ComCheck REVIEWED FOR
ENERGY CODE COMPLIANCE
COMcheck Software Version 4.0.7.2 Review
Envelope Compliance Certificate
(141
Project Information -1 ----
�I
Energy Code: 2015 IECC I ;► JUL 0 3 2019 i Iji
Project Title: Addictions Care Of Queensbury U
Location: Glens Falls, New York ------..---_..
Climate Zone: 6a TOWN OF QUEENSBURY
Project Type: Alteration BUILDING&CODES
Vertical Glazing/Wall Area: 19%
Construction Site: Owner/Agent: Designer/Contractor:
79 Glenwood Ave Keith Stack James Coleman
Queensbury, NY 12804 The Addictions Care Center of hcp Architects LLP
Albany, Inc 302 Washington Avenue Ext
FILE COPY 90 McCarty Avenue Albany, NY 12203
Albany, New York, NY 12202 518-218-0614
jcoleman@hcpdesign.com
Building Area Floor Area
1-Dormitory: Residential 4200
Envelope Assemblies
R-Value Proposed Max.Allowed
Post-Alteration Assembly Cavity Cont. U-Factor SHGC U-Factor SHGC
Roof 1:Attic Roof with Wood Joists,[Bldg.Use 1-Dormitory], -- -- -- --- — --
Exemption:Framing cavity filled with insulation.
NORTH
Exterior Wall 1:Wood-Framed,16"o.c.,[Bldg.Use 1 - --- --- -- -- — —
Dormitory],Exemption:Framing cavity filled with insulation.
EAST
Exterior Wall 3:Wood-Framed, 16"o.c.,[Bldg.Use 1 - -- --- -- --- — ---
Dormitory],Exemption:Framing cavity filled with insulation.
SOUTH
Exterior Wall 2:Wood-Framed,16"o.c.,[Bldg.Use 1 - --- -- -- --- -- ---
Dormitory],Exemption:Framing cavity filled with insulation.
WEST
Exterior Wall 4:Wood-Framed,16"o.c.,[Bldg.Use 1 - --- --- -- --- — --
Dormitory],Exemption:Framing cavity filled with insulation.
Window 1:Wood Frame:Operable,Other,Operable,Operable, --- --- 0.330 0.400 0.430 0.400
[Bldg.Use 1 -Dormitory]
Door 1:Other Door,Swinging,[Bldg.Use 1 -Dormitory) --- --- 0.200 --- 0.370 ---
Door 2:Other Door,Swinging,[Bldg.Use 1 -Dormitory] -- -- 0.200 --- 0.370 ---
(a)'Other'components require supporting documentation for proposed U-factors.
(b)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 1 of 10
Envelope PASSES
Envelope Compliance Statement
Compliance Statement: The proposed envelope alteration project represented in this document is consistent with the building
plans,specifications,and other calculations submitted with this permit applica ion.The proposed envelope systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.7.2 R= iew and to comply with any applicable
m.ndatory requirements listed in the Inspection Checklist.
//e�,,,�.t ��• /
hIYt ♦ •A ► �� J�'J/ �t. ♦ ♦ lL
— Name-Title ure Da
4. •• v •
46
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 2 of 10
iCOMcheck Software Version 4.0.7.2 Review
i Mechanical Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: Addictions Care Of Queensbury
Location: Glens Falls,New York
Climate Zone: 6a
Project Type: Alteration
Construction Site: Owner/Agent: Designer/Contractor:
79 Glenwood Ave Keith Stack James Coleman
Queensbury, NY 12804 The Addictions Care Center of hcp Architects LLP
Albany, Inc 302 Washington Avenue Ext
90 McCarty Avenue Albany, NY 12203
Albany, New York, NY 12202 518-218-0614
jcoleman@hcpdesign.com
Mechanical Systems List
Quantity System Type&Description
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans,specifications,and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.7.2 Review and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Name-Title Signature Date
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 3 of 10
COMcheck Software Version 4.0.7.2 Review
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the"Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table,a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
&Req.ID
C103.2 Plans and/or specifications provide all ❑Complies
[PR1]1 information with which compliance ❑Does Not
can be determined for the building
envelope and document where ❑Not Observable
exceptions to the standard are ❑Not Applicable
claimed.
C402.4.1 The vertical fenestration area<=30 ❑Complies
[PR10]1 percent of the gross above-grade wall ODoes Not
area.
