RC-0155-2019 TOWN OF QUEENSBURY
742 Bay Road, Queensbury,NY 12804-5904 (518)761-8201
Community Development- Building & Codes (518) 761-8256
BUILDING PERMIT
Permit Number: RC-0155-2019
Tax Map No: 309.17-1-2.1
Permission is hereby granted to: Michael Altare
For property located at: 92 EAGAN RD
In the Town of Queensbury,to construct or place at the above location in accordance with application together
with plot plans and other information hereto filed and approved and in compliance with the NYS Uniform
Building Codes and the Queensbury Zoning Ordinance
Type of Construction
Owner Name: Michael Altare Single Family-Addition $261000.00
Owner Address: 92 Eagan RD Total Value $261000.00
Queensbury,NY 12804
Contractor or Builder's Name/Address Electrical Inspection Agency
Honey-Do Man LLC
442 CORINTH RD
Queensbury,NY 12804
Plans& Specifications
Residential Addition 480 s.f.
(bedroom)
$250.00 PERMIT FEE PAID-THIS PERMIT EXPIRES: Monday,April 13, 2020
(If a longer period is required,an application for an extension must be made to the code Enforcement Officer
of the Town of Queensbury before the expiration date.)
Dated at the Town of Queensbury; Friday,April 12, 2019
SIGNED BY. for the Town of Queensbury.
Director of Building&Code Enforcement
.l , 4
Office Use Only
>' : ADDITION/ALTERATION PERMIT Permit#: fZC ` O f S 5 ` ?ol ci
-- APPLICATION Pem,i� e S U_ Cw
To4cn of(Zuecnsbun �/ it
.� _C
742 Bay Road,Queensbury,NY 12804 E C rnvoicc tik: >0
P:518-761-8256 www.queensbury.net
MAR 2 7 2019
Project Location: CID CV04)
TOWNOFG&CODES ENSBURY
Tax Map ID #: 5ja , rk - r — 2.., , 4 ,, ame:
CONTACT INFORMATION:
• Applicant:
Name(s): tkIle-t 4- -k.(1 gtic eZ.t_.
Mailing Address, C/S/Z: ak1i,A Ny IZ$01-1 Ga EcxcI&A Q.d
Cell Phone: ( 551B ) 1Ci1 -33'-iis Land Line: ( )
4 E m a i I: 9 tAkalkk,iite caw..
• Primary Owners):
Name(s): 14 aLSl..
Mailing Address, C/S/Z: a E un ea Q o 1JY 12, aq
Cell Phone: (5lP ) lql - 3,�WQ, Land Line: ( )
i Email: 9Gwt0.k @ tar).
❑ Check if all work will be performed by homeowner only
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contact Name(s): gOi\at- co ian
Contractor Trade: 0.04\413i.c\10(1
Mailing Address, C/S/Z: t-(t.U... Cx t, -`1 2_ 8 gSIan 1\1\( I2f )`-{
Cell Phone: ( `J1$ ) 2_(90 - yS16 Land Line: ( )
Email: hp -& �nr\ e\,,,„,,,,,A lo+,,
**List alradditional contractors on the back of this form
• Architect(s)/Engineer(s):
Business Name: AKCti\Sv_x tko` t
Contact Name(s): )caN AkoAk
Mailing Address, C/S/Z: 11y"b,,y AvL (k rvs '\\3 MN/ )ZSto1
Cell Phone: ( ) +-iIA Land Line: ( SIg ) -7q / -62(0�,
Email: e,Pl>a.�1 e t1yCoP .('('.
