RC-000004-2017 TOWN OF QUEEN S B U RY
742 Bay Road,Queensbury,NY 12804-5904 (518)761-8201
Community Development-Building&Codes (518)761-8256
CERTIFICATE OF OCCUPANCY
Permit Number: RC-000004-2017 Date Issued: Friday, April 27, 2018
This is to certify that work requested to be done as shown by Permit Number RC-000004-2017
has been completed.
Tax Map Number: 278.-2-13
Location: 49 Walkup RD
Owner: Kevin Whiting, Lynsey Whiting
Applicant: Kevin Whiting
This structure may be occupied as a: Single Family Dwelling w/FP 1456 s.f.
Attached 2-car Garage 808 s.f By Order of Town Board
TOWN OF QUEENSBURY
Issuance of this Certificate of Occupancy DOES NOT relieve the
property owner of the responsibility for compliance with Site Plan,
Variance,or other issues and conditions as a result of approvals by the Director ol'Building&Code Enforcement
Planning Board or Zoning Board of Appeals.
TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5904 (518)761-8201
Community Development-Building&Codes (518)761-8256
BUILDING PERMIT
Permit Number: RC-000004-2017
Tax Map No: 278.-2-13
Permission is hereby granted to: Kevin Whiting
For property located at: 49 Walkup RD
In the Town of Queensbury,to construct or place at the above location in accordance with application together
with plot plans and other information hereto filed and approved and in compliance with the NYS Uniform
Building Codes and the Queensbury Zoning Ordinance
Tyne of Construction
Owner Name: Kevin Whiting Single Family-New $177,000.00
Owner Address: 18 COBBLESTONE DR Total Value $177.000.00
Queensbury,NY 12804
Contractor or Builder's Name/Address Electrical Inspection Agency
Peter Campbell
PO Box 124
Weavertown,NY 12886
Plans&Specifications
Single Family Dwelling w/FP 1456 s.f.
Attached 2-car Garage 808 s.f.
$1,312.40 PERMIT FEE PAID-THIS PERMIT EXPIRES: Wednesday.January 31.2018
(If a longer period is required,an application for an extension must be made to the code Enforcement Officer
of the Town of Queensbury before the exp' tion date.)
Dated at the Town of ueensb dues y ry 31,2017
SIGNED BY: ///QQQ for the Town of Queensbury.
Director of Building&Code Enforcement
PRINCIPAL STRUCTURE APPLICATION Office Use Only
Date: /B� v2 D/7 PermitNo.
Tax Map ID .21 7 t• — —/3 Permit Fee
Zone Historic? _Yes No Rec Fee
Subdivision Name Lot# Sixe..glarr# 1 V, I 7-5,}�-
Subdivision#
Project Location oaf
TOWN BD.RESOLUTION 86-2013: $850 recreation fee for new dwelling units—single family,duplexes/two-family, multiple family,
apartments,condominiums,townhouses,and/or manufactured&modular homes,but not mobile homes. This is in addition to the
permit fee(s).
Primary Owner(s) /
f /'l 10 h �h
Address
Phone/Email
cSl75! 4tliq F9 Z- c3-2-7 3
Applicant (� /
h .S n
Address
Phone/Email
Contractor
Address �v 42 ✓w 61,c�n
Phone/Email LQ5,/ SS— 7�;l 5"
Contact Person for Building& Codes Compliance: Kevin \nl�.141 Phone 7 i " WX 9
TYPE OF CONSTRUCTION
-./Check all that apply New Addition Alteration V floor sf 2"d floor sf Total sf Height
Single Family ✓ 140 6-
Two-Family
Multi-Family
(#of units
Townhouse
Business Office
TOoNrVOp -if
Retail -Mercantile - t.naJ & COdES
Factory-Industrial
Attached Garage
0 9U.j 31 4+)
Other
Town of Queensbury Building&Codes Principal Structure Application revised January 2016
If commercial or industrial please indicate name of business
Proposed use of building or addition /tri rr�a /� i ayes.c
Source of Heat (circle one) Gas Oil Propane Solar Other
Fireplace: Complete a separate application for Fuel Burning
Appliances & Chimneys
W ood s�ove
Are there structures not shown on plot plan? N o
Are there easements on the property? /,kj D
Site Information:
a. Dimensions or acreage of lot 2_- 3 Y
b. Is this a corner lot? Yes ✓ No
c. Will the grade be changed as a result of construction Yes ✓ No
d. Public water or Private well (circle one) Public CXdvate
e. Sewer or Private Septic System (circle one) Sewer rivate
Value of all work to be performed (labor or materials) $ /7 -7, oao
DECLARATION:
1. I acknowledge no construction shall be commenced prior to issuance of a valid permit and will be
completed within a 12 month period.
2. If work is not complete by the 1 year expiration date the permit may be renewed, subject to fees and
department approval.
3. I certify that the application, plans and supporting materials are a true and complete statement /
description of the work proposed, that all work will be performed in accordance with the NYS
Building Codes,local building laws and ordinances,and in conformance with local zoning regulations
4. I acknowledge that prior to occupying the facilities proposed, I or my agents will obtain a certificate
of occupancy.
5. I also understand that I /we are required to provide an as-built survey by a licensed land surveyor of
all newly constructed facilities prior to issuance of a certificate of occupancy.
I have read and agree to the above:
PRINT NAME: key1 n DATE: vZ;2.ol l
SIGNATURE: DATE: Z/ v Z 2'x-7
For office use only
Operating Permit Issued: Yes No
Occupancy Type
Construction Classification
Assembly Occupancy Limit
Special Conditions
Town of Queensbury Building&Codes Principal Structure Application Revised January 2016
Fuel Burning Appliance & Chimney Application Office Use Only
Received
DATE: Tax Map ID
TAX MAP ID: X2.7 cY, — ;2-.—/3 Permit No.
Permit Fee
ZONE:
OWNER P�vin ,L n JG {gJ/iifj� PHONE/E-MAIL &/� -7J`j_ cit&t9
ADDRESS
INSTALLER/ a n PHONE/E-MAIL
BUILDER / C,�Gr �—���b�/ 9f-t'77Z 5"
CONTACT PERSON FOR BUILDING&CODE COMPLIANCE:
PHONE/E-MAIL BUILDING ADDRESS
ROOM OF INSTALL: PLANNED INSTALL DATE: 7134
FUEL BURNING APPLIANCE INFORMATION WOOD COAL PELLET GAS OIL NOTE: ROUGH-IN&
STOVE FINAL INSPECTION ARE
FIREPLACE INSERT
REQUIRED.
FIREPLACE,FACTORY BUILT* NOTE:
MANUFACTURER'S
FIREPLACE,MASONRY
INSTALLATION MANUAL
FURNACE(GARAGE ONLY) MUST BE AVAILABLE AT
TIME OF INSPECTION
*If factory built provide manufacturer name: :E-BD ; Model #: TZ 0
Listed by: ::rgv Number: -r15 p
CHIMNEY INFORMATION
Masonry** (check one) BLOCK BRICK STONE
Flue TIE STEEL Size in inches
Material DOUBLE WALL TRIPLE WALL INSULATED
** If non-masonry provide manufacturer name: 6y ; Model#:
DECLARATION: Construction/installation must conform to NYS Fire Prevention & Building Code and/or
manufacturer requirements. The applicant or owner agrees to comply with all applicable laws, ordinances,
regulations, and all conditions that are part of these requirements and also will allow inspector's to enter premises
to perform required inspections.
I HAVE READ AND AGREE TO THE ABOVE:
PRINT NAME: Qy 1 r 1 DATE: o T 2o/y
SIGNATURE: DATE:
Town of Queensbury Building&Codes Principal Structure Application Revised January 2016
SEPTIC DISPOSAL APPLICATION Office Use Only
Received
DATE: 0,Zo 17 Tax Map ID
TAX MAP ID: 2.79 , Z. "' 13 Permit No.
Permit Fee
ZONE:
APPLICANT P�/i rI ,r h S w7L/-i n PHONE/E-MAIL
ADDRESS 1�, �-� OCC4C f-�'ltiG &e- e N y '2
INSTALLER/ Q / / / PHONE/E-MAIL
BUILDER �l G� .�`G �-! v/r e /4) 7f ff-,579-&2
OWNER /f/'C A/ G 67ui i^e
ADDRESS &S' Cr• 77-ek-//5 efoa d T. 4 A m �1
CONTACT PERSON FOR BUILDING&CODE COMPLIANCE:
PHONE/E-MAIL
RESIDENCE INFORMATION
Year Built #of bedrooms X gallons per bedroom =total Daily flow
1980 or older Garbage grinder installed Yes No
1981-1991 Spa or Hot Tub installed Yes No
1992-Present
PARCEL INFORMATION
Topography ✓Flat rolling e Steep slope %Slope
Soil Nature ✓ Sand Loam Clay Other
Groundwater At what depth: D
Bedrock/Impervious material At what depth: 12-0,
Domestic Water Supply Municipal ✓ Well(if well,water supply from any septic system absorption is 17.Dft.)
Percolation Test Rate: I:Ito- ►:26 per minute per inch(test to be completed by licensed engineer/architect)
PROPOSED SYSTEM FOR NEW CONSTRUCTION
Tank size X006 gallons(min.size 1,000 gallons,add 250 gallons to size for each garbage cylinder or spa or hot tub
System Absorption field with 42 stone Total length SOD ft.;Each Trench �PO
Seepage Pit with 43 stone How many: _;Size
Alternative System Bed or other type:
Holding Tank System Total required capacity? Tank size #of tanks
Notes: 1)Alarm system& associated electrical work must be inspected by a Town approved electrical inspection agency;2)We will
no longer allow systems to be covered until such time as an As-Built plan is received&approved. The installed system must match the
septic system layout on file--no exceptions.
Declaration: Any permit or approval granted which is based upon or is granted in reliance upon any material representation or failure
to make a material fact or circumstance known by or on behalf of an applicant, shall be void. I have read the regulations and agree to
abide by these and all requirements of the Town of Queensbury Sanitary Sewage Disposal Ordinance.
PRINT NAME: �,�f �1 _ _ DATE: / //o / 201 1
SIGNATURE: DATE: —1111b7
Town of Queensb �uilding Principal Structure Application Revised January 2016
Town of Queensbury Thomas R. Van Ness
Highway Department Highway Superintendent
742 Bay Road, Queensbury, NY 12804 Home: 518-745-0929
Phone: 518-761-8211
Fax: 518-745-4466 David Duell
Deputy Highway Superintendent
Home: 518-745-0938
DRIVEWAY PERMIT p,�r SN-Klcbmt4w 0-"
Date: -3116/ f'D/6
f-CN
Applicant Name: e ;,, mak:;;
Telephone No.: 51$ 79 / '-/6&9
Address to be Inspected �// ;�,, � �-e1v �vrs-r F 55 "14"F
Return Address:
Applicant must show exact location and width of driveway(s) to be connected to the highway by placing stakes
at the specified location
The Superintendent of Highways of the Town of Queensbury has reviewed this application. The following action
has been taken:
STEP 1: O Preliminary approval
NEED ( 1 Slight. Swale �
O Deep Swale
(' ) Level with the road
( ) Level with the top of the paved wing TOWN OF QUEENSBURY
BUILDING & CODES
Size culvert pipe to be used(if necessary)
( ) 12" ( ) 15" ( ) 18" ( ) 24" ( ) 36"
Preliminary inspection completed by: Date: 3117
Approval by Highway Supt.: or Deputy Supt.:
Upon completion please resubmit this approval permit for a final approval.
STEP 2: ( ) Final Approval ( ) Rejected
Date:
Thomas R. Van Ness, Highway Superintendent David Duell, Deputy Highway Superintendent
Town of Queensbury Building&Codes Principal Structure Application Revised January 2016
,. ;.... -.-., .:.,_._ . A�.:..a '�� af`.'•� .,a,$ r �', ✓o w';� '�'-"...�...."-a��w..'*_ �' ,'�'.,,�,:....a'"".,,•, ,r `,r ap pl r
, - l mJ}FD> '.. +s ! •IiI}!.}jR�- :�ii1111., }>. �
:',,., i.•.._'. ..,.:: •. M. k.`.%>. x t!l.r. -r,. .,�,.°laryib ll....vt}}! l w' ''-'e A. gi$t.�.if R!'Rj d'a.,.. Va9�14• a eJr..iyfJ%>'-e'S�... AAi6ATh4V. :iif 3DR�°'L' x 9RYis.�`i� �:::idR=/ / Vjam
s,' � '• -'.,, 9 ... JOi,r taAa� }/JtJ aiS$ ♦++aJ}Jy 9.+ }R}n $ J} ,S•. al yi
��.oo. .��- � _. y.. .?ra Ai$44i !.J. ..�.� i5 R'i: Ji+J� + °�•na i4sa ! /1 l9 i OJla J �n Gal. `'%iji $o�u l }JJ,
Ida
p 17 E'�'�1��11't1€Ar a ha vlrzg srzccescll Bret the r+er�rrZrlt2ents d "�
of the BPI GoIdStar Contractor Pr agr-ariz, be it known that
{ Y
plortb Cal 22ut"tom5s Mverfarmante 12611,hlbioori
r Rocky RUI P-e Road, Warrensburg, -;V-.f .12885 (�
N to aab Otaubing tf I
j
and tfze-re6y becomes a artzr ipant in the B.PJ Gold itar Contractor.Prog-rizin which verifies that
the Leo.?k erfor�fred l� the BPI Goldstar Copatractor cwOorms to the BPI natiowl standards. is \
l •
�� rf✓. a� �;t
(• f� � �f) J� J� tq3 ./.
