inspection 08262019INSPECTION WORKSHEET (FMGAS-005374-2019)
RC-0170-2019Permit Management
Case Number:Case Module:
08/26/2019Partial Pass
Inspection Date:Inspection Status:
Mike PalmerGas Fireplace/Stove
Inspector:Inspection Type:
289.16-1-10
Job Address:Parcel Number:
57 Grand View Dr
Queensbury, NY 12804
Contact TypeCompany NameName
ApplicantHilltop Construction
ContractorHilltop Construction
Granted PermissionMarc Garvey
Primary OwnerMarc Garvey
Checklist ItemPassedComments
Fire Marshal NotesTrueHeatilator Model A36 w / factory built vertical chimney system
Floor ProtectionTrueZero clearance
CO DetectionFalseReturn to verify
Vent Chimney TerminationFalse
Can't see chimney clearances after firebox opening
Return for termination and raincap
CSST BondingTrue
ICC Trac pipe used for possible gas log set
See page 34 for log set instructions
Gas Shut-off ValveFalseVerify
Mantel-height above fp openingFalseSee page 32 for directions - return to verify
Hearth Extension (if any)FalseSee page 28 for directions return to verify
Combustion AirTrue
Vent Clearance to CombustiblesTrue
Clearances to Combustibles (all sides)True3/4 side and rear ok
Firestop(s) - Vertical ChaseTrue
December 11, 2019Page 1 of 1