Contact Person for Building & Code Compliance: 1(EV1u /tv`( &
Cell Phone: (5 t8 ) 21,1,6 - -I'3 Land Line: ( ) �t�i4
Email: Y1 o r�l,k) .do ,�c&n e h4.„a,l .Co,N•
Addition/Alteration Application Revised February 2019
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contact Name(s):
Contractor Trade:
Mailing Address, C/S/Z:
Cell Phone: ( ) Land Line: (
Email:
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contact Name(s):
Contractor Trade:
Mailing Address, C/S/Z:
Cell Phone: ( ) Land Line: (
Email:
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contact Name(s):
Contractor Trade:
Mailing Address, C/S/Z:
Cell Phone: ( ) Land Line: (
Email:
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contact Name(s):
Contractor Trade:
Mailing Address, C/S/Z:
Cell Phone: ( ) Land Line: (
Email:
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contact Name(s):
Contractor Trade:
Mailing Address, C/S/Z:
Cell Phone: ( ) Land Line: (
Email:
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contact Name(s):
Contractor Trade:
Mailing Address, C/S/Z:
Cell Phone: ( ) Land Line: (
Email:
Addition/Alteration Application Revised February 2019
r it
t
PROJECT INFORMATION:
TYPE: Commercial )c Residential
WORK CLASS:
XSingle-Family Two-Family Multi-Family (# of units
Townhouse Business Office Retail
Industrial/Warehouse Garage (# of cars ) Other (describe
ADDITION SQUARE FOOTAGE: ALTERATION SQUARE FOOTAGE:
1st floor: W 1st floor:
2nd floor: 2nd floor:
3rd floor: 3rd floor:
Basement (habitable space):Ipp �,, Basement (habitable space):
Total square feet: `'1W Total square feet:
ADDITIONAL PROJECT INFORMATION:
1. Estimated Cost of Construction: $ au
)(5730
2. If Commercial project, what is the proposed use:
13. Source of Heat (circle one): Gas Oil Propane Solar Other hl
Fireplaces need a separate Fuel Burning Appliances & Chimney Application
4. Are there any structures not shown on the plot plan? YES NO Explain:
5. Are there any easements on the property? YES NO�;
6. SITE INFORMATION:
vt a. What is the dimensions or acreage of the rcel? _off .
b. Is this a corner lot? YES NO
c. Will the grade be changed as a result of the construction? YES NO,
d. What is the water source? PUBLIC PRIVATE WELL
e. Is the parcel on SEWER or a PRIVATE SEPTIC system? AkC.r
Addition/Alteration Application Revised February 2019
-
DECLARATION:
1. I acknowledge that no construction shall be commenced prior to issuance of a valid permit and will be
completed within a 12 month period.
2. If the work is not completed by the 1 year expiration date the permit may be renewed, subject to
fees and department approval.
3. I certify that the application, plans and supporting materials are a true and complete statement and/or
description of the work proposed, that all work will be performed in accordance with the NYS Building
Codes, local building laws and ordinances, and in conformance with local zoning regulations.
4. I acknowledge that prior to occupying the facilities proposed I, or my agents, will obtain a certificate
of occupancy.
5. I also understand that I/we are required to provide an as-built survey by a licensed land surveyor of all
newly constructed facilities prior to issuance of a certificate of occupancy.
I have read and agree to the above:
PRINT NAME:
CL
-/ -7e4
SIGNATURE: /�� '/ DATE: ]\2___(Ji \q
Addition/Alteration Application Revised February 2019
4 Highland Ave,
a P a:n 90 Queensbury, NY 12804
Phone: 518-798-0793
Fax: 5 i$-798-48b2
Precisfi®w l www.lapansprecision.com
EXECUTIVE DIVISION -) ;. CA
April 11, 2019
APR122019
of ow
RE: 92 Eagan Road, Queensbury BUILDING&
To Whom It May Concern:
The Burnham oil boiler model V-73 with net I=B=R rating of 105 MBH will
adequately heat existing home and new addition. Providing the new addition is
equipped with its own zone and thermostat control.
Sincerely,
Kevin Sumner
BHL Enterprises, LLC dba LaPan's Precision Page 1 of 1
[ � tEDlI
, 0
REScheck Software Version 4.6.3 MAR 2 9 2019
Compliance Certificate
TOWN OF QUEENSBURY
BUILDING&CODES
REVIEWED FOR
Project Residential Addition ENERGY CODE COMPLIANC
Energy Code: 2015 IECC
Location: Glens Falls, New York
Construction Type: Single-family FILE COPY
Project Type: Addition
Climate Zone: 6 (7635 HDD)
Permit Date:
Permit Number:
Construction Site: Owner/Agent: Designer/Contractor:
92 Eagan Road Michael Altare Ethan Peter Hall
Queensbury, NY 12804 92 Eagan Road Rucinski Hall Architecture
Queensbury, NY 12804 134 Dix Ave
Glens Falls, NY 12801
518-741-0268
ephall@nycap.rr.com
Compliance: Passes using UA trade-off
Compliance: 3.4%u Better Than Code Maximum UA: 88 Your UA: 85
The%Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.
