inspectionsINSPECTION WORKSHEET (BINS-001808-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Wed Apr 3, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Insulation
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Agent White, Richard
Engineer Hutchins Engineering
Granted Permission Bette & Cring, LLC
Architect Silvestri Architects, PC
Primary Owner Exit 18 Development LLC
Contractor Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Applicant Bette & Cring, LLC
Checklist Item Passed Comments
Apr 03, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001808-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
- 3rd Floor Corridor return Ductwork at south end corridor.
3/22/19 Insulation Partial Approval-2nd Floor South Wing
- 3 1/2" Sound batts in ceilings of rooms except bathrooms.
- R19 fiberglass insulation and poly vapor barrier exterior
walls.
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
3/29/19 Insulation Partial Approval
- 2nd Floor window sealing with sprayfoam approved.
- Sound vinyl between rooms approved south wing 2nd floor.
4/2/19 Insulation Partial Approval - 2nd Floor
- Balance of sound vinyl between rooms approved
4/3/19 Insulation Partial Approval - 2nd Floor Only!
- Bathroom sound batt Insulation approved except for 2
bathrooms below 3rd floor tub trap leak.
Window Sealing NO
U Factors = .3 cfm for windows, .5 cfm for doors NO
Tyvek or Similar Exterior Sealant NO
Proper Vent, Attic Vent NO
Apr 03, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001808-2019)
Checklist Item Passed Comments
Insulation Residential Check Commercial Check NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/22/19 Insulation Partial Approval-2nd Floor South Wing
- 3 1/2" Sound batts in ceilings of rooms except bathrooms.
- R19 fiberglass insulation and poly vapor barrier exterior
walls.
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
3/29/19 Insulation Partial Approval
- 2nd Floor window sealing with sprayfoam approved.
- Sound vinyl between rooms approved south wing 2nd floor.
4/2/19 Insulation Partial Approval - 2nd Floor
- Balance of sound vinyl between rooms approved
4/3/19 Insulation Partial Approval - 2nd Floor Only!
- Bathroom sound batt Insulation approved except for 2
bathrooms below 3rd floor tub trap leak.
Blower Door Test NO
Combustion Air Supply for Furnace NO
Fresh air supply 3' from grade NO
Duct Insulation - if required in unheated spaces NO
Door / Window Sealed (No Insulation)NO 3/22/19
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
3/29/19 Insulation Partial Approval
- 2nd Floor window sealing with sprayfoam approved.
- Sound vinyl between rooms approved south wing 2nd floor.
Apr 03, 2019 Page (3)
INSPECTION WORKSHEET (BINS-001808-2019)
Checklist Item Passed Comments
Tub Shower R-20 with Vapor Barrier NO
Air Barrier behind Knee Walls NO
All Ductwork Sealed Return and Supply NO 3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
- 3rd Floor Corridor except return ductwork at south end
corridor.
Duct Blaster Test for duct work, R-8 NO
All Return Air Hard Duct Work NO
House Wrap Taped at all Seams NO
Apr 03, 2019 Page (4)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001735-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Tue Apr 2, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Insulation
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Contractor Bette & Cring, LLC
Engineer Hutchins Engineering
Architect Silvestri Architects, PC
Applicant Bette & Cring, LLC
Granted Permission Bette & Cring, LLC
Agent White, Richard
Primary Owner Exit 18 Development LLC
Primary Owner Ed & Ed T Enterprises, LLC
Checklist Item Passed Comments
Apr 02, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001735-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
- 3rd Floor Corridor return Ductwork at south end corridor.
3/22/19 Insulation Partial Approval-2nd Floor South Wing
- 3 1/2" Sound batts in ceilings of rooms except bathrooms.
- R19 fiberglass insulation and poly vapor barrier exterior
walls.
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
3/29/19 Insulation Partial Approval
- 2nd Floor window sealing with sprayfoam approved.
- Sound vinyl between rooms approved south wing 2nd floor.
4/2/19 Insulation Partial Approval - 2nd Floor
- Balance of sound vinyl between rooms approved
Window Sealing NO
U Factors = .3 cfm for windows, .5 cfm for doors NO
Tyvek or Similar Exterior Sealant NO
Proper Vent, Attic Vent NO
Apr 02, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001735-2019)
Checklist Item Passed Comments
Insulation Residential Check Commercial Check NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/22/19 Insulation Partial Approval-2nd Floor South Wing
- 3 1/2" Sound batts in ceilings of rooms except bathrooms.
- R19 fiberglass insulation and poly vapor barrier exterior
walls.
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
3/29/19 Insulation Partial Approval
- 2nd Floor window sealing with sprayfoam approved.
- Sound vinyl between rooms approved south wing 2nd floor.
