ComCheck COMcheck Software Version 4.0.8.1 3 cc 3
• Interior Lighting Compliance Certificatect) a .
Project Information7:3 CA
12 I co
t�
Energy Code: 90.1 (2013)Standard DEC 2 8 2018 l� ta<
Project Title: Walmart Store#4403 '� C n
Project Type: Alteration O WN` --q----- n
BU!ii;,;OF� E�tSuU�Y O
ul
Construction Site: Owner/Agent: Designer/Contractor: ;�"" N C)
24 quaker Ridge Blvd -P W
Queensbury, NY 12804
to O
Allowed Interior Lighting Power H co
A B C
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B X C)
1-Breakroom(Common Space Types:Lounge/Breakroom) 856 0.73 625
2-Rear Mens Restroom(Common Space Types:Restrooms) 245 0.98 240
3-Rear Womens Restroom(Common Space Types:Restrooms) 310 0.98 304
4-Mothers Room(Common Space Types:Restrooms) 113 0.98 111
5-Front Mens Restroom(Common Space Types:Restrooms) 246 0.98 241
6-Front Womens Restroom(Common Space Types:Restrooms) 321 0.98 315
7-Grocery Sales(Retail:Sales Area) 23060 1.44 33206
8-Deli(Common Space Types:Food Preparation) 972 1.21 1176
9-Health Services(Healthcare Facility:Pharmacy) 50 1.68 84
10-Receiving(Common Space Types:Storage) 11342 0.63 7145
11-Bakery(Common Space Types:Food Preparation) 540 1.21 653
12-Bakery Sales(Common Space Types:Food Preparation) 1600 1.21 1936
13-Site-to-Store Storage(Common Space Types:Storage) 1011 0.63 637
14-Rear Office Hallway(Common Space Types:Storage) 1517 0.63 956
Total Allowed Watts= 47629
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Waft.
Breakroom(Common Space Types:Lounge/Breakroom 856 so.ft.)
LED 1: 10:2'X4'LED Troffer:Other: 1 19 30 570
Rear Mens Restroom(Common Space Types:Restrooms 245 sq.ft.)
LED 2:existing:Circular Recessed Downlight:Other: 1 10 12 120
LED 3:65:2'Vanity Light:Other: 1 3 21 63
Rear Womens Restroom(Common Space Types:Restrooms 310 sq.ft.)
LED 4:existing:Circular Recessed Downlight:Other: 1 14 12 168
LED 5:65:2'Vanity Light:Other: 1 3 21 63
Mothers Room(Common Space Types:Restrooms 113 sq.ft.)
LED 7:68:Circular Recessed Downlight:Other: 1 2 12 24
Front Mens Restroom(Common Space Types:Restrooms 246 sq.ft.1
LED 8:68R:Circular Recessed Downlight:Other: 1 11 12 132
Project Title: Walmart Store#4403 Report date: 12/03/18
Data filename: M:\02\02-19-24403 Queensbury, NY 4403\MEPF\ELEC\ELEC\ComCheck\4403 Queensbury, NY.ct Page 1 of 7
•
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Waft.
LED 9:65:2'Vanity Light:Other: 1 4 21 84
Front Womens Restroom(Common Space Types:Restrooms 321 sq.ft.)
LED 10:existing:Circular Recessed Downlight:Other: 1 15 12 180
LED 11:65:2'Vanity Light:Other: 1 4 21 84
Grocery Sales(Retail:Sales Area 23060 sq.ft.)
Linear Fluorescent 1: Existing:8'Fluorescent Strip:Other:Electronic: 4 187 120 22440
LED 15:34:8'LED Strip:Other: 1 14 53 742
Deli(Common Space Types:Food Preparation 972 sa.ft.)
LED 12:7: 1'X4'LED Troffer:Other: 1 9 30 270
LED 13:9:2'X2'LED Troffer:Other: 1 24 32 768
Health Services(Healthcare Facility:Pharmacv 50 soft.)
LED 14:9:2'X2'LED Troffer:Other: 1 2 32 64
Receiving(Common Space Types:Storage 11342 sa.ft.)
