CC-0675-2019link T&B CERTIFIED TEST ADJUST BALANCE REPORT PROJECT:Target #1830 LOCATION:578 Aviation Rd,Queensbury,NY 12804 ARCHITECT:HYN MECH.ENGINEER:HYN GEN.CONTRACTOR:Groom Construction PROJECT NUMBER:111391 THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL, ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEB PROCEDURAL STANDARDS FOR TESTING,ADJUSTING,AND BALANCING OF ENVIRONMENTAL SYSTEMS, ANY VARIANCES FROM DESIGN QUANTITES,WHICH EXCEED NEBB TOLERANCES,ARE NOTED IN THE TEST-ADJUST-BALANCE REPORT PROJECT SUMMARY.” ORIGINAL VISIT DATE:06/09/20 5140 River Road,Milford,Ohio 45150 USA Phone:(513)965-7300 +Fax:(513)965-7350 www.melinkcorp.com +mail@melinkcorp.com NEBB TAB CERTIFICATION PROJECT:Target #1830 DATE:6/9/2020 LOCATION:578 Aviation Rd,Queensbury,NY 12804 NEB Certified Professional:Larry Moore NEBB Certified Professional:Darren Witter Melink Corporation Energy solutions for a brighter tomorrow Page: TABLE OF CONTE! PROJECT:Target #1830 LOCATION:578 Aviation Rd,Queensbury,NY 12804 Table Of Contents Cover PageveeNEBBCertification... Table of Contents Abbreviations... Melink Credentials Contact Information.. Equipment Information.. 1st Visit Summary..... Punch List (Airflow Related). Punch List (Non-Airflow Related)1st Visit Photos...oe Rooftop Inspection...... Above Ceiling.Inspection.. Below Ceiling.Inspection Building Balance Motor Load Summary. RTUData.... RTU Air Distribution Data - Exhaust Fan Data EF Air Distribution Data Thermostat Settings.. Building Layout .. Melink Corporation DATE:6/9/2020 Energy solutions for a brighter tomorrow Page: ABBREVIATIONS PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 ABBREVIATIONS AHU Air Handling Unit AMP -Amperage BP ~Building Pressure CFM -Cubic Feet/Minute EF—-Exhaust Fan EH -Entry Heater ERU=Energy Recycling Unit ESP External Static Pressure FLA Full Load Amperage HP.-Horse Power HZ -Hertz KH -Kitchen Hood KW -Kilowatt MUA -Makeup Air Unit Volts -voltage OA—-Outside Air RA ~Return Air RPM -Revolutions Per Minute RTU—-Roof Top Unit SF Supply Fan /Safety Factor SP -Static Pressure VAV Variable Air Volume WC Water Column Melink Corporation Energy solutions for a brighter tomorrow Page « MELINK CREDENTIALS PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 About Melink Values Our core values -integrity,innovation,and service excellence -are the essence of who we are as a company.They serve as the foundation for our words,actions and goals.Our culture starts with the above core values but also promotes professionalism,excellence,and leadership,as well as respect,faimess and charity. Experience For more than 25 years,Melink has been providing independent testing and balancing and installation verification services,thereby reducing operating costs and improving comfort for thousands of buildings.Collectively,Melink staff has over 150 years of experience in testing and balancing,installation verification,kitchen ventilation controls,HVAC design/consulting, HVAC service/installation,LEED building certification,indoor air quality testing,and solar PV installation/application Certifications Melink has individuals on staff with the following certifications: NEBB Certified TAB Professionals NEBB Certified TAB Technicians Professional Engineers (PE) LEED Accredited Professionals (LEED AP) North American Board of Certified Energy Practitioners (NABCEP) Project Management Professionals (PMP) Certified Project Managers (CPM) Six Sigma Certified (SSWB,SSGB,SSBB) Affiliations Melink is proud to be associated with the following organizations: The National Environmental Balancing Bureau (NEBB) The American Society of Heating,Refrigerating and Air-Conditioning Engineers (ASHRAE) The U.S.Green Building Council (USGBC) The Professional Retail Store Maintenance Association (PRSM) The