Manual S
;® M_ _= _ w _ _ 155MAX HEAT RECOVERY VENTILATOR =WWW.LIFEB REATH.COM ENGINEERING DATA Performance (HVlcertified) Net supply airflow in cfm(L/s)against external static pressure THERMALLY CONDUCTIVE,PATENTED ALUMINUM CORE - - -- --'- The counter-flow heat recovery core transfers heat between the two airstreams.It is easily External Static Pressure Airflow removed for cleaning or service. MOTORS AND BLOWERS @ 0.1 in(25 Pa) 184 cfm (87 L/s) Each airstream has one centrifugal blower driven by a common PSC motor,with multiple @ 0.2 in(50 Pa) 163 cfm (77 L/s) fanspeed operations. @ 0.3 in(75 Pa) 146 cfm (69 L/s) FILTERS @ 0.4in(100 Pa) 132 cfm (62 L/s) Washable air filters in exhaust and supply airstreams. @ 0.5 in(125 Pa) 115 cfm (54 L/s) MOUNTING THE HRV @ 0.6 in(150 Pa) 92 cfm (43 L/s) Threaded inserts at corners of the cabinet designed to accept the"S"hooks and hanging straps supplied with the unit. @ 0.7 in(175 Pa) 60 cfm (28 L/s) DEFROST Recirculating damper defrost system. Max.Temperature Recovery 86% CASE ---Sensible 20 gauge prepainted galvanized steel for superior corrosion resistance,insulated to prevent Effectiveness(ASE) exterior condensation.Drain connections:Two 1/2 in(12 mm)OD.Balancing ports are @ 59 cfm(28 L/s) 32°F(0°C) 84% located on unit. Sensible Efficiency (SRE) ELECTRONICS @ 64 cfm(30 L/s) 32°F(0°C) 75% Control included with the unit can be wall mounted in a central location of the home.3 wire Sensible Efficiency(SRE) 20 gauge(min.)100 ft length(max.). @ 64 cfm(30 L/s) -13°F(-25°C) 71% CONTROL VAC @ 60Hz 115 99-DXPLO2 Lifebreath Digital Control • 5 speed operation on each mode Watt /Low speed 66 • 5 user selectable operational modes:Continuous Ventilation,Continuous Watt /High speed 118 Recirculation,20 ON/40 OFF,10 ON/50 OFF,20 ON/40 Recirculation • Compatible with 99-DET02 Wireless Timers Amp rating 1.4 • Humidity control through adjustable Dehumidistat Sensible Efficiency:Thermal • 20/40/60 High speed override button Effectiveness:Based on temperature differential b tween • 3 wire connection the 2 airstreams TIMER OPTIONS Efficiency:Takes into account all power inputs 99-DET01 Lifebreath 20/40/60 Minute Timer-Initiates High speed Ventilation for 20,40 or 60 minutes.3 wire connection. 200 99-DET02 WIRELESS Lifebreath 20/40/60 Minute Timer-Initiates High speed Ventilation for 20, 180 5 -- 40 or 60 minutes.Wirelessly connects to main control for ease of installation. 40' 160-4 - --- - approximate range. 140 3 - 99-RX02 WIRELESS Repeater-Used to extend range of 99-DET02 Wireless Timers. Plugs into 2 120V power outlet. Wirelessly connects to main control and 99-DET02.Install at G 120 1 halfway point between timer and main wall control if timer is out of range. 0100 ACCESSORY OPTIONS a 80 99-163 Duct Heater w/Electronic SCR Thermostat-1 kW,6 in(152 mm). 60 -- '-. f - - 99-186 Weatherhoods-Two 6 in(152 mm). 40 i 20 ........... ..._...-.. .............. WEIGHT 71 lbs(32 kg)SHIPPING WEIGHT 73 lbs(33 kg) 00 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Static Pressure(in w.g.) DIMENSIONS 1551VIAX cql� g U'_ IS9000, Fresh Air Stale Air ..v... CERTIFIED RMsreerD From Outside From Inside 14 3/4 In(375 mm) Filter Recirculating .j. 4 Defrost — • Note:Front Damper _.... �--� ( � � clearance of 25 in WARRANTY Removable t .- ' -- Blower w (635 mm)is Heat `,A '`" recommended for Units carry a lifetime warranty on the HRV core Recovery } Motor servicing unit.All and a 5 year replacement parts warranty. Core % ( ducts use 6 in(152 (., mm)connections. Stale Fresh Air To r�Air To 3 NOTE:All specifications are subject to change without notice. Outside ��_�,.:----- -- -- Inside All units conform to CSA and UL standards 33 5/8 in(854 mm) , PAIN 63 elde�ew Condensate Drain Front View Date: Contractor: Tag: Qty: Supplier: Project: Quote#: Engineer: Submi ed By: Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 System I Design Conditions Location: Elevation: 0 Daily Range: 0 Design Data: Outdoor Dry Bulb Indoor Dry Bulb Latitude: 0 Design Grains: 0 Summer: 92 72 Summer Design RH% 0 Winter: -15 70 Heating Equipment Mfg: Heating Input(btuh): N/A Model: Heating Output(btuh): 0 AHRI Ref#: Calculated HeatPump 0 Efficiency (AFUE): NIA Output @ Design (btuh): Outdoor Equipment Mfg: CHAMPION BY JOHNSON Rated Total Cooling (btuh): 24000 Oudoor Unit Model: TC3132421 Sensible Cooling (btuh): 18000 Coil: CF/CM/CU30C Latent Cooling (btuh): 6000 Indoor Unit: TM9E100C20MP11 AHRI Ref#: 8534947 Adtek AccuLoad Report Version 17.3.5 Page 12 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 System I (Average Load Procedure) Design Conditions Location: Glens Falls AP, New York Elevation: 335 ft Daily Range: Medium Input Data: Outdoor Dry Bulb Indoor Dry Bulb Latitude: 430 N Design Grains: 26 Summer: 92 72 Heated Area 2912 Sq.Ft. Winter: -15 70 Cooled Area 2912 Sq.Ft. Heat/Loss Summary (July Heat Load Calculations) Gross Sensible Latent Area Loss Gain Gain Walls 3480.5 30104 2824 0 Windows 348.5 13308 8719 0 Doors 42 1392 508 0 Ceilings 1141 2813 891 0 Skylights 0 0 0 0 Floors 2912.35 3640 347 0 Room Internal Loads 0 4003 800 Blower Load 1707 0 Hot Water Piping Load 0 0 0 4 F fi Winter Humidification Load 0 0 0 ' Infiltration 17786 1918 1542 Approved ACCA Ventilation 12155 2860 2298 MJ8 Calculations Duct Loss/Gain EHLF=O ESGF=O 6904 961 603 AED Excursion n/a 988 n/a Subtotal 88102 25726 5243 Total Heating 88102 Btuh Total Cooling 30969 Btuh 173 Linear ft. of Hydronic Baseboard *Calculations are based on the ACCA Manual J 8th Edition and are approved by RCCA.All computed calculations are estimates based on building use, weather data, and inputted values such as R-Values,window types, duct loss, etc. Equipment selection should meet both the latent and sensible gain as well as building heat loss. This application has glass areas that produce relatively large cooling loads for part of the day. Variable air volume devices may be required to overcome spikes in solar load for one or more rooms.A zoned system may be required, or some rooms may require zone control(provided by individual, motorized, thermostatically controlled dampers). Adtek AccuLoad Report Version 17.3.5 Page 1 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 Equipment Selection Design Conditions Design Location: Glens Falls AP, New York Relative Humidity: 50% Elevation: 335 ft Summer Outdoor Design: 92 Latitude: 430 N Winter Outdoor Design: -15 Daily Range: Medium Summer Indoor Design: 72 Design Grains 26 Winter Indoor Design: 70 Heating Equipment Mfg: Altitude Correction Factor: 0 Model: Heating Input(btuh): AHRI Ref#: Heating Output(btuh): 0 Efficiency (AFUE): Calculated HeatPump 0 Output @ Design (btuh): Cooling Equipment Mfg: CHAMPION BY JOHNSON Altitude Correction Factor: 0 Oudoor Unit Model: TC3132421 Rated Total Cooling (btuh): 24000 Coil: CF/CM/CU30C Sensible Cooling (btuh): 18000 Furnace: TM9E100C20MP11 Latent Cooling (btuh): 6000 AHRI Ref#: 8534947 SEER - EER@95: Heat Pump HSPF: Summary MJ8 Calculations Status Equipment Capacities Sensible Gain (btuh): 25726 Not Sufficient Sensible Capacity (btuh): 18000 Latent Gain (btuh): 5243 Sufficient Latent Capacity (btuh): 6000 Total Heat Gain (btuh): 30969 Not Sufficient Total Capacity (btuh): 24000 Heat Loss (btuh): 88102 Not Sufficient Heating Capacity (btuh): 0 Adtek AccuLoad Report Version 17.3.5 Page 2 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 System l AED Curve — DAL 1.3 — 1.5 14000 12000 10000 = 8000 3 6000 4000 2000 0 8 9 10 11 12 13 14 15 16 17 18 19 20 Hour AED Excursion: 988 btuh AED Status: System does NOT have Adequate Exposure Diversity. AED Flag: This application has glass areas that produce relatively large cooling loads for part of the day.Variable air volume devices may be required to overcome spikes in solar load for one or more rooms.A zoned system may be required, or some rooms may require zone control (provided by individual, motorized, thermostatically controlled dampers). Hours are listed in 24-hour format: 8 is 8am, 20 is 8pm. Adtek AccuLoad Report Version 17.3.5 Page 3 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 System t Breakdown Item Name U-Value /SHGC Net Area Htg. HTM. Clg. HTM Sens. Htg. Sens. Clg. Lat. Clg. Total Clg. Construction Type ................................................