2004-664 TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5902 (518)761-8201
Community Development - Building & Codes (518) 761-8256
CERTIFICATE OF OCCUPANCY
Permit Number: P20040664 Date Issued: Monday, September 26, 2005
This is to certify that work requested to be done as shown by Permit Number P20040664
has been completed.
Tax Map Number: 523400-296-011-0001-042-000-0000
Location: 543 BAY Rd
Owner: ARCANGELA BANNON
Applicant: ARCANGELA BANNON
This structure may be occupied as a:
Commercial Addition By Order of Town Board
TOWN OF QUEENSBURY
Issuance of this Certificate of Occupancy DOES NOT relieve the
property owner of the responsibility for compliance with Site Plan,
Variance, or other issues and conditions as a result of approvals by the Director of Building&Code Enforcement
Planning Board or Zoning Board of Appeals.
TOWN OF QUEENSB.URY
742 Bay Road,Queensbiiiy,NY 12804-5902 (518)761-8201
Community Development-Building&Codes (518) 761-8256
BUILDING PERMIT
Permit Number: P20040664 Application Number: A20040664
Tax Map No: 523400-296-011-0001-042-000-0000
Permission is hereby grained to: ARC;ANCTFLA BANNON
For property located at: 543 BAY Rd
in the Town of Queensbury,to construct or,place
at the above location in accordance with application together with plot plans and other information hereto filed
and approved and in compliance with the NYS Uniform Building Codes and the Queensbury Zoning
Ordinance. j '' 'Tie of Construction Value
Owner Address: ARCANGELA BANNON
543 BAY Rd Commercial Addition $80,000.00
Total Value $80,000.00
QUEENSBURY,'NY 12804
Contractor or Builder's Name /Address ;! ; i, i ,Electrical Inspection Agency
i
it
Plans&Specifications
2004-664
900 SQ FT COMMERCIAL ADDITION .
+
$126.00 PERMIT FEE PAID-THIS PERMIT EXPIRES: Friday, September 30, 2005
(If a longer period is required,an application for an extension rinist be made to the code Enforcement Officer
of the Town of Queensbury before the expiration date.
Dated at the T wn of Que sbury; day, tptember 30, 2004
SIGNED B A id for the Town of Queensbury.
Director of Build, lfig& e Enforcement
Building Perron Applitatiou
Town of Queensbury-Dept of Community Development,742 Bay Road,Quednsbury,NY
( 18)761.8256
A permit must be obtained before beginning construction. Permit File No. rid'
No spection will be made until applicant has received a Feo paid $ -'Div
valid building permit. All applicants' spaces on this Roc.Fee Paid $
application mustbe completed and must appear on the Reviewed By:
Applidation form.
.:7; /)AV1 v 6a9NA/6n/ 41)
Applicant: iAR AI&6i-A BAMAI V Owner: RPCAil7� 1- 6A iZ.—V
w Address: � C L 'MZS Address:,,,ta
Phone#( ) ?. Phone#(, Ld').711- -,(z3 IrJ
Property Location: Lot Number: ;�,/ House Number�-31 16A Y RD A A ,
Subd3visionName:B,QVLoao Q PRoEaLs .ALTax Map Number: :Z 94 ,, //; I - d1 Z.
O FFt CES
o New Building: residence_Lcomaiero1 ='Estimated Market Value of Construction_$ _fO,
c Addition: residence/ ommerc if ah Addition,what will use of new addition be?
o .Alteration: residence! commercial
O Vo change to exterior sire: residence/com'1 '
d Other wcr'k(describe
Check occupancylnformatlon V Floor 2 Floor Other floor Total
Below sq.ft: sq.ft. eq.M Square Fact
o Sin a*47 dwelling
o Two PS&dwellin
o Townhouse
o Multifamily dwelling
#of units
�osioe 1 9 49 v a o
o Mercaat3le
o Msauf3aectutin
0 1 car detached MLO
a 2 oar detached fmge
a 3 car detached Z=Se
a 1 car attached ggage
a 2 oar attached gamge
o . 3 car attached pMe ZOO
0 Storage building
commercial EENSBURY
o Storage building- 8UI ING
resideatiat ;
a O er
What is the proposed height of the structure_._._Q_._feet 0 inches
Will any second-baud or ungraded lumber be used? If so,for what? /1/0
Type of Heating System: electric/ oil / gas/wood / creed hDairbaseboard/other:
Number ofFd�=kgg to be installed 0 Number of j'&*djj=to be installed_0
List below the person(s)responsible for supervision of work as regards to building codes:
Name Address Phone Nutnbor
D NyC /4A,E'4mm7e)&1 io/ FiF . DAN 2 S6 F Z9tij ..�2 7.6
Ean� RM S s .Zt VagRso-V W GF I'5F,?-Ssd c')
Mason e ug,F e CA IS 74AIAI 7 9,:2 -%3'r
Electrician TN Z 18( iT E t_i� 2 7�13 /9 -
Mwb -r ./fReaw-64A a/1vAfoA/ 7ViZ- 773 y
'LUNf3E,� SCv7rG'DP£<fDUSE 45 .YACo6/E RoAD "7Q3 —01114
pleat sign below after you have carelUy read the statement:
To the best of my knowledge the statements contained in this application,together with the plans and specifications
submitted,are a true and complete statement of all proposed work to be done on the described premises and that all
provisions of the Building Code,the Zoning Ordinance and all other laws pertaining to the proposed work shall be complied
ith,w whether specified or noted,and that such work is authorized by the owner; Further,it is understood that Vwe shall
submit,prior to a Certificate of Occupancy or Certificate of Compliance being issued,as requested by the Zoning
Adminiatrator,,o ector of Building attd-R—'odes,as As Balle arVev by a licensed surveyor;drawn to scale,showing actual
location of all ne coastsuctio c� /
Si ! I �'J$nature owners ownar's agents arohitect,contracto
r
DRAFT COPY
(3121103)
CHECKLIST
NYS BUILDING CODE(BC) Building: _
NYS FIRE CODE(FC)
NYS PLUMBING CODE(PC) Location:
NYS MECHANICAL CODE (MC)
NYS FUEL GAS CODE (FGC) Date:
NYS ENERGY CODE (ECC)
Reviewer:
Publication Date: May 2002
COMMERCIAL&
MULTIPLE DWELLING OCCUPANCIES
No. Topic Code Page Required Actual_
Section No. or Allowed
1 Jurisdiction BC-101.2 1
2 Flood Plain BC-1603.1.E 285
3 Separated or Non-Separated BC-302.3 18
Occupancies*
4 Occupancy BC-302 17 �3
5 Type of Construction BC-Table 601 81 5V
6 No. of Sleeping Units/Level BC-202 14&
No, of Units—Total 31
No, of Occupants BC Table 1003.2.2.2 201
7 Covered Malls BC-402 33
Hi-Rise (75'Rule) BG-403 36'
Atriums BC-404 37
8 Basement Definition BC-502.1 71
(See page 8 of this check list)
Legend: NR= Not Required NS= Not Shown NA= Not Applicable
Note: * Non-separated occupancies impose the most restrictive requirements
JAM
Page 1 of 10
• V
No. Topic Code Page Required Actual
Section No. or Allowed
9. Heights & Building Areas
Maximum Tabular Area BC-Table 503 72
Maximum Tabular Height BC-Table 503 72
Maximum Stories BC-Table 503 72 � 3�
Mezzanines BC-505 73
10. Sprinkler System (water) BC-903 168
Basement Sprinkler BC-903.2.10.1 170
Water Source Sprinkler BC-903.3.5 172
Water Source Site FC-508.1 31
11. Frontage&Sprinkler Credits
Area Modifications (calc.) BC-506 74
Height Modifications BC-504 73
12. Height&Area Summary: HtlArea Ht/Area
Tabular Area BC-Table 503 72
Frontage Credit BC-506 74
Sprinkler Credit BC-506.3 75
Total Allowable Area
Max Aggregate Area BC-503.3 73
(Allowable Area/Fir. x No. of
Stories up to 3 maximum)
13. Fire Apparatus Road FC-503A 29
(150'rule) �, ,� lie 908.5' 31
14. Exterior Walls
Distance Separation* BC-Table 602 82
Exterior Wall Openings BC-Table 704.8 87
Parapets BC-704.11 88
Exterior Wall Coverings' BC-Table 1405.2 257
Exterior Wall Finishes BC-Table 1406.2 261
Combustible
*Distance separations are doubled if fire fighting water is not available (FC-508.1.3).
