sprayed fireproof testing ATLANTIC TESTING LABORATORIES WBE certified company SPRAYED FIRE RESISTIVE MATERIAL AT3042F-01-06-19 CLIENT: Bette & Cring Construction Group DATE: June 14, 2019 (Friday) PROJECT: Fairfield Inn ATL REPRESENTATIVE: C. Cronin Queensbury, New York DISPATCH NO.: 20657 CONTRACTOR: Frank J. Ryan & Sons, Inc. TEST METHOD STANDARD: Thickness ASTM E 605 FIREPROOFING BRAND: Monokote MK-6 AMBIENT TEMPERATURE (at the time of testing) ° F: 70 THICKNESS MINIMUM MINIMUM REQUIRED REQUIRED TEST MINIMUM INDIVIDUAL MAXIMUM AVERAGE AVERAGE NO. LOCATION THICKNESS (in) THICKNESS (in) THICKNESS (in) THICKNESS (in) THICKNESS (in) 1. W18x76 Beam: Line 6, A.08 to B.4 (Pool Area) 6/16 6/16 10/16 10/16 8/16 2. W18x76 Beam: Line 5, A.08 to B.4 (Pool Area) 10/16 6/16 10/16 10/16 8/16 3. W18x76 Beam: Line 7, A.08 to B.4 (Pool Area) 6/16 6/16 10/16 10/16 8/16 4. W18x55 Beam: Line4, A to B.4 11/16 7/16 11/16 11/16 9/16 5. W16x67 Beam: Line, A to B.4 6/16 6/16 10/16 9/16 8/16 6. W18x55 Beam: Line 9, C to D 8/16 7/16 11/16 10/16 9/16 7. W18x55 Beam: Line 10, C to D 8/16 7/16 11/16 11/16 9/16 REMARKS The test locations were selected by ATL. Mr. Fred Palma, representing Bette & Cring Construction Group, was informed of field observations and test results prior to departure from the site. Reviewed by: Date: June 21, 2019