcement Arrive: am/pm Depart:t K---am/pm
64,..X)742 Bay Rd.,Queensbury,NY 12804 Inspector's Initials:�
NAME:
L 1 .1c PERMIT#: / �— 1 y
ALOTION: rl •�cINSPECT ON: / v •-/ E
TYPE OF STRUCTURE: h
Comment
N N/A
Footings
Piers
Monolithic Slab
Reinforcement in Place ( .ia
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement � �`�
of the concrete.
Materials for this purpose on site.
Foundation/Wallpour ( )J1-e‘.
Reinforcement in Place (`ra—Q
Footing Dowels or Keyway in place
Foundation Dampproofing -�v
Foundation Waterproofing
Footing Drain Daylight or Sump
Footing Drain Stone:
12 inch width
6 inches above footing
6 mil poly for wet areas under slab
Backfill Approval
Plumbing Under Slab
PVC/Cast/Copper
Foundation Insulation Interior/Exterior
R-
Rough Grade 6 inch drop within 10 ft.
L:\Building&Codes Forms\Building&Codes\Inspectlon Forms\Foundation Inspection Report.doc
Last printed 12/20/2005 9:24:00 AM
Framing / Firestopping Inspection Report
Office No. (518) 761-8256 Date Inspection request received:
Queensbury Building &Code Enforcement Arrive: am/ part:/.tam/pm
742 Bay Road, Queensbury, NY 12804 Inspector's Initials:
NAME: PERMIT#:
LOCATION: `� INSPECT ON: 1�
TYPE OF STRUCTURE: vf)
N N/A COMMENTS:
Framing
Attic Access 22" x 30" minimum Jack Studs/Headers
Bracing t Bridging (/"f--
Joist hangers
Jack Posts/Main Beams
Exterior sheeting nailed properly
12" O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Exterior Deck Bracing
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate
1 %(w) 16 gauge (8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
Ice and water shield 24 inches from wall
Fire separation 1, 2, 3 hour -�-
Fire wall 2, 3, 4 hour
Firestopping
,111
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side %inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/Bedrooms
24 in. (H)
20 in. (VV)
5.7 sf above/below grade
5.0 sf grade
L:1Building&Codes Forms-0LD18uilding&CodesUnspection Fomis\Framing Firestopping Inspection Report.doc Revised January 7,2008
Framing / Firestopping Inspection Report r(''(c1c \ ,) '
Office No. (518) 761-8256 Date Inspection request received:
Queensbury Building & Code Enforcement Arrive: am/pm Depart-), fj am/pm
742 Bay Road, Queensbury, NY 12804 Inspector's Initials:0 -7 . )L1
NAME:
PERMIT#: /
LOCATION: 7'' 1 iL.11 FT_ INSPECT ON: /
TYPE OF STRUCTURE: Re S 6cid
Y N N/A COMMENTS:
(rarg )i
Attic Access 22" x 30" minimum
Jack Studs/ Headers j
Bracing I Bridging '7
Joist hangers
Jack Posts/Main Beams
Exterior sheeting nailed properly
12" O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Exterior Deck Bracing
Headroom 6 ft. 8 in.
Notches I Holes 1 Bearing Walls
Metal Strapping for Notches Top Plate -'
1 '/2(w) 16 gauge (8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Botts 6 ft. or less on center
Ice and water shield 24 inches from wall
Fire separation 1, 2, 3 hour
Fire wall 2, 3, 4 hour 47\
Firestopping ( j )
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side 1/2 inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/ Bedrooms
24 in. (H)
20 in. (W)
5.7 sf above/ below grade
5.0 sf grade
L:1Building&Codes Forms OLD\Building&Codes\nspection Forms\Framing Firestopping Inspection Report.doc Revised January 7,2008