NOTES;
JAM
Page 2 of 10
No. Topic Code Page Required Actual
Section No. or Allowed
15. Fire Rated Construction
Incidental Use Areas BC-Table 302.1.1 17 W/1`
Accessory Occupancy BC-302.2 18
Mixed Occupancy -BC-Table 302.3.3 19
Control Areas BC-414.2 52
Fire Walls BC-705 89
Fire Barrier BC-706 91
Shaft Enclosure BC-707 92
Fire Partition (Tenant Sep.) BC-708 95
Smoke Barriers BC-709 96
Opening Protectives BC Table 714.2 101
Fire Blocking BC-716 107
Draft Stopping BC-716.3 108
16, Space 6W IZOB 25�
Min. Rm. Dimensions j, 9- BC-1207.1 251
Min. Ceiling Height BC-1207.2 251
17. Ventilation (Nat. or Mech.) BC-1202.1 249
18. Light(-Nat. or Mech.) BC-1204.1 250
19. Exits fcerno ,efs j�� 1o0q,
Occupancy Load BC Table 1003.2.2.2 201 04
One Exit Permitted BC Table1005.2.2 224
Stair Enclosure BC-1005.3.2 224
Emergency Egress BC-1009.1 235
Distance of Travel BC-Table 1-004.2.4 .220
Aisle Width BC-1.004.3.1.1 221
Corridor Width BC-1004.3.2.2 221
Capacity of Exits (calc.). BC-Table 1003.2.3 202
Corridor Wall Fire Rating BC Table1004.3.2.1 222
Corridor Dead End BC-1004.3.2.3 222
Door Width BC-1003.3.1.1 208
Door Swing BC-1003.3.1.2 208
Panic Hardware BC-1003.3.1.9 213
20. Stairs
Riser BC-1003.3.3.3 213
Tread BC-1003.3.3.3 213
Width BC-1003.3.3.1 213
Headroom BC-1003.3.3.2 213
Vertical Rise BC-1003.3.3.6 215
Handrails BC-1003.3.3.11 215
26C
Mav gise 12-'t4k " 3 R- 1003.3A, a►s
JAM
Page 3 of 10
No Topic Code Page Required Actual
Section No. or Allowed
-� 21. Structural
Snovw�oading—Ground BC Fig 1608.2 296
Snow Loading—Roof(calc.) ASCE 7-98
Drifting Snow BC-1608.7 295
Ponding BC-1608.3.5 295
Floor Loading BC Table 1607.1 291
Balcony Loading BC-Table 1607.1 291
Wind Loading (calc.) BC-1609 297
Roof
Walls
Windows
Seismic Loading (calc.) BC-1614 315
Foundation Depth BC-1805.2 398
22. Interior Finishes BC-Table 803.4 161
23. Swimming Pools BC-3109 629
24. Sun Rooms BC Appendix 1 693
25. Electrical
Exit Lights or Signs BC-1003.2.10 203
Emergency Lights BC-1003.2.11.2 204
Emergency Power BC-2702 611
General Lighting-Exits-Stairs BC-1003.2.11 204
26. HC ACCESS
Exempt Buildings BC-1104.4 238
Parking BC Table 1106.1 239
Route BC-1104.1 . 238
Entrance BC-1105.1 239
#of Sleeping Rooms BC-Table-1,107.6.1.1 241
#of Dwelling Units BC-1107.6.2 241
Toilet Facilities BC-1109.2 244
Service Counters BC-1109.12.3 246
Areas of Refuge BC-1003.2.13.5 207
Signage
Supplemental HC Req'mts. Appendix E 681
27. SPECIAL INSPECTIONS rBC-1704 379
Notes:
5 k1p L) -e K 4mhcts 64C qr*C1
JAM
Page 4 of 10
No. Topic Code Page Required Actual
Section No. or Allowed
28. Fire Protection Equipment
Central Station Monitoring FC-901.9 52
Sprinkler Systems . FC-903 55
Other Extingushing Syst. FC-904 59
Kitchen Hood Extinguisher FC-609.8 41
Standpipe Systems FC-905 62
Fire Extingushers FC-906 64
Fire Alarm Systems &SD FC-907.2 66
Fire Alarm Boxes+2avaf FC-907.4.1 967.9 72,'73
Smoke Detection FC-907.2.10 68
Hi-Rise Fire Safety FC-907.2.12 69
Visible Alarms FC-Table 907.10.1.2 73
Smoke Control FC-909 75
Smoke Vents FC-910 82
Fire Pumps FC-913 . 85
W sewmed3
29. Plumbing Code
Fixture Count PC-Table 403.1 21
(: 11
hk
Water S11ppIY
Service Pipe Size _ PC-603 33
Fixture Pipe Size PC-603.1 33
Pipe Material PC-Table 605.4 36
Labor Law Art. 10-A UFPBC-904.6 12,340
Pipe Insulation See Energy Code
Backflow Prevention PC-Table 608.1 41
Sprinkler System PC-608.16.4 44
Lawn Irrigation PC-608.16.5 44
Pipe Freezing PC-305.6 14
Sanitary Drainage
Drain Pipe Size PC-Table 709.1 54
Drain Pipe Material PC-702 47
Labor Law Art. 10-A UFPBC-904.6 12,340
Vent Size PC-Table 910.4 63
Pipe Hangers PC-Table 308.5 17
Air Admittance Valves PC-917 67
Notes:
JAM
Page 5 of 10
`f
No. Topic Code Page Required Actual
Section No. or Allowed
30. Mechanical Code
Ventilqtion Rates MC-Table 403.3 24
Propane Below Grade MC-502.8.10.1 31
Dryer Exhaust MG-504 33
Kitchen Exhaust MC-506 34
Kitchen Hoods MC-507 37
Kitchen Make-Up Air MC-508 39
Chimney Termination MC-Table 511.2 41
Air Plenums MC-602 47
Fire&Smoke Dampers MC-607.5.1 52
Combustion Air MC-701 55
Confined Spaces-Def. MC-202 5
31. Fuel Gas Code
Appliance Location FGC-303 18
Combustion Air FGC-304 19
Clearance to Combust. FGC-Table 308.2 25
Pipe Material FGC-403 46
Shut Off Valves FGC-409 53
Chimney Termination FGC-Fig. 503.5A 63
Gas Vent Termination FGC-Fig. 503.6.6 65
Exit Terminal Location FGC-503.8 68
Clothes Dryer Exhaust FGC-613 96
Unvented Room Heaters FGC-620 99
32. Energy Code
Prescriptive Method ECCC-Table 602.1(1) 50
High Truss Credit ECCC-602.1.2 51
Pipe Insulation-Heating ECCC-Table 503.3.3.1 44
Duct Insulation-Heating ECCC-Table 503.3.3.3 45
Pipe Insulation-Hot Water ECCC-Table 504.2 47-
HWH Heat Trap ECCC-504.7 47
COMcheck Computer Software
Compliance Report Required
Notes:
JAM
Page 6 of 10
LIST OF CALCULATIONS THAT MAY BE REQUIRED FOR A COMPLETE CODE REVIEW.
1. Area Increase Based Upon Frontage And Sprinkler Increase.
Frontage'Increase: If= 10b(FIP-0.25)W = Answer in %
30
Note: If=75%when 4 sides accessible&water available
Allowable Area: Aa=AtabJe+ (At,,,p x tf)+LAw x I =Answer in Square Feet
(BC—Pg. 74) 100 100
2. Exit Capacity Calculations (Table 1003.2.3)(BC-Pg. 202)
(Occupancy Load for Exit)x(Egress Width per Occupant)_ (Required Width)
3. Snow Loading Calculations. (ASCE 7-98)(Eq. 7-1)(pg-69)& (Eq. 7-2)(pg-70)
(ASCE=American Society of Civil Engineers)
Pf=0.7CeCtIP9= Flat Roof Snow Load
Where: Pf= Flat Roof Snow Load (Calculated Above,Answer in#per SF)
Ce= Exposure Factor (BC-Table 1608.3.1)(Pg.297)
Ct=Thermal Factor (BC Table 1608.3.2)(Pg.297)
1 = Importance Factor (BC-Table 1604.5)(Pg. 287)
P9 = Ground Snow Load (BC Fig. 1608.2)(Pg.296)
PS=CSPf=Sloped-Roof Snow Load
Where: PS= Sloped-Roof Snow Load
CS= Roof Slope Factor (ASCE 7-98)(Pg. 70)
4. Wind loading calculations. (Refer to Chapter 6 of ASCE 7-98)
5. Seismic Calculations. (See page 10 of this list)
6. COMCheck calculations (For verification of compliance with the Energy Code)
JAM
Page 7 of 10
S. GRADE PLANE: A reference plane representing the average of finished ground level
adjoining the building at exterior walls.Where the finished ground level slopes away from the M
exterior walls, the reference plane shall be established by the lowest points within the area
between the building and the lot line or,where the lot line is more than 6 feet from the building,
between the building and a point 6 feet from the building.
9. MEZZANINE: An intermediate level or levels between the floor and ceiling of any story with
an aggregate floor area of not more than 113rd of the area of the room or space in which the
level or levels are located. (Mezzanine area does not contribute to the building area or the
height in stories but does contribute to the fire area, aggregate area)..
10. SMOKE BARRIER: A continuous membrane, either vertical or horizontal,such as a wall.-
floor,or ceiling assembly, that is designed and constructed to restrict the movement of smoke.
(Required to have a 9 hr Are rating).
11. STORY ABOVE GRADE PLANE: Any story having its finished floor surface entirely above
grade plane, except that a basement shall be considered as a story above grade plane where
the finished surface of the floor above the basement is: 1. More than 6 feet above grade plane
or 2. More than 6 feet above the finished ground level for more than 50% of the total building
perimeter or 3. More than 12 feet above the finished ground level at any point.
