air test APPOLO
HEATING
Degrees Above The Rest, s/NCE 1968.E
Certificate of Completion _
Duct Sealing Performed For:
350
Michaels Group , Appolo Heating
11 Wooden Lane 300
Queensbury , NY 12804
250
Overall Sealing Results 200
When we arrived,
YOUR DUCTS HAD: 2 150
u<
325.6 CFM of Leakage, equivalent to a 100
61.5 Square Inch Hole
This equals 195.3 refrigerators full of air loss every 50
hour.
After we finished, o
YOUR DUCTS HAVE: 0 5 10 15 20 25 30 35 40 45
6.8 CFM of Leakage, equivalent to a Sealing Time in Minutes
1.3 Square Inch Hole
This corresponds to a 97.9% Reduction in Aeroseal Technician David
Duct Leakage. Aeroseal Case ID 5068
Date of Seal 10/17/2019
System Description Basement Upflow
Note: Duct Leakage results are calculated in
Cubic Feet per Minute (CFM) measured at a Seal Description Supply
standard OPERATING PRESSURE of 25 Pa. Hardware HomeSeal Connect
A ERLSEAL® Duct Sealing Performed By:
Duct Sealing From The Inside
Appolo Heating, Inc.
868 Burdeck St
Schenectady, NY 12306
Phone:(518)355-0433