Restaurant Facility Management Association (RFMA) The Association of Energy Engineers (AEE) The American Solar Energy Society (ASES) The Solar Energy Industries Asso,oan*The North American Asgpgiatjan, ration ivRTENaRUfRarers (NAFEM)Page! TEST AND BALANCE CONTACT INFORMATION PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804. PROJECT MANAGER:Theresa Croaston Phone:N/A E-mail:theresa.croaston@target.com SUPERINTENDENT:George Ste Marie Phone:(651)245-1735 E-mail:gstemarie@groomco.com MECH.CONTRACTOR:N/A Phone:N/A E-mail:N/A MELINK TECHNICIAN:Issac Clarke Phone:(513)965-6063 iclarke@melinkcorp.comE-ma STRATEGIC ACCOUNT MANAGER:Megan Parker Phone:(513)965-7302 E-mail:target@melinkcorp.com Melink Corporation Energy solutions for a brighter tomorrow Page ¢ EQUIPMENT INFORMATION PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 FLOW Hoop: Model #: Serial #: Calibration Due Date: TEMPERATURE/HUMIDITY PROBE: Model #: Serial #: Calibration Due Date: VOLTMETER/AMPMETER: Model #: Serial #: TACHOMETER: Model #: Serial #; Calibration Due Date: MANOMETER: Model #: Serial #: Calibration Due Date: Evergreen 318 1800110 11/25/20 Evergreen PR-T-5ISH3-5 1900539/2000110 4nisi2i Fluke 43230883WS 2 12/13/24 Extech RPM33 190329264 213/21 Evergreen NA 1800331 7/8/20 Melink Corporation Energy solutions for a brighter tomorrow Page * FIELD MARY:CORRECTIONS PROJECT:Target #1830 DATE:06/09/20 NY 12804 This air balance report is based on actual field readings and measurements taken from the store’s HVAC systems during operation.All systems were also balanced to within +/-10%of design unless noted otherwise. The following corrections were performed by Melink and/or the contractors on-site. Arrival and Contact Field Notes: Melink arrived onsite and met with the Superintendent,George.The scope of work was discussed and access was granted to all areas of the store needed to complete the scope. The visit began with initial safety inspections and verification of relocated or newly installed diffusers. Prior to beginning the balance,Melink was informed that the fitting rooms area was uncomfortable and there have been many customer complaints. Roof Top Unit "RTU"Field Not This condensed scope balance did not include the RTU's,only diffusers that had been relocated or newly installed.No RTU unit or test data was collected. Exhaust Fan Field Notes: The restroom exhaust fan was not included in the scope,only the two diffusers in the restrooms.No unit or test datawascollectedfromthisfan. TF-2 was found to be operational upon initial inspection,however this unit is installed backwards and is providing exhaust from the open office area.This will need to be corrected in order to operate as designed.It should be notedthatthefanspeedwassetandmarked,in order to avoid an additionally revisit for this fan,should this be approved by the appropriate party. Air Di Many diffuser were found to be operating below design airflow with the volume dampers 100%open.This includes the fitting rooms,open office,AP office and market area.A full balance of these systems should be performed in order to ensure overall comfort. Diffusers that were operating at or above near design airflow were properly balanced for airflow. Air Distribution EF Field Note: TF-2 was measured and the speed control marked,although this fan is installed backwards. The exhaust fan which serves the restrooms is operating below design airflow.A full balance of this system should be performed in order to ensure proper exhaust airflow. Building Balance and Project Completion Field Note: Upon completion of the balance Melink spoke again with the Superintendent,George as well as the PMT.All punchlistitemswerediscussedaswellastheoverallresultsofthebalance. Melink Corporation Energy solutions for a brighter tomorrow Page t FIELD