Linear Fluorescent 2:2C:4'Fluorescent Strip:Other:Electronic: 2 2 58 116
Linear Fluorescent 3:Existing:8'Fluorescent Strip:Other:Electronic: 4 44 120 5280
Bakery(Common Space Types:Food Preparation 540 sq.ft.)
LED 15:7: 1'X4'LED Troffer:Other: 1 4 30 120
LED 16:9:2'X2'LED Troffer:Other: 1 12 32 384
Bakery Sales(Common Space Types:Food Preparation 1600 sq.ft.)
LED 17:7: 1'X4'LED Troffer:Other: 1 9 30 270
LED 18:9:2'X2'LED Troffer:Other: 1 43 32 1376
Site-to-Store Storage(Common Space Types:Storage 1011 sq.ft.)
Linear Fluorescent 4:existing:2'X4'Fluorescent Troffer:Other: 2 13 79 1027
Rear Office Hallway(Common Space Types:Storage 1517 sq.ft.)
Linear Fluorescent 5:2C:4'Fluorescent Strip:Other:Electronic: 2 2 58 116
Linear Fluorescent 6:Existing:8'Fluorescent Strip:Other:Electronic: 4 11 120 1320
Total Proposed Watts= 35781
nterior Lighting PASSES
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application.The proposed interior lighting
systems have been designed to meet the 90.1 (2013)Standard requirements in COMcheck Version 4.0.8.1 and to comply with
any applicable mandatory requirements listed in the Inspection Che klist.
z t-: c.,0A _ / ('- • • 1)-
Name Title Signature —�7i Date
a .
r �L'"d,7111-
_
/1,i
� ww �
m —.. •i w
?r 092954-1 c.
Fo i(cr
A
R�FESSi0''�'
NEW PORK
ALTER A T ION WARNING
IT IS A VIOLATION O!'NEW YORK
REGULATION 7200 FOR ANY PERSON.
UNLESS WING UNDER THE
DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER.TO ALTER
AN ITEM IN ANY WAY WI'PiaU''
AFFIXING TO THE ITEM HIS SEAL AND
THE NOTIFICATION"ALTERED Er.
FOLLOWED BY A SIGNATURE.DATE OF
SUCH ALTERATION.AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
Project Title: Walmart Store#4403 Report date: 12/03/18
Data filename: M:\02\02-19-24403 Queensbury, NY 4403\MEPF\ELEC\ELEC\ComCheck\4403 Queensbury, NY.cc Page 2 of 7
COMcheck Software Version 4.0.8.1
raft Exterior Lighting Compliance Certificate
Project Information
Energy Code: 90.1 (2013)Standard
Project Title: Walmart Store#4403
Project Type: Alteration
Exterior Lighting Zone 2(Residential mixed use area)
Construction Site: Owner/Agent: Designer/Contractor:
24 quaker Ridge Blvd
Queensbury, NY 12804
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts/Unit Wattage (B X C)
Total Tradable Watts(a)= 0
Total Allowed Watts= 0
Total Allowed Supplemental Watts(b)= 600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
Exterior Lighting TBD: Invalid exterior use type
Project Title: Walmart Store#4403 Report date: 12/03/18
Data filename: M:\02\02-19-24403 Queensbury, NY 4403\MEPF\ELEC\ELEC\ComCheck\4403 Queensbury, NY.cc Page 3 of 7
COMcheck Software Version 4.0.8.1
Inspection Checklist
Energy Code: 90.1 (2013) Standard
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
' Section
# Nan Review ; Complies? I Comments/Assumptions
&-Req.ID
4.2.2, Plans, specifications, and/or ❑Complies Requirement will be met.
8.4.1.1, calculations provide all information ❑Does Not
8.4.1.2, with which compliance can be
8.7 determined for the electrical systems ❑Not Observable
[PR6I2 and equipment and document where ❑Not Applicable 1
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
'sized for maximum drop of 3%.
4.2.2, Plans, specifications, and/or ❑Complies Requirement will be met.