❑Not Observable
DNot Applicable
C402.4.1 The skylight area<=3 percent of the ❑Complies
[PR11]1 gross roof area. DDoes Not
❑Not Observable
❑Not Applicable
C405.6 Group R-2 dwelling units have ❑Complies
[PR16]1 separate electrical meters. ❑Does Not
:Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 4 of 10
Section
# Footing/Foundation Inspection Complies? Comments/Assumptions
& Req.ID
C303.2.1 Exterior insulation protected against ❑Complies
[FO6]1 damage,sunlight, moisture,wind, Does Not
landscaping and equipment ❑Not Observable
maintenance activities.
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 5 of 10
•
Section
# Framing/Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C303.1.3 Fenestration products rated in ❑Complies
[FR12]2 accordance with NFRC. ❑Does Not
ONot Observable
ONot Applicable
C303.1.3 Fenestration products are certified as ❑Complies
[FR13]' to performance labels or certificates ❑Does Not
provided. ONot Observable
ONot Applicable
C402.4.3 Vertical fenestration SHGC value. ❑Complies See the Envelope Assemblies table for values.
[FR10]' ❑Does Not
ONot Observable
❑Not Applicable
C402.4.3, Vertical fenestration U-Factor. OComplies See the Envelope Assemblies table for values.
C402.4.3. ❑Does Not
4 ' ONot Observable
[FR8] ❑Not Applicable
C402.4.4 U-factor of opaque doors associated ❑Complies See the Envelope Assemblies table for values.
[FR14]2 with the building thermal envelope ❑Does Not
meets requirements.
:Not Observable
❑Not Applicable
C402.5.1 The building envelope contains a ❑Complies
[FR16]' continuous air barrier that is sealed in ❑Does Not
an approved manner and either [Not Observable
constructed or tested in an approved
manner.Air barrier penetrations are ❑Not Applicable
sealed in an approved manner.
C402.5.2, Factory-built fenestration and doors ❑Complies
C402.5.4 are labeled as meeting air leakage ❑Does Not
[FR18]3 requirements. ONot Observable
ONot Applicable
C402.5.7 Vestibules are installed on all building ❑Complies
[FR17]3 entrances. Doors have self-closing ❑Does Not
devices.
ONot Observable
❑Not Applicable
Additional Comments/Assumptions:
Ill High Impact(Tier 1) Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 6 of 10
•
Section
# Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C402.5.5, Stair and elevator shaft vents have ❑Complies
C403.2.4. motorized dampers that automatically ❑Does Not
3
(MEW close. :Not Observable
❑Not Applicable
C402.5.5, Outdoor air and exhaust systems have ❑Complies
C403.2.4. motorized dampers that automatically ❑Does Not
3 shut when not in use and meet
(ME58]3 maximum leakage rates.Check ❑Not Observable
gravity dampers where allowed. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 7 of 10
Section
# Insulation Inspection Complies? Comments/Assumptions
& Req.ID
C303.1 Roof insulation installed per ❑Complies
(IN3]1 manufacturer's instructions.Blown or ❑Does Not
poured loose-fill insulation is installed
only where the roof slope is<=3 in ONot Observable
12. ONot Applicable
C303.1 Building envelope insulation is labeled ❑Complies
[IN10]2 with R-value or insulation certificate ❑Does Not
providing R-value and other relevant
data. ONot Observable
ONot Applicable
C303.2 Above-grade wall insulation installed ❑Complies
[IN7]1 per manufacturer's instructions. ❑Does Not
ONot Observable
ONot Applicable
C303.2.1 Exterior insulation is protected from ❑Complies
[1N14]2 damage with a protective material. ❑Does Not
Verification for exposed foundation
insulation may need to occur during ONot Observable
Foundation Inspection. ONot Applicable
C402.2.1 Insulation intended to meet the roof ❑Complies
[IN17]3 insulation requirements cannot be ❑Does Not
installed on top of a suspended
ceiling.Mark this requirement ['Not Observable
compliant if insulation is installed ONot Applicable
accordingly.
C402.2.3 Above-grade wall insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[IN6]1 ❑Does Not
[Not Observable
ONot Applicable
C402.2.6 Radiant panels and associated ❑Complies
[IN18]3 components,designed for heat ❑Does Not
transfer from the panel surfaces to the ONot Observable
occupants or indoor space are
insulated with a minimum of R-3.5. ONot Applicable
C402.2.2 Roof R-value. For some ceiling ❑Complies See the Envelope Assemblies table for values.