JAM
Page 9 of 10
Commercial Final Inspection Report
Office No.: (518)761-8256 Date Inspection r uest e iv ,
Queensbury Building&Code Enforcement Arrive: am/ Depart: -a/pm
742 Bay Road, Queensbury,NY 12804 Inspector's In ' �J
NAME: ` PERM I J' ` �(J j"�
LOCATION: DATE:
COMMENTS:
Y N NA
Chimney/"B"Vent/Direct Vent Location
Plumbing Vent Through Roof 6"/Roof Complete
Exterior Finish Grade Complete 6"in 10' or Equivalent /
Interior/Exterior Guardrails 42 in. Platform/Decks
Interior/Exterior Ballisters 4 in. Spacing Platform/Decks
Stair Handrail 34 in.—38 in./Step Risers 7"/Treads 11"
Vestibules For Exit doors>3000 s . ft.
All Doors 36 in,w/Lever Dandles/Panic Hardware,if required
Exits At Grade Or Platform 36 (w)x 44"(1)/Canopy or Equiv.
Gas Valve Shut-off Exposed&Regulator 18")Above Grade
Floor Bathroom Watertight/Other Floors Oka
Relief Valve,Heat Trap/Water Temp. 110 Degrees Maximum
Boiler/Furnace Enclosure 1 hr. or Fire Extinguishing System
Fresh Air Supply for Occupancy/Ventilation Combustion
Low Water Shut Off For Boilers
Gas Furnace Shut Off Within 30 ft. or Within Line Of Site
Oil'Furnace Shut Off at Entrance to Furnace Area
Stockroom/Storage/Receiving/Shipping Room(2 hr.), 1 '/z doors
> 10%> 1000 sq. ft.
3/a Hour Corridor Doors&Closers
Firewalls/Fire Separation,2 Hour, 3 Hour Complete/Fire
Dampers/Fire Doors
'Ceiling Fire Stopping, 3,000 s . ft.Wood Frame
Attic Access 30"x 20"x 30"(h),Crawl Space Access 18"x 24"
Smoke Vents Or Fan, if required
Elevator Operation and Si a e/Shaft Sealed
Handica ped Bathroom Grab Bars/Sinks/Toilets
Handicapped Bath/Parking Lot Si na e
Public Toilet Room Handicapped Accessible
Handicapped Service Counters, 34 in., Checkout 36"
Handicapped Ramp/Handrails Continuous/12 in.Beyond
Active Listening System and Signage Assembly Space
Final Electrical
Site Plan/Variance required
Final Survey,New Structure/Flood Plain certification,if req.
As-built Septic System Layout Required or On File
Building Number or Tenant Address on Building or Driveway
Water Fountain or Cooler
Building Access All Sides rhea urface 20'wide
Okay To Issue Tem r Permanent C/O
Okay To Issue C/C
Last printod 6/3/2003 9:27 AML:\PamW\Building&Codes\Commercial Final Inspection Report.doc
Commercial.Final Inspection Report J l
Office No.: (518) 761-8256 Date Inspection req st r ve v 16
Queensbury Building&Code Enforcement Arrive: a pm Depart: __4WZawAjm
742 Bay Road,Queensbury,NY 12804 Inspector's Initial
NAME: % /t//1!l/,� PERMIT
LOCATION: DATE: Z
COMMENTS:
Y N NA
Chimney/"B"Vent/Direct Vent Location
Plumbing Vent Through Roof 6"/Roof Complete
Exterior Finish Grade Complete 6"in 10' or Equivalent
Interior/Exterior Guardrails 42 in. Platform/Decks
Interior/Exterior Ballisters 4 in. Spacing Platform/Decks
Stair Handrail 34 in,—3 8 in./Step Risers 7"/Treads 11"
Vestibules For Exit doors>3000 s . ft.
All Doors 36 in.w/Lever Handles/Panic Hardware,if required
Exits At Grade Or Platform 36 (w)x 44" 1)/Canopy or Equiv.
Gas Valve Shut-off Exposed&Regulator 18")Above Grade
Floor Bathroom Watertight/Other Floors Oka
Relief Valve,Heat Trap/Water Temp. 110 Degrees Maximum
Boiler/Furnace Enclosure 1 hr. or Fire Extinguishing System
Fresh Air Supply for Occupancy/Ventilation Combustion
Low Water Shut Off For Boilers
Gas Furnace Shut Off Within 30 ft. or Within Line Of Site
Oil Furnace Shut Off at Entrance to Furnace Area _
Stockroom/Storage/Receiving/Shipping Room(2 hr.), 1 '/Z doors
> 10%> 1000 s .ft.
'/a Hour Corridor Doors&Closers
Firewalls/Fire Separation, 2 Hour, 3 Hour Complete/Fire
Dampers/Fire Doors
'Ceiling Fire Stopping, 3,000 s . ft. Wood Frame
Attic Access 30"x 20"x 30"(h), Crawl Space Access 18"x 24"
Smoke Vents Or Fan, if required
Elevator Operation and Si a e/Shaft Sealed
Handicapped Bathroom Grab Bars/Sinks/Toilets
Handicapped Bath/Parking Lot Si na e
Public Toilet Room Handicapped Accessible Zl y F F
Handicapped Service Counters, 34 in., Checkout 36" .22 l
Handicapped Ram /Handrails Continuous/12 in.Beyond
Active Listening System and Signage Assembly Space
Final Electrical
Site Plan/Variance required Z1 r � � .-1� i_Ci✓E
Final Survey,New Structure/Flood Plain certification,if req.
As-built Septic System Layout Required or On File L("WEj
Building Number or Tenant Address on Building or Driveway
Water Fountain or Cooler
Building Access All Sides by 20' /Driveable Surface 20'wide
00kay To Issue Temp. or Permanent C/O �^
Okay To Issue C/C
Last printed 6/3/2003 9:27 AML:\FamW\Building&Codes\Commercial Final Inspection Report.doc ��-
Commercial Final Inspection Deport
Office No.: (518)761-8256 Date Inspection requ eiv d: S
Queensbury Building&Code Enforcement Arrive: °, a p Depart:
742 Bay Road,Queensbury,NY 12804 Inspector's Initia
NAME: PERMIT o ,
LOCATION: /Z,) DATE: n
COMMENTS:
Y N NA
Chimney/"B"Vent/Direct Vent Location
Plumbing Vent Through Roof 6"/Roof Complete
Exterior Finish Grade Complete 6"in 10' or Equivalent
Interior/Exterior Guardrails 42 in.Platform/Decks �.
Interior/Exterior Ballisters 4 in. Spacing Platform/Decks 2U,
Stair Handrail 34 in.—3 8 in./Step Risers 7"/Treads 11"
Vestibules For Exit doors>3000 s . ft.
All Doors 36 in.w/Lever Handles/Panic Hardware,if required !�
Exits At Grade Or Platform 36 (w)x 44"(1)/Cano y or Equiv.
Gas Valve Shut-off Exposed&Re ulator 18")Above Grade 111
Floor Bathroom Watertight/Other Floors Oka
Relief Valve,Heat Trap/Water Temp.110 Degrees Maximum
Boiler/Furnace Enclosure 1 hr. or Fire Extinguishing System
Fresh Air Supply for Occupancy/Ventilation Combustion
Low Water Shut Off For Boilers
Gas Furnace Shut Off Within 30 ft.or Within Line Of Site
Oil Furnace Shut Off at Entrance to Furnace Area
Stoclaoom/Storage/Receiving/Shipping Room(2 hr.), 1 '/2 doors
> 10%> 1000 s . ft.
3/a Hour Corridor Doors&Closers
Firewalls/Fire Separation, 2 Hour, 3 Hour Complete/Fire
Dampers/Fire Doors
Ceiling Fire Stopping, 3,000 s . ft.Wood Frame
Attic Access 30"x 20"x 30"(h),Crawl Space Access 18"x 24"
Smoke Vents Or Fan, if required
Elevator Operation and Si a e/Shaft Sealed
Handicapped Bathroom Grab Bars/Sinks/Toilets
Handicapped Bath/Parking Lot Si na e
Public Toilet Room Handica ed Accessible
Handicapped Service Counters, 34 in., Checkout 3611
Handicapped Ramp/Handrails Continuous/12 in.Beyond
Active Listening System and Signa e Assembly Space
Final Electrical
Site Plan/Variance required v /�
Final Survey,New Structure/Flood Plain certification,if req.