Envelope Assemblies
Gross Area Cavity Cont.
Assembly or R-Value R-Value U-Factor UA
Perimeter
Ceiling 1: Raised or Energy Truss 480 49.0 0.0 0.020 10
Wall 1: Wood Frame, 16" o.c. 216 21.0 3.6 0.046 9
Window 1: Wood Frame:Double Pane with Low-E 14 0.290 4
Wall 2: Wood Frame, 16" o.c. 180 21.0 3.6 0.046 7
Window 2: Wood Frame:Double Pane with Low-E 28 0.290 8
Wall 3: Wood Frame, 16" o.c. 216 21.0 3.6 0.046 8
Window 3: Wood Frame:Double Pane with Low-E 14 0.290 4
Door 1: Solid 20 0.300 6
Basement Wall 1: Solid Concrete or Masonry 190 0.0 15.0 0.051 10
Wall height: 7.9'
Depth below grade: 6.0'
Insulation depth: 7.5'
Basement Wall 2: Solid Concrete or Masonry 158 0.0 15.0 0.051 8
Wall height: 7.9'
Depth below grade: 6.0'
Insulation depth: 7.5'
Basement Wall 3: Solid Concrete or Masonry 190 0.0 15.0 0.051 9
Wall height: 7.9'
Depth below grade: 6.0'
Insulation depth: 7.5'
Window 4: Vinyl/Fiberglass Frame:Double Pane with Low-E 6 0.290 2
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence - Eagan Road\Altare.rck Page 1 of10
Compliance Statement: The proposed building design described here is consistent with the building plans,specifications,and other
calculations submitted with the permit application.The proposed building has been designed to meet the 2015 IECC requirements in
REScheck Version 4.6.3 and to comply with the mandatory requiremen isted in t RES ck Inspection Checklist.Ethan Peter Hall-Architect •C 0 g4g. !�/�,,
(J
Name-Title Signa ure,;_ , Date
,, f
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence-Eagan Road\Altare.rck Page 2 of10
,
0 REScheck Software Version 4.6.3
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 100.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section ; Plans Verified Field Verified
& Re ID Pre-Inspection/Plan Review Value i Value Complies? Comments/Assumptions
q .
103.1, Construction drawings and ❑Complies Requirement will be met.
103.2 documentation demonstrate ❑Does Not
[PR1]1 energy code compliance for the Location on plans/spec:A-
building envelope.Thermal ❑Not Observable 1
envelope represented on ❑Not Applicable
construction documents.
103.1, Construction drawings and ElComplies Requirement will be met.
103.2, documentation demonstrate ❑Does Not
I403.7 energy code compliance for Location on plans/spec:A-
[PR3]1 lighting and mechanical systems. [Not Observable 1
Systems serving multiple ❑Not Applicable
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
302.1, Heating and cooling equipment is Heating: Heating: ❑Complies Requirement will be met.
403.7 sized per ACCA Manual S based Btu/hr Btu/hr ❑Does Not
[PR2]z on loads calculated per ACCA Cooling: Cooling: Location on plans/spec: A-
Manual] or other methods Btu/hr Btu/hr [Not Observable 1
approved by the code official. ❑Not Applicable
Additional Comments/Assumptions:
I 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence - Eagan Road\Altare.rck Page 3 of10
Section Plans Verified Field Verified
# Foundation Inspection Value Value Complies? Comments/Assumptions
& Req.ID 1
402.1.1 Conditioned basement wall R- R- ❑Complies See the Envelope Assemblies
[FO4]1 insulation R-value.Where interior R- R- ❑ table for values.
insulation is used, verification Does Not
may need to occur during ENot Observable
Insulation Inspection. Not ❑Not Applicable
required in warm-humid locations
in Climate Zone 3.