(IN2]1 systems,verification may need to ❑Does Not
occur during Framing Inspection.
ONot Observable
ONot Applicable
C402.5.1. All sources of air leakage in the ❑Complies
1 building thermal envelope are sealed, ODoes Not
[IN1]1 caulked,gasketed,weather stripped
or wrapped with moisture vapor- ONot Observable
permeable wrapping material to ONot Applicable
minimize air leakage.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 8 of 10
Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
C402.5.3 Where open combustion air ducts ❑Complies
[FI51]3 provide combustion air to open Does Not
combustion fuel burning appliances,
the appliances and combustion air ONot Observable
opening are located outside the ONot Applicable
building thermal envelope or enclosed
in a room,isolated from inside the
thermal envelope.Such rooms are
sealed and insulated.
C402.5.6 Weatherseals installed on all loading ❑Complies
[FI3711 dock cargo doors. ❑Does Not
:Not Observable
ONot Applicable
C402.5.8 Recessed luminaires in thermal ❑Complies
(FI2613 envelope to limit infiltration and be IC ❑Does Not
rated and labeled.Seal between
interior finish and luminaire housing. :Not Observable
ONot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 9 of 10
• Y
Project Title: Addictions Care Of Queensbury Report date: 07/01/19
Data filename: Untitled.cck Page 10 of 10
'illArlfil COMcheck Software Version 4.1.1.0
Mechanical Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: Addictions Care of Queensbury
Location: Glens Falls, New York
Climate Zone: 6a
Project Type: Alteration
Construction Site: Owner/Agent: Designer/Contractor:
79 Glenwood Avenue Paul Martin
Queensbury, NY 12804 Sigma Psi Consulting
4 Collamer Road
Malta, NY 12020
518-581-9428
paulm@sigmapsi.com
Mechanical Systems List
Quantity System Type&Description
2 HVAC System F1/F3(Single Zone):
Heating:2 each-Central Fumace,Gas,Capacity=60 kBtu/h
Proposed Efficiency=92.00%Et,Required Efficiency: 80.00%Et or 78%AFUE
Cooling:2 each-Split System,Capacity=36 kBtu/h,Air-Cooled Condenser,Unknown Economizer
Proposed Efficiency=13.00 SEER,Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 1 I Furnace F1 and F3--Compliance(Motor nameplate HP method):Passes
Fans:
FAN 1 Supply,Constant Volume, 1200 CFM,0.5 motor nameplate hp,0.0 fan efficiency grade
2 HVAC System F2/F4(Single Zone):
Heating:2 each-Central Furnace,Gas,Capacity=60 kBtu/h
Proposed Efficiency=92.00%Et,Required Efficiency: 80.00%Et or 78%AFUE
Cooling:2 each-Split System,Capacity=30 kBtu/h,Air-Cooled Condenser,Unknown Economizer
Proposed Efficiency=13.00 SEER,Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 2 I Furnace F2 and F4--Compliance(Motor nameplate HP method):Passes
Fans:
FAN 2 Supply,Constant Volume, 1000 CFM,0.5 motor nameplate hp,0.0 fan efficiency grade
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans,specifications,and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist. �����
Paul Martin 7/2/19
Name-Title Signature Date
P "E�'r
iet,,
4,4evo
Na'.
Project Title: Addictions Care of Queensbury Report date: 07/02/19
Data filename: \\Spcserver\SPC_SERVER_DATA_G\Sigma_Psi\19124-ACCA-79-glenwood-CA-group\19124-hvac- Page 1 of 9
comcheck.cck
Section
Footing/Foundation Inspection Complies? Comments/Assumptions
& Req.ID
C403.2.4. Snow/ice melting system sensors for ❑Complies
5, future connection to controls. Freeze ❑Does Not
C403.2.4. protection systems have automatic
6 controls installed. ❑Not Observable
[FO9]3 ONot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care of Queensbury Report date: 07/02/19
Data filename: \\Spcserver\SPC SERVER DATA G\Sigma Psi\19124-ACCA-79-glenwood-CA-group\19124-hvac- Page 3 of 9
comcheck.cck
COMcheck Software Version 4.1.1.0
Inspection CCChecklist
Energy Code: 2015 IE
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
Plan Review Complies? Comments/Assumptions
&Req.ID
C103.2 Plans, specifications, and/or ❑Complies
[PR2]1 calculations provide all information ODoes Not
with which compliance can be
determined for the mechanical ❑Not Observable
systems and equipment and ONot Applicable
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care of Queensbury Report date: 07/02/19
Data filename: \\Spcserver\SPC_SERVER DATA G\Sigma_Psi\19124-ACCA-79-glenwood-CA-group\19124-hvac- Page 2 of 9
comcheck.cck
Section
Plumbing Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C404.5, Heated water supply piping conforms ❑Complies
C404.5.1, to pipe length and volume ODoes Not
C404.5.2 requirements. Refer to section details.