SUMMARY:PUNCH LIST (Airflow Related) PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 The following list details the remaining deficiencies of the store’s HVAC and exhaust systems.These corrections are necessary to comply with the design specifications. Contractor Responsible 1:Reverse orientation of TF-2,which serves the TSC room Mechanical TF-2 which serves the TSC room is installed backwards and is exhausting air from the office area into the TSC room.This fan must be reversed in order to provide exhaust to the TSC room.It should be noted that this fan is balanced and the speed control position marked. 2: PerformafullbalanceoftheRTUwhichservestheopenofficearea. Owner Diffuser XM which serves the open office area is operating below design airflow with the damper 100% open.A full balance of the RTU and connected load should be performed in order to ensure comfort in this area 3:Perform a full balance of the RTU which serves the AP office Owner Diffuser XL which serves the AP office has no recordable airflow with the damper 100%open.The RTU should be investigated for proper operation andafullbalanceoftheRTUandconnectedloadshouldbeperformedinordertoensurecomfortinthisarea. 4;Performafullbalanceoftheexhaustfanwhichservestherestrooms.Owner The exhaust grilles which serve both the men's and women's restrooms are operating below design airflow with the dampers 100%open.A full balance of this exhaust fan is recommended in order to ensure proper exhaust airflow 5:Perform a full balance of the RTU which serves the fitting rooms.Owner The fitting room diffusers are operating below design airflow with the dampers 100%open.A full balance of the RTU and the connected load should be performed in order to properly balance these diffusers and ensure comfort in the conditioned space. 6:Perform a full balance of the RTU which serves the market area.Owner The market area diffusers are operating below design airflow with the dampers 100%open.A full balance of the RTU and the conditioned space should be performed in order to properly balance these grilles as well and ensure comfort in the conditioned space. Melink recommends a revisit due to the airflow deficiencies listed above. Recommended Revisit:_Yes Before Opening:_N/A After Opening:N/A Please contact Melink to request a revisit.(513)965-7300 Melink Corporation Energy solutions for a brighter tomorrow Page ¢ FIELD IMMARY:PUNCH LIST (Non:low Related) PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 The following list details the remaining deficiencies of the store’s HVAC and exhaust systems.These corrections are necessary to comply with the design specifications. Contractor Responsible 1:Install thermostat in TSC room for TF-2.Mechanical There is not thermostat installed in the TSC room at this time.This must be completed in order to comply with the design prints as well as to ensure the room is comfortable. Melink Corporation Energy solutions for a brighter tomorrow Page 1( iF tence PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 a2:Linear diffuser installed in the correctarea1:Diffuser installed in the correct area. 5:Safety disconnect installed for TF-2.FgrilleinstalledwithdampersMelinkCorporation Energy solutions for a brighter tomorrow Page 1° PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 a9:TF-2 thermostat not installed.10:Damper 100%open (diffuser operating below design airflow). Melink Corporation Energy solutions for a brighter tomorrow Page 1% ROOFTOP INSPECTION PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 A\n Rd,Queensbury,NY 12804 DESCRIPTION STATUS STANDARD Verify proper unit locations Verify units marked for easy identification Inspect units Unit sealed and properly seated to roof curb Unit nameplate data matches design Motor nameplate data matches