11•A�1V!'.?• I �qr// �f r
Larry Zarker,Chief Executive Officer
�ad yn,7 kr s i P
6P1 C-on1ractor D# 1 X172965
D BPI GoIdOLar
rI,r�dal•i a�n'�Y.�\+l4V'.d i,i'� L�e-lf�y1il!>y/yJ�>I!r•J"};"�m..J!J.�.•�./l.,.,a.{yy4h4.sa.�is_�a!i iai;°q.ia!aS�si 4s°„ ",:��s\.sldDi}Da+-/1/f!my'!i},i F}s,y}}/s},J+-•�t�.r:x o+�:b.iea.iv9m,Yt3+'aria°�L�',�.Sm$i,a%1.'+_a.-'x- �'x�`'s+._!4r+.�}>i>�!�s!a!F>y.9+lt/mf1.p•.4,l�Ril.rte'�~.y e.•s.ai1?�i,,;1a1:1li�1:"�i:.is"iS.�.i°.;'i.•.`,.'..l.,. 's-J:Rti:J'..J_'.�•p1.l'';'o�1.+J!P'`�/y}I!5!Y):1!J,JJJ:�v•,".:.'.a.;♦ia\ial�l\>\�.1a.S„.S.AW-1
!r':..al.V•?iii.a4`i.1ia1\$9iiP C0NTRACTOR FILE C -
-A'!
iA$ . 'yR.t}}fJ+dR`}+m}J;♦}f S.✓Jttx:•' '•:a.tip1l:si?1A♦<aq1 a3YaAy°.y� yJi+f./9'''s,slJa.r%t�e. . e'8�.-,;,}i�[�N�"`yi'r1`��,^lJ':%,Y+:tv.r�t.�'��:«e!"i`r/1it
�
tiv .
405336
Specification Da 016-01 r
FLEX 100HOY CO.,,
fLE �j[�O.�• CS CERTIFlED
Heat Recovery Ventilator
Product #: 44001
Fans
Two(2)factory-balanced fans with backward curved blades. Motors come
with permanently lubricated, sealed ball-bearings to guarantee long life
N f and maintenance-free operation.
Heat Recovery Core
Aluminum heat recovery core covered by a limited lifetime warranty. Core
dimensions are 8.5"x 8.5"(216 x 216 mm)with a 12"(305 mm)depth.
Our heat exchangers are designed and manufactured to withstand
extreme temperature variations.
WinterguardTm Defrost
i The FLEX 100H incorporates a unique and quiet internal recirculation
defrost that does not depressurize the home during the defrost cycle.A
preset defrost sequence is activated when the outdoor temperature falls
below 23° F(-5°C)and automatically adjusts itself based on operating
As Fantech's masterpiece of versatility, features and efficiency, the Flex conditions.The fan speed is also adjusted automatically to provide a
100H is ideal for high-rise apartment applications, condominiums, single smooth and quiet transition between Ventilation&Defrost mode.
and multi family homes. With its compact top port design featuring 5 Serviceability
inch oval collars and the included EZ-MountTM wall bracket, the Flex Core, filters, fans and electronic panel can be accesses easily from the
100H can be installed in spaces as small as 24 inches, such as a closet access panel. Core conveniently slides out with only 14"1356 mm)
or maintenance room. clearance.
Unlike traditional HRVs that require excessive power to meet Duct Connections
supplemental ventilation needs, the compact, yet powerful Flex 100H 5"(125mm) Oval plastic duct connections with integrated balancing
allows for sizing based entirely on principal ventilation requirements. damper and airflow measurement ports.
With its exclusive TurboTouchTM feature, the Flex 100H can deliver up to
50%more exhaust capacity to easily meet supplemental ventilation Case
needs whenever additional airflow is required. 24 gauge galvanized steel. Baked power-coated paint for a superior
adhesion and resistance.
Features
• TurboTouch function boosts exhaust capacity by up to 50% Insulation
• 5" (125mm) oval duct connections with integrated airflow Cabinet is fully insulated with 1"(25 mm)high density expanded
measurement polystyrene.
• Removable screw terminal for easy connection Filters
• Lightweight: only 39 lbs (17.7 kg) including core Two (2)washable electrostatic panel type air filters 8.5" (216mm)x
• Super compact size 12.5" (318 mm)x 0.125"(3mm).
• Top port design fits in tight spaces
• Includes EZ-Mount wall bracket Drain
• Aluminum heat recovery core 1/2"(13mm) OD(outside diameter)drain spout provided, entire bottom
• Multiple speed operation of unit covered by drain pan.
• Internal recirculation defrost
Warranty
Optional Controls: Limited lifetime on aluminum core, 7 year on motors, and 5 year on parts.
• ECO-TOUCH8(#44929( — Programmable Touch Screen Wall Control
• EDF7 (#44883) — Electronic multi-function dehumidistat
• RTS2 (#40164( — 20 minute timer over-ride
• RTS5 (#447941 — 20/40/60 minute timer
• MDEH1 (#40172( — Dehumidistat
Specifications
• Duct size — 5"(125mm)oval
• Voltage/Phase — 120/1
• Power rated — 168 W
• Amp — 1.4 A
• Average airflow — 105 cfm (50 Vs)
@ 0.4"PS(100Pa)
fantech
a systemair company
Dimensions&Airflow
E F t
T r fresh air
to inside
o C fresh air
from outside
stale air
from inside
stale air
to outside
®®®®®®®®®®®®®
Flex 100H 21 1/2 546 141/2 368 155/8 397 177/8 454 221/2 572 15 381
Cir ienal Informatitn r,ur vrres.Uaarnn,e A 14"t3!j6mrnl in front of the unit ierecommended fur i einval
of core.All units feature three foot plug-in power cord with 3-prong plug.
Airflow(Us)
Ventilation Performance
0 12 24 35 47 59 71 82 94
1.2 300
' ITurbo Reduced Speed
1.0 Med Speed250
0
x Normal SpeedNet supply airflow 146(69) 129(61) 116(55) 105(49) 96(45) 88(411 80(381 73(34)
Gross supply airflow 148(70) 132(621 118(56) 107(501 97(46) 89(42) 82(39) 74(35) = 0.8 200 a
Gross exhaust airflow 148(70) 133(63) 120(571 107(511 95(45) 85(40) 73(35) 63(30)
2 0.6 150 'm
"Turho Mode is an intermittent made only It can be activated with the RTS2,RTS5 and the ECO Touch for up to 60 minutes. CL m
Only the data of the normal speed are HVI certified 2 a
. 0.4 1 2 3 4 100
63
0.2 50
0 25 50 75 100 125 150 175 200
Airflow(cfm)
Energy performance
MSupply temperature Consumed power Sensible recovery Apparent sensible Latent recovery/moisture
efficiency effectiveness transfer
32 0 52 24 46 70 80 -0.08
32 0 69 33 56 67 75 -0.06
32 0 99 47 102 64 73 -0.04
-13 -25 72 34 69 66 78 0.00
Requirements and standards
• Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
• Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
• Complies with the CSA F326 requirements regulating the installation of Heat Recovery Ventilators
• Technical data was obtained from published results of test relating to CSA C439 Standards
• HVI certified and ENERGY STAR®qualified*
[1_da
Contacts Distributed by:
Submitted by Date:
Quantity Model: Project#:
Comments:
Location:
Architect:
Engineer Contractor:
United States 10048 Industrial Blvd.•Lenexa KS 66215 1.800 747.1762•www.fantech.net
fantech0
Canada 50 Kanalflakt Way•Bouctouche,NB E4S 3M5 1 800.565 3548•www fantech.net •�
,ot:rr� .z ias a igot r. �dity,at n� i�'a a 1 ..r;ut� '_ _mj , iii .°,�s, � i�•.::
rents and specifications to maintain their technological leadership position. •;;
a systemair company
Manual S Compliance Report Job: 7
Date: Jan 06,2017
Entire House By: SCOTT LANGWORTHY
NYRP
WARRENSBURG,NY 12885
Project •
For: WHITING
49 WALKUP RD, QUEENSBURY, NY 12804
Cooling Equipment
Design Conditions
Outdoor design DB: 85.0°F Sensible gain: 14715 Btuh Entering coil DB: 0°F
Outdoor design WB: 71.0°F Latent gain: 363 Btuh Entering coil WB: 0°F
Indoor design DB: 75.0°F Total gain: 0 Btuh
Indoor RH: 50% Estimated airflow: 677 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: CQ��
Manufacturer: Model: RLE
L
Actual airflow: 677 cfm
Sensibly:capacity: 0 Btuh 0% of load
Latent capacity: 0 Btuh 0% of load
Total capacity: 0 Btuh 0% of load SHR: 0%
EquipmentHeating
Design Conditions
Outdoor design DB: -4.0°F Heat loss: 39023 Btuh Entering coil DB: 70.0°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Gas boiler
Manufacturer: BOSCH Model: ZBR16
Actual airflow: 0 cfm
Output capacity: 52000 Btuh 133% of load
Meets are all requirements of ACCA Manual S.
2017-Jan-25 09:18:31
* wrightsoft® Right-Suite®Universal 2017 17.0.16 RSU25i16 page 1
...Cott.IangsworthylDccuments\YorkIWHITINGNYRP.rup Calc=MJ8 Front Door faces: N
Form
Residential Review •
RIPER 1
ACCP® for HVAC Systern Design • • 15 Mar 09
Pt cactzr irg omtrackm a knagim
LAKE GEORGE NY
Header Information
Contractor: REQUIRED ATTACHMENTS ATTACHED
Manual J1 Form(and supporting worksheets): Yes ❑ No ❑
Mechanical license: or MJ1AE Form'(and supporting worksheets): Yes ❑ No ❑
OEM performance data(heating,cooling,blower): Yes ❑ No ❑
Building plan#: Manual D Friction Rate Worksheet: Yes ❑ No ❑
Duct distribution sketch: Yes ❑ No ❑
Home address(Street or Lot#,Block,Subdivision): 49 WALKUP RD, Entire House
HVAC • 40
Design Conditions Building Construction Information
Winter Design Conditions Building
Outdoor temperature: -4 -F Orientation: Front Door faces North
Indoor temperature: 70 ^F North,east,west,south,Northeast,Northwest,Southeast,southwest
Total heat loss: 39023 Btuh Number of bedrooms: 0
Conditioned floor area: 2610 ft2
Summer Design Conditions Number of occupants: 0
Outdoor temperature: 85 °F
Indoor temperature: 75 aF Windows Roor
Grains difference: 28 gr/lb Cp50% RH Eave overhang depth: 0 ft
Sensible heat gain: 16350 Btuh Internal shade: none
Blinds,drapes,etc. Eays
Latent heal gain: 4Q4 Btuh Depth window
Total heat gain: 16753 Btuh Number of skylights: 0
EQUIPMENTHVAC •
Heating Equipment Data Cooling Equipment Data Blower Data
Equipment type: Gas boiler ETiEment type: Heating cfm: 0
urnace,He pump,Boiler,etc. Ir ondhioner,Heat pump,etc. Cooling cfm: 677
Model: BOSCH Model Static pressure: 0 in H2O
ZBR16 Fan's rated external static pressure for
design airflow
Heating output capacity: 0 Btuh Total cooling capacity: 0 Btuh
Heat pumps-capacity at winterdestgn outdoor conditions Sensible cooling capacity: 0 Btuh
Aux.heating output capacity: Q Btuh Latent cooling capacity: 0 Btuh
DUCT DISTRIBUTION SYSTEM iESIGN (IRC M1601.11)
Design airflow: fi77 cfm Longest supply duct: 0 ft Duct Materials Used
Equipment design ESP: 0 in H2O Longest return duct: 0 It Trunk duct:
Total device pressure losses: 0 in H2O Total effective length(TEL): 0 ft
Available static pressure(ASP): 0 in H2O Friction rate: $ in/100ft Branch duct: Sheet metal
Friction Rate=ASP=tTEI.x10
I declare the load calculation,eq uipment,equipment selection and duct design were rigorously performed based an the budding
plan listed above. I understand the claims made on these forms will be subject to review and verification.