[PL6]3 ['Not Observable
❑Not Applicable
C404.5, Heated water supply piping conforms ❑Complies
C404.5.1, to pipe length and volume DDoes Not
C404.5.2 requirements. Refer to section details.
[PL6]3 ❑Not Observable
❑Not Applicable
C404.6.3 Pumps that circulate water between a ❑Complies
[PL7]3 heater and storage tank have controls ODoes Not
that limit operation from startup to
<= 5 minutes after end of heating ONot Observable
cycle. ❑Not Applicable
C404.6.3 Pumps that circulate water between a ❑Complies
[PL7]3 heater and storage tank have controls ❑Does Not
that limit operation from startup to
<= 5 minutes after end of heating ❑Not Observable
cycle. ❑Not Applicable
C404.7 Water distribution system that pumps OComplies
[PL8]3 water from a heated-water supply ODoes Not
pipe back to the heated-water source
through a cold-water supply pipe is a ❑Not Observable
demand recirculation water system. ❑Not Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
C404.7 Water distribution system that pumps ❑Complies
[PL8]3 water from a heated-water supply ODoes Not
pipe back to the heated-water source
through a cold-water supply pipe is a Not Observable
demand recirculation water system. ❑Not Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care of Queensbury Report date: 07/02/19
Data filename: \\Spcserver\SPC_SERVER_DATA_G\Sigma_Psi\19124-ACCA-79-glenwood-CA-group\19124-hvac- Page 4 of 9
comcheck.cck
•
Section
# Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C402.2.6 Thermally ineffective panel surfaces of OComplies
[ME41]3 sensible heating panels have ODoes Not
insulation >= R-3.5.
ONot Observable
ONot Applicable
C403.2.13 Unenclosed spaces that are heated OComplies
[ME71]2 use only radiant heat. ODoes Not
❑Not Observable
[Not Applicable
C403.2.3 HVAC equipment efficiency verified. OComplies See the Mechanical Systems list for values.
[ME55]2 ODoes Not
ONot Observable
ONot Applicable
C403.2.6. Demand control ventilation provided OComplies
1 for spaces >500 ft2 and >25 ODoes Not
[ME59]1 people/1000 ft2 occupant density and
served by systems with air side ONot Observable
economizer, auto modulating outside ONot Applicable
air damper control,or design airflow
>3,000 cfm.
C403.2.6. Enclosed parking garage ventilation DComplies
2 has automatic contaminant detection ODoes Not
[ME115]3 and capacity to stage or modulate
fans to 50%or less of design capacity. ['Not Observable
❑Not Applicable
C403.2.7 Exhaust air energy recovery on DComplies
[ME57]1 systems meeting Table C403.2.7(1) DDoes Not
and C403.2.7(2). ONot Observable
ONot Applicable
C403.2.8 Kitchen exhaust systems comply with DComplies
[ME116]3 replacement air and conditioned ['Does Not
supply air limitations, and satisfy hood
rating requirements and maximum Not Observable
exhaust rate criteria. ONot Applicable
C403.2.9 HVAC ducts and plenums insulated. OComplies
[ME60]2 Where ducts or plenums are installed ODoes Not
in or under a slab,verification may
need to occur during Foundation Not Observable
Inspection. ONot Applicable
C403.2.9 Ducts and plenums sealed based on ❑Complies
[ME10]2 static pressure and location. DDoes Not
O Not Observable
O Not Applicable
C403.2.9. Ductwork operating >3 in. water OComplies
1.3 column requires air leakage testing. ODoes Not
[ME11]3 ONot Observable
ONot Applicable
C403.2.9. Ductwork operating >3 in. water OComplies
1.3 column requires air leakage testing. DDoes Not
[ME11]3 ONot Observable
O Not Applicable
C403.4.4. Multiple zone VAV systems with DDC OComplies See the Mechanical Systems list for values.
