Loading...
building footings 28 days QCQA Concrete Field Observation Report DRILLING & TESTING SERVICES Project: Stewarts-Queensbury,NY Report No.: C-081219 Client: Stewarfs Shop Date: 8/1212019 Contractor: KM Masonry Job No.: 19-078 Concrete Supplier: Pallette Mix No.: 40001 Weather: Sunny;Breezy Air Temp.:AM PM 84 General Placement Location: Building Perimeter Footings Sheet: 1 of 1 Time Test Data Air Unit Conc. Load Ticket Truck Cubic Water Start End Slump Content Weight Temp No. No. No. Yards Added Batched Discharge Dischar a Tested In. % Pcf F. Specimen Set_..Remarks 1 833802 4525 10 2:03 2:40 2:55 2:44 4.25 6.0 85 Set 1 6 C finders 2 833803 4913 10 2:22 2:56 3:10 14 I I I Remarks: Cubic yards placed: 20 Rejected: TECHNICIAN: Tod Kobik COMPRESSIVE STRENGTH DATA Set Lab Cylinder Date Age Load Fracture in No. No. Diameter Area Tested (days) Ibs. Type 1 5698 6.0 28.27 8/19/2019 7 100,640 5 5699 6.0 28.27 8/19/2019 7 104,160 5 5700 6.0 28.27 9/9/2019 28 130,940 5 5701 6.0 28.27 9/9/2019 28 115,010 4 5702 6.0 28.27 9/9/2019 28 126,080 5 4,460 5703 6.0 28.27 9/9/2019 28 121,030 5 4,280 f I Specification Requirement at 28 days 4,000 Cylinder Size:6"x 12"unless otherwise noted Slump in accord with ASTM C-143 FRACTURE TYPE: Sampled in accord with ASTM C-172 Air in accord with ASTM C-231 1=Cone Both Ends Tested in accord with ASTM C-39 Unit Wt.in accord with ASTM C-138 2=Cone 1 End Tod Kobik Cast in accord with ASTM C-31 Temp in accord with ASTM C-1064 3=Columnar QC1QA Laboratories Inc. 4=Diagonal Fracture Vice-President 5=Side Fracture 6=Side Fracture(2) 877 Route 4S-Schuylerville,NY 12871-Phone:(518)372-4067-Fax:(518)507-6113