303.2 Conditioned basement wall ❑Complies Requirement will be met.
[FO5]1 insulation installed per ❑Does Not
manufacturer's instructions. Location on plans/spec: A-
"
'Not Observable 1
ENot Applicable
402.2.9 Conditioned basement wall ft ft ElComplies See the Envelope Assemblies
[FO611 insulation depth of burial or ❑Does Not table for values.
distance from top of wall.
[Not Observable
❑Not Applicable
303.2.1 A protective covering is installed UComplies Exception: Requirement is
[F01l]2 to protect exposed exterior ❑Does Not not applicable.
I insulation and extends a
minimum of 6 in. below grade. ENot Observable
❑Not Applicable
403.9 Snow-and ice-melting system ❑Complies Exception: Requirement is
[FO1212 controls installed. ❑Does Not not applicable.
['Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence- Eagan Road\Altare.rck Page 4 of10
Section Plans Verified Field Verified
# Framing/Rough-In Inspection Value Value Complies? Comments/Assumptions
& Req.lD i _
402.1.1, Door U-factor. U- U- EComplies See the Envelope Assemblies
402.3.4 ❑Does Not table for values.
[FR1]1 ['Not Observable
❑Not Applicable
402.1.1, Glazing U-factor(area-weighted U- U- EComplies See the Envelope Assemblies !
402.3.1, average). ❑Does Not table for values.
402.3.3, '
402.3.6, ['Not Observable i
402.5 ❑Not Applicable
[FR2]1
303.1.3 U-factors of fenestration products EComplies Requirement will be met.
[FR4]1 are determined in accordance ❑Does Not
with the NFRC test procedure or ['Not Observable Location on plans/spec: A-
taken from the default table. 1
ENot Applicable —
402.4.1.1 Air barrier and thermal barrier ❑Complies Requirement will be met.
[FR23]1 installed per manufacturer's ❑Does Not
instructions. Location on plans/spec:A-
❑Not Observable 1
ENot Applicable
402.4.3 Fenestration that is not site built EComplies Requirement will be met.
[FR20]1 is listed and labeled as meeting ❑Does Not
AAMA/WDMA/CSA 101/I.S.2/A440
or has infiltration rates per NFRC ENot Observable
400 that do not exceed code ENot Applicable
limits.
i
1402.4.5 IC-rated recessed lighting fixtures EComplies Exception: Requirement is
'[FR16]z sealed at housing/interior finish ❑Does Not not applicable.
and labeled to indicate <_2.0 cfm
leakage at 75 Pa. ENot Observable
ENot Applicable
403.2.1 Supply and return ducts in attics EComplies Exception: Ducts located
[FR12]1 insulated >= R-8 where duct is EDoes Not completely inside the
>= 3 inches in diameter and >= building envelope.
R-6 where < 3 inches.Supply and Not Observable
return ducts in other portions of ENot Applicable
the building insulated >= R-6 for
diameter>= 3 inches and R-4.2
for< 3 inches in diameter.
403.3.3.5 Building cavities are not used as EComplies Requirement will be met.
[FR15]3 ducts or plenums. ❑Does Not
ENot Observable Location on plans/spec: A-
❑Not Applicable 1
i
403.4 HVAC piping conveying fluids R- R- EComplies Exception: Requirement is
[FR17]z above 105°F or chilled fluids ❑Does Not not applicable.
below 55°F are insulated to?._R- ['Not Observable
3.
ENot Applicable
403.4.1 Protection of insulation on HVAC EComplies Exception: Requirement is
[FR24]1 piping. ❑Does Not not applicable.
=_ ENot Observable
ENot Applicable
403.5.3 Hot water pipes are insulated to R- R- ElComplies Exception: Requirement is
[FR18]2 >_R-3. ❑Does Not not applicable.
[Not Observable
ENot Applicable ___
403.6 Automatic or gravity dampers are EComplies Requirement will be met.
[FR19]2 installed on all outdoor air ❑Does Not
intakes and exhausts. Location on plans/spec: A-
❑Not Observable 1
ENot Applicable
I 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence- Eagan Road\Altare.rck Page 5 of10
•
Additional Comments/Assumptions:
1 L High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence - Eagan Road\Altare.rck Page 6 of10
Section Plans Verified Field Verified
# Insulation Inspection Value ! Value Complies? Comments/Assumptions
& Req.ID i
303.1 All installed insulation is labeled ❑Complies Requirement will be met.
[IN13]2 or the installed R-values ❑Does Not
provided.