6 of individual zone boxes have static ODoes Not
[ME110]3 pressure setpoint reset controls.
:Not Observable
ONot Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care of Queensbury Report date: 07/02/19
Data filename: \\Spcserver\SPC_SERVER_DATA_G\Sigma_Psi\19124-ACCA-79-glenwood-CA-group\19124-hvac- Page 5 of 9
comcheck.cck
Section
Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C403.4.4. Multiple zone VAV systems with DDC ❑Complies See the Mechanical Systems list for values.
6 of individual zone boxes have static ❑Does Not
[ME110]3 pressure setpoint reset controls. ['Not Observable
❑Not Applicable
C408.2.2. Air outlets and zone terminal devices ❑Complies
1 have means for air balancing. ❑Does Not
[ME53]3 ONot Observable
❑Not Applicable
C403.5, Refrigerated display cases, walk-in ❑Complies
C403.5.1, coolers or walk-in freezers served by ❑Does Not
C403.5.2 remote compressors and remote
[ME123]3 condensers not located in a :Not Observable
condensing unit, have fan-powered ❑Not Applicable
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care of Queensbury Report date: 07/02/19
Data filename: \\Spcserver\SPC SERVER_DATA G\Sigma_Psi\19124-ACCA-79-glenwood-CA-group\19124-hvac- Page 6 of 9
comcheck.cck
, ' Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
C303.3, Furnished O&M manuals for HVAC ❑Complies
C408.2.5. systems within 90 days of system Does Not
3 acceptance.
[F18]3 :Not Observable
❑Not Applicable
C403.2.2 HVAC systems and equipment ❑Complies
[FI27]3 capacity does not exceed calculated ❑Does Not
loads.
❑Not Observable
❑Not Applicable
C403.2.4. Heating and cooling to each zone is ❑Complies
1 controlled by a thermostat control. ❑Does Not
[FI47]3 Minimum one humidity control device
per installed ['Not Observable
humidification/dehumidification ❑Not Applicable
system.
C403.2.4. Heating and cooling to each zone is ❑Complies
1 controlled by a thermostat control. ❑Does Not
[F147]3 Minimum one humidity control device
per installed ❑Not Observable
humidification/dehumidification ❑Not Applicable
system.
C403.2.4. Thermostatic controls have a 5°F ❑Complies
1.2 deadband. ODoes Not
[FI38]3 ONot Observable
❑Not Applicable
C403.2.4. Temperature controls have setpoint ❑Complies
1.3 overlap restrictions. ❑Does Not
[FI20]3 :Not Observable
❑Not Applicable
C403.2.4. Each zone equipped with setback ❑Complies
2 controls using automatic time clock or ❑Does Not
[F139]3 programmable control system.
❑Not Observable
❑Not Applicable
C403.2.4. Automatic Controls: Setback to 55°F ❑Complies
2.1, (heat)and 85°F(cool); 7-day clock, 2- ❑Does Not
C403.2.4. hour occupant override, 10-hour
2.2 backup ['Not Observable
[F140]3 ❑Not Applicable
C403.2.4. Systems include optimum start OComplies
2.3 controls. ❑Does Not
[FI41J3 plot Observable
❑Not Applicable
C403.2.4. Systems include optimum start ❑Complies
2.3 controls. ❑Does Not
[FI41]3 [Not Observable
❑Not Applicable
C408.2.1 Commissioning plan developed by ❑Complies
[F128]' registered design professional or ❑Does Not
approved agency.
❑Not Observable
❑Not Applicable
C408.2.3. HVAC equipment has been tested to ❑Complies
1 ensure proper operation. ❑Does Not
[FI31]' ❑Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care of Queensbury Report date: 07/02/19
Data filename: \\Spcserver\SPC_SERVER DATA_G\Sigma_Psi\19124-ACCA-79-glenwood-CA-group\19124-hvac- Page 7 of 9
comcheck.cck
, Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
C408.2.3. HVAC control systems have been OComplies
2 tested to ensure proper operation, ODoes Not
[FI10]' calibration and adjustment of controls. ❑Not Observable
❑Not Applicable
C408.2.4 Preliminary commissioning report DComplies
[FI29]' completed and certified by registered ❑Does Not
design professional or approved
agency. ❑Not Observable
❑Not Applicable
C408.2.5. Furnished HVAC as-built drawings ❑Complies
1 submitted within 90 days of system ❑Does Not
[F17]3 acceptance.