_..._..---..............................._........... ........................................................................_........................................._................................................. .................................................I.............__._................................................................__...................................._.._...... ....... System I 0 1707 0 1707 ....................................................................--— --... -..._._........--.............._.................................._-_�....................... _.._._._............................__..._................._.._.._.. _ ... .._..---.._._._...._ ......._................. _._..._........ ._.._...._......... ---............._........_ ........................................... 1/2 BATH 0 0 0 0 ..........._... _..._......._.....-----.-...__............................................................................................_....__._.............................................._.........__....--.--...._...............................-.................---.--............................................._.._.._...........................-.........-..........._�_......... -.............. Floor 0.368 40 31.28 59 13 0 13 Floor Over Enclosed Unconditioned Crawl Space or Basementl R-1 9 Insulation on Exposed Walls, Sea ................................--................................._.. --_._.._.....................1-1-1................-........_........................................................................................................................._................._.........................__................................................................................................................................................................................................................ South Wall 0.065 39 5.525 1.31 215 51 0 51 Frame Wal l/PartitionINAI NAI Wood IR-21 INoneINAISiding or StuccoINA ......`._.............._.........................................................._..-.._..............--._.......................1--l'...................................................................._.........................................................-......................._..............._......._.._.._..............-...................._................................................_.._..................._.._...._....._......_.........._----............--......._...__....._ Window-2x3 0.45/0.36 6 38.25 23.83 230 143 0 143 FixedlNormal WindowlLow-e(0.20)12 Pane (0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ..................................................................................................................................—._.........................._.............._.........................._..-----------..........................._......_...._...__-............... __.._.._..---........................_._..............._...._....._..................... ........._......_. 2ND FLOOR BATHROOMM 0 0 0 0 ......_........................._...._................._..-__.................................._._....._.__._...................._................-..................---................._........................._..._.__.._.._....................._.._..._..............._......_.............._......__...__.._..._..._...................................__........._....__....................................._....................................._.._................__......................_................ Ceiling 0.029 64 2.465 0.78 158 50 0 50 Ceiling Below Roof JoistsjDark or Bold Color Asphalt ShinglesINAIR-38 blanket or loose fill .................-_._.._._._..._............_.._._................-........ _ _...........__............................................_...._......_.................................._........._..............-._........__--................._...._....._.........................._..................................._.......................-.__-..........__._..._...._........_.........................__..._....................................... .......... Floor 0 64 0 0 0 0 Floor Over Conditioned SpaceINAINAINAINAINAINAINA ............................................................__._..........._........................-.__......................................................................_................................................_......................................-..................-............_.._...-............................................-..................._..................................................................._...................................--_....._....... ........__........ South Wall 0.065 58 5.525 1.33 320 77 0 77 .. Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA .................................................-......................................__...........................-.................._........................__......-.................._._......................_....._............................._...__.._........................_............._.. Window-2x3 0.47/0.31 6 39.95 22.17 240 133 0 133 OperablelNormal WindowlLow-e(0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Viny _._......................................................__..—................................................_._............._....................._._................._....._.__._._.................._.......__....__..._...............__..............................__.._........__.......................-.........................---._...._..._............................_.__.._...-...._..........._....._...._...----............................................ .... basement 0 0 0 0 ................._............._......_.---.................._.._...-.....................-...............................-_-_-.._.................._...................--......._....._........ - -._._....._--------.__......__._............................................-.....__........................................_._....._..__...._............ __...-...................._..................... .... Floor 0.022 1120 1.87 2094 0 0 0 Basement Floor(2ft+ Below Grade)INAINAINAINo InsulationjAny Floor Covering128 feetINA _.._..._..... -- _--_.._...._..........._._.._........_.._._............................................... .........................................._.................................. _.....................__.... ----._...................._...._...................................._...