inspectionsINSPECTION WORKSHEET (FM-001451-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0028-2019 Case Module:Permit
Inspection Date:Fri Mar 15, 2019 Inspection Status:Passed
Inspector:Mike Palmer Inspection Type:OCC-Inspections
Job Address:Parcel Number:735 GLEN ST
Queensbury, NY 12804
302.6-1-22
Contact Type Company Name Name
Contractor James Cahill & Son Electric Service
Primary Owner Upper Glen Street Assoc., LLC Powers, Steve
Granted Permission Five Guys Burgers and Fries
Applicant RSVT Queensbury LLC
Checklist Item Passed Comments
Fire Marshal YES
Exit Access YES
Exit Enclosure YES
Exit Discharge YES
Locks and Latches YES
Sign: Normal YES
Sign: Backup YES
Mar 15, 2019 Page (1)
INSPECTION WORKSHEET (FM-001451-2019)
Checklist Item Passed Comments
Main Aisle Width YES
Secondary Aisle Width YES
Fire Extinguisher Hung YES Rehang in kitchen
Inspection of Extinguisher YES
Evac Plan YES Rehang
Truss ID Signage YES
Emergency Lighting Interior YES
Emergency Lighting Exterior YES
Clearance to Electrical YES
Electrical Wiring Enclosed/Labeled YES Add all outlet covers
Combustibles in Equipment Rooms YES
Storage YES
Compressed Gas YES
Interior Finishes YES Add all ceiling tiles
CO Detectors YES
Clearance to Sprinkler/Ceiling YES
Mar 15, 2019 Page (2)
INSPECTION WORKSHEET (FM-001451-2019)
Checklist Item Passed Comments
Hood Installation YES
FIRE ALARM Annual YES Need test report based on past alarms
HVAC Shutdown YES
Sprinkler System Annual YES
Sprinkler FDC YES
Kitchen Suppression Semi Annual YES Need to be repaired for full coverage
Hood Cleaning 3-6 Annual YES
Knox Box: installed/checked YES
Occupancy Cycle YES A
Mar 15, 2019 Page (3)
Bill Palmer, Mike (Inspector)
INSPECTION WORKSHEET (BINS-001452-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0028-2019 Case Module:Permit
Inspection Date:Fri Mar 15, 2019 Inspection Status:Passed
Inspector:Dave Hatin Inspection Type:Commercial Final Inspection
Job Address:Parcel Number:735 GLEN ST
Queensbury, NY 12804
302.6-1-22
Contact Type Company Name Name
Applicant RSVT Queensbury LLC
Contractor James Cahill & Son Electric Service
Primary Owner Upper Glen Street Assoc., LLC Powers, Steve
Granted Permission Five Guys Burgers and Fries
Checklist Item Passed Comments
Doors 36 inch wLever Hand Panic Hardware, if
req
YES Repair rear exit door threshold drop to existing sidewalk
Handicapped Bath/Parking Lot Signage YES Install bathroom signs
Final Electrical / Flex Gas Piping Bonded YES Install all outlet covers and main panel covers
OK to Issue C/O YES All items done
Mar 15, 2019 Page (1)
Hatin, Dave (Inspector)
INSPECTION WORKSHEET (FM-001406-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-0028-2019 Case Module:Permit
Inspection Date:Wed Mar 13, 2019 Inspection Status:Partial Pass
Inspector:Mike Palmer Inspection Type:OCC-Inspections
Job Address:Parcel Number:735 GLEN ST
Queensbury, NY 12804
302.6-1-22
Contact Type Company Name Name
Contractor James Cahill & Son Electric Service
Primary Owner Upper Glen Street Assoc., LLC Powers, Steve
Applicant RSVT Queensbury LLC
Granted Permission Five Guys Burgers and Fries
Checklist Item Passed Comments
Fire Marshal YES
Exit Access YES
Exit Enclosure YES
Exit Discharge YES
Locks and Latches YES
Sign: Normal YES
Sign: Backup YES
Mar 13, 2019 Page (1)
INSPECTION WORKSHEET (FM-001406-2019)
Checklist Item Passed Comments
Main Aisle Width YES
Secondary Aisle Width YES
Fire Extinguisher Hung NO Rehang in kitchen
Inspection of Extinguisher YES
Evac Plan NO Rehang
Truss ID Signage YES
Emergency Lighting Interior NO
Emergency Lighting Exterior NO
Clearance to Electrical YES
Electrical Wiring Enclosed/Labeled NO Add all outlet covers
Combustibles in Equipment Rooms YES
Storage YES
Compressed Gas YES
Interior Finishes NO Add all ceiling tiles
CO Detectors YES
Clearance to Sprinkler/Ceiling YES
Mar 13, 2019 Page (2)
INSPECTION WORKSHEET (FM-001406-2019)
Checklist Item Passed Comments
Hood Installation YES
FIRE ALARM Annual NO Need test report based on past alarms
HVAC Shutdown YES
Sprinkler System Annual YES
Sprinkler FDC YES
Kitchen Suppression Semi Annual NO Need to be repaired for full coverage
Hood Cleaning 3-6 Annual YES
Knox Box: installed/checked YES
Occupancy Cycle YES A
Mar 13, 2019 Page (3)