❑Not Observable
❑Not Applicable
C408.2.5. An air and/or hydronic system ❑Complies
3 balancing report is provided for HVAC DDoes Not
[FI43]' systems. ❑Not Observable
❑Not Applicable
C408.2.5. Final commissioning report due to ❑Complies
4 building owner within 90 days of ❑Does Not
[F130]' receipt of certificate of occupancy.
DNot Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Addictions Care of Queensbury Report date: 07/02/19
Data filename: \\Spcserver\SPC SERVER DATA_G\Sigma Psi\19124-ACCA-79-glenwood-CA-group\19124-hvac- Page 8 of 9
comcheck.cck
•
•
Project Title: Addictions Care of Queensbury Report date: 07/02/19
Data filename: \\Spcserver\SPC_SERVER_DATA_G\Sigma_Psi\19124-ACCA-79-glenwood-CA-group\19124-hvac- Page 9 of 9
comcheck.cck
Irit‘Al COMcheck Software Version COMcheckWeb
11 Interior Lighting Compliance Certificate
Project Information
Energy Code 2015 IECC
Project Title: ACCA of Queensbury
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
79 Glenwood Ave.
Queensbury, New York 12804
Additional Efficiency Package(s)
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed
(ft2) Watts / ft2 Watts
1-Dormitory 7000 0.51 3591
Total Allowed Watts = 3591
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
1-Dormitory
LED: LED Panel 19W: 0 28 41 1148
LED: LED Panel 19W: 0 12 29 348
LED: LED Linear 8W: 0 4 41 164
LED: LED Linear 8W: 0 7 30 210
LED: LED Linear 8W: 0 11 34 374
LED: LED PAR 7W: 0 5 11 55
LED: LED PAR 7W: 0 1 10 10
Total Proposed Watts = 2309
Interior Lighting PASSES: Design 36% better than code
Interior Lighting Compliance
Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Paul J. Martin, PE `'°"�"°�-- 7/3/19
Name-Title Signature Date
4,0E NEwr
(... ; 1/4���,
, qt- ,,0..*.... :fi _
�ey.i40
SSIU J
Project Title: ACCA of Queensbury Report date: 07/03/19
Data filename: Page 1 of 5
•
'‘/Ifri COMcheck Software Version COMcheckWeb
Exterior Lighting Compliance Certificate
finfl
Project Information
Energy Code 2015 IECC
Project Title: ACCA of Queensbury
Project Type: New Construction
Exterior Lighting Zone 2 (Residentially zoned area)
Construction Site: Owner/Agent: Designer/Contractor:
79 Glenwood Ave.
Queensbury, New York 12804
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts / Wattage (B X C)
Parking area 1000 ft2 0.06 Yes 60
Total Tradable Watts(a) = 60
Total Allowed Watts = 60
Total Allowed Supplemental Watts(b) = 600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable
areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
Parking area (1000 ft2): Tradable Wattage
LED: LED Other Fixture Unit 6.5W: 0 4 40 160
Total Tradable Proposed Watts = 160
Exterior Lighting PASSES: Design 76% better than code
Exterior Lighting Compliance
Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist. �l
Paul J. Martin, PE ��� 7/3/19
Name-Title Signature Date
<4,-Va.4 � .tp rf'
,V 4. :i
ik.
°b y.i.01
'.rQo�pY
Project Title: ACCA of Queensbury Report date: 07/03/19
Data filename: Page 2 of 5
.11 COMcheck Software Version COMcheckWeb
Inspection Checklist
Energy Code: 2015 IECC
in11
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
_
C103.2 Plans, specifications, and/or ❑Complies Requirement will be met.
[PR4J' calculations provide all information ❑Does Not
with which compliance can be
determined for the interior lighting Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations,wattage of
bulbs and ballasts, transformers and
control devices.
C103.2 Plans, specifications, and/or ❑Complies Requirement will be met.
[PR8]' calculations provide all information ❑Does Not
with which compliance can be
determined for the exterior lighting ['Not Observable
and electrical systems and equipment ENot Applicable
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
C405.6 Group R-2 dwelling units have ❑Complies Requirement will be met.