9.4.3, 9.7 calculations provide all information ❑Does Not
[PR4]1 with which compliance can be ❑Not Observable'.
determined for the interior lighting
and electrical systems and equipment :ENot Applicable
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
9.7 Plans, specifications, and/or DComplies
[PR8]1 !calculations provide all information LiDoes Not
with which compliance can be
determined for the exterior lighting Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Walmart Store #4403 Report date: 12/03/18
Data filename: M:\02\02-19-24403 Queensbury, NY 4403\MEPF\ELEC\ELEC\ComCheck\4403 Queensbury, NY.cc Page 4 of 7
section I ,... .. r i �"4,,t
$�'� # Rough-in Electrical' Inspection Co n� �' �'„� �
Regsl®
8.4.2 At least 50%of all 125 volt 15-and DComplies Requirement will be met.
[EL10]2 20-Amp receptacles are controlled by ❑Does Not
an automatic control device.
❑Not Observable
❑Not Applicable
9,4.1.1 : Automatic control requirements DComplies Requirement will be met.
EL1]2 prescribed in Table 9.6.1,for the ❑Does Not •
appropriate space type, are installed. ENot Observable
Mandatory lighting controls (labeled
as 'REQ') and optional choice controls ❑Not Applicable
(labeled as'ADD1' and 'ADD2')are
implemented. •
9.4 1.1 ' Independent lighting controls installed DComplies Requirement will be met.
EL2]2 per approved lighting plans and all ❑Does Not
manual controls readily accessible and!
visible to occupants. ❑Not Observable
❑Not Applicable
9.4.1.2 Parking garage lighting is equipped `❑Complies Requirement will be met.
[EL11]2 with required lighting controls and !❑Does Not
daylight transition zone lighting.
"❑Not Observable
❑Not Applicable
9.4.1.1f Daylight areas under skylights and DComplies Requirement will be met.
[EL13]1 roof monitors that have more than ❑Does Not
150 W combined input power for
general lighting are controlled by ❑Not Observable
_ photocontrols. ❑Not Applicable
9.4.1.4 m`.Automatic lighting controls for exterior DComplies
[EL3]2 lighting installed. ❑Does Not
❑Not Observable
❑Not Applicable
9.4.1.3 Separate lighting control devices for DComplies Requirement will be met.
[EL4]1 specific uses installed per approved ;❑Does Not
lighting plans.
❑Not Observable
•
❑Not Applicable
9.6.2 Additional interior lighting power '❑Complies Requirement will be met.
[EL8]1 allowed for special functions per the ❑Does Not
approved lighting plans and is ❑Not Observable
automatically controlled and
separated from general lighting. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) .2-'Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Walmart Store#4403 Report date: 12/03/18
Data filename: M:\02\02-19-24403 Queensbury, NY 4403\MEPF\ELEC\ELEC\ComCheck\4403 Queensbury, NY.c( Page 5 of 7
z y a` .
Section
# Final!ospectkin' C pttes'
s
tit #' . 3zce.s N %
_ _
87,1 Furnished-as-built drawings for ❑Complies Requirement will be met.
1FI1613 electric power systems within 30 days ❑Does Not
of system acceptance.
DNot Observable
❑Not Applicable
8.7.2 Furnished O&M instructions for ❑Complies Requirement will be met.
[E117]3 systems and equipment to the ❑Does Not
building owner or designated DNot Observable
representative.
❑Not Applicable
9.2.2.3 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values.
[F118]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans, demonstrating proposed watts DNot Observable
are less than or equal to allowed _Not Applicable
watts.
9.4.2 Exterior lighting power is consistent ❑Complies See the Exterior Lighting fixture schedule for values.
[F119]1 with what is shown on the approved ❑Does Not
lighting plans, demonstrating
proposed watts are less than or equal DNot Observable
to allowed watts. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Walmart Store#4403 Report date: 12/03/18
Data filename: M:\02\02-19-24403 Queensbury, NY 4403\MEPF\ELEC\ELEC\ComCheck\4403 Queensbury, NY.cc Page 6 of 7