ComCheck COMcheck Software Version 4.1.1.0
ii Interior Lighting Compliance Certificate
ipil
REVIEWED FOR TECEOWER
Project Information ENERGY CODE COMPLIANCE
Energy Code: 2015 IECC I JAN 2 3 2019 1 [1..j
Project Title: Five Guys Queensbury Interior Renovation
Project Type: Alteration TOWN OF QUEENSBURY
BUILDING&CODES
Construction Site: r/Agent: Designer/Contractor:
735 Upper Glen Stre C2 Architecture
Queensbury, NY r �C G p 340 Broadway
r G Schenectady, NY 12305
�-- 518-320-8250
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B X C)
1-Common Space Types:Dining Area-Family Restaurant 1704 0.89 1517
2-Common Space Types:Restrooms 100 0.98 98
3-Common Space Types:Food Preparation 1040 1.21 1258
Total Allowed Watts= 2873
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Common Space Types:Dining Area-Family Restaurant(1704 sq.ft.)
LED 2:LED Other Fixture Unit 28W: 3 31 30 930
LED 3:LED PAR 8W: 1 32 8 256
Track lighting 1:Wattage based on 6 feet of trac: Wattage based on 6 feet of track 0 0 180 180
Common Space Types:Restrooms(100 sq.ft.).
LED 2:LED Other Fixture Unit 28W: 3 2 30 60
Common Space Types:Food Preparation (1040 sq.ft.)
LED 1:LED Panel 44W: 3 19 45 855
Total Proposed Watts= 2281
Interior Lighting PASSES
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans,specifications, and other calculations submitted with this permit application.The proposed interior lighting
systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any
applicable mandatory requirements listed in the Inspectio Checklist.
Michael A Roman, Principal /2 (kA1/22/2019
Name-Title S gnature Date
Project Title: Five Guys Queensbury Interior Renovation Report date: 01/22/19
Data filename: R:\2018 Projects\1826 Five Guys Queensbury\Correspondence\FG Queensbury-Lighting Page 1 of 5
Compliance.cck
COMcheck Software Version 4.1.1.0
II Inspection Checklist
Energy Code: 2015 IECC
IPA
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed.Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 Plans, specifications, and/or ❑Complies
(PR4)1 calculations provide all information ❑Does Not
with which compliance can be
determined for the interior lighting ❑Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed.Information
provided should include interior
lighting power calculations,wattage of
bulbs and ballasts,transformers and
control devices.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Five Guys Queensbury Interior Renovation Report date: 01/22/19
Data filename: R:\2018 Projects\1826 Five Guys Queensbury\Correspondence\FG Queensbury-Lighting Page 2 of 5
Compliance.cck
Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
C405.2.1 Lighting controls installed to uniformly ❑Complies
[EL15]1 reduce the lighting load by at least ❑Does Not
50%. [Not Observable
❑Not Applicable
C405.2.1 Occupancy sensors installed in ❑Complies
[EL18]1 required spaces. ❑Does Not
❑Not Observable
❑Not Applicable
C405.2.1, Independent lighting controls installed ❑Complies��
C405.2.2. per approved lighting plans and all ❑Does Not
3 manual controls readily accessible and Not Observable
[EL23]2 visible to occupants. ❑
❑Not Applicable
C405.2.2. Automatic controls to shutoff all ❑Complies
1 building lighting installed in all ❑Does Not
[EL22]z buildings. [Not Observable
❑Not Applicable
C405.2.3 Daylight zones provided with ❑Complies
[EL16]z individual controls that control the ❑Does Not
lights independent of general area
lighting. DNot Observable
❑Not Applicable
C405.2.3, Primary sidelighted areas are ❑Complies
C405.2.3. equipped with required lighting ElDoes Not
1, controls. ❑Not Observable
C405.2.3.
2 ❑Not Applicable
(EL20]1
C405.2.3, Enclosed spaces with daylight area ❑Complies
C405.2.3. under skylights and rooftop monitors ❑Does Not
1, are equipped with required lighting
C405.2.3. controls. ['Not Observable
3 ❑Not Applicable
[EL21]1
C405.2.4 Separate lighting control devices for ❑Complies
[EL4]1 specific uses installed per approved ❑Does Not
lighting plans. ❑Not Observable
❑Not Applicable
C405.2.4 Additional interior lighting power ❑Complies
[EL8]1 allowed for special functions per the ❑Does Not
approved lighting plans and is
automatically controlled and Not Observable
separated from general lighting. ❑Not Applicable
C405.3 Exit signs do not exceed 5 watts per ❑Complies
[EL6]1 face. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Five Guys Queensbury Interior Renovation Report date: 01/22/19
Data filename: R:\2018 Projects\1826 Five Guys Queensbury\Correspondence\FG Queensbury-Lighting Page 3 of 5
Compliance.cck
Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
C303.3, Furnished O&M instructions for ❑Complies
C408.2.5. systems and equipment to the ❑Does Not
2 building owner or designated
[FI17]3 representative. ❑Not Observable
❑Not Applicable
C405.4.1 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values.
[FI18]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans, demonstrating proposed watts ❑Not Observable
are less than or equal to allowed ❑Not Applicable
watts.
C408.2.5. Furnished as-built drawings for ❑Complies
1 electric power systems within 90 days ❑Does Not
[FI16]3 of system acceptance.
❑Not Observable
❑Not Applicable
C408.3 Lighting systems have been tested to EComplies
[FI33]1 ensure proper calibration,adjustment, ❑Does Not
programming,and operation. ENot Observable
ElNot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Five Guys Queensbury Interior Renovation Report date: 01/22/19
Data filename: R:\2018 Projects\1826 Five Guys Queensbury\Correspondence\FG Queensbury-Lighting Page 4 of 5
Compliance.cck