As-built Septic System Layout Required or On File
Building Number or Tenant Address on Building or Driveway
Water Fountain or Cooler ;✓�^'` 'Building Access All Sides by 20' /Driveable Surface 20'wide
Okay To Issue Temp. or Permanent C/O
Okay To Issue C/C
Last printed 6/3/2003 9:27 AMYL:\ParnW\Building&Codes\Commercial Final Inspection Report.doc
Town of Queensbury
Fire Marshal's Office
742 Bay Road
Queensbury, NY 12804
Phone (518) 761-8205 Fax(518) 745-4437
Fire Marshal's Inspection Report
Request SCHEDULE
Received: Penmit# O9 CQ(o L/ INSPECTION ON: - cD 5
Name: n— a.01,14 4 vj `"r,��� AM PM ANYTIME
Location:
APPROVED -
N/A 'YES NO COMMENTS
EXIT ACCESS
EXIT ENCLOSURE
MAIN AISLE WIDTH,
SECONDARY AISLE WIDTH ���[�-�'C 6,
EXIT SIGN—NORMAL
EXIT SIGN-BATTERY
EMERGENCY LIGHTING
FIRE,EXTINGUISHER HUNG
FIRE EXTINGUISHER
INSPECTION `
FIRE EXTINGUISHER HYDRO
FIRE,ALARM SYSTEM
FIRE ALARM-:-FAN.SHUTDOWN
FIRE SPRINKLER SYSTEM
FIRE SUPPRESSION-KITCHEN
FIRE SUPPRESSION—GAS
ISLAND
HOOD INSTALLATION
INTERIOR FINISHES
STORAGE
COMPRESSED GAS
CLEARANCE TO SPRINKLERS
CLEARANCE TO ELECTRICAL
ELECTRIC WIRING ENCLOSED
COMBUSTIBLE WASTE
VEHICLE IMPACT PROTECTION
FIRE LANE
F.D.SIGNAGE—UTILITY ROOMS
NO SMOKING SIGNS
MAXIMUM OCCUPANCY SIGN
EMERGENCY EVAC PLAN
CTHIS E K F R CO T OK
INSPECTED BY
COMDEV/CHRISJNVORDILETTERS2001/FIREMARS HALINSPECTIONREPORT11022001
WHITE—BUILDING DEPARTMENT COPY YELLOW—OCCUPANT COPY
Town of Queensbury
Fire Marshal's Office
742 Bay Road
Queensbury, NY 12804
Phone (518) 761-8205 Fax(518) 745-4437
Fire Marshal's Inspection Report
Request SCHEDULE
Received: Permit# INSPECTION ON:
Name: % AM PM ANYTIME
Location:
APFkIWVED
N/A. YES NO COMMENTS
EXIT ACCESS
EXIT ENCLOSURE
EXIT DISCHARGE
MAIN AISLE WIDTH �✓�`a ��
SECONDARY AISLE WIDTH 1 ` _ C-
EXIT SIGN-NORMAL
EXIT SIGN-BATTERY
EMERGENCY LIGHTING C- '
FIRE EXTINGUISHER HUNG
FIRE EXTINGUISHER 4N,O C)
INSPECTION
FIRE EXTINGUISHER HYDRO
FIRE ALARM SYSTEM
FIRE ALARM -FAN SHUTDOWN
FIRE SPRINKLER SYSTEM
FIRE SUPPRESSION-KITCHEN ��-� �.� I bc,, it `rCtr-VP,,,
FIRE SUPPRESSION-GAS
ISLAND r
HOOD INSTALLATION
INTERIOR FINISHES
STORAGE
COMPRESSED GAS
CLEARANCE TO SPRINKLERS�G�thCCcL
CLEARANCE TO ELECTRICAL X
ELECTRIC WIRING ENCLOSED
COMBUSTIBLE WASTE
VEHICLE IMPACT PROTECTION
FIRE LANE
F.D.SIGNAGE-UTILITY ROOMS LL
NO SMOKING SIGNS
MAXIMUM OCCUPANCY SIGN
EMERGENCY EVAC PLAN
OK THIS DATE OR ® OT ®I(
ti
INSPECTED BY
COM DEV/C HRIS JNVVORD/LETTERS2001/F IRE M ARS HALI NS P ECTIO NRE PORT 11022001
WHITE-BUILDING DEPARTMENT COPY YELLOW-OCCUPANT COPY
Commercial Final Inspection Report
Office No.: (518) 761-8256 Date Inspection request received:
Queensbury Building&Code Enforcement Arrive: am/pm Depart: am/pm
742 Bay Road, Queensbuuryy,NY 12804 Inspector's Initials: '
NAME: PERMIT#:_c>)- �(�L4
LOCATION�'1 DATE:
COMMENTS:
Y N NA
Chimney/"B"Vent/Direct Vent Location
Plumbing Vent Through Roof 6"/Roof Com fete
Exterior Finish Grade Complete 6"in 10' or.E uivalent
Interior/Exterior Guardrails 42 in. Platform/Decks /nisG�
Interior/Exterior Ballisters 4 in. Spacing Platform/Decks
Stair Handrail 34 in.—38 in./Step Risers 7"/Treads 11"
Vestibules For Exit doors>3000 sq. ft.
All Doors 36 in.w/Lever Handles/Panic Hardware,if required
Exits At Grade Or Platform 36 (w)x 44"(1)/Canopy or Equiv.
Gas Valve Shut-off Exposed&Regulator(18")Above Grade
Floor Bathroom Watertight/Other Floors Oka
Relief Valve,Heat Trap/Water Temp. 110 Degrees Maximum
Boiler/Furnace Enclosure 1 hr. or Fire Extinguishing System
Fresh Air Supply for Occupancy./Ventilation Combustion
Low Water Shut Off For Boilers
Gas Furnace Shut Off Within 30 ft. or Within Line Of Site
Oil Furnace Shut Off at Entrance to Furnace Area
Stockroom/Storage/Receiving/Shipping Room(2 hr.), 1 '/Z doors
> 10%> 1000 s . ft.
3/4 Hour Corridor Doors&Closers
Firewalls/Fire Separation, 2 Hour, 3 Hour Complete/Fire
Dampers/Fire Doors
Ceiling Fire Stopping, 3,000 s . ft. Wood Frame
Attic Access 30"x 20"x 30"(h),Crawl Space Access 18"x 24" L��>-� { � d"',efJ
Smoke Vents Or Fan, if required /
Elevator Operation and Si a e/Shaft Sealed
Handicapped Bathroom Grab Bars/Sinks/Toilets
Handicapped Bath/Parking Lot Si na e
Public Toilet Room Handicapped Accessible
Handicapped Service Counters, 34 in., Checkout 36"
Handicapped Ramp/Handrails Continuous/12 in. Beyond
Active Listening System and Signage Assembly Space
Final Electrical
Site Plan/Variance required
Final Survey,New Structure/Flood Plain certification,if req.
As-built Septic System Layout Required or On File
Building Number or Tenant Address on Building or Driveway
Water Fountain or Cooler
Building Access Al _ ides by 20' /Driveable Surface 20' wide-
Okay To Issu em '. `t Permanent C/O
Okay To Issue
Last printed 6/3/2003 9:27 AML:\PamW\Building&Codes\Commercial Final Inspection Report.doc
Rough Plumbing / Insulation Inspection Report
Office No. (518) 761-8256 Date Inspection request received: a
Queensbury Building& Code Enforcement Arrive: am/1p�nn 'Depart: am/p
742 Bay Road, Queensbury,NY 12804 Inspector's Initials:V `
NAME: l CCU VA O V%- - PERMIT #:
LOCATION: j L LAID INSPECT ON: ' I 4—b
TYPE OF STRUCTURE:
Y N N/A
PVC: R-1,R-2, R-3,R4 Drain/Vents
Cast Iron, Copper Drain/Vent/ Comm.
Plumb' t/ iii Place
C Nail Plates
/z inch min.Drain Size
Washing Machine Drain 2 inch min.
Head or Air Supply Test
Drain and Vents
5 PSI or 10 feet above highest
connection for 15 minutes
Cleanout every 100 feet/change of direction
Water Supply Piping
Cooper Commercial
Cooper, CPVC,Pex One and Two-Family
Insulation/Residential Check/Commercial Check
Proper Vent,Attic Vent
Duct/Hot Water Piping Insulation
If required unheated spaces
Combustion Air Supply for]Furnace
Duct work sealed pWperly/No duct tape
COMMENTS:
LASueHcmingway\Building.Codes.Inspection.FORM S\Rough Plumbing Insulation Repott.doc November 17,2003
l �i-7/2q
QfKQ--1
Rough 'Plumbing / Insulation Inspection Report
Office No. (518) 761-8256 Date Inspection request received: /U y
Queensbury Building&Code Enforcement Arrive: am/ epart: 3rur
742 Bay Road, Queensbury,NY 12804 Inspector's.Initials: '`t`'` ,
's -W
NAME: PERMIT #: IJ4- 44,11
LOCATION: INSPECT ON:
TYPE OF STRUCTURE:
Y N N/A
PVC: R-1,R-2,R-3,R4 Drain/Vents
apt Iron, Copper Drain/Vent/Comm.
um6in _Vent/Vents in Place
Rlbumbn' /Nail Plates
1 % inch min.Drain Size
Washin ,.Machine Drain 2 inch min.
;�He 'd�or'Air Supply Test
Drain and Vents
5.PSI-or 10,feet above highest
connection.for 15 minutes
Cleanout every 100 feet/change of direction
Water Supply Piping
Cooper Commercial
Cooper, CPVC,Pex One and Two-Family
Insulation/Residential Check/Commercial Check
Proper Vent,Attic Vent
Duct/Hot Water Piping Insulation
If required unheated spaces
Combustion Air Su 1 for Furnace
Duct work sealed properly/No duct tape
COMMENTS: /J w
A.
A 2c F Gu� U-5
�u (i--'- vL)T`
�-LL �✓1 /c C—G�(��C�
LASueHemingway\Building.Codes.Inspection.FORMS1Rough Plumbing Insulation Report.doe November 17,2003
11�-1
Rough Plumbing / Insulation Inspection Repor
Office No. (518) 761-8256 Date Inspection request received:
Queensbury Building& Code Enforcement Arrive: am/p Depart: m/pm
742 Bay Road, Queensbury,NY 12804 Inspector's Initials:avz�. I
NAME: PERMIT #: 0 Ll — 62
LOCATION: INSPECT ON: — C
TYPE OF STRUCTURE:
Y N N/A
PVC: R-1,R-2,R-3,R4 Drain/Vents
,Cast Iron, Copper Drain/Vent/ Comm.
