mechanical testing report •
I Mechanical Testing Inc. ac-
Testing Services For Indoor Environments AABC Commissioning
-
Grou
•
CR Bard Building 1 Renovations
FIRM: CUSTOMER:
MTI-Mechanical Testing,Inc. Eckert Mechanical Service Corp
PROJECT#:
4 Chelsea Place,Suite 102 19-433
Clifton Park NY 12065
My Till
PROJECT ADDRESS:
PHONE: 289 Bay Road
(518)450-7292 78 Queensbury NY 12804
FAX: D _ DATE:
(518)450-7295 2019-09-24
SEP 2 6 20192. CONTACT:
Tom Madigan Sustainable Solutions for
TOWN OF QUEENSBURY BUILDING&CODES Efficient Environments
AL,14 WMEN
TM
O PAP B�'o� ,I!
O
. N . OWNED
•��, 15.O' . CERTIFIED BY I NATOENAL C O NCILENT"Pm"
irpt‘vI.1.
�
This is to certify that Mechanical Testing, Inc. has balanced the systems described herein to
their optimum performance capabilities. The testing and balancing has been performed in
accordance with the standard requirements of the Associated Air Balance Council and the
results of these tests are herein recorded.
MTI
Sustainable Solutions for
Efficient Environments
4 Chelsea PI,Suite 102 Clifton Park,NY 12065
Phone:518-450-7292 Fax:518-450-1295
Design Review-Commissioning-Fire Life Safety-Test And Balance-ASHRAE 110-Drone Sales/Inspections
Terms and Abbreviations In.-Inches
In.w.g:Inches of Water Gauge
ACH-Air Changes per Hour ISDFT-Insufficient Straight Duct for Traverse
AHU-Air Handling Unit Kfactor-Correction factor to the free area
AK-Free Area of Duct needed to calculate CFM.
AVG-Average LAT-leaving Air Temperature
BHP-Brake Horsepower LWT-Leaving Water Temperature
BV-Ball Valve(Shut Off Valve) MAU-Make.Up Air Handling Unit
CB-Circuit Breaker MAX-Maximum set point/flow
CBV-Calibrated Balance Valve MIN-Minimum set point/flow
CD-Ceiling Diffuser NI-Not Installed
CFM-Cubic Feet per Minute NIS-Not in Scope
CHWS-Chilled Water System 0/A-Outside Air
CRAC-Computer Room Air Conditioner OBD-Opposed Blade Damper
CS-Circuit Setter 0D-Outside Diameter Measurement of Sheave
CUH-Cabinet Unit Heater. PH-Phase
DAT-Discharge Air Temperature PSI-Pounds per Square Inch
DD-Direct Drive(motor) RA-Return Air
Des.-Design RAT-Return Air Temperature
Disch.-Discharge RF-Return Fan
ONE-Does Not Exist RHC-Reheat Coil
DP-Discharge Pressure of Pump/Pressure Drop RPM-Revolutions per Minute
EA-Exhaust Air RTU-Roof Top Unit
EAV-Exhaust Air Valve SA-Supply Air
EAT-Entering Air Temperature SAV-Supply Air Valve
EF-Exhaust Fan SAT-Supply Air Temperature
EG-Exhaust Grille S.F.-Service Factor
ERU-Energy Recovery Unit SF-Supply Fan
E.S.P.-External Static Pressure SP-Suction Pressure of Pump/Static Pressure
EWT-Entering Water Temperature Sq.ft.-Square Feet
FCU-Fan Coil Unit TAB-Test,Adjust and Balance
FD-Fire Damper TDV-Triple Duty Valve
FLA-Full Load Amperage TP-Thermally Protected
Flow Coeff.—Correction Factor for Flow to VAV TSP-Total Static Pressure
Flow Hood-Instrument that measures airflow. UH-Unit Heater
FPM-Feet per Minute GPM-Gallons Per Minute V-Volts
HEPA-High Efficiency Particulate Arrestance VAV-Variable Air Volume Box
HP-Horsepower VD-Volume Damper
HVAC-Heating Ventilation and Air Conditioning VFD-Variable Frequency Drive
HWS-Hot Water System VVT-Variable Volume Terminal
HX-Heat Exchanger WC-Water Column •
Hz-Hertz
Mechanical Testing Inc, = acg
.11111/' C
Testing Services For Indoor Environments commissionm
AABC Group
LOCATION: PROJECT NUMBER: CONTACT:
CR Bard Building 1 Renovations 19-433 Tom Madigan
289 Bay Road
Queensbury NY 12804
Table of Contents
Instruments Used* 3
Instruments Used 3
Supply Outlet Sheet 4
Supply Outlet Summary.......................... ...... ............... 4.