Contractor's printed name:
Contractor's signature: Date:
Reserved for County,Town Municipality orAuthority having jurisdiction
"Home qualifies for MJ1AE Form based on Abridged Edition Checklist
-P�d-wrightSOW Right-Suite®Universal 2017 17.0.16 RSU25116
i
i
Pro ect Summar Job:
' � y J Date: an 06,2017
Entire House By: SCOTT LANGWORTHY
NYRP
I
WARRENSBURG,NY 12885
-Proiect Information
For: WHITING
49 WALKUP RD, QUEENSBURY, NY 12804
Notes:
Design Information
Weather: Glens Falls AP, NY, US
Winter Design Conditions Summer Design Conditions
Outside db -4 OF Outside db 85 OF
Inside db 70 OF Inside db 75 OF
Design TD 74 OF Design TD 10 OF
Daily range M
Relative humidity 50 %
Moisture difference 28 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 39023 Btuh Structure 14715 Btuh
Ducts 0 Btuh Ducts 0 Btuh
Central vent (0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
none
(none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
E=quipment load 39023 Btuh Use manufacturer's data in
Rate/swing multiplier 0.90
Infiltration Equipment sensible load 13243 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Semi-tight
Fireplaces 0 Structure 363 Btuh
Ducts 0 Btuh
Central vent (0 cfm) 0 Btuh
Heating Coolin (none)
Area(ft') 2610 261$ Equipment latent load 363 Btuh
Volume ft9) 7830 7830
Air changes/hour 0.28 0.15 Equipment total load 13606 Btuh
Equiv.AVF (cfm) 37 20 Req. total capacity at 0.70 SHR 1.6 ton
Heating Equipment Summary Cooling Equipment Summary
Make BOSCH Make n/a
Trade GREENSTAR Trade n/a
Model ZBR16 Cond n/a
AHRE ref 4444598 Coil n/a
AHR1 ref n/a
Efficiency 95AFUE Efficiency n/a
Heating input 57000 Btuh Sensible cooling 0 Btuh
Heating output52000 Btuh Latent cooling 0 Btuh
Temperature rise 0 OF Total cooling 0 Btuh
Actual air flow 0 cfm Actual air flow 677 cfm
Air flow factor 0 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.98
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
writ htsoft®
2017-Jan-25 09:age I
� Right-Suite®Universal 2017 17A.16 RSU25116 Page i
ACACA ...Cott.langeworthylDocumenislYorkIWHITINGNYRP.rup Calc=MJ6 Front Door faces: N
AED Assessment Job: 7
Date: Jan 06,2017
Entine House By: SCOTT LANGWORTHY
NYRP
WARRENSBURG,NY 12885
Project • •
For: WHITING
49 WALKUP RD, QUEENSBURY,NY 12804
Design Conditions
Location: Indoor: Heating Cooling
Glens Falls AP, NY, US Indoor temperature(°F) 70 75
Elevation: 335 ft Design TD (°F) 74 10
Latitude: 43°N Relative humidity{%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/Ib) 51.8 27.6
Dry bulb(°F) -4 85 Infiltration:
Daily range(°F) - 20 ( M )
Wet bulb(°F) - 71
Wind speed (mph) 15.0 7.5
Test forAdequate Exposure
Hourly Glazing Load
18,000-
16,000 -
14,000
m
12,000
10,000
m
8,000
6,000
4,000
2,000
0
8 9 10 11 12 13 14 15 16 17 18 19 20
Hour of Day
/ Haudy /Average / AED fimit
Maximum hourly glazing load exceeds average by 26.0%.
House has adequate exposure diversity (AED), based on AED limit of 30%.
AED excursion: 0 Btuh
wri htsoft' 2017-Jan-25 D9:18:31
9 Right-Suiten Universa]2017 17.D.16 RSU25116
cott.tang eworthy\Documents%York\WH[TIN GNYRP.rup Calc=MJ8 Front Door faces: N Page 1
Right-M Worksheet Job: 7
Entire House Date: Jan 06,2017
NYRP By: SCOTT LANGWORTHY
WARRENSBURG,NY 12885
1 Room name Entire House Rcom1
2 Exposed wall 396.0 ft 140.0 ft
3 Room height 9.0 ft d 9.0 ft heat/cool
4 Room dimensions 1.0 x 1158.0 ft
5 Room area 2610.0 ft' 1168.0 fl'
Ty Construction U-value Or HTM Arear (ftp Load
number (Btuh/ft2°F (Btuh+ft� or perimeter (ft) (Btuh) orperimeter (ft) (Stuh)
Heat Cool Gross N/PIS Heat Cool Grass N!P/S Heat Cool
615613-owc^o 0.093 n 4.77 0.15 1017 949 4524 141 342 342 1679 59
1D-c2ov 0.570 n 42.18 16.36 68 01 2868 1112 0 0 0 0
15613-Dwc-6 0.093 a 4.59 0.12 765 659 3026 82 288 288 1414 50
iD-c2ov 0.570 e 42.18 5B.17 64 0 270D 3723 0 0 0 0
11 D 11 P O 0.290 a 21.45 6.23 42 42 901 262 0 0 0 0
UtJ 15813-Owc� 0.093 s 4.16 0.07 1017 736 3072 48 342 195 667 0
!L_G. 1Dc2ov 0.570 s 42.18 30.57 132 0 5568 4035 0 0 0 0
D 11100 0.290 s 21,46 6.23 147 147 3155 917 147 147 3155 917
W 15813-DNC-6 0.093 w 4.80 0.15 765 725 3480 112 28B 288 1414 50
1--G 1 D,2ov 0.570 w 42.18 58.17 40 0 1687 2327 0 0 0 0
C 16B-30ad 0.032 - 2.37 1.44 1210 1210 2865 1742 62 62 147 89
F 21A-24t 0.025 - 1.85 0.00 1168 1168 2161 0 1168 1168 2161 0
F 21A-24t 0.025 - 1.85 0.00 42 42 78 0 0 0 0 0
6 c)AED excursion 0 -64
Envelope losslgain 36084 14502 10636 1101
12 a) Infiltration 2939 213 1039 75
b) Room ventilation 0 0 0 0
13 Intemal gains: Occupants @ 230 0 0 0 0
Appliances/other 01 0
Subtotal(lines 6 to 13) 39023 14715 11674 1176
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution D 0 0 0
14 Subtotal 39023 14715 11674 1176
15 Duct loads 0% 0% 0 0 -0% 0% 0 0
Total room load 39023 14715 1 11674 1176
Air required(cfm) 0 677 0 54
_ Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
Q -PV Wrlghtsoft` Right•Sulteb Universal 2017 17.0.16 RSU25116 2017-Jan-25 09:18:31
Atm` ...cott.langeNorthy\DocurnentskYork\WHITINGNYRP.rup Calc=MJ8 Front Doorfaces: N Page 1
Right-J®Worksheet Job: 7
Entire House Date: Jan 06,2017
By: SCOTT LANGWORTHY
NYRP
I WARRENSBURG,NY 12885
1 Room name Room2 Room3
2 Exposed wall 26.0 ft 9.0 It
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 10.0 x 12.0 ft 4.0 x 8.0 ft
ft
5 Room area 120.0 ft' 32.0 ft'
Ty Construction Ll-value Or HTM Area ' r� (ftp} Load
number (Btuh/ft�°F) (stuh/ft) or perimeter (ft) (Btuh) or
perimeter (ft) (Btuh)
Heat Cool Gross NIP/S Heat Cool Gross N/PIS Heat Cool
6151313-Owc-6 0.093 n 4.77 0.15 90 78 359 9 36 36 177 6
1 D-c2ov 0.570 n 42.18 16.36 12 0 506 196 0 0 0 0
UI! 11B13-Owc-6 0.093 a 4.59 0.12 36 15 32 0 9 9 44 2
FL--_-_G 1 D-02ov 0.570 a 42.18 58.17 0 0 0 0 0 0 0 0
11 D 11P0 0.290 a 21.46 6,23 21 21 451 131 0 0 0 0
15B 13-Owc-6 0.093 s 4.16 0.07 0 0 0 0 36 36 177 6
1 D-020v 0.570 s 42.18 30.57 O 0 0 0 0 0 0 p
D 11 P O 0.290 s 21.46 6.23 0 0 0 0 0 0 0 0
IW 15B13-0wc-6 0.093 w 4.80 0.15 108 96 448 12 0 0 0 0
L-G 1D-C2ov 0.570 w 42.18 58.17 12 0 506 698 0 0 0 0
C 1613-30ad ao32 - 2.37 1.44 0 0 0 0 0 0 0 0
F 21A-24t 0.025 - 1.85 0.00 0 0 0 0 0 0 0 0
F 21A-24t 0.025 - 1.85 0.00 0 0 0 0 0 0 0 0
6 c)AED excursion 275 1
Envelope losslgain 2302 1322 398 13
12 a) Infiltration 193 14 67 5
b) Room ventilation 0 0
0 0
13 Internal gains: Occupants @ 230 0 p p 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 2495 1336 464 18
Less external load 0 0 0 0
less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 2495 1336 464 18
15 Duct loads -0% 0% 0 0 0% 0% 0 0
Total room load 2495 1336 464 8
Air required(cfm) 0 61 0 11
7
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed
wrightsoft® Right-Suite®Universal 2017 17.0.16 RSU25116 2017-Jan-25 09:18:31
'`CC4'` ...cott.langeworthylDocuments\Yorkc WHITINGNYRP.rup Calc=MJ8 Front Door faces: N Page 2
Right-JO Worksheet Job: 7
Entre House Date: Jan 06,2017
NYRP By: SCOTT LANGWORTHY
WARRENSBURG,NY 12885
1 Room name Room4 Room5
2 Exposedwall 24.0 ft 23.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 12.0 x 7.0 ft 12.0 x 9.0 ft
5 Room area 84.0 ft2 106.0 ft2
Ty Construction U-value Or HTM Area (W) Load (W) Load
number (Btuh/ft?°F) (Btuh/ft� or perimeter r r (ft) (Bt orperimeter (ft) (Bt h)
Heat Cool Gross N/P!S Heat Cool Gross N/P/S Heat Cool
6 1013-0wc-6 0.093 n 4.77 0.15 108 96 448 12 108 96 448 12
1D-c2ov 0.570 n 42.18 16.36 12 0 506 196 12 0 506 196
15613-0wc-6 0.093 a 4.59 0.12 0 0 0 0 81 60 253 3
10-c2ov 0.570 e 42.18 58.17 0 0 0 0 0 0 0 0
17 D 11PO 0.290 a 21.45 6.23 0 0 0 0 21 21 451 131
i5B13-Owc-6 0.093 s 4.16 0.07 108 108 530 19 0 0 a o
1 D-c2ov 0.570 s 42.18 30.57 0 0 0 0 0 0 0 0
D 11P0 0.290 s 21.46 6.23 0 0 0 0 0 0 0 0
IWI - 15613-0wc 6 0.093 w 4.80 0.15 0 0 0 0 18 18 88 3
�--G 1 D-c2ov 0.570 w 42,18 58.17 0 0 0 0 0 0 0 0
C 166-30ad -0.032 - 2.37 1.44 35 35 83 50 108 108 256 156
F 21A-24t 0.025 - 1.85 0.00 0 0 0 0 D 0 0 0
F 21A-24t 0.025 - 1.85 0.00 0 0 0 0 0 0 0 0
i
6 c)AED excursion -15 -27
Envelope loss/gain 1567 263 2002 475
12 a) Infiltration 178 13 171 12
b) Room ventilation 0 01 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Applianceslother 0 0
Subtotal(lines 6 to 13) 1745 276 1 2172 487
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 1745 276 2172 487
15 Dct loads -0% 0% 0 0 -0% 0% 0 0
rrATAil'rt.r'e�q-L�,,-,d'-(ofm)
ad 1745 276 2172 487
0 13 0 22
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed
wrightSOft' 2017-jan-26 09:18:31
Right-Sulfe�Universal 2077 17.0.16 RSU25116 Page&
...coft.langeworthylDocumentslYork\WHITINGNYRP.rup Calc=MJB Front Door faces: N
Right-J®Worksheet Job: 7
Entire House Date: Jan 06,2017
NYRP By. SCOTT LANGWORTHY
WARRENSBURG, NY 12885
1
I 1 Room name Room6
i 2 Exposed wall Room?