(Plumbing Vent/Vents in Place
Tj "Ro'u k Plumbari /Nail Plates
W 1 i%z in h min.. Drain Size
Was ing Machine Drain 2 inch min.
ad or Air Supply Test
Drain and Vents
V 5 PSI or 10 feet above highest
connection for 15 minutes
Cleanout every 100 feet/change of direction
Water Supply Piping
Cooper Commercial
Cooper, CPVC,Pex One and Two-Family
Insulation/Residential Check/Commercial Check
Proper Vent,Attic Vent
Duct/Hot Water Piping Insulation
If required unheated spaces
Combustion Air Supply for Furnace
uct work sealed properly/No duct tape
COMMENTS:
LASueHemingway\l3uilding.Codes.Inspection.FORMS\Rough Plumbing Insulation Report.doc November 17,2003
L/
Framing / Firestopping Inspection Report
Office No. (518) 761-8256 Date Inspection request received:
Queensbury Building&Code Enforcement Arrive: am/ D part: r am/pm
742 Bay Road, Queensbury, NY 12804 Inspector's Initials:
NAME: f:5A wvov PERMIT#:
LOCATION: 6- _ - ® INSPECT ON: ni
TYPE OF STRUCTURE:
Y N N/A COMMENTS
Framing
Jack Studs/Headers
Bracing/Bridging
Joist hangers
Jack Posts/Main Beams
Exterior sheeting nailed properly
12"O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate
1 %2 (w) 16 gauge (8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
An .hor Bolts 6 ft. or less on center
Ace and snow shield 24 inches from wall
Fire separation 1, 2, 3 hour
Fire wall 2, 3, 4 hour
Firestopping
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side %2 inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/Bedrooms
24 in. (H)
20 in. (W)
5.7 sf above/below grade
5.0 sf grade
LASueHemingway\Building.Codes.Inspecti on.FORMS\Framing Firestopping Inspection Report.doc January 28,2003
POO
Rough. Plumbing / Insulation Inspection Report ✓
Office No. (518) 761-8256 Date inspection request received: 6
Queensbury Building&Code Enforcement Arrive: am/p Depart: m/pm
742 Bay Road, Queensbury,NY 12804 Inspector's Initials:
NAME: PERMIT #:
LOCATION: INSPECT ON: / 3 6
TYPE OF STRUCTURE: �--
Q Sn
Y N N/A
PVC: R-1,R-2,R-3,R4 Drain/Vents
Cast Iron, Copper Drain/Vent/Comm.
Plumbing Vent/Vents in Place
R u h lu�nbin ;/Nail Plates /6/;7
1 % inc min. Drain Size
Washing Machine Drain 2 inch nun.
ead or Air Supply Test U
Drain and Vents
5 PSI or 10 feet above highest —
connection for 15 minutes
Cleanout every 100 feet/change of direction
ater Supply Piping
Cooper Commercial
Coo er,CPVC,Pex One and Two-Family
Insu a /:Residential Check/Commercial Check
Proper Vent,Attic Vent
Duct/Hot Water Piping Insulation
If required unheated spaces
Combustion Air Supply for Furnace
Duct work sealed properly/No duct tape
COMMENTS:
LASueHemingway\Building.Codes.Inspection.FORMS\Rough Plumbing Insulation Report.doc November 17,2003
Framing / Firestopping Inspection Report
Office No. (518) 761-8256 Date Inspection request received: U +r
Queensbury Building& Code Enforcement Arrive: am/ m epart:: m/pm
742 Bay Road, Queensbury,NY 12804 Inspector's Initials:
NAME: /-?),tA} fV0 PERMIT#: tl
LOCATION: INSPECT ON: / S v
TYPE OF STRUCTURE:
I
Y IN N/A
Fraining..,� COMMENTS
Jack Studs/Headers
Bracing/Bridging
Joist hangers
Jack Posts/Main Beams
Exterior sheeting nailed properly
12"O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate
1 % (w) 16 gauge (8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
Ice and snow shield 24 inches from wall
Fire separation 1, 2, 3 hour
Pre wall 2, 3, 4 hour
* 'Eirestopping P� "Gi(1: OV o( c:A-D
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side % inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/Bedrooms
24 in. (H)
20 in. (W) Pp c�PC je VC�,J
5.7 sf above/below grade /, '�
5.0 sf grade hV
C��u
L:\SueHeminaway\Building.Codes.[nspection.FORMS\ ming Fu o D ction Report.doe January 28,2003
Ir U
Ir
Al /jo l
A
V�
✓ �- -5r k
Framing / Firestopping Inspection Report
Office No. (518) 761-8256 Date Inspection request received: �®
Queensbury Building&Code Enforcement Arrive: am/ epart: am/pm
742 Bay Road, Queensbury,NY 12804 Inspector's Initials:
NAME: N" PERMIT#:
LOCATION: VO4,i1 imp INSPECT ON: dy
TYPE OF STRUCTURE: /
Framing Y N N/A COMMENTS
Jack Studs/Headers
Bracing/Bridging
Joist hangers
Jack Posts/Main Beams
Exterior sheeting nailed properly
12" O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate
1 %2 (w) 16 gauge (8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
Ice and snow shield 24 inches from wall
Fire separation 1, 2, 3 hour
F' all 2, 3, 4 hour
Firestopping
Penetration sealed _
16 inch insulation in cavity min.
Garage Fire Separation
House side '/2 inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/Bedrooms
24 in. (H)
20.in. (W)
5.7 sf above/below grade
5.0 sf grade
L:\SueHemingway\Building.Codes.Inspection.FORMS\Framing Firestopping Inspection Report.doc January 28,2003
Framing / Firestopping Inspection Report
Office No. (518) 761-8256 Date Inspection request received:. rpm
Queensbury Building & Code Enforcement Arrive: a _ De 3 part:
742 Bay Road, Queensbury, NY 12804 Inspector's Initial
NAME: . PERMIT#: U
LOCATION: _ INSPECT ON: ! `�
TYPE OF STRUCTURE:
Framing
Y N i /A COMMENTS
�
Jack Studs/Headers
Bracing/Bridging
Joist hangers
Jack Posts/Main Beams
Exterior sheeting nailed properly
12"O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate
1 '/2 (w) 16 gauge (8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
Ice and snow shield 24 inches from wall
Fire separation 1, 2, 3 hour
Fire wall 2, 3, 4 hour
Firestopping
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side %2 inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/Bedrooms
24 in. (H)
20 in. (W)
5.7 sf above/below grade
5.0 sf grade
LASueHemingway\Building.Codes.Inspection.FORMS\Framing Firestopping Inspection Report.doc January 28,2003
Framing / Firestopping Inspectio Report
Office No. (518) 761-8256 Date Inspection request received:
Queensbury Building&Code Enforcement Arrive: am/ n depart: m/pm
742 Bay Road, Queensbury, NY 12804 Inspector's Initials: /��
NAME: PERMIT#:
01-/-- (�
LOCATION: ( INSPECT ON:
TYPE OF STR C RE:
Y N N/a.aming COMMENTS
Jack Studs/Headers / Kd V��� v �S ��✓C
Bracing/Bridging �7��CC
Joist hangers
Jack Posts/Main Beams
Exterior sheeting nailed properly
12"O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate
1 %2 (w) 16 gauge (8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
Ice and snow shield 24 inches from wall
Fire separation 1, 2, 3 hour
Fire wall 2, 3, 4 hour
Firestopping
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side %2 inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/Bedrooms
24 in. (H)
20 in. (W)
5.7 sf above/below grade
5.0 sf grade
LASueHemingway\BuiIding.0 odes.Inspection.FORMS\Framing Firestopping Inspection Report.doc January 28,2003
Foundation Inspection Report
Office No. (518) 761-82.56 Date Inspection request receive .
Queensbury Building&Code Enforcement Arrive: am/pm e rt: b am/pm
742 Bay Rd.; Queensbury,NY 12804 Inspector's Initials: -
NAME: _ ^ PE I #:
LOCA'TIUN: IN ON:
TYPE OF STRUCTURE:
Comments
X N N/A
Footings
Piers
Monolithic Slab
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this purpose on site.
Foundation/Wallpour
Reinforcement in Place
Foundation Dampproofing
Foundation/Waterproofing
"Type of Dampproofing/Waterproofing
Footing Drain Daylight or Sump
Footing Drain Stone: T
12 inch width
6 inches above footing
it poly for wet areas under slab
ackfill Approval
Plumbing Under Slab
PVC/Cast/Copper
Foundation Insulatio Interior Exterior
R-
Rough Grade 6 inch drop within 10 ft.
LASuellemingway\Building.Codes.Inspection.PURMSII-oundation Inspection Report.doc January 28,2003
Foundation Inspection Report
Office No. (518) 761-8256 Date Inspection re est r 've
Queensbury Building&Code Enforcement Arrive: nVpm Depart: "-�- ' pm
742 Bay Rd., Queensbury, NY 12804 Inspector's Init al
Zj
NAME: _ 1C\ F,RMIT#: q op
LOCATION: _ _ INSPECT ON: — L
TYPE OF STRUCTURE:
Comments
ootuigs
Piers
Monolithic Slab
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this pu_pr ose on site.
