HVAC calculator EMS Calculator Page 1 of 14
pECEOWE
EMS HVAC Load Calculator DEC o 7 2018
www.hvacloadcalculator.com
TOWN OF OUEENSBURY
BUILDING&CODES
Date: Fri Dec 7 Loaded Document: gf info -
2018 09:39am
Company Info Client Information
Company GF HEATING OIL LLC Name Mary McCoslin
Preparer BRIAN NELSON Addressl 65 ROCKHURST RD QUEEN
Phone (518) 792-2220 Address2
Email brian@gfheatingoil.com Address3
Phone (321) 231-4597
Email
Date 07-Dec-2018
This HVAC load calculation has been performed using sound engineering principles as
prescribed by Manual J eighth edition and ASHRAE Handbook of Fundamentals. Duct sizing has
been performed as prescribed by Manual D.
1. Design Conditions(Temp. F)
Check If Using Celcius
INDOOR OUTDOOR TEMP Front of West
DIFF Building is
Facing
WINTER 70 -20 90
Total 1400 Sq.Ft
SUMMER 65 90 25 Conditioned
Area
https://ems-residential.hvacloadcalculator.com/app/ 12/7/2018
EMS Calculator Page 3 of 14
Distance of OH from top of 1.6 1.6 1.6 1.6
window (A)
Length of overhang (B) 1.6 1.6 1.6 1.6
Total linear ft. across top 4 7 0 0
of windows located below
overhang
Solar GainThrough Glass
Check this box if using manufacturer specifications and enter the latitude, U-value
and SHGC
Latitude 45 U-Value SHGC
Facing Area(sq ft) Type Glass HTM Unshaded Shaded BTUH
North or 51 Double v 24.00 0 51 1,224
Shaded
NE/NW 0 v 0.00 0 0 0
South 45 Double v 40.00 45 0 1,800
SE/SW 0 v 0.00 0 0 0
East 19 Double v 75.00 19 0 1,425
West 200 Double v 75.00 200 0 15,000
Does glass have reflective Yes v 0.6 11,669
coating?
Skylight 0 Clear v 150 0
Total 11,669
Solar Gain
https://ems-residential.hvacloadcalculator.com/app/ 12/7/2018
EMS Calculator Page 6 of 14
* CAUTION - The cooling capacity of the air conditioner must meet
both, sensible and latent loads. It is recommended a Manual S
calculation be performed. Using manufacturer's specs. The nominal
tons assume .75 S/T ratio at the chosen outdoor design temperature.
Summary Including Basement
Heating Load Sensible Cooling Latent Cooling Total Cooling Load Nominal Tons
39,870 19,342 3,101 22,442 2.04
Whole House (Block Load) Completed
Scroll to top For Additional Options
Solar Gain Through Glass
.m�Check if Using Manufacturer specs
Latitude 40 U-Value SHGC
Facing Area(sq ft) Type Glass HTM BTUH
North or 0 Double 24.00 0
Shaded
NE/NW 0 \, 0.00 0
South 0 Single ' 50.00 0
SE/SW 0 v 0.00 0
East 0 V 0.00 0
West 70 Tripl or Low-I v 65.00 4,550
Does glass have reflective coating? Yes v 2,730
https://ems-residential.hvacloadcalculator.com/app/ 12/7/2018
EMS Calculator Page 8 of 14
Basement Summary
Heating Load Sensible Cooling Latent Cooling Total Cooling Load *Nominal Tons
7,377 3,789 851 4,141 0.40
* CAUTION - The cooling capacity of the air conditioner must meet
both, sensible and latent loads. It is recommended a Manual S
calculation be performed. Using manufacturer's specs. The nominal
tons assume .75 S/T ratio at the chosen outdoor design temperature.
Room by Room Load Calculation
Total House Total House System CFM
Cooling Heating
Heat Loss Sensible Heat 1200 800
Gain
39,870
19,342
♦Add Room Room HeatLoss HeatGain CFM_Heat CFM_Cool
Name
:iCheck-Calculations-When-Completed
auto- 7,377 3,789 148 235
basement
Totals: 7,377 3,789 148 235
Percent Of Original: 18% 19%
IRound to Rectangle Conversion Calculator(Optional)
Enter Round Side A (Inches) Side B (Inches)
Diameter
0 0
https://ems-residential.hvacloadcalculator.com/app/ 12/7/2018
EMS Calculator Page 10 of 14
4th reduction or branch 0
5th reduction or branch 0
Basement supply and return 148
trunk
Room Runs cfm no of outlet duct air
outlets cfm dia vel
auto-basement 0 0
Duct Sizing Completed
Scroll to top For Additional Options -►
Equipment selection as per Manual S
Instructions: enter load, weather and manufacture's data in white cells
Auto Complete
BTUH
Total Heat Loss 39870 Design Outdoor Indoor
Conditions
Total Heat Gain 21942 -20 70
Sensible Heat 19342 90 65
Gain
Latent Heat Gain 2,601 ID Design RH 50%, 63F WB
Sensible/Total 0.88 Altitude 344
Ratio
target clg Temp. 17 Predominantly Heating climat v
Drop
Manufactures Equipment Specifications
https://ems-residential.hvacloadcalculator.com/app/ 12/7/2018
EMS Calculator Page 11 of 14
Equipment Manufacturer Model BTUH Total Sensible Latent
No output cooling BTUH BTUH
(heating) BTUH ®
OD
design
temp
Furnace RUUD R9 60000 r2.,gCt��0bDi31-1 YY15A
Boiler 0 0
Heat Pump RUUD RA 24000 24000 0
or Air
Conditioner SQ.1\13)-4 1 it A
Evaporator RUUD RC at-i(`lST/ayy)c-is
Coil
Air Handler
Total 59174.4 23876.16 23876.16 0
Capacity
with
Altitude
Correction
Selected OVERSIZED OK OK UNDERSIZED
Equipment
Size
Heating CFM Cooling CFM External Static Pressure of
(recommended) Blower
1200 1,277 0
Available static presure for Supplemental heat needed for heat
duct system pump
Blower ext. 0 HP capacity @ 47F 0
static press
Coil press HP capacity @ 17F 0
0
drop*
https://ems-residential.hvacloadcalculator.com/app/ 12/7/2018
EMS Calculator Page 12 of 14
Filter press 0 HP capacity ® 0
drop* ODDT
Register press 0 BTUH 39,870
drop supplemental heat
Grille Pressure 0 KW supplemental 12
Drop heat
Other 0
Other 0
Other 0
Available SP 0
for duct
Equipment Size Limits
Air conditioner- Furnace Boiler
heat Pump
Cool Climate Heat output output
Climate
Maximum Size 25,234 27,428 55,818 55,818
Selected OK OK OVERSIZED OVERSIZED
Size
Energy Cost Analysis
Heat Loss 39,869.91 Heating Degree Days 7000
Heat Gain 21,942.44 Cooling Degree Days 500
Summer Design 90 Summer Design Temp 25
Temp Diff
https://ems-residential.hvacloadcalculator.com/app/ 12/7/2018