68.0 ft 32.0 ft
3 Room height 9.0 ft heaucool 9.0 ft heat/cool
4 Room dimensions 1.0 x 546.0 ft 12.0 x 18.0 ft
5 Room area 546.0 ft2 216.0 ft'
Ty Construction U-value Or HTMArea (ft') Load Area (ftp Load
number (Btuh/ft'°F) (BtulVft') or perimeter (ft) (Btuh) or
perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 15B13-Wvc-6 0.093 n 4.77 0.15 126 126 618 22 18 18 88 3
10-c2ov 0.570 n 42.18 16.36 0 0 0 0 0 0 0 0
V}J 15613.Owc8 0.093 a 4.59 0.12 207 175 796 19 0 0 0 0
II-`D 1 D-c2ov 0.570 a 42.18 58.17 32 0 1350 1861 0 0 0 0
11 D 11P0 0.290 a 21.46 6.23 0 0 0 0 0 0 0 0
iQJ 15813 W✓c-6 0.093 S 4.16 . 0.07 234 162 653 3 108 96 44B 12
{l-_�p 1 Dc2ov 0.570 s 42.18 30.57 72 0 3037 2201 12 0 506 367
11PO 0.290 S 21.46 6.23 0 0 0 0 0 0 0 0
W 15B13-Wuc-6 0,093 w 4.80 0.15 45 45 221 8 162 150 713 22
1D-c2ov 0.570 w 42.18 58.17 0 0 0 0 12 0 506 698
C 166-30ad 0.032 - 2.37 1.44 501 501 1186 721 168 168 398 242
F 21A-24t 0.025 - 1.85 0.00 0 0 0 0 0 0 0 0
F 21A-24t 0.025 - 1,85 0.0D 0 0 0 0 0 0 0 0
e
6 c)AED excursion -34 144
Envelope losslgain 7861 4802 2559 1488
12 a) Infiltration 505 37 237 17
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 8366 4838 2896 1505
Less external load 0 0 0 0
Less transfer 0 D
0 0
Redistribution 0 0 0 0
14 Subtotal 8366 4838 2896 1505
15 Duct loads -0% 0% 0 0 -0% 0% 0 0
Total room load 8366 4838 2896 1505
Air required(cfm) OL- 223 0 69
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed
Awrightsoft- Right-Suttee Universal 2017 17.0.16 RSU25116 2017-Jan-25 09:18:31
age 4
Cott.lengeworthylDocumentslYork\AHI TIN GNYRP.rup Cato=MJ8 Front Door faces: N
{' Right-J®Worksheet Job; 7
Entire House Date: Jan 06,2017
NYRP By: SCOTT LANGWORTHY
WARRENSBURG,NY 12885
1 Roan name Room8 Room9
2 Exposed wall 11.0 ft 63,0 ft
3 Room height 9.0 ft heaticool 9.0 ft heat/cool
4 Room dimensions 6.0 x 5.0 ft 1.0 x 306.0 ft
5 Room area 30.0 ft' 306.0 ftz
Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load
i
number (Btuh/ft2°F) (Btulvft=) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
I Heat Cool Gross NIP/S Heat Cool Gross N/P/S Heat Cool
6 15613-0wc-6 0.093 n 4.77 0.15 54 38 155 1 135 119 553 15
1 Dc2ov 0.570 n 42.18 16.36 16 0 575 262 16 0 675 262
15B 13-Owc-6 0.093 a 4.59 0.12 0 0 0 0 144 112 487 8
1Dc2ov 0,570 a 42.18 58.17 0 0 0 0 32 0 1350 1861
11 D 11 P O 0.290 a 21.46 6.23 0 0 0 0 0 0 0 0
15B 13-Owc-6 0.093 $ 4.16 0.07 0 0 0 0 189 141 597 8
1 Dc2ov 0.570 s 42.18 30.57 0 0 0 0 48 0 2025 1467
11130 0.290 s 21.46 6.23 0 0 0 0 0 0 0 0
W __ 15B 13-0wc-6 0.093 w 4.80 0.15 45 45 221 6 99 83 376 9
L-G 1 D-c2ov 0.570 w 42.18 58.17 0 0 0 0 16 0 675 931
C 16B-30ad 0.032 - 2.37 1.44 30 30 71 43 306 306 725 441
F 21A-24t 0.025 - 1.85 0.00 0 0 0 0 0 0 0 0
F 21A-24t 0.025 - 1.85 0.00 0 0 0 0 42 42 78 0
6 a)AED excursion -17 -261
Envelope loss/gain 1122 297 7539 4741
12 a) Infiltration 82 6 467 34
b) Room ventilation 0 0 0 0
13 interna gains. Occupants 230 0 0 0 0
Appliances/other 01 1 0
Subtotal(lines 6 to 13) 1203 303 8006 4775
Less external toad 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 1203 303 8006 4775
15 Duct loads -0% 0% 0 0 -0% 0% 0 0
Total room toad 1203 303 8006 4775
Air required(cfm) 0 14
0 220
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed
-Fkwrightsoft® 2017-Jan-25 09:18:31
�--�A Right-Suite�3 Universal 2017 17.0.16 RSU25116 Page 5
,.cott.langeworthy4Documents\YorkIWHITINGNYRP.rup Calc=MJ8 Front Door faces: N
f /
F.W. Webb Company Quote
3 Highland Avenue Date Number
Queensbury, NY 12804 01/06/17 53489514
TEL# (518-792-1316)
FAX# (518-792-1335)
To:
NEW YORK REPLACEMENT PARTS SAME
4033 MAIN ST. 4033 MAIN ST.
WARRENSBURG NY 12885 WARRENSBURG, NY 12885
(518-623-2900) Fax# (XXX-XXX-XXXX)
Cust ## Customer Po# Rel# Writer Date Req
152756 WHITING SLL 01/06/17
PAGE 1 OF 3
Quoted By: SCOTT LANGWORTHY
*-----------------------------------------------------------------------------*
Quantity Description Net Price Exten Ln#
*-----------------------------------------------------------------------------*
1 * COND BLR GREENSTAR 131 HTR 3086.100 3086.10 ( 1)
BCHZER35-3 (452271)
1 * COND PMP VCMA-20UL AUTO 1/30HP 115V 38 .610 38.61 ( 2)
L/G554421 (50095)
10 PIPE WHT PVC 3/4"x10' S40 0.250 2 .50 ( 3)
P/P34S4010 (111196)
6 * ELL 90DEG PVC 3/4 SOC S40 406-007 0.160 0.96 ( 4)
PVP3490 (16078)
40 PIPE WHT PVC 3"x20' S40 PE 1.430 57.20 ( 5)
P/P3DWV (15265)
6 ELL LS 90DEG 3" PVC HxH 304 6.020 36 .12 ( 6)
PVC3LS90 (36210)
1 ELL ST 45DEG 3" PVC SPGxH 323 3 .970 3.97 ( 7)
PVC3S45 (36227)
1 * VNT KIT CONC TRMTN 3" 31.920 31.92 ( 8)
SORS1-1CT0303 (336300)
1 * TSTAT NPROG 1H 40-90DEG F 22 .440 22.44 ( 9)
HONTH1100DV1000/U (493465)
1 * BLR TRM KIT PUREPRO DLX 1-1/4" 262.230 262.23 ( 10)
PROPPBTK-114DLX (316486)
5 * CIRC PMP OOR CI W/IFC L/FLG KIT 3-SPD 92.370 461.85 ( 11)
TAC0015MSFIFC (370056)
6 * B/V ISOLTR UNI-FLG BRS 3/4" SWTxFLG 15.130 90.78 ( 12)
WBS50403 (247630)
4 * B/V ISOLTR UNI-FLG BRS 1" SWTxFLG 18 .240 72 . 96 ( 13)
WBS50404 (254109)
3 * B/V PRO-PAL BRS 3/4" SWT W/DRN 12 .350 37. 05 ( 14)
WBS50613 (315668)
2 * B/V PRO-PAL BRS 1" SWT W/DRN 17.710 35.42 ( 15)
WBS50614 (315511)
20 TUBE M COP HRD 1-1/4"x20' 3.430 68.60 ( 16)
C/T114M (2564)
20 TUBE M COP HRD 1"x20' 2 .360 47.20 ( 17)
C/T1M (2563)
FILE COPY
r
F.W. Webb Company Quote
3 Highland Avenue Date Number
Queensbury, NY 12804 01/06/17 53489514
TEL# (518-792-1316)
FAX# (518-792-1335)
To:
NEW YORK REPLACEMENT PARTS SAME
4033 MAIN ST. 4033 MAIN ST.
WARRENSBURG NY 12885 WARRENSBURG, NY 12885
(518-623-2900) Fax# (XXX-XXX-XXXX)
Cust # Customer Po# Rel# Writer Date Req
152756 WHITING SLL 01/06/17
PAGE 2 OF 3
Quoted By: SCOTT LANGWORTHY
*-----------------------------------------------------------------------------*
Quantity Description Net Price Exten Ln#
*-----------------------------------------------------------------------------*
40 TUBE M COP HRD 3/4"x20 ' 1.590 63 .60 ( 18)
C/T34M (2562)
2 * MXG VLV LF BRS 3/4" SWT ADJ TEMP GA 93 .180 186 .36 ( 19)
CLF521519A (423293)
2 * MIX VLV 1" SWT W/TEMP GA LF 107.290 214 .58 ( 20)
CLF521619A (425599)
1 * SAFEGUARD 1100 MINI 24V LWCO 73 .060 73 .06 ( 21)
HYL1100 (268513)
1 * SWTCH RLY Z-ONE 6 ZONE PMP CTRL 188.940 188.94 ( 22)
CLFZSR106 (508118)
26 * CLMP 3/8" STL ZN 0.810 21.06 ( 23)
WRP663019-10 (68296)
3 * NAILTITE 3/8" 8.160 24.48 ( 24)
WRP691060-100 (68297)
2 * KIT REPAIR 3/8 ET 660075 11.070 22 .14 ( 25)
WRP660075 (68298)
3 * STPL 3/8" & 1/2" 24.260 72 .78 ( 26)
WRP668018-1660 (68302)
10 * CMPRN FTG 1/2" SS BRS 5.905 59.05 ( 27)
WRPPX690002-10 (244197)
1 * FLOWMTR MNFLD 1" SS M-2 124.400 124.40 ( 28)
WRPD3803002SS (251396)
2 * FLOWMTR MNFLD 1" SS M-3 157.820 315.64 ( 29)
WRPD3803003SS (251397)
2 * FLOWMTR MNFLD 1" SS M-6 267.870 535.74 ( 30)
WRPD3803006SS (251399)
4 * ISO CAP CIRC SS 6 .510 26 .04 ( 31)
WRPD4201700S (251410)
5 * TUBE RADIANT PERT PE 1/21IX300' 91.440 457.20 ( 32)
WRP81016323 (472728)
5 * MNFLD KIT 1" W/TRUNK ISO B/V SS 92 .730 463 .65 ( 33)
WRPDK1000 (368185)
13 * RDNT TBNG ONIX 3/8"x200' EPDM 267.970 3483.61 ( 34)
WRP086061-200 (68292)
F.W. Webb Company Quote
3 Highland Avenue Date Number
Queensbury, NY 12804 01/06/17 53489514
TEL# (518-792-1316)
FAX# (518-792-1335)
To:
NEW YORK REPLACEMENT PARTS SAME
4033 MAIN ST. 4033 MAIN ST.
WARRENSBURG NY 12885 WARRENSBURG, NY 12885
(518-623-2900) Fax# (XXX-XXX-XXXX)
Cust # Customer Po# Rel# Writer Date Req
152756 WHITING SLL 01/06/17
PAGE 3 OF 3
Quoted By: SCOTT LANGWORTHY
*-----------------------------------------------------------------------------*
Quantity Description Net Price Exten Ln#
*-----------------------------------------------------------------------------*
200 RDNT STICK TBNG RADIANTPEX 3/4"x20' P 0.740 148 . 00 ( 35)
WRPPB81007368 (318652)
120 RDNT STICK TBNG RADIANTPEX 1"x20' PE 1.180 141.60 ( 36)
WRPPB81007367 (318653)
1 #MISC. MATERIAL + 900.000 900.00 ( 37)
MISMATERIAL (S751840)
Sub Total: 11877.84
Tax: 0.00
Total: 11877.84
*** NUMBER OF DAYS QUOTE VALID IS 15 ***
PLEASE REFERENCE QUOTE # 53489514 FOR INQUIRIES OR ORDER OF ABOVE MATERIAL
+ THIS PRODUCT IS A SPECIAL ITEM. RESTOCKING FEES MAY APPLY.