Foundation/Wallpour
Reinforcement in Place
Foundation Dampproofing
Foundation/Waterproofing
Type of Dampproofing/Waterproofing
Footing Drain Daylight or Sump
Footing Drain Stone:
12 inch width
6 inches above footing
6 mil poly for wet areas under slab
Backfrll Approval
Plumbing Under SIab
PVC/Cast/Copper
Foundation Insulation Interior/Exterior
R- _
Rough Grade 6 inch drop within 10 ft.
LASueHemingway\Building.Codes.Inspection.PORMS\I-oundation Inspection Report.doc January 28,2003
SEISMIC REVIEVH SUMMARY
PROJECT:
LOCATION: ZIP CODE: /2 IR a
ITEM Value BCNYS BCNYS
Code Section Page No.
Site Class Table 1615.1.1 317
(default to site class D) j45 S Section 1615.1.1 316
S,(short period) p, .3 Z Figure 1615(1) 318
S, (9 second period) O Figure 1615(2) 319
F.(site coefficlent—short) /,�-3 . Table 1615.1.2(1) 320
F, (site coefficient-1 sec.) Table 1615.1.2(2) 320
S., (short period adjusted) Equation 16-16 317
S,,, (1 sec. period adjusted) ' 471, Z y 3 Equation 16-17 317
SD, (short period) 9, y9 Equation 16-18 320
Sp, (1 sec. period) 40, Equation 16-19 320
Seismic Use Group j' Table 1604.5 287
Seismic Design Category :G Table 1616.3(1) ' 324
(short period)
Seismic Design Category G Table 1616.3(2) 324
(1 sec.period)
SEISMIC DESIGN CATEGORY This category determines the
(most severia of above two) design analysis and whether MEP
systems must be braced.
Analysis Procedure Used ��f',.,., j,�� ' 4/ Section 1616.6 326
- Building Components Subject To Section 1621 345
Seismic Design Requirements: �`'' f pa,�,/'o 5
Architectural 5 u g . C C (�+�y S Section 1621.1.1 & 345
Mechanical - /vq�,Go 5 p�� Ih Section 1621.1.6 347lp
.
Plumbing ... _ : - M o� e ditto - 347
Electrical ditto 347
SCHODER RIVERS ASSOC. PROJECT: Bannon Office Addition. SHEET: Cover
Consulting Engineers, P.C. O
2315-2 Route 9N LOCATION: Queensbury, NY DATE: 9/28/2004
Lake George, NY 12845 BY: LC
Phone: (518)668-2918 PC- 04-521 CHK: DWE
Fax: 518 668-2919
Lateral Load Analysis
TrussLoads.......................................................................1
Wind Loads.........:........ ..2 to 3
Seismic Loads (Does not Control).......................................... 4 to 5
Roof Diaphragm/Shear Wall................................................6
Roof Diaphragm Chord........................................................ 7
Truss Connection to Top/Bott:Plate.......................................8
Shear Wall End Reactions....................................................9 to 11
�tfe�l Fouz�
rJ -( ' .r y.6
v tZ
s -
_. .... . _ .'ry Gh+w� . - -.. I ..ps F.�z 1� '_-1• �'.Q�r-....__— .__.._3-yes ----
. 0
.--------------------
CS
5 s
0�16.y 5' 5 —q•44 J U.g.
------'-- '------'---r--� --'- --�-- � ' ' �
' | !
' ------�--'-- - -- ----' �' \--��/ �-�»~~� ��{r---'------------_-______ _
�
. �
- - ' -
_
C,,� mad : - - � Z-----_----•-- -----------P-'-- ---• -------•-----
yS�
Z -G •
: I
•
,
1 •
:
i I
I
I
r
_ . _..Fes.- - �-�-.� - ------- ---------_. ------- -- ---- ---- ------- ---- .
-..______ I ' --_--yam 1!-�QM�q 1�Y i I I✓V� 1 I I --
' SAS - SZ� --------•----- --- .._..------------------ --
,
V
-
L/3 �I7 2 psT
--__—_--------- --- �5�3\1J � --_ .--- ------- -----.._�
— 2y
—Z-7
-
- =1 b. P7 --- --
O -
06)_
i
•---
Bannon Office `
Date and Time: 9/27/04 1:45:36 PM
MCE Parameters - Conterminous 48 States
Zip Code - 12804. Central Latitude = 43.349572
Central Longitude = -073.677666
Data are based on the 0.10 deg grid set
Period SA
(sec) (%g)
0.2 034.2 Map Value, Soil Factor of 1.0
1.0 010.1 Map Value, Soil Factor of 1.0
MCE Parameters x Specified Soil Factors
0.2 052.3 Soil Factor of 1.53
1.0 024.2 Soil Factor of 2.40
MCE Parameters - Conterminous 48 States
Zip Code - 12804 Central Latitude = 43.349572
Central Longitude = -073.677666
Data are based on the 0.10 deg grid set
Period SA
(sec) (%g)
0.2 034.2 Map Value, Soil Factor of 1.0
1.0 010.1 Map Value, Soil Factor of 1.0
MCE SPECTRUM x SOIL FACTORS
Fa = 1.53
Fv = 2.40
Period SA
(sec) (%g)
0.000 020.9 0.4FaSs
0.093 052.3 To
0'200 052.3 T=0.2, FaSs r
0.465 052.3 Ts
0.500 048.6
0.600 040.5
0.700 034.7
0.800 030.4
0.900 027.0
1.000 024.3 T=1.0, FvS 1
1.100 022.1
1.200 020.3
1.300 018.7
1.400 017.4
1.500 016.2
1.600 015.2
1.700 014.3
1.800 013.5
1.900 012.8
2.000 012.2
:
L�
— -- — - --- —15---- _..--- -- ----------- --� ---
6. v •
x a
v
&40
��.g _ max,, sE�,--_Z���l_F-�-(iy�%�•�Z =-��'L�-�-�Y��,�e =�l
-- �J � 1•�� �����" ' � � --- �/`!/ --...!.��—I�/)L-�/Q,.�.Uk__—f.V�__11J1��)-.-L/�.I�`2 ii �, —'_��I�Lc3rr.=l..—V���
1t�°-
19 : lo.� a.1C
----�--3_ z �.—_a _�,�,�-�3,_G --�---=H�a,�;_ �,Q�,�,_,�:-5��--W�-�-- -� '3 ti 3°� ---��3�,_616�2 l o•5=2"
3ll
--
,
:
i
i
,
I i i
i
---.. ------=----�sG-Q 9�-(-9 'I�—off�=�`a7'�_•��-'���__, � � �—, j
0
z I
f i
-To
179t
ev
4, j,51 h
•
7'
-�j f,�tt'6f 1— _ �sd�-�j- ��•91) 9 • .a- (��d h�i1=��=�I�t (�sd-�:i=�_�,0,9•_,�-
hzr 1(7—
-7
,
Ce7)
---- =---------
Vi
•f
,A ?IZ�../ iif--
. ( U 7
d �R
i
------ -----��� - f-a ,4 r c� ---------- --------- -- 41 -
e
z
V
Qtl -- - �- �---- - _-
J
- ---------- -- ----------------------------------------
WoodWorks® Sizer SOFTWARE FOR WOOD DESIGN
Postwca WoddWorks®S[zer 2000 Sep.28,2004 14:49:04
COMPANY I PROJECT
ANALYSIS RESULTS.
LOADS: (force=lbs, pressure=psf, udl=plf, location=ft)
»Self-weight of members has NOT been included<<
Load I Type I Distribution I Magnitude I Location. I Pattern
I I I Start End I Start End I Load
-----I--------I--------------I-----------------I-----------------I--------
1 Dead Axial 285 (Eccentricity = 0.0 in)
2 Live Axial 1695 (Eccentricity = 0.0 in)
LOAD COMBINATIONS:.ASCE 7-95
1: D only
2: D+L
(D=dead L=live S=snow' W=wind I=impact C=construction)
AXIAL, SHEAR and BENDING Values:
( +ve axial = tension ) (shear and bending are due to side loads only)
Load I Axial I Shear@ I Bending@ I Span_Bending
Combo I I bottom top I base I mag. loc.
I [ lbs] I [ lbs] I [lbs-ft] I [lbs-ft] [ft]
--------I----------I--------------------I----------I--------------------
1 I -285
2 I -1980
COMPANY PROJECT /v
�76
Woodworks
SOFTWARE FOR WOOD DESIGN
Sep.28,2004 14:49:02 Post.wwc
Design Check Calculation Sheet
LOADS: (lbs,psf,or plf)
Load Type Distribution Magnitude Location [ft] Pattern
Start End Start End Load?
