inspectionsINSPECTION WORKSHEET (FIST-000619-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0005-2019 Case Module:Permit
Inspection Date:Mon Jan 28, 2019 Inspection Status:Failed
Inspector:John O'Brien Inspection Type:Firestopping
Job Address:Parcel Number:75 CAREY RD
Queensbury, NY 12804
308.20-1-3.3
Contact Type Company Name Name
Architect Monarch Design Group LLC
Contractor J. Luke Construction
Applicant J. Luke Construction
Primary Owner Okie Properties, LLC
Granted Permission Okie Properties, LLC
Checklist Item Passed Comments
Building Inspector Notes NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
1/28/19 Sample Fire Caulking at top of tenant separation wall
approved.
Jan 28, 2019 Page (1)
INSPECTION WORKSHEET (FIST-000619-2019)
Checklist Item Passed Comments
Fire separation 1, 2, 3 hour NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
1/28/19 Sample Fire Caulking at top of tenant separation wall
approved.
Penetration sealed NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
Jan 28, 2019 Page (2)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (FIST-000712-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0005-2019 Case Module:Permit
Inspection Date:Fri Feb 1, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Firestopping
Job Address:Parcel Number:75 CAREY RD
Queensbury, NY 12804
308.20-1-3.3
Contact Type Company Name Name
Applicant J. Luke Construction
Primary Owner Okie Properties, LLC
Granted Permission Okie Properties, LLC
Architect Monarch Design Group LLC
Contractor J. Luke Construction
Checklist Item Passed Comments
Building Inspector Notes NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
1/28/19 Sample Fire Caulking at top of tenant separation wall
approved.
1/31/19 Firestopping Partial Approval
- Fire Caulking at Suite 1 side of Demise Wall except over
bathroom area.
Feb 01, 2019 Page (1)
INSPECTION WORKSHEET (FIST-000712-2019)
Checklist Item Passed Comments
Fire separation 1, 2, 3 hour NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
1/28/19 Sample Fire Caulking at top of tenant separation wall
approved.
1/31/19 Firestopping Partial Approval
- Fire Caulking at Suite 1 side of Demise Wall except over
bathroom area.
Penetration sealed NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
Feb 01, 2019 Page (2)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001190-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0005-2019 Case Module:Permit
Inspection Date:Thu Feb 28, 2019 Inspection Status:Failed
Inspector:John O'Brien Inspection Type:Commercial Final Inspection
Job Address:Parcel Number:75 CAREY RD
Queensbury, NY 12804
308.20-1-3.3
Contact Type Company Name Name
Primary Owner Okie Properties, LLC
Applicant J. Luke Construction
Granted Permission Okie Properties, LLC
Architect Monarch Design Group LLC
Tenant Motimac USA
Contractor J. Luke Construction
Checklist Item Passed Comments
Firewalls, 2 Hr, 3 Hr / Fire Dampers / Fire Doors NO
H/C Bathroom Grab Bars /Sinks/Toilets/Mirrors NO
Low flow toilet 1.3 gal/flushing cycle -
showerhead/faucet
NO
Handicapped Service Counters 34 inch NO -Install break room counter with sink as per plan no stove.
Bldg Num or Tenant Address on Bld or Drive NO Install Suite Number
Engineer or Architect Approval NO
Feb 28, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001190-2019)
Checklist Item Passed Comments
Special Inspections NO Submit HVAC Air Balancing Report for Suite #1 & #2
OK to Issue Temporary C/O NO
OK to Issue C/O NO 2/28/19 Final Inspection Not Approved
Remaining Items:
-Submit HVAC Air Balancing Report for Suite #1 & #2
-Install Suite Number
-Install right handed flush handle handicapped toilet.
-Install break room counter with sink as per plan no stove.
-Complete Fire Marshal's Items.