__..................................................................................._._...._..................._..._............................... North Wall 0.232 340 19.72 6705 0 0 0 Adtek Accul-oad Report Version 17.3.5 Page 4 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 Basement WalljNAjEight Inch Brick, Stone or Concrete WalliNo FramingINAINoneINAlBlockl2ft ..........-............................._-......._..._........._.......................................................................................................................... ................................................................................................................................................................................. South Wall 0.232 340 19.72 6705 0 0 0 Basement WallINAlEight Inch Brick, Stone or Concrete WalljNo FramingINAINoneINAlBlockl2ft ................................................................. . .........................................._.._..........................._....__..._............................................................ East Wall 0.232 238 19.72 4693 0 0 0 Basement WallINAlEight Inch Brick, Stone or Concrete WalljNo FramingINAINoneINAlBlockl2ft ........................................_.........................................._..-....._.._..........__.........----..................................................--..................................................................................................__..........................._._............._...._.....................................................---..............................................._...__.._.._...................._...._-._........_............_............ West Wall 0.065 171 5.525 1.32 945 226 0 226 Frame Wall/PartitionINAINAlWoodIR-21 INoneiNAISiding or StuccoINA - --......_......----.........._._................._._.._......................._..._._................................_..._............................---...............-.-----._.................._.......................---...._........................_._.....---..........---.....__.._.............._.__................................ Window-2.5x5 0.47/0 12.5 39.95 38.64 499 483 0 483 OperablelNormal WindowiLow-e(0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ....................._...._.__......................................_......................_.._._...........................--.... —_-__............_..._._........_......................................................_._...._....................................._......_....._.__......_..._._............ ................. Window-2.5x5 0.47/0 12.5 39.95 38.64 499 483 0 483 OperablelNormal WindowjLow-e (0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ........................_.._...._......................................................................................._..........__.................................--......................................................................................................................._.............................................-.................._....................--.................................................-.._................_..........................__......_................ ................................. ........ Window-6x7 0.42/0 42 35.7 34.17 1499 1435 0 1435 French DoorlFrench DoorjClearj2 PanelWood, Wood with Metal Clad, or Vinyl ._._....... _..................._..._._..........—.----.--..............................._...................... ....__._._.........._....__..............................................................................-_--....._._..................----.-....................._._.....---..........................................._.._._..................................................................................................... __.. Bedroom 2 0 230 200 430 _......... _....--__ - --........_...... .............._._.............................................................._._.-..--..__......__...._............................................ _ .. ......................................__.... _ _......_....--.._........_.._ .._.....................__. ............._._ Ceiling 0.029 143 2.465 0.78 352 112 0 112 Ceiling Below Roof Joistsj Dark or Bold Color Asphalt ShingleslNAIR-38 blanket or loose fill ................................. . . I. . . . . . . . . . . .. . . . ._. ...........................---_..........._..-_.-........._......._.._....._._._..............._...._._....._._............-................................_..... _ ..__... _.........._....__.._.._._..........._......._........................_.._.__..................____...................._......_..........._........................_..........._.......................................... Floor 0 143 0 0 0 0 Floor Over Conditioned SpaceINAINAINAINAINAINAINA _......................................................................................................._........................_...._.._....................................................................................................._..__...._........................................................................................._................_............................................................................................................................................_.__........................_......_.............................. North Wall 0.065 63 5.525 1.32 348 83 0 83 Frame Wall/Partition INAI NAIWoodlR-21INonelNAI Siding or StuccoINA ......_.......__..._......................................................................................._........................................................................_....................................._...-.................._............................................................................................._...__..._............................................................................................._..----.................._.....__.._................ .................. Window-2.5x5 0.45/0.36 12.5 38.25 15.92 478 199 0 199 FixedlNormal WindowlLow-e (0.20)2 Pane (0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl .................................................._..........................._..........----................................_.................................................................................................................._.......... Window-2.5x5 0.45/0.36 12.5 38.25 15.92 478 199 0 199 FixedlNormal WindowlLow-e(0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl .............................................................................._..............................................................................................................................................._...............__....11 ......... West Wall 0.065 92 5.525 1.32 508 121 0 Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA ..............._..............._.............................................................................................................................................................................................--..............................................................................-.................._...._..................................._._........................_......................................._._............................................................._....._.._............................................................ Window-3x4 0.45/0.36 12 38.25 43 459 516 0 516 Adtek Accul-oad Report Version 17.3.5 Page 5 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 FixedlNormal WindowlLow-e(0.20)12 Pane (0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ............................................................................................................................................................................................................................................................................................................................................__...............__-............................_.................. BEDROOM.....................................3 ....................................................................................... 0 230 200 430 ............................................................_................................._...._-..._...............................--......................_......_.............---........_..._._-..................._._............---.._..................... _...--- Ceilin 0.029 143 2.465 0.78 352 112 0 112 Ceiling Below Roof Joistsj Dark or Bold Color Asphalt Shinglesl NAI R-38 blanket or loose fill ......._.._.....---..........--- -- ............... -._._......._.._._.__._.._............................._._......._........._........................_.........._._....._....................... __ -----_.....-......---._..................._..........—..........._..—._........._..._............................__............_.............................._................. Floor 0 143 0 0 0 0 Floor Over Conditioned Spacel NAI NAI NAI NAI NAI NAI NA West Wall 0.065 92 5.525 1.32 508 121 0 121 Frame Wal l/PartitionINAI NAI WoodlR-21 INoneINAISiding or StuccoINA ......................................._._...................................................._....._................................_...._...----......_.._.................................................................._............................................._........_........................._..._....._......................................................... Window-3x4 0.45/0.36 12 38.25 43 459 516 0 516 FixedlNormal WindowjLow-e(0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl .......__............._..._....._.......---..._..............................._..........--- ............_._............. ----............... ..........---............._.... ..................._......._ ........_......._.....___..........-..._.. South Wall 0.065 75.5 5.525 1.32 417 100 0 100 Frame Wal l/PartitionINAI NAI Wood IR-21 INoneINAISiding or StuccoINA 0 __ ............................................................_...--......_........_.............................................._.................................._ ....................... _ .._._................................................. Window-2.5x5 .45/0.36 12.5 38.25 23.84 478 298 0 298 FixedlNormal WindowlLow-e(0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ........................................................................................_-.._...._........................................................................................................................................................---.._...._.__..._..............._.._.._....-..................._.........................................................................................................................................................................................-................................. ...... Dining Room 0 0 0 0 .......................................-----_....- --....._.._...__..__......._.................-___..._...................................................._............----........._--.........._...._-._.........._....--_-._............................................._._.............—_.-_.-........--._.........—__....._......_.....-..._..._.................................................... Floor 0.368 103.5 31.28 152 34 0 34 Floor Over Enclosed Unconditioned Crawl Space or BasementIR-19 Insulation on Exposed Walls, See SpacelPassiveiNAINo InsulationjAny Floor CoveringINAINA .......................................__.._._....._._......._.............----...............................................-......................................................._ ...................................---............................_.................._........................................-........................................................................................._.............................................................. South Wall 0.065 39 5.525 1.31 215 51 0 51 Frame Wal l/PartitionINAI NAI Wood IR-21 INoneINAISiding or StuccoINA .................................................................................................................................................................................--.................._......._..................................__.................................... Window-6x7 0.6/0.39 42 35.7 19.62 1499 824 0 824 French DoorlFrench DoorjClearj2 PanelWood, Wood with Metal Clad, or Vinyl .._................................._. ........................_.-............._......_....._..............._..........................._.................................................................................................................._......_......................._.... .. _................ West Wall 0.065 88.5 5.525 1.32 489 117 _11.7. Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA ................................__.................__...._...................-_.-...-----...._..._................_._._......._.......-.............................._._..... Window-3x5 0.45/0.36 15 38.25 42.93 574 644 0 644 FixedlNormal WindowlLow-e(0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ......................_._._-__.-........_.........-_-----------..........._.............._......_................................................._.._........................................................ Kitchen 0 0 0 0 Adtek Accul-oad Report Version 17.3.5 Page 6 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 ..................................... ............................................................_........_._............._....._....................................................................................................................................................................._._..............................................__. Floor 0.368 172.5 31.28 254 57 0 57 Floor Over Enclosed Unconditioned Crawl Space or BasementIR-19 Insulation on Exposed Walls, Sea SpacelPassive�NA�No InsulationjAny Floor CoveringINAINA _ ..................................................................................._...._....—...........................__.._........................_..--....- ................... South Wall 0.065 135 5.525 1.32 746 178 0 178 Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA .... ........__..........._......................._.................................................................................................................................._..._............................................................._..........._............................................ ......................... ......................... _..........._..