1 Dead Axial 285 (Eccen ricity = 0.0 in
2 Live Axial - 1695 (Eccen ricit = 0.0 in
MAXIMUM REACTIONS (Ibs)and BEARING LENGTHS :
Cr g
Lumber n-ply,S-P-F(S), No.2, 20",2-Plys
pinned base,Loadface=depth(d)built-up fastener.nails Ke x Lb:1.20 x 0.00=0.00 Ift]Ke x Ld:1.20 x 9.00=10.80 Ift]repetitive factor applied
where permitted(refer to online help)Load Combinations:ASCE 7-95
SECTION vs. DESIGN CODE NDS4997:(stress=psl,and In)
Criterion lAnalysis Value Des i n Value Anal sis/Desi n
Axial fc = 189 Fc' = 230 fc/Fc' = 0.82
Axial Bearing fg = 189 Fg' = 1220 fg/Fg' = 0.15
ADDITIONAL DATA:
FACTORS: F CD CM Ct CL CF CV Cfu Cr LC#
Fc' = 1000 1.00 1.00 1.00 1.15 (Cp = 0.200) 2
E' = 1.1 million 1.00 1.00 0
Fg' = 1220 1.00 1.00 2
Axial : LC# 2 = D+L, P = 1980 lbs Kf = 1.00
(D=dead L=1ive S=snow W=wind I=impact C=construction)
(All LC's are listed in the Analysis output)
DESIGN NOTES:
1.Please verify that the default deflection limits are appropriate for your application.
2.BUILT-UP COLUMNS:nailed or bolted built-up columns shall conform to the provisions of NDS Clause 15.3.
RUCINSKI HALL ARCHITECTURE
Ronald.Richard Rucinski
Ethan Peter Hall
G�
627 Maple Avenue
Saratoga Springs NY 12866
Voice 518 580 1905
Fax 518 584 5012
Email rrr@nycap.rr.com
ephall@nycap.rr.com
Transmittal
To: David Hatin—Town of Queensbury—Building and Code Enforcement
From: Ethan Hall
Date: 29 September, 2004
Re: Bannon Medical Office Addition
Attached are 2 copies of revised drawings and one copy of structural load calculations for the
above referenced project. These revisions are in response to your review letter dated 20 Sept.
2004.
In regards to Item #4 in your letter there is no fire alarm system in the building.
Please let me know.if-there are any additional questions.
Xc: Connie Bannon (1MAttachments)
CAACAMBannon[Dave and Connie]\Medical OfficeTaperworkUransmittal 29 Sept 2004.doc
Permit Number
Envelope Compliance Certificate Checked By/Date
New York State Energy Conservation Construction Code
COMchecl-EZ Software Version 3.0 Release 1
Data filename:C:\ACAD\Bannon[Dave and Connie]\Medical Office\Bannon.cck � �
Section 1: Project Informationi�
AEG 2
Project Name: J.David Bannon TO 72004
Bay Road,Queensbury,New York
ro �Ul Ql Q pNSB(i �►
Designer/Contractor: Rucski Hall Architecture CDOE
627 Maple Ave,Saratoga Springs,New York
Document Author:
Telephone:
Date:
Section 2: General Information
Building Location(for weather data): Warren,New York
Climate Zone: 15
Heating Degree Days(base 65 degrees F): 7635
Cooling Degree Days(base 65 degrees F): 366
Project Type: Addition
Window/Wall Ratio: 0.12
Building Type Floor Area
Office 900
Section 3: Requirements Checklist
Bldg.
Dept.
Use
Air Leakage,Component Certification,and Vapor Retarder Requirements
[ ] I 1. All joints and penetrations are caulked,gasketed,weather-stripped,or otherwise sealed.
[ ] 2. Windows, doors,and skylights certified as meeting leakage requirements.
[ ] 3. Component R-values&U-factors labeled as certified.
[ ] 4. Fireplaces installed with tight fitting non-combustible fireplace doors.
[ ] 5. Stair,elevator.shaft vents,and other dampers integral to the building envelope are equipped
with motorized dampers.
[ ] 6. Cargo doors and loading dock doors are weather sealed.
[ ] 7. Recessed lighting fixtures are: (i)Type IC rated and sealed or gasketed;or(ii)installed inside an
appropriate air-tight assembly with a 0.5 inch clearance from combustible materials and
with 3 inches clearance from insulation material.
,
Climate-Specific Requirements
Gross Cavity Cont. Proposed Budget
Component Name/Description Area R-Value R-Value U-Factor U-Factor
Roof 1:All-Wood Joist/Rafter/Truss 900 38.0 0.0 0.028 0.051
Exterior Wall I:.Wood Frame,Any Spacing 720 21.0 . 0.0 0.062 0.074
Window 1:Wood Frame:Double Pane,Clear,SHGC 0.57 94 --- --- 0.480 0.520
Basement Wall 1: Solid Concrete or Masonry<=8"
Furring:None,Wall Ht 3.8,Depth B.G.3.3 263 --- 10.0 0.088 0.098
Floor 1:Slab-On-Grade:Unheated,Vertical 4 ft.. 49 --- 10.0 --- ---
(a)Budget U-factors are used for software baseline calculations ONLY,and are not code requirements.
Envelope PASSES: Design 11%better than bode,
Section 4: Compliance Statement
The proposed envelope.design represented in this document is consistent with the building plans,specifications and other
calculations submitted with this permit application. The proposed envelope system has been designed to meet the New
York State Energy Conservation Construction Code requirements in COM check-EZ Version 3.0 Release'l and to comply
with the mandatory requirements in the Requirements Checklist.
When a Registered Design Professional has stamped and signed this page,they are attesting that to the best of his/her
knowledge,belief,and professional judgment,such plans or specific ions are in compliance with this Code.
Principal Envelope Designer-Name Signature Date
Permit Number
Lighting and Power Compliance Certificate Checked By/Date
New York State Energy Conservation Construction Code
COMcheck-EZSoftware Version 3.0 Release 1
Data filename:C:WCAD\Bannon[Dave and Connie]1Medical Office\Bannon.cck
Section 1: Project Information
Project Name: J.David Bannon
Bay Road,Queensbury,New York
Designer/Contractor: Rucinski Hall Architecture
627 Maple Ave,Saratoga Springs,New York
Document Author:
Telephone:
Date:
Section 2: General Information
Building Use Description by: Whole Building Type
Project Type: Addition
Building Type Floor Area
Office 900
Section 3: Requirements Checklist
Bldg.
Dept.
Use
[ ] Interior Lighting
1. Total actual watts must be less than or equal to total allowed watts
Allowed Watts Actual Watts Complies(Y/N)
900 704 YES
Exterior Lighting
[ ] 2. Type(s)of exterior lighting sources:
_Fluorescent _Metal Halide —High-Pr. Sodium
Exceptions-
Specialized signal,directional,and marker lighting; lighting highlighting exterior features of
historic buildings;advertising signage;safety or security lighting;low-voltage landscape lighting.
Controls,Switching,and Wiring
[ ] 3. Master switch at entry to hotel/motel guest room.
[ ] 4. Individual dwelling units separately metered.
[ ] 5. Minimum of two switches,dimmer,or occupancy sensor in each space.
Exceptions:
Only one luminaire in space;
Security lighting,24 hour lighting;
The area is a corridor,storage,restroom,retail sales area or lobby.
[ ] 6. Automatic lighting shutoff control in spaces greater than 250 sq.ft in buildings larger than 5,000 sq.ft.
[ ] 7. Photocell/astronomical time switch on exterior lights.
Exceptions: Areas requiring lighting during daylight hours
[ ] 8. Tandem wired one-lamp and three-lamp ballasted luminaires.
Exceptions
Electronic high-frequency ballasted luminaires not on same switch
[ ] 9. Transformers meet minimum efficiencies listed in Table 805.6.1 or 805.6.2.
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent with the building plans,specifications and other
calculations submitted with this permit application. The proposed lighting system has been designed to meet the New
York State Energy Conservation Construction Code requirements in COM check-EZ Version 3.0 Release 1 and to comply
with the mandatory requirements in the Requirements Checklist.
When a Registered Design Professional has stamped and signed this page,they are attesting that to the best of his/her
knowledge,belief,and professional judgment,such plans or specifi ations are in compliance with this Code.
Principal Lighting Designer-Name STgnature Date
Lighting Application Worksheet
New York State Energy Conservation Construction Code .
COMcheck-EZ Software Version 3.0 Release 1
Section 1: Allowed Lighting Power Calculation
A B C D
Total
Floor Allowed Allowed
Area Watts Watts
Building Type (ft21 (watts/ft2) (B x Cl
Office 900 1 900
Total Allowed Watts= 900
Section 2: Actual Lighting Power Calculation
A B C D E F
Fixture Fixture Description/ Lamps/ #of Fixture
ID Lamp Description/Wattage Per Lamp/Ballast Fixture Fixtures Watt. D x E
1 48"T8 32W/Electronic 3 8 88 704
Total Actual Watts= 704
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero,the building complies.
Total Allowed Watts= 900
Total Actual Watts= 704
Project Compliance= 196
Lighting PASSES: Design 22%better than code
Permit Number
Mechanical Compliance Certificate Checked By/Date
New York State Energy Conservation Construction Code
COMcheck-EZSoftware Version 3.0 Release 1
Data filename:C:\ACAD\Bannon[Dave and Connie]\Medical Office\Bannon.cck
Section 1: Project Information
Project Name: J.David Bannon
Bay Road,Queensbury,New York
Designer/Contractor: Rucinski Hall Architecture
627 Maple Ave, Saratoga Springs,New York
Document Author:
Telephone:
Date:
Section 2: General Information
Building Location(for weather data): Warren,New York
Climate Zone: 15
Heating Degree Days(base 65 degrees F): 7635
Cooling Degree Days(base 65 degrees F): 366
Project Type: Addition
Section 3: Mechanical Systems List
Quanti1y System Type&Description
1 HVAC System 1: Heating:Central Furnace,Gas/Cooling:Field-Assembled DX System,Capacity<65
kBtu/h,Air-Cooled Condenser/Single Zone
Section 4: Requirements Checklist
Bldg.