Feb 28, 2019 Page (2)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (FM-001189-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0005-2019 Case Module:Permit
Inspection Date:Thu Feb 28, 2019 Inspection Status:Partial Pass
Inspector:Mike Palmer Inspection Type:OCC-Inspections
Job Address:Parcel Number:75 CAREY RD
Queensbury, NY 12804
308.20-1-3.3
Contact Type Company Name Name
Architect Monarch Design Group LLC
Applicant J. Luke Construction
Granted Permission Okie Properties, LLC
Contractor J. Luke Construction
Tenant Motimac USA
Primary Owner Okie Properties, LLC
Checklist Item Passed Comments
Fire Marshal YES Inspection of Suite 2
Exit Access YES
Exit Enclosure YES
Exit Discharge YES
Locks and Latches YES
Sign: Normal YES
Feb 28, 2019 Page (1)
INSPECTION WORKSHEET (FM-001189-2019)
Checklist Item Passed Comments
Sign: Backup NO Need to verify
Main Aisle Width YES
Secondary Aisle Width YES
Fire Extinguisher Hung NO Need to verify
Inspection of Extinguisher YES
Emergency Lighting Interior NO Need to verify
Clearance to Electrical YES
Electrical Wiring Enclosed/Labeled NO Need permanent labelling
Storage YES
Interior Finishes YES
CO Detectors YES
Clearance to Sprinkler/Ceiling YES
Knox Box: installed/checked YES
Occupancy Cycle YES B
Feb 28, 2019 Page (2)
Patrick Palmer, Mike (Inspector)
INSPECTION WORKSHEET (FM-001225-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0005-2019 Case Module:Permit
Inspection Date:Fri Mar 1, 2019 Inspection Status:Partial Pass
Inspector:Mike Palmer Inspection Type:OCC-Inspections
Job Address:Parcel Number:75 CAREY RD
Queensbury, NY 12804
308.20-1-3.3
Contact Type Company Name Name
Primary Owner Okie Properties, LLC
Contractor J. Luke Construction
Architect Monarch Design Group LLC
Applicant J. Luke Construction
Granted Permission Okie Properties, LLC
Tenant Motimac USA
Checklist Item Passed Comments
Fire Marshal YES Inspection of Suite 2
Exit Access YES
Exit Enclosure YES
Exit Discharge YES
Locks and Latches YES
Sign: Normal YES
Mar 01, 2019 Page (1)
INSPECTION WORKSHEET (FM-001225-2019)
Checklist Item Passed Comments
Sign: Backup NO Need to verify
Main Aisle Width YES
Secondary Aisle Width YES
Fire Extinguisher Hung YES Need to verify
Inspection of Extinguisher YES
Emergency Lighting Interior YES Need to verify
Clearance to Electrical YES
Electrical Wiring Enclosed/Labeled NO Need permanent labelling
3/1. - breaker to test door fixtures is in space 1. Wire
devices to activate in Space 2 service panel
Storage YES
Interior Finishes YES
CO Detectors YES
Clearance to Sprinkler/Ceiling YES
Knox Box: installed/checked YES
Occupancy Cycle YES B
Mar 01, 2019 Page (2)
Patrick Palmer, Mike (Inspector)
INSPECTION WORKSHEET (BINS-001217-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0005-2019 Case Module:Permit
Inspection Date:Fri Mar 1, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Commercial Final Inspection
Job Address:Parcel Number:75 CAREY RD
Queensbury, NY 12804
308.20-1-3.3
Contact Type Company Name Name
Applicant J. Luke Construction
Primary Owner Okie Properties, LLC
Granted Permission Okie Properties, LLC
Architect Monarch Design Group LLC
Contractor J. Luke Construction
Tenant Motimac USA
Checklist Item Passed Comments
Firewalls, 2 Hr, 3 Hr / Fire Dampers / Fire Doors NO
Handicapped Service Counters 34 inch NO -Install break room counter with sink as per plan, range not
allowed. Remove outlet box from break room partition, wiring
and breakers from panel for range.
Bldg Num or Tenant Address on Bld or Drive YES Install Suite Number
Special Inspections NO -Submit HVAC Air Balancing Report for Suite #2
Mar 01, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001217-2019)
Checklist Item Passed Comments
OK to Issue Temporary C/O NO 3/1/19 Final Inspection Partial Approval-Ok to Issue a
Temporary CO!
Conditions
-Submit HVAC Air Balancing Report for Suite #2
-Install break room counter with sink as per plan, range not
allowed. Remove outlet box from break room partition, wiring
and breakers from panel for range.
-Complete outstanding Fire Marshal's item regarding wiring
of emergency lights and exit signs for each individual tenant
space.
OK to Issue C/O NO 2/28/19 Final Inspection Not Approved
Remaining Items:
-Submit HVAC Air Balancing Report for Suite #1 & #2
-Install Suite Number
-Install right handed flush handle handicapped toilet.
-Install break room counter with sink as per plan no stove.
-Complete Fire Marshal's Items.
Mar 01, 2019 Page (2)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (FIST-001138-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0005-2019 Case Module:Permit
Inspection Date:Mon Feb 25, 2019 Inspection Status:Passed
Inspector:John O'Brien Inspection Type:Firestopping
Job Address:Parcel Number:75 CAREY RD
Queensbury, NY 12804
308.20-1-3.3
Contact Type Company Name Name
Tenant Motimac USA
Contractor J. Luke Construction
Architect Monarch Design Group LLC
Applicant J. Luke Construction
Primary Owner Okie Properties, LLC
Granted Permission Okie Properties, LLC
Checklist Item Passed Comments
Building Inspector Notes YES 1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
1/28/19 Sample Fire Caulking at top of tenant separation wall
approved.
1/31/19 Firestopping Partial Approval
- Fire Caulking at Suite 1 side of Demise Wall except over
bathroom area.
2/25/19 Fire Separation Approved - Suite #2 wall between
Suite #1 & Suite #2.
Feb 25, 2019 Page (1)
INSPECTION WORKSHEET (FIST-001138-2019)
Checklist Item Passed Comments
Fire separation 1, 2, 3 hour YES 1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
1/28/19 Sample Fire Caulking at top of tenant separation wall
approved.