-.......................... ................. Living Room 0 2400 0 2400 ......_..._................-..................................__...--_ _.._..----............................................................--.-......................-................._...........--.............................................._....--.....__...- -..._.._._..._..................................—..............................--.....__._.............................__........................................ ........ Ceiling 0.029 400 2.465 0.78 986 312 0 312 Ceiling Below Roof JoistsjDark or Bold Color Asphalt ShinglesINAIR-38 blanket or loose fill .................................._............................._..._._.........._.._-...._.............--................................................._-............................................._...........................................__.........__.................................... .... ..... ...__............. _.._ . _......._......_...__._u_._..._......__...._............_...__................................._..................................._............... . Floor 0.368 400 31.28 588 132 0 132 Floor Over Enclosed Unconditioned Crawl Space or BasementIR-19 Insulation on Exposed Walls, Sea SpacelPassiveiNAINo InsulationjAny Floor Covering�NA�NA ....................................................................--...............................................................................................................__......--—.........................._.................................................... West Wall 0.065 241 5.525 1.32 1332 318 0 318 Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA Window-3x5 ..............,__.......................-----._._........._..__._..._.._........................................................----................................_....._.__._.....................................__._._....—.-_.........._..._..._.........__............--........................... Window-3x5 0.45/0.36 15 38.25 42.93 574 644 0 644 FixedlNormal WindowlLow-e (0.20)12 Pane (0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ......................................................................._...._....................................................................................................................................................................-.1-.................................................... .. North Wall 0.065 308 5.525 1.32 1702 407 0 407 Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA _ —.......... _............_--.._..._.._...............--................................._._..............................................................................................................................................._---......................-................................................................_.....-_._...........---_—_._............._..._..---.................... Door-....._.__._3x..7 0.39 21 33.15 12.1 696 254 0 254 WoodlSolid CorejNo Storm _......_._...._..--...................................._---......................................................................................._..__........................................................ Window-1x7 0.45/0.36 7 38.25 16 268 112 0 112 FixedlNormal WindowlLow-e (0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl .............................__..............................................................................................................._..__._...._..._.._._........................................................................._..._...................._.........................................................._............_......................................I............ ..... Window-1 x7 0.45/0.36 7 38.25 16 268 112 0 112 FixedlNormal WindowlLow-e (0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ._.........._...__................................................................._ _`.__........................................................_._.........................................................._............. ........................................................................__.._........................................................................................................................................................................................................_._.... Window-3x5 0.47/0.31 15 39.95 15.4 599 231 0 231 OperablelNormal WindowlLow-e (0.20)12 Pane (0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ................._...................................................:......................................................_..........................................................................................................................................................................-.....................................................................................................................................-..........................................................................................................................I....................... Window-3x5 0.47/0.31 15 39.95 15.4 599 231 0 231 OperablelNormal WindowjLow-e(0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl _.............—.................................................................................. _._.........._.........................................................................................................................................................._.....--- ............— .._...___ ._.._.........._.._._.- -.._..._..._.._._.__._.—_...._....__.—__......_......... Window-6x4.5 0.47/0.31 27 39.95 15.41 1079 416 0 416 Adtek Accul-oad Report Version 17.3.5 Page 7 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here.. Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 ' Phone Here..... . Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 OperablejNormal Windowl Low-e(0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl .......................................... ........................................................................................11...........................................................................................................................................................................................-.............-................................................".........................................--.............--................................................................................. Master Bathroom 0 460 400 860 ..................t................................................................................................................I I............................-............................................................................................................................... ................................... .....................I............................. . .................................................................. Ceiling 0.029 105 2.465 0.78 259 82 0 82 Ceiling Below Roof Joistsj Dark or Bold Color Asphalt Shinglesl NAI R-38 blanket or loose fill .......................-0-................ .......1 0 5.........................***"**................ ---———------------------------------0 0... ,-,*"*....................--------- .............. .........-------------------0............ Floor Floor Over Conditioned SpaceINAINAINAINAINAINAINA ............. ......................................... ..................................................-- ............................................................................. ..................... .................................................................. .................................. South Wall .065 106 5.525 1.32 586 140 0 140 Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA ...................... ....................................... ......................... ....................................................... ....... ....................I......................................................... ..............I.........................................................I--.................................................................. Window-2x3 0.45/0.36 6 38.25 23.83 230 143 0 143 FixedlNormal WindowlLow-e (0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ................. ................----......................................................................................................................................................................... -................ ..........................................................-.....................................................................-.................. ..............................................-.1 1.- -I East Wall 0.065 40 5.525 1.33 221 53 0 53 Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA ......................................................................................................................................................................... ....................-................................................................................................................................................................................................... MASTER ED 0 0 0 0 ............... ....................................................-................ ........................................... .................................................. ...................I--......................................................................................... ..................... ........................I............. .................... ............................................................................. eiling 0.029 182 2.465 0.78 449 142 0 142 Ceiling Below Roof Joistsj Dark or Bold Color Asphalt Shinglesl NAI R-38 blanket or loose fill .......... .............. ..................................................................................... I............................I...............I.....................................................................................-.-....................................... ......................... .............................................................................................-.................................... Floor 0 182 0 0 0 0 Floor Over Conditioned SpaceINAINAINAINAINAINAINA ......................... .........................I........... ...............................................................................- ........................................... ............................I-- I I............................. .....................I.......................... ................. .................................... .................... ....................................................................................... East Wall 0.065 104 5.525 1.32 575 137 0 137 Frame Wall/Partitionj NAINAlWoodIR-21 INoneINAISiding or StuccoINA .......... .......................-.I-...-................................ ... ---.................I............. . ...........-1..................... -1 .............I....................—.1-1..................-.1...........I .............I....................................................................................................................... No & . 5 .5 5 1.32 481 115 0 115 Frame Wal I/Partition I NAI NAI Wood I R-21 I NoneINAISiding or StuccojNA ...................... .......................*"**' ' ---------------- 2 Window-2.5x5" ' ' ** --- .......... 0.47/0.31 12.5 39.95 15.36 499 192 0 OperablelNormal WindowlLow-e (0.20)12 Pane (0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ----—----------- ...... . .....*.. .... ............... Window-2.5x5 ' 0.47/0.31 12.5 39.95 15.36 499 192 0 192 OperablelNormal WindowlLow-e (0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ................................................................................................................................. ................ .......................................................................................... ...............I....................... ........................................................-............................................................................... MUD ROOM .........i.LAUNDRY 0 0 0 0 Adtek Accul-oad Report Version 17.3.5 Page 8 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 ................................................................................_..................................................................._........................................................-.............._.................._.................................................................._..--- ...._ _..._....................._....._...............----............._..........._-.---.......................................—......................................... ......... Floor 0.368 168.75 31.28 248 56 0 56 Floor Over Enclosed Unconditioned Crawl Space or BasementIR-19 Insulation on Exposed Walls, See SpacelPassiveINAINo InsulationjAny Floor CoveringINAINA .....................................__._...._._._.._.....................__........_............._...._._........................................................_......... ............................................................_..... .................._._..................._._..............................._................................................................ ._.................._.....................__......................0_.................._...._.._._...........73._.............._. East Wall 0.065 87 5.525 0.84 481 73 Frame Wal l/PartitionINAI NAI Wood IR-21 INoneINAISiding or StuccoINA ........................................._................._..._.._-._-............_......._...—_...__......................_...__........................._................._..-..........................._....._.—_..........._............._..................... Door-3x7 0.39 21 33.15 12.1 696 254 0 254 WoodlSolid CorejNo Storm 161 --.................__..........._................................._......._......._.........._..__..._.... ......__..._............ ...................----........................................................................................ ........_..._........_......._..._...__._._..............._.........................._._..._......._._...__.....__.........._..............._......_..._._.__........._................_.__.._...__._._................. South Wall 0.065 122 5.525 1.32 674 161 0 Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA ......_...___...-- .........._.......................--.--._.----._................................................................................._........................................................__......_...........................................................................