[PR16)' separate electrical meters. ❑Does Not
❑Not Observable
❑Not Applicable
C406 Plans,specifications,and/or EComplies Requirement will be met.
[PR9J' calculations provide all information ❑Does Not
with which compliance can be
determined for the additional energy ['Not Observable
efficiency package options. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 !Medium Impact(Tier 2) 3 Low Impact(Tier 3) 1
Project Title: ACCA of Queensbury Report date: 07/03/19
Data filename: Page 3 of 5
Section
Rough-In Electrical Inspection Complies? Comments/Assumptions
& Re..ID
C405.2.1 Lighting controls installed to uniformly ❑Complies Requirement will be met.
[EL151' reduce the lighting load by at least ❑Does Not
50%. ❑Not Observable
❑Not Applicable
C405.2.1 Occupancy sensors installed in ❑Complies Requirement will be met.
[EL18)' required spaces. ❑Does Not
❑Not Observable
❑Not Applicable
C405.2.1, Independent lighting controls installed ❑Complies Requirement will be met.
C405.2.2. per approved lighting plans and all ❑Does Not
3 manual controls readily accessible and
[EL23)2 visible to occupants. ❑Not Observable
❑Not Applicable
C405.2.2. Automatic controls to shut off all ❑Complies Requirement will be met.
1 building lighting installed in all ❑Does Not
[EL22]2 buildings.
❑Not Observable
❑Not Applicable
C405.2.3 Daylight zones provided with ❑Complies Requirement will be met.
[EL16)2 individual controls that control the ❑Does Not
lights independent of general area
lighting. ❑Not Observable
❑Not Applicable
C405.2.3, Primary sidelighted areas are ❑Complies Requirement will be met.
C405.2.3. equipped with required lighting ❑Does Not
1, controls.
C405.2.3. ❑Not Observable
2 ❑Not Applicable
(EL20)'
C405.2.3, Enclosed spaces with daylight area ❑Complies Requirement will be met.
C405.2.3. under skylights and rooftop monitors ❑Does Not
1, are equipped with required lighting
C405.2.3. controls. ❑Not Observable
3 [Not Applicable
[EL21)'
C405.2.4 Separate lighting control devices for ❑Complies Requirement will be met.
(EL4)' specific uses installed per approved ❑Does Not
lighting plans.
❑Not Observable
❑Not Applicable
C405.2.4 Additional interior lighting power ❑Complies Requirement will be met.
[EL8)' allowed for special functions per the ❑Does Not
approved lighting plans and is
automatically controlled and pilot Obsen able
separated fium yeneial liylrliny. ❑Not Applicable
C405.2.5 Automatic lighting controls for exterior ❑Complies Requirement will be met.
[EL25)"°" lighting installed. Controls will be ❑Does Not
daylight controlled, set based on
business operation time-of-day,or ❑Not Observable
reduce connected lighting > 30%. ❑Not Applicable
C405.3 Exit signs do not exceed 5 watts per ❑Complies Requirement will be met.
[EL6)' face. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title: ACCA of Queensbury Report date: 07/03/19
Data filename: Page 4 of 5
Section
Final Inspection Complies? Comments/Assumptions
& R• ..ID
C303.3, Furnished O&M instructions for ❑Complies Requirement will be met.
C408.2.5. systems and equipment to the ❑Does Not
2 building owner or designated Not Observable
[FI1/]3 representative. ❑
❑Not Applicable
C405.4.1 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values.
[F118]' lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans, demonstrating proposed watts ❑Not Observable
are less than or equal to allowed Observable„
Applicable
watts.
C405.5.1 Exterior lighting power is consistent ❑Complies See the Exterior Lighting fixture schedule for values.
[FI19]' with what is shown on the approved ❑Does Not
lighting plans,demonstrating
proposed watts are less than or equal [Not Observable
to allowed watts. ❑Not Applicable
C408.2.5. Furnished as-built drawings for ❑Complies Requirement will be met.
1 electric power systems within 90 days ❑Does Not
[F116]3 of system acceptance.
❑Not Observable
❑Not Applicable
C408.3 Lighting systems have been tested to ❑Complies Requirement will be met.
[F133]' ensure proper calibration, adjustment, ❑Does Not
programming,and operation. Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 'Medium Impact(Tier 2) 13 ILow Impact(Tier 3)
Project Title: ACCA of Queensbury Report date: 07/03/19