air ventilation report •
' Glens Falls Therapy Room
L 152 Sherman Ave.
A I R T A C Glens Falls, NY 12801
MECHANICAL
AIR VENTILATION REPORT
AIR DEFFUSER TAG SERVICE DESIGN CFM ACTUAL CFM
CD-1 TREATMENT 250 245
CD-2 CHARTING 250 245
CD-3 OT/PT 500 465
CD-4 OT/PT 500 485
CD-5 �OT/PT 500 525
CD-6 OFFICE 200 225
TOTAL 2200 2190
RETURN AIR TAG
RR-1(RETURN) OT/PT 1100 1095
RR-2(RETURN) OT/PT 1100 1095
TOTAL 2200 2190
EX-1(EXHAUST) RESTROOM 50 50
NOTES No changes were made to the existing mechanical equipment.
We rerouted and adjusted the CFM on the new ductwork as
specified on the drawings.
s '
•