design No unusual vibration or noise All filters installed,clean and secure Condenser coil clean and free of damage Evaporator coil clean and free of damage Gas cocks tured on Gas pipe painted Condensate drain lines properly installed P-Traps properly installed Drain lines properly sloped Remove unit access panels Panels open freely and fully Panels latch securely Belts properly tensioned and free of damage Pulleys properly aligned Set screws properly secured Blower wheel clean and free of damage Control transformer wired for correct voltage Check disconnect switches and covers Verify on/off disconnects work Verify voltage input correct Verify switch covers installed Power-on diagnostic check Fans operating in correct rotation Compressors operating in correct rotation No unusual vibration or noise Outside air (OA)dampers Outside air dampers installed and operational Ensure slightly positive building pressure Position marked for reference Sticker affixed to unit to preclude tampering Melink Corporation Energy solutions for a brighter tomorrow Page 1: ROOFTOP INSPECTION PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 DESCRIPTION STATUS TFIEF STANDARD Verify proper unit locations Verify units marked for easy identification Inspect units Unit sealed and properly seated to roofcurb INZAT NIA] Unit nameplate data matches design VINA Motor nameplate data matches design V[NAl No unusual vibration or noise Vv [NAl Exhaust fans (EF) Transition from exhaust ductto fan installed N/ATN/Al Duct continuously welded and liquid tight NAL NA| Fan hinged and opened for easy access IN/AIN/Al Grease traps properly installed N/ALN/Al Remove unit access panels Panels open freely and fully NIAINZA Panels latch securely N/A|N/Al Belts property tensioned and free of damage NAINA Pulleys properly aligned NAINA Set screws properly secured N/A|N/Al Blower wheel clean and free of damage IN/alN/Al Check disconnect switches and covers Verify on/off disconnects work Verify voltage input correct Verify switch covers installed Power-on diagnostic check Fans operating in correct rotation Melink Corporation Energy solutions for a brighter tomorrow Page 1 BELOW CEILING INSPECTION PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 A\jon Rd,Queensbury,NY 12804 DESCRIPTION STATUS STANDARD Thermostats Remote sensor is installed in its correct location Remote sensor is wired to the proper thermostat Thermostat has proper operation Thermostat is programmed correctly Unit was cycled to verify proper operation Heating mode tested satisfactorily Cooling mode tested satisfactorily Comfort Noticeable drafts?No Comfort is good in all areas?No Communication Final results were discussed with Superintendent Yes Project manager N/A Store manager (if applicable)No A punch list of deficiencies was provided to: Superintendent and/or operations Yes Project manager N/A Store manager (if applicable)No Business card was left on site with contact info.[Yes Melink Corporation Energy solutions for a brighter tomorrow Page 1f MOTOR LOAD SUMMARY PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 INITIAL RTUX 0 TF2 EF-B TOTAL +03 TEST RESULTS IN AMPS ) FINAL RTUX o TF2 o7 EFB 0 TOTAL -O07 MOTOR AMP SAVINGS -0.4 AMPS EFFICIENCY 119 % Melink Corporation Energy solutions for a brighter tomorrow Page 1€ ROOFTOP UNITS (RTU)DATA PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 Design Data Scheduled CFM (SA) Supply CFM (Load)| Return CFM. Outside Air CFM Outside Air Ratio %| Model Number Capacity (Tons) External SP. Fan HP. Volts/Phase Fan RPM Equip.Data Unit MFR Model No. Serial No. Rated Tons Fan Motor 7 HP Volts/Phase FLAISF Belts) Sheave Centerline Test Data RPM -Initial/Final Actual Volts Final Operating Amps RevSuction/Discharge| External SP. Motor Hertz Supply CFM Return CFM. Outside