Return Inlet Sheet 5
Return Inlet Summary 5
Page 2 of 5 2019-09-24
Mechanical Testing Inc. - aC
AABc g
Testing Services For Indoor Environments CommissionimT1
ng Group—
LOCATION: PROJECT NUMBER: CONTACT:
CR Bard Building 1 Renovations 19-433 Tom Madigan
289 Bay Road
Queensbury NY 12804
Instruments Used*
Instruments Used
AIR
Manufacturer Evergreen Calibration Date. 8/19/19
Model No. S-PVF-1 Tech Name TM
Serial No. 1500192
WATER
Manufacturer Not Applicable Calibration Date Not Applicable
Model No. Not Applicable Tech Name Not Applicable
Serial No. Not Applicable
IMAGES:
Air
r e:.
ac-
Calibrat1an Certificate
amsase.wr,EVERGREEH7LlEpgrpy .custa, Haa�s.ca�Tiay k...
Ned* $PVF.1 . a+o wo}
540Ia111mbw:1500102 NYryfidh �,
Anal 15.Wn MRma:
� r
rraG..w.M LLO�MNeMea.L.e�.aLareaveatltparl�w� aatlpY�ayrrwgy
5nw suq.onurwrrx�.aal+vvmwm+eso.evm�m+trrv.xnowermur
ssa.r.aum�va�l:vasnrrRaat�uewdmea�avrew yrybn?Way
"'"'mrum"u2""***m c96S..(GUK awcL mrtsn.n? r
wu.eot.aer.rw .m., aimes.% w.rnlWW'
�wnlou
r..., aw.anuesawnwamauam:e.r.rw
s.rsnetrr,
c -ao.nowwm.onsw,.ssowsu.ana ammo
'^r .sw.arwsm..vmrwrwme.smv v0.10,srm
rnnrr darn.ars.w.masap arruura:rv¢vnanm.
rune asap ea=cummaTcn io •r
rune raaa..armsrmnrtwure r.wevrt : aaM e
si.weamuom.meuw emu. `. sn
wIWTeHW.uw.:'rtR 6 N MM. '
r
olgv
hIDar fe Avg 2019 CypfieataNumber -
Instruments Used Page 3 of 5 2019-09-24
Mechanical Testing Incl. = acg
MTI N AABC
E�5trng Services For Indoor Environments commissioning AABC croup—
LOCATION: PROJECT NUMBER: CONTACT:
CR Bard Building 1 Renovations 19-433 Tom Madigan
289 Bay Road
Queensbuty NY 12804
Supply Outlet Sheet
Supply Outlet Summary .
SUPPLY OUTLET SUMMARY
Name Room No. Type. Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM %of Design
SO-001 119 SA 24x24 1.000 70 70 76 76 76 109 -
SO-002 119 SA 24x24 1.000 70 70 75 75 75 107
SO-003 119 SA 24x24 1.000 70 70 71 71 71 101
SO-004 119 SA 24x24 1.000 70 70 72 72 72 103
SO-005 130 SA 24x24 1.000 80 80 81 81 81 101
SO-006 130' SA, 24x24 3.000 80 80 80 80 - 80 100
SO-007 131 SA 24x24 1.000 70 70 69 70 70 100
Totals - - 510 ., 525
Supply Outlet Summary Page 4 of 5 2019-09-24
•
•
Mechanical Testinginc. = acg
{, AABC
TeSting 'Seri/ices For Indoor Environments Commissioning Group
LOCATION: PROJECT NUMBER: CONTACT:
CR Bard Building 1 Renovations • 19-433 Tom Madigan
289 Bay Road
Queensbury NY 12804
• Return Inlet Sheet
Return Inlet Summary
RETURN INLET SUMMARY
Name Room No. -Type Size AK Factor .Design FPM Design CFM Reading 1 Reading 2 Final CFM %of Design
RI-001 119 RA 24x24 1.100 255 280 155 155 171 61
RI-002 130 RA 24x24 1.100 145 160 180 180 198 124
RI-003 131 RA 24x24 1.100 64 70 45 45 50 71
. Totals '- 510 - 419
NOTES:
Return Inlet Summary
RI-0011%of Design
Damper is verified 100%open.Duct Is off existing system which serves inlets outside of the project scope.
RI-0021%of Design
No volume damper installed.Unable to reduce flow.
RI-0031 Final CFM •
Damper is verified 100%open.
•
Return Inlet Summary Page 5 of 5 2019-09-24