❑Not Observable l
❑Not Applicable
402.1.1, Wall insulation R-value. If this is a R- R- ❑Complies See the Envelope Assemblies
402.2.5, mass wall with at least 1/2 of the ❑ Wood ❑ Wood ❑Does Not table for values.
402.2.E wall insulation on the wall
[IN3]1 exterior,the exterior insulation ❑ Mass ❑ Mass ❑Not Observable
requirement applies(FR10). ❑ Steel ❑ Steel ❑Not Applicable
303.2 Wall insulation is installed per ❑Complies Requirement will be met.
[IN4]1 manufacturer's instructions. ❑Does Not
Location on plans/spec: A-
❑Not Observable 1
❑Not Applicable
Additional Comments/Assumptions:
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence - Eagan Road\Altare.rck Page 7 of10
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID 1
402.1.1, Ceiling insulation R-value. R- R- ❑Complies See the Envelope Assemblies
402.2.1, ❑ Wood ❑ Wood ❑Does Not table for values.
402.2.2, ❑ Steel ❑ Steel ENot Observable
402.2.6
[FI1]1 ❑Not Applicable
303.1.1.1, Ceiling insulation installed per ❑Complies Requirement will be met.
303.2 manufacturer's instructions. ❑Does Not
[F12]1 Blown insulation marked every ['Not Observable Location on plans/spec: A-
300 ft2. 1
❑Not Applicable
402.2.3 Vented attics with air permeable ❑Complies Requirement will be met.
[F122]2 insulation include baffle adjacent ❑Does Not
to soffit and eave vents that Location on plans/spec:A-
extends over insulation. ❑Not Observable 1
❑Not Applicable
402.2.4 Attic access hatch and door R- R- EComplies Requirement will be met.
[F13]1 insulation __R-value of the ❑Does Not
adjacent assembly. Location on plans/spec: A-
❑Not Observable 1
❑Not Applicable
402.4.1.2 Blower door test @ 50 Pa. <=5 ACH 50 = ACH 50 = EComplies Requirement will be met.
[F117]1 ach in Climate Zones 1-2, and EDoes Not
<=3 ach in Climate Zones 3-8. ❑Not Observable Location on plans/spec: A-
1
❑Not Applicable
403.2.3 Duct tightness test result of<=4 cfm/100 cfm/100 EComplies Exception: All ducts and air
[F14]1 cfm/100 ft2 across the system or ft2 ft2 ❑Does Not handlers are located within
<=3 cfm/100 ft2 without air [Not Observable conditioned space.
handler @ 25 Pa. For rough-in
tests,verification may need to ❑Not Applicable
occur during Framing Inspection.
403.3.2 Ducts are pressure tested to cfm/100 cfm/100 EComplies Exception: All ducts and air
[F127]1 determine air leakage with ft2 ft2 ❑Does Not handlers are located within
either: Rough-in test:Total conditioned space.
leakage measured with a ['Not Observable
pressure differential of 0.1 inch ❑Not Applicable
w.g. across the system including
the manufacturer's air handler
enclosure if installed at time of •
test. Postconstruction test:Total
leakage measured with a
i pressure differential of 0.1 inch
I w.g. across the entire system
including the manufacturer's air
handler enclosure.
403.3.2.1 Air handler leakage designated ❑Complies Exception: Requirement is
[F124]1 by manufacturer at<=2%of ❑Does Not not applicable.
design air flow.
❑Not Observable
❑Not Applicable ..I
403.1.1 Programmable thermostats EComplies Requirement will be met.
[FI9]2 installed for control of primary ❑Does Not
heating and cooling systems and Location on plans/spec: A-
initially set by manufacturer to 1
code specifications. ❑Not Applicable
403.1.2 Heat pump thermostat installed EComplies Exception: Requirement is
[FI10]2 on heat pumps. ❑Does Not not applicable.