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Project Information Contact Information Project Assumptions
Project Number Designed By Outdoor Temp -20°F
Project Quote Company Name Elevation 328 ft
Project Name New Project Phone Number Wind Speed 6 mph
Designed For , FILE COPY
Job Type Residential
Glens Falls,NY
Pump Specs
Zone Name Flow Head Delta T Supply Fluid Temp
Zone 1 4.9 GPM 9.5 ft 20 107.1 °F
Zone 2 1.4 GPM 6 ft 20 143.6°F
Zone 3 0.8 GPM 3.9 ft 20 126°F
Zone 4 1.7 GPM 3.8 ft 20 128.9°F
Zone 5 2 GPM 9.8 ft 20 180°F
Heated Area Descriptions
Application Construction Heated Area Product Totals
Zone 1 — Room List(BASEMENT)
Radiant Heating Slab 1168 ft2 (5)250'Lengths of 1/2"
Cable Ties RadiantPERT
Zone 2 — Room List(MASTER BED,GUEST,LAUNDRY)
Radiant Heating UnderFloor 368 ft2 (3)200'Lengths of 3/8"
Staples&5%NailTites Onix
Zone 3 — Room List(BATH,MUD)
Radiant Heating UnderFloor 204 ft2 (2)180'Lengths of 3/8"
Staples&5%NailTites Onix
Zone 4 — Room List(LIVING)
Radiant Heating UnderFloor 616 ft2 (5)200'Lengths of 3/8"
Staples&5%NailTites Onix
Zone 5 — Room List(CUPOLA)
Radiant Heating UnderFloor 336 ft2 (3)180'Lengths of 3/8"
Staples&5%NailTites Onix
Heating Load Summary
Tube Back/Edge Total Total
Spacing Intensity Losses Required Provided Supp.
(in) (BTU/h•ft2) (BTU/h•ft2) (BTU/h) (BTU/h) Needed
Zone 42528 42688
BASEMENT 12 36.41 5.41 42528 42688
NY RP.rad C,ryright(c)Watts Radiant 2068 Page;;of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Zone 2 9776 9899
MASTER BED 8 27.61 12.03 5964 5678 YES
GUEST 8 28.1 15.35 3372 3103 YES
LAUNDRY 8 13.74 9.97 440 1118
Zone 3 5015 5294
BATH 8 23.02 10.85 1934 2209
MUD 8 25.68 13.76 3081 3085
Zone 4 13125 13148
LIVING 8 21.31 6.99 13125 13148
Zone 5 13588 13125
CUPOLA 8 40.44 21.53 13588 13125 YES
Project Summary
Total Flow: 10.8 GPM
Total System Head: 9.8 ft
Boiler Load: 108195 BTU/h
Total System Volume: 28 Gallons
Total Heated Area: 2692 ft2
Please verify all project information for accuracy.
Signature: Date:
NYRP.rad Copyright(c;1.7atts Radiant 2008 Page 15 of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Project Information Contact Information Project Assumptions
Project Number Designed By Outdoor Temp -20°F
Project Name New Project Company Name Elevation 328 ft
Designed For Phone Number Wind Speed 6 mph
Job Type Residential
Glens Falls,NY
Design
Application: Radiant Heating Supply Fluid Temp: 107.1 °F
Product: 1/2"RadiantPERT Delta T: 20°F
#of Circuits: 5 Flow: 4.88 GPM
Circuit Length: 250 ft Head: 9.5 ft
Manifold Distance: 0 ft Radiant Capacity: 42688 BTU/h
Heated Area: Required Heat: 42528 BTU/h
Panel Load: 48849 BTU/h
%Glycol: 0%
Construction -Slab
Slab Thickness: 4 in Thickness Above Tube: 2 in
Slab Conductivity: 0.81 BTU/(h•ft•°F)
BASEMENT (Zone 1)
Floor Coverings Quantity Area R-Value Infiltration Total Heat Loss
No Floor Covering R-0
Walls Quantity Area R-Value Infiltration Total Heat Loss
Wall 1 1 1260 ft2 R-3 0.06 32477 BTU/h
Doors Quantity Area R-Value Infiltration Total Heat Loss
Door 1 1 21 ft2 R-2 0.095 976 BTU/h
Door 2 1 63 ft2 R-2 0.095 2928 BTU/h
Windows Quantity Area R-Value Infiltration Total Heat Loss
No Windows 0 0 ft2 R-0 0 int
Ceilings Quantity Area R-Value Infiltration Total Heat Loss
No Ceilings 0 0 ft2 R-0 0 int
NYRP.rad Copyright(c)Watts Radi?nt 2008 Page 1 of 15
RadiantWorks Professional RadiantWorks Reports 1i6i2017
Skylights Quantity Area R-Value Infiltration Total Heat Loss
No Skylights 0 0 ft2 R-0 0 int
BASEMENT Heat Loss Summary
2.7%
No Floor Covering
8.0% M Wall 1
Door 1
0.0% 0 Door 2
No Windows
89.3% No Ceilings
EM No Skylights
Zone Notes:
NYRP.rad Copyright(c)Wafts Radiant 2008 Page 2 of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Design
Application: Radiant Heating Supply Fluid Temp: 143.6°F
Product: 3/8"Onix Delta T: 20°F
#of Circuits: 3 Flow: 1.4 GPM
Circuit Length: 200 ft Head: 6 ft
Manifold Distance: 0 ft Radiant Capacity: 9898 BTU/h
Heated Area: Required Heat: 9776 BTU/h
Panel Load: 13980 BTU/h
%Glycol: 0%
Construction - UnderFloor
Joist Spacing: 16 in Subfloor Thickness: 0.75 in
Subfloor Conductivity: 0.085 BTU/(h•ft-°F)
(ZoneMASTER BED
Floor Coverings Quantity Area R-Value Infiltration Total Heat Loss
Hardwood-3/4":R-0.90 R-0.9
Walls Quantity Area R-Value Infiltration Total Heat Loss
Wall 1 1 240 ft2 R-17 0.06 1195 BTU/h
Windows Quantity Area R-Value Infiltration Total Heat Loss
Window 1 4 15 ft2 R-1.41 0.016 3273 BTU/h
Ceilings Quantity Area R-Value Infiltration Total Heat Loss
Ceiling 1 1 216 ft2 R-38 0 497 BTU/h
Doors Quantity Area R-Value Infiltration Total Heat Loss
No Doors 0 0 ft2 R-0 0 int
Skylights Quantity Area R-Value Infiltration Total Heat Loss
No Skylights 0 0 ft2 R-0 0 in
NY RP.rad Copyright(c)Watts Radiant 2008 Page 3 of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
MASTER BED Heat Loss Summary
65.9
10.0% Hardwood-3/4": R-0.90
Wall 1
0.0
Window 1
[ Ceiling 1
No Doors
No Skylights
24.1 %
(ZoneGUEST
Floor Coverings Quantity Area R-Value Infiltration Total Heat Loss
Hardwood-3/4":R-0.90 R-0.9
Walls Quantity Area R-Value Infiltration Total Heat Loss
Wall 1 1 176 ft2 R-17 0.06 982 BTU/h
Windows Quantity Area R-Value Infiltration Total Heat Loss
Window 1 2 15 ft2 R-1.41 0.016 1636 BTU/h
Ceilings Quantity Area R-Value Infiltration Total Heat Loss
Ceiling 1 1 120 ft2 R-38 0 276 BTU/h
Doors Quantity Area R-Value Infiltration Total Heat Loss
No Doors 0 0 ft2 R-0 0 int
NYRP.rad Copyrig^t;c)Wafts Radiant 2008 Page 4 of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Skylights Quantity Area R-Value Infiltration Total Heat Loss
No Skylights 0 0 ft2 R-0 0 int
GUEST Heat Loss Summary
56.5
Hardwood-3/4": R-0.90
9.5% M Wall 1
,.� Window 1
0.0% Ceiling 1
No Doors
No Skylights
33.9%
LAUNDRY
Floor Coverings Quantity Area R-Value Infiltration Total Heat Loss
Tile-w/Mudset:R-0.15 R-0.15
Walls Quantity Area R-Value Infiltration Total Heat Loss
Wall 1 1 32 ft2 R-17 0.06 264 BTU/h
Ceilings Quantity Area R-Value Infiltration Total Heat Loss
Ceiling 1 1 32 ft2 R-38 0 74 BTU/h
Windows Quantity Area R-Value Infiltration Total Heat Loss
No Windows 0 0 ft2 R-0 0 int
NYRP.rad Copyright(c)Watts radiant 2008 Page 5 of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Doors Quantity Area R-Value Infiltration Total Heat Loss
No Doors 0 0 ft2 R-0 0 int
Skylights Quantity Area R-Value Infiltration Total Heat Loss
No Skylights 0 0 ftz R-0 0 int
LAUNDRY Heat Loss Summary
21.8%
Tile-w/Mudset:R-0.15
Wall 1
0.0% Ceiling 1
[ No Windows
No Doors
No Skylights
78.2%
Zone Notes:
Design
Application: Radiant Heating Supply Fluid Temp: 126°F
Product: 3/8"Onix Delta T: 20°F
#of Circuits: 2 Flow: 0.76 GPM
Circuit Length: 180 ft Head: 3.9 ft
Manifold Distance: 0 ft Radiant Capacity: 5294 BTU/h
Heated Area: Required Heat: 5015 BTU/h
Panel Load: 7579 BTU/h
%Glycol: 0%
Construction - UnderFloor
Joist Spacing: 16 in Subfloor Thickness: 0.75 in
Subfloor Conductivity: 0.085 BTU/(h-ft.°F)
:A (Zone
Floor Coverings Quantity Area R-Value Infiltration Total Heat Loss
Tile-w/Mudset:R-0.15 R-0.15
Walls Quantity Area R-Value Infiltration Total Heat Loss
Wall 1 1 96 ft' R-17 0.06 588 BTU/h
NYRP.rad Copyright(c)Watts Radiant 2,T3 Page of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Windows Quantity Area R-Value Infiltration Total Heat Loss
Window 1 2 7.5 ft2 R-1.41 0.016 828 BTU/h
Ceilings Quantity Area R-Value Infiltration Total Heat Loss
Ceiling 1 1 84 ft2 R-38 0 193 BTU/h
Doors Quantity Area R-Value Infiltration Total Heat Loss
No Doors 0 0 ft2 R-0 0 int
Skylights Quantity Area R-Value Infiltration Total Heat Loss
No Skylights 0 0 ft2 R-0 0 int
BATH Heat Loss Summary
51.4
12.0% M Tile-w/Mudset:R-0.15
Wall 1
0.0% Window 1
Ceiling 1
No Doors
No Skylights
36.6%
(ZoneMUD
Floor Coverings Quantity Area R-Value Infiltration Total Heat Loss
Tile-w/Mudset:R-0.15 R-0.15
Walls Quantity Area R-Value Infiltration Total Heat Loss
Wall 1 1 120 ft2 R-17 0.06 624 BTU/h
Windows Quantity Area R-Value Infiltration Total Heat Loss
Window 1 1 15 ft2 R-1.41 0.016 818 BTU/h
Doors Quantity Area R-Value Infiltration Total Heat Loss
Door 1 1 21 ft2 R-2 0.095 976 BTU/h
Ceilings Quantity Area R-Value Infiltration Total Heat Loss
Ceiling 1 1 120 ft2 R-38 0 276 BTU/h
NYRP.rad Copyrig,�(c}Watts Radiant 2008 Page 7 of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Skylights Quantity Area R-Value Infiltration Total Heat Loss
No Skylights 0 0 ft2 R-0 0 int
MUD Heat Loss Summary
36.2%
max` Tile-w/Mudset:R-0.15
10.2% Wall
0.0% Window 1
Door 1
Ceiling 1
No Skylights
30.4% 23.2%
Zone Notes:
NYRP.rad Copyright(c)Watts Radiant 2008 Page 8 of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Design
Application: Radiant Heating Supply Fluid Temp: 128.9°F
Product: 3/8"Onix Delta T: 20°F
#of Circuits: 5 Flow: 1.74 GPM
Circuit Length: 200 ft Head: 3.8 ft
Manifold Distance: 0 ft Radiant Capacity: 13148 BTU/h
Heated Area: Required Heat: 13125 BTU/h
Panel Load: 17431 BTU/h
%Glycol: 0%
Construction - UnderFloor
Joist Spacing: 16 in Subfloor Thickness: 0.75 in
Subfloor Conductivity: 0.085 BTU/(h•ft•°F)
LIVING • -
Floor Coverings Quantity Area R-Value Infiltration Total Heat Loss
Hardwood-3/4":R-0.90 R-0.9
Walls Quantity Area R-Value Infiltration Total Heat Loss
Wall 1 1 408 ft2 R-17 0.06 1754 BTU/h
Windows Quantity Area R-Value Infiltration Total Heat Loss
Window 1 5 15 ft2 R-1.41 0.016 4091 BTU/h
Window 2 2 9 ft2 R-1.41 0.016 990 BTU/h
Doors Quantity Area R-Value Infiltration Total Heat Loss
Door 1 1 42 ft2 R-2 0.095 1952 BTU/h
Ceilings Quantity Area R-Value Infiltration Total Heat Loss
Ceiling 1 1 546 ft2 R-38 0 1256 BTU/h
Skylights Quantity Area R-Value Infiltration Total Heat Loss
No Skylights 0 0 ft2 R-0 0 int
NYRP.rad Copyrigiit(c)Watts Radiant 2uu8 Page 9 of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
LIVING Heat Loss Summary
19.4%
9.9%
Hardwood-3/4": R-0.90
E
12,5% Wall 1
Window 1
0.0% Window 2
Door 1
Ceiling 1
17.5% RM No Skylights
40.7%
Zone Notes:
Design
Application: Radiant Heating Supply Fluid Temp: 180°F
Product: 3/8"Onix Delta T: 20°F
#of Circuits: 3 Flow: 2.04 GPM
Circuit Length: 180 ft Head: 9.8 ft
Manifold Distance: 0 ft Radiant Capacity: 13125 BTU/h
Heated Area: Required Heat: 13588 BTU/h
Panel Load: 20357 BTU/h
%Glycol: 0%
Construction - UnderFloor
Joist Spacing: 16 in Subfloor Thickness: 0.75 in
Subfloor Conductivity: 0.085 BTU/(h-ft-°F)
CUPOLA
Floor Coverings Quantity Area R-Value Infiltration Total Heat Loss
Hardwood-3/4":R-0.90 R-0.9
Walls Quantity Area R-Value Infiltration Total Heat Loss
Wall 1 1 592 ft2 R-17 0.06 2639 BTU/h
Windows Quantity Area R-Value Infiltration Total Heat Loss
Window 1 8 20 ft2 R-1.41 0.016 8695 BTU/h
Ceilings Quantity Area R-Value Infiltration Total Heat Loss
Ceiling 1 1 336 ft2 R-38 0 773 BTU/h
NYRP.rad Copyright(c)Watts Radiant 2uO8 Page 10 of 15
RadiantWorks Professional RadiantWorks Reports 1/6/2017
Doors Quantity Area R-Value Infiltration Total Heat Loss
No Doors 0 0 ft2 R-0 0 int
Skylights Quantity Area R-Value Infiltration Total Heat Loss
No Skylights 0 0 ft2 R-0 0 int
CUPOLA Heat Loss Summary
71.8%
Hardwood-3/4": R-0.90
6.4% ® Wall 1
IIIIIIIIIIIIEWindow 1
0.0% Ceiling 1
No Doors
No Skylights
21.8%
Zone Notes:
Project Heat Load Summary
9% 12%
13%
Zone 1
27% Zone 2
Zone 3
Zone 4
Zone 5
39%
Project Notes:
Please verify all project information for accuracy.
Signature: Date:
NYRP.rad Cop;right(c)Watts Radiant 2008 Page 11 of 15
Project Summa Job: 7
Date: Jan 06,2017
Enure House By:
NYRP
WARRENSBURG,NY 12885
Prooect Information
For: whiting
Notes:
Design Information
Weather: Glens Falls AP, NY, US
Winter Design Conditions Summer Design Conditions
Outside db -4 OF Outside db 85 OF
Inside db 70 OF Inside db 75 OF
Design TD 74 OF Design TD 10 OF
Daily range M
Relative humidity 50 %
Moisture difference 28 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 39023 Btuh Structure 14715 Btuh
Ducts 0 Btuh Ducts 0 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
(none)
0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 39023 Btuh Use manufacturer's data n
Rate/swing multiplier 0.90
Infiltration Equipment sensible load 13243 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Semi-tight
Fireplaces 0 Structure 363 Btuh
Ducts 0 Btuh
Central vent (0 cfm) 0 Btuh
Heating Cooling (none)
Area(ftp 2610 2610 Equipment latent load 363 Btuh
Volume(ft') 7830 7830
Air changes/hour 0.28 0.15 Equipment total load 13606 Btuh
Equiv.AVF (cfm) 37 20 Req. total capacity at 0.70 SHR 1.6 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make
Trade Trade
Model Cond
AHRI ref Coil
AHRI ref
Efficiency 80AFUE Efficiency 0 SEER
Heating input 0 Btuh Sensible cooling 0 Btuh
Heating output0 Btuh Latent cooling 0 Btuh
Temperature rise 0 OF Total cooling 0 Btuh
Actual air flow 677 cfm Actual air flow 677 cfm
Air flow factor 0.017 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.98
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
Wrl 17t5Oft® 2017-Jan-06 10:age 1
9 Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1
ACCK ...cott.lanoeworthv\Documents\Yor4`WHITINGNYRP.rup talc=MJ8 Front Door faces: N
AED Assessment Job: 7
Date: Jan 06,2017
Entire House By:
NYRP
WARRENSBURG, NY 12885
Project • •
For: whiting
Design Conditions
Location: Indoor: Heating Cooling
Glens Falls AP, NY, US Indoor temperature(°F) 70 75
Elevation: 335 ft Design TD (°F) 74 10
Latitude: 430N Relative humidity (%) 50 50
Outdoor: Heating Cooling Moisture difference (gr/Ib) 51.8 27.6
Dry bulb (°F) -4 85 Infiltration:
Daily range(°F) - 20 ( M )
Wet bulb (°F) - 71
Wind speed (mph) 15.0 7.5
Test for Adequate Exposure
Hourly Glazing Load
18,000
16,000
14,000
m
12,000
0 10,000
0
m
C p
_@ ,000
6,000--
4,000--
2,000-
8
,0004,0002,0008 9 10 11 12 13 14 15 16 17 18 19 20
Hour of Day
/ Hourly / Average / AED limit
Maximum hourly glazing load exceeds average by 26.0%.
House has adequate exposure diversity (AED), based on AED limit of 30%.
AED excursion: 0 Btuh
Wrl htsoft• 2017-Jan-0610:43:28
9 Right-Suite®Universal 2017 17.0.16 RSU25116
�� ...cott.langeworthy\Documents\York\WHITINGNYRP.rup Calc=MJ8 Front Door faces: N Page 1
Right-J®Worksheet Job: 7
Entire House Date: Jan 06,2017
NYRP By.
WARRENSBURG, NY 12885
1 Room name Entire House Room1
2 Exposed wall 396.0 ft 140.0 ft
3 Room height 9.0 ft d 9.0 ft heat/cool
4 Room dimensions 1.0 x 1168.0 ft
5 Room area 2610.0 ft2 1168.0 ft'
Ty Construction U-value Or HTM Area (ft') Load Area (ft2) Load
number (Btuh/ft'°F) (Btuh/ft') or perimeter (ft) (Btuh) or
perimeter (ft) (Btuh)
Heat Cooi Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�/ 15B 13-Owc-6 0.093 n 4.77 0.15 1017 949 4524 141 342 342 1679 59
I G 1Dc2ov 0.570 n 42.18 16.36 68 0 2868 1112 0 0 0 0
W 15613-0wc-6 0.093 e 4.59 0.12 765 659 3026 82 288 288 1414 50
LG 1D-c20v 0.570 e 42.18 58.17 64 0 2700 3723 0 0 0 0
1 1 D 11 P O 0.290 e 21.46 6.23 42 42 901 262 0 0 0 0
15B13-Owc-6 0.093 s 4.16 0.07 1017 738 3072 48 342 195 667 0
1 D-c2ov 0.570 s 42.18 30.57 132 0 5568 4035 0 0 0 0
D 11P0 0.290 s 21.46 6.23 147 147 3155 917 147 147 3155 917
W 15813-0wc-6 0.093 w 4.80 0.15 765 725 3480 112 288 288 1414 50
1 D-c2ov 0.570 w 42.18 58.17 40 0 1687 2327 0 0 0 0
C 16B-30ad 0.032 2.37 1.44 1210 1210 2865 1742 62 62 147 89
F 21A-24t 0.025 1.85 0.00 1168 1168 2161 0 1168 1168 2161 0
F 21A-24t 0.025 1.85 0.00 42 42 78 0 0 0 0 0
6 c)AED excursion 0 -64
Envelope loss/gain 36084 14502 10636 1101
12 a) Infiltration 2939 213 1039 75
b) Room ventilation 0 0 0 0
13 1ntemal gains Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 39023 14715 11674 1176
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 39023 14715 11674 1176
15 Duct loads 0/ Oo/ 0 0 -0% 0% 0 0
Total room load 39023 14715 11674 1176
Air required(cfm) 677 677 203 54
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrightsoft' 2017-Jan-0610:43:28
Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1
colt iangeworthy\Documents\York\WH171NGNYRP.rup �,alc=M.18 Front Door}aces: N
Right-J®Worksheet Job: 7
Entire House Date: Jan 06,2017
NYRP By:
WARRENSBURG, NY 12885
1 Room name Rocm2 Room3
2 Exposed wall 26.0 ft 9.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 10.0 x 12.0 ft 4.0 x 8.0 ft
5 Room area 120.0 ft2 32.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft') Load
number (Btuh/ftz°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 Wi15B13-4wc-6 0.093 n 4.77 0.15 90 78 359 9 36 36 177 6
C, 1 D-c2ov 0.570 n 42.18 16.36 12 0 506 196 0 0 0 0
IW 15813-Owc-6 0.093 e 4.59 0.12 36 15 32 0 9 9 44 2
C, 1 D-c2ov 0.570 e 42.18 58.17 0 0 0 0 0 0 0 0
11 III D 11P0 0.290 e 21.46 6.23 21 21 451 131 0 0 0 0
15813-Owc-6 0.093 s 4.16 0.07 0 0 0 0 36 36 177 6
1 D-c2ov 0.570 s 42.18 30.57 0 0 0 0 0 0 0 0
D 11 P O 0.290 s 21.46 6.23 0 0 0 0 0 0 0 0
W 15B 13-Owc-6 0.093 w 4.80 0.15 106 96 448 12 0 0 0 0
1-G 1 D-c2ov 0.570 w 42.18 58.17 12 0 506 698 0 0 0 0
C 16B-30ad 0.032 2.37 1.44 0 0 0 0 0 0 0 0
F 21A-24t 0.025 1.85 0,00 0 0 0 0 0 0 0 0
F 21A-24t 0.025 - 1.85 0.00 0 0 0 0 0 0 0 0
6 c)AED excursion 275 -1
Envelope loss/gain 2302 1322 398 13
12 a) Infiltration 193 14 67 5
b) Room ventilation 0 0 0 0
13 Intemal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 2495 1336 464 18
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 2495 1336 464 18
15 Duct loads 1 -0% 0% 0 0 -0%10% 0 0
Total room load 2495 1336 464 18
Air required(cfm) 43 61 8 1
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
.4C�P w�ig1ltSOfC 2017-Jan-06 10:age 2
Right-Suite®Universal 2017 17.0.16 RSU25116 Page 2
._cott.Iangeworthylflocuments\York\WHITINGNYRP.rup Calc=MJ8 Frort Door faces: N
Right-J®Worksheet Job: 7
Entire House Date: Jan 06,2017
NYRP By:
WARRENSBURG, NY 12885
1 Room name Ro0m4 Room5
2 Exposed wall 24.0 ft 23.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 12.0 x 7.0 ft 12.0 x 9.0 ft
5 Room area 84.0 ft2 108.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/t2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 % 15613-0wc-6 0.093 n 4.77 0.15 108 96 448 12 108 96 448 12
1 D-c2ov 0.570 n 42.18 16.36 12 0 506 196 12 0 506 196
W 15813-0wc-6 0.093 e 4.59 0.12 0 0 0 0 81 60 253 3
1 D-c2ov 0.570 e 42.18 58.17 0 0 0 0 0 0 0 0
11 D 11 P O 0.290 e 21.46 6.23 0 0 0 0 21 21 451 131
15B 13-0wc-6 0.093 s 4.16 0.07 108 108 530 19 0 0 0 0
JD1 D-c2ov 0.570 s 42.18 30.57 0 0 0 0 0 0 0 0
11 P O 0.290 s 21.46 6.23 0 0 0 0 0 0 0 0
W 15813-0wc-6 0.093 w 4.80 0.15 0 0 0 0 18 18 88 3
1 D-c2ov 0.570 w 42.18 58.17 0 0 0 0 0 0 0 0
C 16B-30ad 0.032 2.37 1.44 35 35 83 50 108 108 256 156
F 21A-24t 0.025 1.85 0.00 0 0 0 0 0 0 0 0
F 21A-24t 0.025 1.85 0.00 0 0 0 0 0 0 0 0
6 c)AED excursion -15 -27
Envelope loss/gain 1567 263 2002 475
12 a) Infiltration 178 13 171 12
b) Room ventilation 0 0 0 0
13 Intemal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 17451 276 2172 487
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 1745 276 2172 487
15 Duct loads -0°/ 0% 0 0 -0%10%1 01 0
Total room load 1745 276 2172 487
Air required(cfm) 30 13 38 22
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrightsoft- 2017-Jan-06 10:43:28
Right-Suite®Universal 2017 17.0.16 RSU25116 Page e 3
cott.langeworthy\Documents\York\WHITINGNYRP.rup .alc=MJ3 Front Door races: N
Right-J®Worksheet Job: 7
Entire House Date: Jan 06,2017
By:
NYRP
WARRENSBURG,NY 12885
1 Room name ROom6 Room7
2 Exposed wall 68.0 ft 32.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 1.0 x 546.0 ft 12.0 x 18.0 ft
5 Room area 546.0 ft2 216.0 ft2
Ty Construction U-value Or HTM Area (W) Load Area (ft') Load
number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 IW 151313-0wc-6 0.093 n 4.77 0.15 126 126 618 22 18 18 88 3
�--G 1 D-c2ov 0.570 n 42.18 16.36 0 0 0 0 0 0 0 0
WI _ 15B13-0wc-6 0.093 e 4.59 0.12 207 175 796 19 0 0 0 0
1 D-c2ov 0.570 e 42.18 58.17 32 0 1350 1861 0 0 0 0
11 D 11 P O 0.290 e 21.46 6.23 0 0 0 0 0 0 0 0
15B13-Owc-6 0.093 s 4.16 0.07 234 162 653 3 108 96 448 12
1D-c2ov 0.570 s 42.18 30.57 72 0 3037 2201 12 0 506 367
D 11 PO 0.290 s 21.46 6.23 0 0 0 0 0 0 0 0
W 15813-0wc-6 0.093 w 4.80 0.15 45 45 221 8 162 150 713 22
L-G 1 D-c2ov 0.570 w 42.18 58.17 0 0 0 0 12 0 506 698
C 16B-30ad 0.032 - 2.37 1.44 501 501 1186 721 168 168 398 242
F 21A-24t 0.025 1.85 0.00 0 0 0 0 0 0 0 0
F 21A-24t 0.025 - 1.85 0.00 0 0 0 0 0 0 0 0
6 c)AED excursion -34 144
Envelope loss/gain 7861 4802 2659 1488
12 a) Infiltration 505 37 237 17
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 8366 4838 2896 1505
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 8366 4838 2896 1505
F1
15 Duct loads -0%1 0%1 0 0 -0% 0% 0 0
Total room load 8366 4838 2896 1505
Air required(cfm) 145 223 50 69
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
ja wrightsoft® 2017-Jan-06 10:43:28
Right-Suite®Universal 2017 17.0.16 RSU25116 Page 4
...cott.lanceworthy\Documents\York\\iVHI1 jNGNYRP.rup Calc=MJ8 Front Door races: N
Right-J®Worksheet Job: 7
Entire House Date: Jan 06,2017
NYRP By:
WARRENSBURG,NY 12885
1 Room name Room8 Room9
2 Exposed wall 11.0 ft 63.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 6.0 x 5.0 ft 1.0 x 306.0 ft
5 Room area 30.0 ft2 306.0 ft2
Ty Construction U-value Or HTM Area (W) Load Area (ft2) Load
number (Btuh/W2'F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6VE-G15B 13-Owc-6 0.093 n 4.77 0.15 54 38 155 1 135 119 553 15
1 D-c2ov 0.570 n 42.18 16.36 16 0 675 262 16 0 675 262
W 15B 13-Owc-6 0.093 e 4.59 0.12 0 0 0 0 144 112 487 8
1 D-c2ov 0.570 e 42.18 58.17 0 0 0 0 32 0 1350 1861
11 D 11 P O 0.290 e 21.46 6.23 0 0 0 0 0 0 0 0
15B 13-Owc-6 0.093 s 4.16 0.07 0 0 0 0 189 141 597 8
1 D-c2ov 0.570 s 42.18 30.57 0 0 0 0 48 0 2025 1467
D 11 P O 0.290 s 21.46 6.23 0 0 0 0 0 0 0 0
I
WI - 15B13-0wc-6 0.093 w 4.80 0.15 45 45 221 8 99 83 376 9
L--G 1 D-c2ov 0.570 w 42.18 58.17 0 0 0 0 16 0 675 931
C 1613-30ad 0.032 2.37 1.44 30 30 71 43 306 306 725 441
F 21A-24t 0.025 1.85 0.00 0 0 0 0 0 0 0 0
F 21A-24t 0.025 1.85 0.00 0 0 0 0 42 42 78 0
6 c)AED excursion -17 -261
Envelope loss/gain 1122 297 7539 4741
12 a) Infiltration 82 6 467 34
b) Room ventilation 0 0 0 0
13 Intemal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 1203 303 8006 4775
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 S ubtotal 1203 303 8006 4775
15 Duct loads -0% 01/ 0 0 -0% 0% 0 0
Total room load 1203 303 8006 4775
Air required(cfm) 21 14 139 220
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
.4C k Ad- wrightsoft' 2017-Jan-06 10:43:28
Right-Suite®Universal 2017 17.0.16 RSU25116 Page 5
..cott.:angeworthy\Dccuments\York\WHITINGNYRPriIo Calc=MJ8 Front Door faces. N
1 0
REScheck Software Version 4.6.3 FILE COPY
Compliance Certificate
278.-2-13 RC-000004-2017
Project Whiting Residence Whiting, Kevin & Lynsey
49 Walkup Rd.
Energy Code: 2015 IECC SFD w/FP 1456 s.f., Garage 808 s.f.
Location: Lake George, New York
Construction Type: Single-family n(/
Project Type: New Construction E v
Orientation: Bldg. faces 180 deg. from North U
Conditioned Floor Area: 1,168 ft2 '
Glazing Area 9%
Climate Zone: 6 (7377 HDD) TOWt3 QF QUER�SI3t1RY
Permit Date:
Permit Number:
BUILDING$�CC�DE i
Construction Site: Owner/Agent: Designer/Contractor:
49 Walkup Rd Kevin Whiting Peter Campbell
Lake George, NY 12845 18 Cobblestone Dr. Along The Lake Construction
Queensbury, NY 12804 P.O. Box 124
(518)791-4689 Weavertown, NY 12886
(518)955-7725
Compliance: Passes using UA trade-off
Compliance: 2.7%Better Than Code Maximum UA: 411 Your UA: 400
The a Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.
Envelope Assemblies
Gross Area Cavity Cont.
Perimeter
Ceiling 1: Flat Ceiling or Scissor Truss 1,168 38.0 0.0 0.030 35
Ceiling 2: Flat Ceiling or Scissor Truss 303 38.0 0.0 0.030 9
Wall 1: Wood Frame, 16" o.c. 378 21.0 0.0 0.057 15
Orientation: Front
Door 1: Glass 40 0.300 12
Orientation: Front
Door 2: Glass 40 0.300 12
Orientation: Front
Door 3: Glass 40 0.300 12
Orientation: Front
Wall 2:Wood Frame, 16" D.C. 342 21.0 0.0 0.057 17
Orientation: Back
Window 1: Metal Frame:Double Pane with Low-E 12 0.290 3
Orientation: Back
Window 2: Metal Frame:Double Pane with Low-E 6 0.290 2
Orientation: Back
Window 3: Metal Frame:Double Pane with Low-E 6 0.290 2
Orientation: Back
Window 4: Metal Frame:Double Pane with Low-E 16 0.280 4
Orientation: Back
270 21.0 0.0 0.057 13
Project Title: Whiting Residence Report date: 11/29/16
Data filename: C:\Documents and Setti n gs\H UTZ E\Desktop\CAD\Autocad 2008\WHITING Page 1 of 3
RESIDENCE\ENERGY CODE COMPLIANCE.rck
r �
Gross
Assembly U-Factor UA
or
Perimeter
Window 5: Metal Frame:Double Pane with Low-E 12 0.290 3
Orientation: Left side
Window 6: Metal Frame:Double Pane with low-E 12 0.290 3
Orientation: Left side
Window 7: Metal Frame:Double Pane with Low-E 12 0.290 3
Orientation: Left side
Wall 4: Wood Frame, 16"o.c. 270 21.0 0.0 0.057 13
Orientation: Right side
Window 8: Metal Frame:Double Pane with Low-E 12 0.290 3
Orientation: Right side
Window 9: Metal Frame:Double Pane with Low-E 6 0.290 2
Orientation: Right side
Window 10: Metal Frame:Double Pane with Low-E 6 0.290 2
Orientation: Right side
Door 4: Solid 20 0.230 5
Orientation: Right side
Wall 5: Wood Frame, 16" o.c. 152 21.0 0.0 0.057 7
Orientation: Front
Window 11: Metal Frame:Double Pane with Low-E 8 0.290 2
Orientation: Front
Window 12: Metal Frame:Double Pane with Low-E 8 0.290 2
Orientation: Front
Window 13: Metal Frame:Double Pane with Low-E 8 0.290 2
Orientation: Front
Wall 6: Wood Frame, 16"o.c. 152 21.0 0.0 0.057 8
Orientation: Back
Window 14: Metal Frame:Double Pane with low-E 8 0.290 2
Orientation: Back
Window 15: Metal Frame:Double Pane with Low-E 8 0.290 2
Orientation: Back
Wall 7: Wood Frame, 16" o.c. 128 21.0 0.0 0.057 7
Orientation: Left side
Window 16: Metal Frame:Double Pane with Low-E 8 0.290 2
Orientation: Left side
Wall 8:Wood Frame, 16" o.c. 128 21.0 0.0 0.057 6
Orientation: Right side
Window 17: Metal Frame:Double Pane with Low-E 8 0.290 2
Orientation: Right side
Window 18: Metal Frame:Double Pane with Low-E 8 0.290 2
Orientation: Right side
Wall 9: Solid Concrete or Masonry:lnterior Insulation 460 21.0 0.0 0.056 17
Orientation: Front
Door 5: Solid 72 0.110 8
Orientation: Front
Door 6: Solid 72 0.110 8
Orientation: Front
Door 7: Solid 20 0.230 5
Orientation: Front
Wall 10: Wood Frame, 16" o.c. 380 21.0 0.0 0.057 22
Orientation: Back
Wall 11: Wood Frame, 16" o.c. 300 21.0 0.0 0.057 17
Orientation: Left side
Wall 12:Wood Frame, 16" o.c. 300 21.0 0.0 0.057 17
Orientation: Right side
Floor 1: Slab-On-Grade:Heated 135 10.0 0.684 92
Insulation depth: 4.0'
Project Title: Whiting Residence Report date: 11/29/16
Data filename: C:\Documents and Settings\HUTZE\Desktop\CAD\Autocad 2008\WHITING Page 2 of 3
RESIDENCE\ENERGY CODE COMPLIANCE.rck
Compliance Statement: The proposed building design described here is consistent with the building plans,specifications, and other
calculations submitted with the permit application.The proposed building has been designed to meet the 2015 IECC requirements in
REScheck Version 4.6.3 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Name-Title Signature Date
Q�pE�SS10
Hu
J'l ry0. p519�,
OF N E W
Project Title: Whiting Residence Report date: 11/29/16
Data filename: CADocuments and Setting s\H UTZ E\Desktop\CAD\Autocad 2008\WHITING Page 3 of 3
RESIDENCE\ENERGY CODE COMPLIANCE.rck
� ������������"���� ���=���~�~N =����
Inspection Checklist
U�
�����° n�"mm ���� �m
Energy Code: 2015iEC[
Requirements: 0.096 were addressed directly in the RE5checksoftware
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented' or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Value Value ed Complies? Comments/Assumptions
Sec ion Plans Verified Field Verif!
Pre-inspection/Plan Review
103.1, Construction drawings and ElComplies
103,2 documentation demonstrate E]Does Not
[PR111 energy code compliance for the
building envelope,Thermal E]Not Observable
envelope represented on E]Not Applicable
1103.1, Construction drawings and ElComplies
103.2, documentation demonstrate
E]Does Not
'403.7 energy code compliance for
[PR311 fighting and mechanical systems. F]Not Observable
Systems serving multiple E]Not Applicable
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
Heating and cooling equipment is Heating: Heating: OComplies
403.7 sized per ACCA Manual S based Btu/hr Btu/hr— []Does Not
[PR2]2 on loads calculated per ACCA Cooling: Cooling: nNot Observable
Manual J or other methods Btu/hr Btu/hr
approved by the code official, ONot Applicable
AdditimnaKCammmnawts/Assummptimms:
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) t 3 -bow Impact(Tle�3)
Project Title: Whiting Residence Report date: 01/20/17
Data filename: CADucumentsand Setdngs\HUTZE\Oesktnp\CAD\AutocadZOU8VNH|T|NG Page 4oflI
RES|DENCE\ENERGYCODE COMPL|AN[E.rck
Section 1
Plans Verified I Field Verified lies? Comments/Assumptions
# Foundation Inspection I Value Value , Complies?
14-0 2-.-1--.-2--- Slab edge insulation -R-value. R- R- ❑Complies See the Envelope Assemblies
I[FO1]1 ❑ Unheated EJUnheated ❑Does Not table for values.
j ❑ Heated ❑ Heated ❑Not Observable
1 ❑Not Applicable
402.1.2 Slab edge insulation ft ft ❑Complies See the Envelope Assemblies
[F03]1 depth/length. ❑Does Not table for values.
[]Not Observable
❑Not Applicable
303.2.1 A protective covering is installed ❑Complies
[FO11]2 to protect exposed exterior ❑Does Not
insulation and extends a ❑Not Observable
minimum of 6 in, below grade.
❑Not Applicable
Snow-and ice-melting system ❑Complies
1-403.9
[FO12]2 controls installed. ❑Does Not
❑Not Observable
❑Not Applicable -
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 iMedium Impact(Tier 2) 3 1-ow Impact(Tier 3)—
Project Title: Whiting Residence Report date: 01/20/17
Data filename: C:\Documents and Settings\HUTZE\Desktop\CAD\Autocad 2008\WHITING Page 5 ofll
RESIDENCE\ENERGY CODE COMPLIANCE.rck
---
Section—
I # Framing J Rough-In InspectionPians Verified Field Verified Complies? I Comments/Assumptions �
{ Value Value i
402.1.1, Door U-factor. U- U- ❑Complies See the Envelope Assemblies
402.3.4 ❑Does Not table for values.
[FRlh x
❑Not Observable f
_ ❑Not Applicable 1
i402.1.1, Glazing U-factor(area-weighted U- U- ❑Complies See the Envelope Assemblies
402.3.1, average). ❑Does Not table for values.
402.3.3,
402.3.6, ❑Not Observable 1
402.5 ❑Not Applicable
[FR2]1
303.1.3 U-factors of fenestration products ❑Complies
[FR4]1 are determined in accordance ❑Does Not
with the NFRC test procedure or
taken from the default table. ❑Not Observable
❑Not Applicable
402.4.1.1 Air barrier and thermal barrier ❑Complies
[FR23]1 installed per manufacturer's ❑Does Not
instructions.
❑Not Observable
_ ❑Not Applicable
402.4.3 Fenestration that is not site built ❑Complies v �—
[FR20]1 is listed and labeled as meeting ❑Does Not
AAMA/WDMA/CSA 101/I.S.2/A440
or has infiltration rates per NFRC ❑Not Observable
400 that do not exceed code ❑Not Applicable
limits
}402.4.5 IC-rated recessed lighting fixtures ❑Complies
i[FR16]2 sealed at housing/interior finish ❑Does Not
± and labeled to indicate <2.0 cfm
leakage at 75 Pa. ❑Not Observable
1 ❑Not Applicable
403.2.1 Supply and return ducts in attics ❑Complies
[FR12]1 insulated >= R-8 where duct is ❑Does Not
>=3 inches in diameter and >=
R-6 where < 3 inches.Supply and ❑Not Observable
return ducts in other portions of ❑Not Applicable
the building insulated >= R-6 for
diameter>= 3 inches and R-4.2
for<3 inches in diameter.
403.3.3.5 Building cavities are not used as ❑Complies
[FR15]3 ducts or plenums. ❑Does Not 4
[]Not Observable I
[]Not Applicable
403.4 HVAC piping conveying fluids R- R- ❑Complies
j[FR17]2 above 105 4F or chilled fluids ❑Does Not
below 55 QF are insulated to>R-
[]Not❑Not Observable
_❑Not Applicable
403.4.1 Protection of insulation on HVAC ❑Complies
[FR24]1 piping. ❑Does Not
❑Not Observable
❑Not Applicable
1403.5.3 Hot water pipes are insulated to R- R- ❑Complies
[FR18]2 >11-3. ❑Does Not
E
❑Not Observable
❑Not Applicable
��__—_--__ ------
403.6 Automatic Automatic or gravity dampers are ❑Complies
[FR19]2 installed on all outdoor air ❑Does Not
intakes and exhausts.
❑Not Observable
❑Not Applicable
i 1 1 High Impact(Tier 1) ^; 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Whiting Residence Report date: 01/20/17
Data filename: C:\Documents and Setti ngs\H UTZ E\Desktop\CAD\Autoca d 2008\WHITING Page 6 of11
RESIDENCE\ENERGY CODE COMPLIANCE.rck
Additional Comments/Assumptions:
1 1 High Impact(Tier 1) i 2 iMedium Impact(Tier 2) 3 !Low Impact(Tier 3)
Project Title: Whiting Residence Report date: 01/20/17
Data filename: C:\Documents and Settings\HUTZE\Desktop\CAD\Autocad 2008\WHITING Page 7 of 11
RESIDENCE\ENERGY CODE COMPLIANCE.rck
I Section -- ----irvT
s 1 Plans Verified Field Verified
# Insulation Inspection lies? Comments/AlComplies?
& Re ID I Value Value � ,
303.1 All installed insulation is labeled ❑Complies v
[IN13)2 or the installed R-values ❑Does Not j
! provided. ❑Not Observable
❑Not Applicable
402.1.1, Wall insulation R-value.If this is a R- R ❑Complies See the Envelope Assemblies I
402.2.5, mass wall with at least 1/:of the ❑ Wood ❑ Wood ❑Does Not table for values.
402.2.6 wall insulation on the wall
[IN3)1 exterior,the exterior insulation Mass E] mass ❑Not Observable
requirement applies(FR10). [J Steel ❑ Steel ❑Not Applicable
I
303.2 Wall insulation is installed per ❑Complies
[IN4]1 manufacturer's instructions. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 ,Hi h pact-(-T-ie—r1) 2 Medium Impact(Tier 2) 1 3 Low Impact(Tier 3) _!
Project Title: Whiting Residence Report date: 01/20/17
Data filename: C:\Documents and Settings\HUTZE\Desktop\CAD\Autocad 2008\WHITING Page 8 of 11
RESIDENCE\ENERGY CODE COMPLIANCE.rck
` .
PI
0 !on Provisions an Ver
402.1.1, Ceiling insulation R-value. R- R- ElComplies See the Envelope Assemblies
;402.2.1, Wood E] Wood E]Does Not table for values.
E] Steel E] Steel FINot Observable
E]Not Applicable
303.1.1.1, Ceiling insulation installed per ElComplies
i 303.2 manufacturer's instructions. E]Does Not
[F1211 Blown insulation marked every
[]Not Observable
300 ft2.
0Not Applicable
A02.2.3 Vented attics with air permeable ElComplies
[F122]2 insulation include baffle adjacent 0Does Not
to soffit and eave vents that
[]Not Observable
extends over insulation.
E]Not Applicable
402.2.4 Attic access hatch and door R- R- ElComplies
[F1311 insulation �R-value of the []Does Not
adjacent assembly.
E]Not Observable
ONot Applicable
'1402.4.1.2 Blower door test @ 50 Pa. <=5 ACH 50 ACH 50 ElComplies
[FI17]1 ach in Climate Zones 1-2, and E]Does Not
<=3 ach in Climate Zones 3-8.
ONot Observable
E]Not Applicable
'402.4.2 Wood-burning fireplaces have OComplies
[F18]2 tight fitting flue dampers and E]Does Not
outdoor air for combustion.
[]Not Observable
E]Not Applicable
403.2.3 Duct tightness test result of<=4 cfm/100 cfm/100 ElComplies
[F[4]1 cfm/100 ft2 across the system or ft2 ft2 []Does Not
<=3 cfm/100 ft2 without air E]Not Observable
handler @ 25 Pa.For rough-in
tests,verification may need to ONot Applicable
occur during Framing Inspection.
403.3.2 Ducts are pressure tested to cfm/100 cfm/100 ElComplies
[F12711 determine air leakage with ft2 ft2 E]Does Not
either: Rough-in test:Total E]Not Observable
leakage measured with a
pressure differential of 0.1 inch E]Not Applicable
w.g.across the system including
the manufacturer's air handler
enclosure if installed at time of
test. Postconstruction test:Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the entire system
including the manufacturer's air
handler enclosure.
403.3.2.1 Air handler leakage designated OComplies
[F12411 by manufacturer at<=2%of ODoes Not
design air flow. E]Not Observable
ONot Applicable
1403.1.1 Programmable thermostats OComplies
[F1912 installed for control of primary E]Does Not
heating and cooling systems and E]Not Observable
initially set by manufacturer to
code specifications. E]Not Applicable
403.1.2 Heat pump thermostat installed ElComplies
[FIJO]2 on heat pumps. []Does Not
0Not Observable
ONot Applicable
Project Title: Whiting Residence Report date: 01/20/17
Data filename: [A]ocurnentsand Settings\HUTZE\Desktop\CAD\Autocad28U8\NUHOONG Page Qofll
RES|DENCE\ENERGYCODE [OMPL|AN[E.nck
section - -___-_ _ Fii
' Plans Verified eld Verified
Re ,ID
# � Final Inspection Provisions Value Value Complies? Comments/Assumptions
& i
1403.5.1 Circulating service hot water [ Complies
JFI11]2 systems have automatic or ❑Does Not i
accessible manual controls.
❑Not Observable
❑Not Applicable j
:403.6.1 All mechanical ventilation system ❑Complies j
[FI25]2 fans not part of tested and listed ❑Does Not
HVAC equipment meet efficacy +
and air flow limits. ❑Not Observable i
❑Not Applicable
1403.2 Hot water boilers supplying heat ❑Complies {
[F126]2 through one-or two-pipe heating ❑Does Not
systems have outdoor setback
control to lower boiler water []Not Observable
temperature based on outdoor []Not Applicable
temperature.
1403.5.1.1 Heated water circulation systems ❑Complies
(F128]2 have a circulation pump.The []Does Not
system return pipe is a dedicated
return pipe or a cold water supply ❑Not Observable
pipe.Gravity and thermos- ❑Not Applicable
syphon circulation systems are
not present.Controls for
circulating hot water system
pumps start the pump with signal
for hot water demand within the
occupancy.Controls
automatically turn off the pump
when water is in circulation loop
is at set-point temperature and
no demand for hot water exists. `
403.5.1.2 Electric heat trace systems ❑Complies
[F129]2 comply with IEEE 515.1 or UL ❑Does Not
515.Controls automatically
adjust the energy input to the []Not Observable
heat tracing to maintain the ❑Not Applicable
desired water temperature in the
piping.
403.5.2 Water distribution systems that ❑Complies
[F130]2 have recirculation pumps that ❑Does Not
pump water from a heated water
supply pipe back to the heated ❑Not Observable
water source through a cold ❑Not Applicable '
water supply pipe have a
demand recirculation water
system. Pumps have controls
that manage operation of the
pump and limit the temperature
of the water entering the cold
water piping to 1049F.
403.5.4 Drain water heat recovery units ❑Complies
![FI31]2 tested in accordance with CSA ❑Does Not
855.1. Potable water-side
pressure loss of drain water heat ❑Not Observable
recovery units< 3 psi for []Not Applicable
individual units connected to one
or two showers. Potable water-
side pressure loss of drain water
heat recovery units< 2 psi for
individual units connected to
three or more showers.
404.1 75%of lamps in permanent ❑Complies
!(F16]1 fixtures or 75%of permanent ❑Does Not
j fixtures have high efficacy lamps.
Does not apply to low-voltage ❑Not Observable
lighting. ❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)--1
Project Title: Whiting Residence Report date: 01/20/17
Data filename: C:\Documents and Setti ngs\H UTZ E\Desktop\CAD\Autoca d 2008\WHITING Page 10 ofll
RESIDE NCE\ENERGY CODE COMPLIANCE.rck
Section i Plans PlVerified Field Verified '
# I Final Inspection Provisions - Value Value Complies? Comments/Assumptions
c.
&ReID
1404.1.1 Fuel gas lighting systems have ❑Complies !
(FI23]3 no continuous pilot light. ❑Does Not
❑Not Observable
[]Not Applicable
401.3 Compliance certificate posted. ❑Complies
i[FI7]2 ❑Does Not I
❑Not Observable
❑Not Applicable
303.3 Manufacturer manuals for ❑Complies
[FI18]3 mechanical and water heating ❑Does Not
systems have been provided.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions: _
1
High Impact(Tier 1) 2Medium Impact(Tier 2) 3 ,Low Impact(Tier 3)
Project Title: Whiting Residence Report date: 01/20/17
Data filename: C:\Documents and Setting s\H UTZE\Des ktop\CAD\Autoca d 2008\WHITING Page it ofll
RESIDENCE\ENERGY CODE COMPLIANCE.rck