1/31/19 Firestopping Partial Approval
- Fire Caulking at Suite 1 side of Demise Wall except over
bathroom area.
2/25/19 Fire Separation Approved - Suite #2 wall between
Suite #1 & Suite #2.
Penetration sealed YES 1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
2/25/19 Fire Separation Approved - Suite #2 wall between
Suite #1 & Suite #2.
Feb 25, 2019 Page (2)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (RPLUM-000833-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0005-2019 Case Module:Permit
Inspection Date:Fri Feb 8, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:75 CAREY RD
Queensbury, NY 12804
308.20-1-3.3
Contact Type Company Name Name
Contractor J. Luke Construction
Applicant J. Luke Construction
Architect Monarch Design Group LLC
Granted Permission Okie Properties, LLC
Primary Owner Okie Properties, LLC
Checklist Item Passed Comments
Building Inspector Notes NO 2/8/19 Plumbing Partial Approval - Sanitary & Water
Remaining Items:
- Need to Install and pressurize vent stack to exterior side
wall termination location.
Rough Plumbing / Nail Plates YES 2/8/19 Plumbing Partial Approval - Sanitary & Water
Remaining Items:
- Need to Install and pressurize vent stack to exterior side
wall termination location.
Plumbing Vent Vents in Place NO 2/8/19 Plumbing Partial Approval - Sanitary & Water
Remaining Items:
- Need to Install and pressurize vent stack to exterior side
wall termination location.
3" Vent Through Roof NO
Feb 08, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-000833-2019)
Checklist Item Passed Comments
Pressure Test YES Sanitary
Air Head YES Head
5 psi or 10 ft. above highest conn. for 15 minutes YES 10 ft head
Pressure Test YES Water
Air Head YES Air
50 P.S.I for 15 minutes YES 100 psi
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO
Feb 08, 2019 Page (2)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-000933-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0005-2019 Case Module:Permit
Inspection Date:Wed Feb 13, 2019 Inspection Status:Passed
Inspector:John O'Brien Inspection Type:Building Insulation
Job Address:Parcel Number:75 CAREY RD
Queensbury, NY 12804
308.20-1-3.3
Contact Type Company Name Name
Contractor J. Luke Construction
Granted Permission Okie Properties, LLC
Architect Monarch Design Group LLC
Applicant J. Luke Construction
Primary Owner Okie Properties, LLC
Checklist Item Passed Comments
Building Inspector Notes YES 2/13/19 Insulation Approved-Interior partitions
Insulation Residential Check Commercial Check YES 2/13/19 Insulation Approved-Interior partitions
Feb 13, 2019 Page (1)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (FIST-000519-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
CC-0005-2019Permit
Case Number:Case Module:
Wed Jan 23, 2019Failed
Inspection Date:Inspection Status:
John O'BrienFirestopping
Inspector:Inspection Type:
75 CAREY RD308.20-1-3.3
Job Address:Parcel Number:
Queensbury, NY 12804
Contact TypeCompany NameName
ArchitectMonarch Design Group LLC
ContractorJ. Luke Construction
Primary OwnerOkie Properties, LLC
Granted PermissionOkie Properties, LLC
ApplicantJ. Luke Construction
Checklist ItemPassedComments
Building Inspector NotesNO1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
Fire separation 1, 2, 3 hourNO1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
Jan 23, 2019Page (1)
INSPECTION WORKSHEET (FIST-000519-2019)
Checklist ItemPassedComments
Penetration sealedNO1/23/19 Firestopping Not Approved- Tenant Separation Wall
Remaining Items:
- Need to fire caulk joint between top of wall and roof panels
both sides of wall.
- Need to fire caulk joints at ends of walls and exterior wall
panels on both sides of wall.
- Seal all wall penetrations with fire caulk on both sides of
wall.
O'Brien, John (Inspector)
Jan 23, 2019Page (2)
INSPECTION WORKSHEET (BINS-000518-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
CC-0005-2019Permit
Case Number:Case Module:
Wed Jan 23, 2019Partial Pass
Inspection Date:Inspection Status:
John O'BrienBuilding Framing
Inspector:Inspection Type:
75 CAREY RD308.20-1-3.3
Job Address:Parcel Number:
Queensbury, NY 12804
Contact TypeCompany NameName
ArchitectMonarch Design Group LLC
ContractorJ. Luke Construction
Primary OwnerOkie Properties, LLC
Granted PermissionOkie Properties, LLC
ApplicantJ. Luke Construction
Checklist ItemPassedComments
Building Inspector NotesNO1/23/19 Framing Partial Approval- Non-bearing Interior
partitions for Bathroom, Mechanical Room, and coffee area.
FramingYES1/23/19 Framing Partial Approval- Non-bearing Interior
partitions for Bathroom, Mechanical Room, and coffee area.
Design Professional Sign-off, if requiredNO
O'Brien, John (Inspector)
Jan 23, 2019Page (1)