['Not Observable
❑Not Applicable
403.5.1 Circulating service hot water ❑Complies Exception: Requirement is
i[FI11]2 systems have automatic or ❑Does Not not applicable.
accessible manual controls.
1 ❑Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) j 3 Low Impact(Tier 3)
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence- Eagan Road\Altare.rck Page 8 of10
Section I
I Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
403.6.1 All mechanical ventilation system ❑Complies Exception: Requirement is
1[FI25]2 fans not part of tested and listed ❑Does Not not applicable.
HVAC equipment meet efficacy
and air flow limits. ['Not Observable
ENot Applicable
403.2 Hot water boilers supplying heat ❑Complies Exception: Requirement is
[F126]2 through one-or two-pipe heating ❑Does Not not applicable.
systems have outdoor setback
control to lower boiler water [Not Observable
temperature based on outdoor ENot Applicable
temperature.
403.5.1.1 Heated water circulation systems EComplies Exception: Requirement is
[F128]2 have a circulation pump.The ❑Does Not not applicable.
system return pipe is a dedicated
return pipe or a cold water supply ENot Observable
pipe. Gravity and thermos- ENot Applicable
syphon circulation systems are
not present.Controls for
circulating hot water system
pumps start the pump with signal
for hot water demand within the
occupancy. Controls
automatically turn off the pump
when water is in circulation loop
is at set-point temperature and
no demand for hot water exists.
403.5.1.2 Electric heat trace systems ❑Complies Exception: Requirement is
1[F129]2 comply with IEEE 515.1 or UL ❑Does Not not applicable.
515. Controls automatically
adjust the energy input to the ENot Observable
heat tracing to maintain the ENot Applicable
desired water temperature in the
piping.
403.5.2 Water distribution systems that ❑Complies Exception: Requirement is
[FI30]2 have recirculation pumps that ❑Does Not not applicable.
pump water from a heated water
supply pipe back to the heated ['Not Observable
water source through a cold ❑Not Applicable
water supply pipe have a
demand recirculation water
system. Pumps have controls
that manage operation of the
pump and limit the temperature
of the water entering the cold
water piping to 104°F.
403.5.4 Drain water heat recovery units ❑Complies Requirement will be met.
[F131]2 tested in accordance with CSA ❑Does Not
B55.1. Potable water-side [Not Observable Location on plans/spec: A-
pressure loss of drain water heat 1
recovery units< 3 psi for ENot Applicable
individual units connected to one
or two showers. Potable water-
side pressure loss of drain water
heat recovery units< 2 psi for
individual units connected to
three or more showers.
404.1 75%of lamps in permanent ❑Complies Requirement will be met.
[F16]' fixtures or 75%of permanent ❑Does Not
fixtures have high efficacy lamps. ['Not Observable Location on plans/spec: A-
Does not apply to low-voltage 1
lighting. ENot Applicable
1404.1.1 Fuel gas lighting systems have ❑Complies Requirement will be met.
1
[F123]3 no continuous pilot light. ❑Does Not
ENot Observable Location on plans/spec:A-
1 ENot Applicable
l 1 lHigh Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence - Eagan Road\Altare.rck Page 9 of10
Section Plans Verified Field Verified
Final Inspection Provisions i Value Value Complies? Comments/Assumptions
& Req.ID
401.3 Compliance certificate posted. ❑Complies Requirement will be met.
[F17]2 ❑Does Not
['Not Observable
❑Not Applicable
303.3 Manufacturer manuals for EComplies Requirement will be met.
[F11813 mechanical and water heating ❑Does Not
systems have been provided.
['Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 I Low Impact(Tier 3)
Project Title: Residential Addition Report date: 03/29/19
Data filename: Y:\Honey-Do Man\Altare Residence- Eagan Road\Altare.rck Page 10 of10
2015 IECC Energy
Efficiency Certificate
Insulation Rating R-Value
Above-Grade Wall 24.60
Below-Grade Wall 15.00
Floor 0.00
Ceiling / Roof 49.00
Ductwork (unconditioned spaces):
Glass&Door Rating U-Factor SHGC
Window 0.29
Door 0.30
Heating&Cooling Equipment Efficiency
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments