BINS-000932-2019 02142019INSPECTION WORKSHEET (BINS-000932-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0072-2018 Case Module:Permit
Inspection Date:Thu Feb 14, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Insulation
Job Address:Parcel Number:119 SEELYE RD
Queensbury, NY 12804
227.17-1-49
Contact Type Company Name Name
Granted Permission Giordano, Victoria
Architect Dybas, Curtis
Primary Owner Giordano, Victoria
Applicant Giordano, Ken
Engineer Environmental Design Partnership, LLC
Granted Permission Giordano, Ken
Primary Owner Giordano, Ken
Checklist Item Passed Comments
Building Inspector Notes NO 2/14/19 Insulation Not Approved
Remaining Items:
- Provide an updated REScheck for spray foam insulation.
- Seal all narrow stud bays or cracks between studs, around
receptacles and switches, ductwork and at the top and
bottom plates where foam is missing.
- Install Roxul Rock wool insulation equal to the ceiling R
value with a vapor barrier at fireplace chimney 2nd floor.
- Basement Insulation not done.
- Provide certified field report from foam insulation contractor
listing type of foam, R Values and thickness for ceilings, walls
and box sill areas.
- Accessible areas larger than 32 sf will need intumescent
coating applied to foam insulation not covered by 1/2"
sheetrock.
Feb 14, 2019 Page (1)
INSPECTION WORKSHEET (BINS-000932-2019)
Checklist Item Passed Comments
Window Sealing NO
U Factors = .3 cfm for windows, .5 cfm for doors NO
Tyvek or Similar Exterior Sealant NO
Proper Vent, Attic Vent NO
Insulation Residential Check Commercial Check NO 2/14/19 Insulation Not Approved
Remaining Items:
- Provide an updated REScheck for spray foam insulation.
- Seal all narrow stud bays or cracks between studs, around
receptacles and switches, ductwork and at the top and
bottom plates where foam is missing.
- Install Roxul Rock wool insulation equal to the ceiling R
value with a vapor barrier at fireplace chimney 2nd floor.
- Basement Insulation not done.
- Provide certified field report from foam insulation contractor
listing type of foam, R Values and thickness for ceilings, walls
and box sill areas.
- Accessible areas larger than 32 sf will need intumescent
coating applied to foam insulation not covered by 1/2"
sheetrock.
Blower Door Test NO
Combustion Air Supply for Furnace NO
Fresh air supply 3' from grade NO
Duct Insulation - if required in unheated spaces NO
Door / Window Sealed (No Insulation)NO
Tub Shower R-20 with Vapor Barrier NO
Feb 14, 2019 Page (2)
INSPECTION WORKSHEET (BINS-000932-2019)
Checklist Item Passed Comments
Air Barrier behind Knee Walls NO
All Ductwork Sealed Return and Supply NO
Duct Blaster Test for duct work, R-8 NO
All Return Air Hard Duct Work NO
House Wrap Taped at all Seams NO
Feb 14, 2019 Page (3)
O'Brien, John (Inspector)