Dept.
Use
Requirements Specific To:HVAC System 1
[ ] 1. Newly purchased heating equipment meets the heating efficiency requirements
[ ] 2. Specified equipment consists of field-assembled components-efficiency documentation provided
Generic Requirements: Must be met by all systems to which the requirement is applicable'
[ ] 1. Load calculations per 1997 ASHRAE Fundamentals
[ ] 2. Plant equipment and system capacity no greater than needed to meet loads
-Exception: Standby equipment automatically off when primary system is operating
-Exception:Multiple units controlled to sequence operation as a function of load
[ ] 3. Minimum one temperature control device per system
[ ] 4. Minimum one humidity control device per installed humidification/dehumidification system
[ ] 5. Thermostatic controls has 5 deg.F deadband
-Exception:Thermostats requiring manual changeover between heating and cooling
[ ] 6. Automatic Controls: Setback to 55 deg.F(heat)and 85 deg.F.(cool);7-day clock,
2-hour occupant override, 10-hour backup
-Exception:Continuously operating zones
-Exception:2 kW demand or less,submit calculations
[ ] 7. Automatic shut-off dampers on exhaust systems and supply systems.with airflow>3,000 cfin
[ ] 8. Outside-air source for ventilation;system capable of reducing OSA to required minimum
[ ] 9. R-5 supply and return air duct insulation in unconditioned spaces
R-8 supply and return air duct insulation outside the building
R-8 insulation between ducts and the building exterior when ducts are part of a building assembly
-Exception:Ducts located within equipment
-Exception:Ducts with interior and exterior temperature difference not exceeding 15 deg.F.
[ ] 10. Ducts sealed-longitudinal seams on rigid ducts;transverse seams on all ducts;
UL 181A or 181B tapes and mastics
-Exception: Continuously welded and locking-type longitudinal joints and seams on ducts
operating at static pressures less than 2 inches w.g.pressure classification
[ ] 11. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
[ ] 12. Hot water pipe insulation: 1 in.for pipes<=1.5 in.and 2 in.for pipes>1.5 in.
Chilled water/refrigerant/brine pipe insulation: 1 in.for pipes<=1.5 in.and 1.5 in.for pipes>1.5 in.
Steam pipe insulation: 1.5 in.for pipes<=1.5 in.and 3 in.for pipes >1.5 in.
-Exception:Piping within HVAC equipment
-Exception: Fluid temperatures between 55 and 105 deg.F
-Exception:Fluid not heated or cooled
-Exception:Runouts<4 ft in length
[ ] 13. Operation and maintenance manual provided to building owner
[ ] 14. Balancing devices provided in accordance with 603.15 of Mechanical Code for New York State
Section 5: Compliance Statement
The proposed mechanical design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet
the New York State Energy Conservation Construction Code requirements in CUM check-EZ Version 3.0 Release 1 and
to comply with the mandatory requirements in the Requirements Checklist.
The design professional shall provide to the code enforcement official a written certification that the required HVAC tests,
system balancing,etc.,have been performed and the system is operating as designed. The design professional shall retain
copies of the test reports to be provided to the code enforcement official,if requested.When a Registered Design
Professional has stamped and signed this page,they are attesting that to the best of his/her knowledge,belief,and
professional judgment, such plans or specifications are in compliance with this Code.
/d'W'Z& 0"_
Principal Mechanical Designer-Name ' ature Date
Mechanical Requirements Description
New York State Energy Conservation Construction Code
COMcheck-EZSoftware Version 3.0 Release 1
Data filename: C:WCAD\Bannon [Dave and Connie]1Medical Office\Bannon.cck
The following list provides more detailed description of the requirements in Section 4 of the Mechanical Compliance
Certificate.
Requirements Specific To: HVAC System 1
1. The specified heating equipment is covered by Federal minimum efficiency requirements.New equipment of this type
can be assumed to meet or exceed New York State Energy Conservation Code requirements for equipment efficiency.
2. The specified cooling system consists of field-assembled components.Documentation must be submitted showing
the system meets New York State Energy Conservation Code equipment efficiency requirements for a comparable
package equipment type and capacity range.
Generic Requirements: Must be met by all systems to which the requirement is applicable
1. Design heating and cooling loads for the building must be determined using procedures equivalent to those in
Chapters 27 and 28 of the ASHRAE Handbook of Fundamentals or an approved equivalent calculation procedure.
2. All equipment and systems must be sized to be no greater than needed to meet calculated loads. A single piece of
equipment providing both heating and cooling must satisfy this provision for one function with the capacity for the
other function as small as possible,within available equipment options.
-Exception: The equipment and/or system capacity may be greater than calculated loads for standby purposes.
Standby equipment must be automatically controlled to be off when the primary equipment and/or system is operating.
-Exception: Multiple units of the same equipment type whose combined capacities exceed the calculated load are
allowed if they are provided with controls to sequence operation of the units as the load increases or decreases.
3. Each heating or cooling system serving a single zone must have its own temperature control device.
4. Each humidification system must have its own humidity control device.
5. Thermostats controlling both heating and cooling must be capable of maintaining a 5 degree F deadband(a range of
temperature where no heating or cooling is provided).
-Exception: Deadband capability is not required if the thermostat does not have automatic changeover capability
between heating and cooling.
6. The system or zone control must be a programmable thermostat or other automatic control meeting the following
criteria:a) capable of setting back temperature to 55 degree F during heating and setting up to 85 degree F during
coolingb) capable of automatically setting back or shutting down systems during unoccupied hours using 7 different
day schedulesc) have an accessible 2-hour occupant overrided) have a battery back-up capable of maintaining
programmed settings for at least 10 hours without power.
-Exception:A setback or shutoff control is not required on thermostats that control systems serving areas that operate
continuously.
-Exception: A setback or shutoff control is not required on systems with total energy demand of 2 kW(6,826 Btu/h)
or less.
7. Outdoor-air supply systems with design airflow rates>3,000 cfm of outdoor air and all exhaust systems must have
dampers that are automatically closed while the equipment is not operating.
8. The system must supply outside ventilation air as required by Chapter 4 of the Mechanical Code for New York State.
If the ventilation system is designed to supply outdoor-air quantities exceeding minimum required levels,the system
must be capable of reducing outdoor-air flow to the minimum required levels.
9. Air ducts must be insulated to the following levels:a) Supply and return air ducts for conditioned air located in
unconditioned spaces(spaces neither heated nor cooled)must be insulated with a minimum of R-5.Unconditioned
spaces include attics,crawl spaces,unheated basements,and unheated garages.b) Supply and return air ducts and
plenums must be insulated to a minimum of R-8 when located outside the building.c) When ducts are located within
exterior components(e.g., floors or roofs),minimum R-8 insulation is required only between the duct and the
building exterior.
-Exception: Duct insulation is not required on ducts located within equipment.
-Exception: Duct insulation is not required when the design temperature difference between the interior and exterior
of the duct or plenum does not exceed 15 degree F.
10. All joints,longitudinal and transverse seams,and connections in ductwork must be securely sealed using
weldments;mechanical fasteners with seals,gaskets,or mastics;mesh and mastic sealing systems;or tapes.Tapes
and mastics must be listed and labeled in accordance with UL 181A or UL 181 B.
-Exception: Continuously welded and locking-type longitudinal joints and seams on ducts operating at static
pressures less than 2 inches w.g.pressure classification.
11. Mechanical fasteners and seals,mastics,or gaskets must be used when connecting ducts to fans and other air
distribution equipment, including multiple-zone terminal units.
12. All pipes serving space-conditioning systems must be insulated as follows:
Hot water piping for heating systems:
1 in.for pipes<=1 1/2-in.nominal diameter
2 in.for pipes>1 1/2-in.nominal diameter.
Chilled water,refrigerant,and brine piping systems:
1 in. insulation for pipes<=1 1/2-in.nominal diameter
1 1/2 in. insulation for pipes>1 1/2-in.nominal diameter.
Steam piping:.
1 1/2 in. insulation for pipes<=1 1/2-in.nominal diameter
3 in.insulation for pipes>1 1/2-in.nominal diameter.
-Exception: Pipe insulation is not required for factory-installed piping within HVAC equipment.
-Exception: Pipe insulation is not required for piping that conveys fluids having a design operating temperature
range between 55 degrees F and 105 degrees F.
-Exception: Pipe insulation is not required for piping that conveys fluids that have not been heated or cooled through
the use of fossil fuels or electric power.
-Exception: Pipe insulation is not required for runout piping not exceeding 4.ft in length and 1 in. in diameter
between the control valve and HVAC coil.
13. Operation and maintenance documentation must be provided to the owner that includes at least the following
information:a) equipment capacity(input and output)and required maintenance actionsb) equipment operation and
maintenance manualsc) HVAC system control maintenance and calibration information, including wiring diagrams,
schematics,and control sequence descriptions;desired or field-determined set points must be permanently recorded on
control drawings,at control devices,or,for digital control systems, in programming commentsd) complete narrative
of how each system is intended to operate.
14. Each supply air outlet or diffuser and each zone terminal device(such as VAV or mixing box)must have its own
balancing device.Acceptable balancing devices include adjustable dampers located within the ductwork,terminal
devices,and supply air diffusers.