__..............................................-_._...._....._....._.__..._.._........_... ...-_...__................................—._.............................I................... Window-2x2 0.45/0.36 4 38.25 23.75 153 95 0 95 FixedlNormal WindowlLow-e (0.20)12 Pane (0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ...............—. _ -- ....._._.....__—._ — .............._..._..- ....__..........--._ .................. —— ..._._....__.........0...-..........----................683............—..._..................0....._.........__............683 .. OFFICE l ... ....................................... F oor 0.368 166.6 31.28 245 55 0 55 Floor Over Enclosed Unconditioned Crawl Space or Basementl R-1 9 Insulation on Exposed Walls, See Space I Passivel NAI No InsulationjAny Floor CoveringINAINA ...... ...... ......_. ....................................................-............................._........_. .. . ___ .-_ ............................__.__............... ..........._... -.......................... . .._.. ... North Wall 0.065 96 5.525 1.32 530 127 0 127 Frame Wall/PartitionINAINAlWoodIR-21 INoneINAISiding or StuccoINA ................................................................._.........................................................._............................................................................................................._...................................................... Window-3x5 0.45/0.36 15 38.25 15.93 574 239 0 239 FixedlNormal WindowlLow-e (0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ........................._............................_..............._....................................................._................................................................................ ............. Window-3x5 0.45/0.36 15 38.25 15.93 574 239 0 239 FixedlNormal WindowlLow-e (0.20)12 Pane(0.05) Surface 21Wood, Wood with Metal Clad, or Vinyl ....................._.._.._. .. . ................-. . . . ____. ....---...._...._._..... _.................................................................-............................................................................................._.........................................._..........................................................................................................-................................................................................................................................... WIC 0 0 0 0 ..............._—.... ................._.................—._ _—......._..............._....—_.............................................................................................................................._............................................................._._........................................................................................................._._-._........................................................._-....._.....--.................. Ceiling 0.029 64 2.465 0.78 158 50 0 50 Ceiling Below Roof JoistsjDark or Bold Color Asphalt ShinglesINAIR-38 blanket or loose fill ......._..._._............._........._..__...._..................................................................................................... ............................................................._..._�... .._......_................0_...._..._._._............_.._.._..0........._..........._._._...................�--........--._........................_0.................... _. Floor---- -- 0 64 Floor Over Conditioned SpaceINAINAINAINAINAINAINA ................................._._._..._........................................................_.....................................................................111......1....... ........111.1........................................__._..._...__.._..................._..._......._........._.__..........._....................._..........................._...---..................._.........._......................................................... East Wall 0.065 64 5.525 1.31 354 84 0 84 Adtek Accul-oad Report Version 17.3.5 Page 9 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 Frame Wall/Partition I NAI NAIWoodIR-21 I Nonel NAI Siding or StuccoINA ............ C._...-............_._...................._._..........................................................................................-..............................-11-..........................................._........................._..__.._................_._..--...-............-....—0...................................................0...................._.._......_.............0........_............._....-... ................. ..........................................................................................._...................................................................................................................................................._.................................................................._.__........_............................................_._....._..................._..............__....................._.................._...............................0............._....-....._............. -'31..................... Ceiling 0.029 40 2.465 0.78 99 31 Ceiling Below Roof JoistsjDark or Bold Color Asphalt ShinglesINAIR-38 blanket or loose fill ..__........-_................. -----....................................-...-._------__-...................._..._................._....._..................................._..._._....................................__..................__...__....__._..._....._-.__............._.................._.....__............._....._.................-........_..................................................._.._........................_...-....._......._ Floor 0 40 0 0 0 0 Floor Over Conditioned SpacejNAjNAjNAjNAjNAjNAjNA ..................................._._.................._.................._..._.__._._...-......................._..........._....................._........._.._............................._....._....................._..._........................_..---- _._._....._..--....._._......_.._.._..........................._----.................................................---............................_.....-...._._......................................_._ South Wall 0.065 64 5.525 1.31 354 84 0 84 Frame Wal l/PartitionINAI NAI Wood IR-21 iNoneINAISiding or StuccoINA Adtek AccuLoad Report Version 17.3.5 Page 10 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here.. Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 Phone Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 System I CFM Duct sizes and velocities based on settings selected in the setup screen. `Duct sizes calculated using this CFM. Winter Summer Winter Summer Return Supply Calculated Calculated System System Item Name Velocity RA Duct Size Velocity SA Duct Size CFM CFM CFM CFM _..._....._._—. -----_-_.------.--...._......_..__.._........................__....._.__....__._......-- --.._........._...__._._ ................__........................._.........._..--............_......._..............._..........----......_.......... ..............._............._.......--- System I 515 14 x 8 600 12 x 8 1602 1323 400 *400 ..................................._....----....--....._......_.._.._......................................._...