Air CFM Outside Air Ratio %| RTU-X General N/A 4125, 4125 0 0% N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A|N/A N/A|N/A N/A|N/A N/A N/A 3325 3325 0 0% Melink Corporation Energy solutions for a brighter tomorrow Page 17 AIR DISTRIBUTION PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 SYSTEM:RTU-X General DESIGN PRELIM FINAL No.AREA SERVED TYPE OUTLET SIZE CFM cFM cFM XA Fitting aay 24"x24"135 73 73 XB Fitting Linear ax"250 142 142 XC Fitting linear ax 250 134 134 xO Fitting Linear axr 250)106)106 XE Guest Services Linear axi"260 278 267 XF Guest Services Linear axi 260 303 258 XG Flexible Fulfillment|Wall Grille a"x8"250 189 240 XH Flexible Fulfilment|Wall Grille "xe"200 202 193, XI Coffee Service a-Way 24"x24"460 768 446 xi Food Prep.4-Way 10"x10"250 261 261 XK Food Prep Way 10"x 10"250 290 256 XL AP Office 4-Way 24"x24"220 0 0 XM.Office a-Way 24"x24"110 146 iii XN Open Office away 24"x24"180 115 115) XO Market Ceiling Grille|24"x6"400 366 366 XP Market CeilingGrille|24"x6"400 357 357 RXA N/A [NA |NA |[4125 [|3325 RTU-X SUPPLY AIR CFM 4125 3730 3325 RTU-X RETURN AIR CFM 4125 3325 RTU-X OUTSIDE AIR CFM 0 a RTU-X OUTSIDE AIR RATIO %0%0% Melink Corporation Energy solutions for a brighter tomorrow 54% 57% 54% 42% 103 % 99% 96% 97% 97% 104% 102% 0% 1101 % 64% 92% 89% 81% 81% 81% Page 1 Ge PROJECT:Target #1830 fay OK) DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 Design Data Scheduled CFM (EA) Exhaust CFM (Load) Model Number External SP. Fan HP Volts/Phase Fan RPM, Equip.Data Unit MFR Model No| Serial No. Fan Motor HP. RPM Volts/Phase FLAISF, Motor Sheave Fan Sheave Belt(s) Sheave Centerline Test Data RPM -Initial/Final Actual Volts Final Operating Amps| Ret/Suction/Discharge| External S.P. Motor Hertz Exhaust CFM TF-2 TSC Room 140 140 SQ-70 0.25" N/A 120/1 1550 Greenheck 0-70-6 16636110 N/A N/A N/A N/A N/A_[_N/A Direct Drive Direct Drive Direct Drive Direct Drive vsc_[vsC 118|N/A|N/A 07|N/A|N/A N/A|N/A [N/A N/A N/A 140 EF-B Restrooms N/A 1100 N/A N/A N/A N/A N/A N/A NA N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 442 Melink Corporation Energy solutions for a brighter tomorrow Page 1 ONS Me aiden le)ey wey PROJECT:Target #1830 LOCATION:578 Aviation Rd,Queensbury,NY 12804 DATE:06/09/20 SYSTEM:TF-2 TSC Room DESIGN PRELIM FINAL, No.AREA SERVED TYPE OUTLET SIZE CFM CFM cFM[aT TSC [Ceiling Gritle |2a"x12"][140 [465 140 ]100% TF-2 EXHAUST AIR CFM ][1407 T 465 TJ 140 ]100% SYSTEM:EF-B Restrooms DESIGN PRELIM FINAL No.AREA SERVED TYPE OUTLET SIZE CEM crm cFM EBA Men Ceiling Grille 8"x8"550 275 275 |50% EBB Women Ceiling Grille axe"550 167 167 |30% EF-B EXHAUST AIR CFM ‘|[2t00 TT 4a2 442 ]40% Melink Corporation Energy solutions for a brighter tomorrow Page 2( ERMOSTAT SETTINGS PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 Equip.Data RTU-X General Manufacturer Model Number Location Program OCCUPIED Heat °F Cool °F Start Time (Primary) Start Time (Secondary) UNOCCUPIED Heat °F Cool *F Start Time (Primary) Start Time (Secondary) Setup Fan Occupied Fan Unoccupied Sensor Lock-Out EMS Installed Melink Corporation Energy solutions for a brighter tomorrow Page 2° BUILDING LAYOUT PROJECT:Target #1830 LOCATION:578 Aviation Rd,Queensbury,NY 12804 DATE:06/09/20> N DETAIL le DETAI! 1 DETAI 2 DETAIL DETAIL | 5 |4 DETAIL 3 Melink Corporation Energy solutions for a brighter tomorrow Page 2: BUILDING LAYOUT PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 >N ke I ] 4IFlees I d H. eMeNsome__|fn Seeks er es Melink Corporation Energy solutions for a brighter tomorrow Page 2: BUILDING LAY‘ PROJECT:Target #1830 DATE:06/09/20 LOCATION:578 Aviation Rd,Queensbury,NY 12804 >N DETAIL 5 DETAIL 6 F ‘ OPEN mm OFFICE xo MARKET———, AREA Tsc 9. Ps ROOM (7 + xn TRA ” Melink Corporation Energy solutions for a brighter tomorrow Page 2«