__..............................................__....._...._......._..............................._.._.._..........-----._..._....._._...........-................................_._............_........._._...._......_..._................._._..- .._......................_.___..._..............._ 1/2 BATH 412 1-7" Run 561 1-6" Run 19 17 5 *5 -............................... _ ......._........_............._......................_...__......_..........___.._.-..----..................................._....._........._...__.......-...-........_._..................................._.........................__................._........................_.._.__..._................._..._---.................. 2ND FLOOR 412 1-7" Run 561 1-6" Run 27 21 *7 6 ... basement 412 2-7 Runs 561 2-6 Runs 587 193 147 58 -_....___._.._.... ........ ......_.__.._.............__....................._.._.___............................_.._......._._........................_..__..... __ _...................._......__....................._....__...._..........................................._...............-......._...................-----................................. Bedroom 2 412 1-7" Run 561 1-6" Run 92 110 23 *33 -..._........._...._._._..._..............-........_......._..._......_........._.._............_....._.........._..............................................._.......-._..................._..._-...._........_..........................._......_......_._._......_.-„-...__.-._...................._..............................._.....-_-.._..........._....._......................._.....---..._...................---*-._............._.... BEDROOM 3 412 1-7 Run 561 1-6 Run 82 105 21 32 T_..._..-- --........._....._...__...._._......__.....---------.._..........---.._..................................._...-._...._........_.__....---...._.__.._.................._......_..__................-_..-..__..-------......_.-.................._._..........._................._.....--._._..._.._...._._........_.....-----.._.......................__._._.._.................... Dining Room 412 1-7" Run 561 1-6" Run 98 124 24 *38 ._......................_._......_..-_.........._........_.-._........................._...........----.._..........._............................................_......_..........................._.._...._._............_........................................_.........I........_...__._.......... .................--................_..............................._............----......................._........................._......_..............._...._................................ Kitchen 412 1-7" Run 561 1-6" Run 45 23 *11 7 ...............__......_.-_.._........................__......_....._..........---------------------------_........__..................--..........................—_.._..._.. _.._.............-._..........._.....__._................................................._...-----...--------------------------_---------------._-_-..................----___............................---........... .......... Living Room 412 2-7" Runs 561 2-6" Runs 307 417 77 * 126 ...............................__........................_...._..............--._......._.-...__..._............._...._...................................._._..._._............................._._.............._........_........_.............................................--....................__......_................_.....__........._.._.........._.....__..........__....._._..._......................_..........._.__................_..._........................ _. Master Bathroom 412 1-7" Run 561 1-6" Run 55 68 14 *21 _......._...._..-_..___..._._.__....._.......-.. --- .._._.........................._..............-.........._........_... ---_............_...—-...__.._......._........._.__...__.... _-........_......_.......__...............---............._...- ..-....._................_.._.............._......_.._._._.............---- MASTER BEDROOM 412 1-7" Run 561 1-6" Run 93 65 *23 20 ..........._........................ . . .. . . . ..... . .. . . .. . . .. ....................... _-__._._.........................................____......_.................__..__...................................._.__....._................_........_......_—_._......_............._...... MUD ROOM--LAUNDRY 412 1-7" Run 561 1-6" Run 90 56 *22 17 ---......._. --.....................__..._...._._...._..._......._._._....................._..................._.....----....-.._........................_.__..-.....__...__.. __._ .. _---- ...........---....-------.........-.._....._..... --..._...........__....._...._......._...................... ..__-.........._............._._.._._._....._...........__.. OFFICE 412 1-7" Run 561 1$" Run 65 99.. 16.. *30 ..................--.__._......................__.............._..............__..........._...._.......---..........................................__......._....................._......................_......_..................................._....__..__ ................................._._............._........................_........_...__............................._............_.__........__............_.................._....._.................._........ WIC 412 1-7" Run 561 1-6" Run 22 13 *6 4 _-- _ .. -............_.....__...._.__....---..__............._..__....._._.-_...__...................._..._._......- ----..._............. .........................._....-_-_......._._......._.._...__.......__................................. .........................---..__......................... ---........_..._._.__._...._.. —__...._.........._._...... .... WIC 412 1-7" Run 561 1-6" Run 21 11 *5 3 Adtek Accul-oad Report Version 17.3.5 Page 11 Your Company Here... P.J. CALLAHAN Your Address Here... -City Here..., State Here..Zip Here... 40 SUNNYSIDE EAST COUNTY ROUTE 39 'Phdne Here..... - Email Here... QUEENSBURY, NY 12804 Sales Consultant: KEITH SMITH 518-307-8880 Job#: P.J. CALLAHAN Date: 12/05/2017 Expanded Manual S (ACCA Guidelines) MJ8 Design Calculations Sensible Gain (btuh): 25726 Design TD for Airflow: 17 Latent Gain (btuh): 5243 Design CFM: 1027 Total Heat Gain (btuh): 30969 SHR: 0.89 Heat Loss (btuh): 88102 Manufacturers Performance Data(A) Entering Coil Temperature = 75 (F db) Lower Return Air Total Sensible Latent SHR CFM (F wb) BTUH BTUH BTUH Rated CFN @ Rated RA Temperature: 0 0 0 0 Rated CFN @ Design RA Temperature: 0 63 0 0 0 Rated CFN @ Rated RA Temperature: 0 0 0 0 Manufacturers Performance Data (B) Entering Coil Temperature = 75 (F db) Higher Return Air Total Sensible Latent SHR CFM (F wb) BTUH BTUH BTUH Rated CFN @ Rated RA Temperature: 0 0 0 0 Rated CFN @ Design RA Temperature: 0 0 0 0 0 Rated CFN @ Rated RA Temperature: 0 0 0 0 Equipment Performance Data Entering Coil Temperature = 75 (F db) Design Return Air Total Sensible Latent CFM (F wb) BTUH BTUH BTUH SHR Intopolated Equipment Capacity 0 0 0 Excess Latent Capacity Calculation 0 0 0 0 0 Capacity @ Design CFM/RA (F wb) 0 0 0 Equipment Capacity as a % of Design Equipment Performance Data Ca acit Thermal Supplemental Entering Coil Temperature = 75 (F db) Capacity 17 F b Balance Heat Required @ 47 F db @ Point Heat Pump Datal N/A NIA 0 0 Desired Calculated Input Output AFUE Temperature Airflow Capacity Capacity Rise Furnace Data N/A =N/A I N/A N/A 0 Adtek AccuLoad Report Version 17.3.5 Page 13