4/2/19 Insulation Partial Approval - 2nd Floor
- Balance of sound vinyl between rooms approved
Blower Door Test NO
Combustion Air Supply for Furnace NO
Fresh air supply 3' from grade NO
Duct Insulation - if required in unheated spaces NO
Door / Window Sealed (No Insulation)NO 3/22/19
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
3/29/19 Insulation Partial Approval
- 2nd Floor window sealing with sprayfoam approved.
- Sound vinyl between rooms approved south wing 2nd floor.
Air Barrier behind Knee Walls NO
Apr 02, 2019 Page (3)
INSPECTION WORKSHEET (BINS-001735-2019)
Checklist Item Passed Comments
Tub Shower R-20 with Vapor Barrier NO
All Ductwork Sealed Return and Supply NO 3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
- 3rd Floor Corridor except return ductwork at south end
corridor.
Duct Blaster Test for duct work, R-8 NO
All Return Air Hard Duct Work NO
House Wrap Taped at all Seams NO
Apr 02, 2019 Page (4)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (RPLUM-001734-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Tue Apr 2, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Granted Permission Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Architect Silvestri Architects, PC
Primary Owner Exit 18 Development LLC
Contractor Bette & Cring, LLC
Engineer Hutchins Engineering
Agent White, Richard
Applicant Bette & Cring, LLC
Checklist Item Passed Comments
Apr 02, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001734-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
3/19/19 Sealed Ductwork Partial Approval - 2nd Floor
Mechanical Chases
3/22/19 Plumbing Partial Approval - 2nd Floor Only!
- Nail Plates Approved
3/25/19 Plumbing Partial Approval
- Pressure Test Approved waterlines in rooms for 1st, 2nd,
and 3rd Floor. 80 PSI !
- Seal Ductwork Partial Approval north and south wings of 1st
floor.
4/2/19 Plumbing Partial Approval
- 9 Plumbing Vent Stacks Approved (Head Test)
- Roof Drains & Overflows Approved (Head Test)
- 3rd Floor Tub Traps Approved ( Tubs filled w/ water for
flow test)
Plumbing Under Slab YES 11/2/18. Underslab for north half of building
Apr 02, 2019 Page (2)
INSPECTION WORKSHEET (RPLUM-001734-2019)
Checklist Item Passed Comments
Rough Plumbing / Nail Plates NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
3/22/19 Plumbing Partial Approval - 2nd Floor Only!
- Nail Plates Approved
3/25/19 Plumbing Partial Approval
- Pressure Test Approved waterlines in rooms for 1st, 2nd,
and 3rd Floor. 80 PSI !
- Seal Ductwork Partial Approval north and south wings of 1st
floor.
4/2/19 Plumbing Partial Approval
- 9 Plumbing Vent Stacks Approved (Head Test)
- Roof Drains & Overflows Approved (Head Test)
- 3rd Floor Tub Traps Approved ( Tubs filled w/ water for
flow test)
Plumbing Vent Vents in Place NO
3" Vent Through Roof NO
1 ½ inch minimum Drain Size NO
Washing Machine Drain 2 inch minimum NO
Apr 02, 2019 Page (3)
INSPECTION WORKSHEET (RPLUM-001734-2019)
Checklist Item Passed Comments
Washing Machine Trap: 18"-24" discharge NO
Cleanout every 100 feet change of direction NO
Pressure Test NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Drain Vent YES 11/2/18 north half of building water head test ok
Apr 02, 2019 Page (4)
INSPECTION WORKSHEET (RPLUM-001734-2019)
Checklist Item Passed Comments
Air Head NO Air Test
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Apr 02, 2019 Page (5)
INSPECTION WORKSHEET (RPLUM-001734-2019)
Checklist Item Passed Comments
5 psi or 10 ft. above highest conn. for 15 minutes NO 5 PSI
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Pressure Test NO
Water Supply Piping NO 3/25/19 Plumbing Partial Approval
- Pressure Test Approved waterlines in rooms for 1st, 2nd,
and 3rd Floor. 80 PSI !
- Seal Ductwork Partial Approval north and south wings of 1st
floor.
Air Head NO
50 P.S.I for 15 minutes NO
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Apr 02, 2019 Page (6)
INSPECTION WORKSHEET (RPLUM-001734-2019)
Checklist Item Passed Comments
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO 3/19/19 Sealed Ductwork Partial Approval - 2nd Floor
Mechanical Chases
3/25/19 Plumbing Partial Approval
- Pressure Test Approved waterlines in rooms for 1st, 2nd,
and 3rd Floor. 80 PSI !
- Seal Ductwork Partial Approval north and south wings of 1st
floor.
Apr 02, 2019 Page (7)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (FIST-001733-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Mon Apr 1, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Firestopping
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Architect Silvestri Architects, PC
Applicant Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Primary Owner Exit 18 Development LLC
Agent White, Richard
Contractor Bette & Cring, LLC
Engineer Hutchins Engineering
Granted Permission Bette & Cring, LLC
Checklist Item Passed Comments
Apr 01, 2019 Page (1)
INSPECTION WORKSHEET (FIST-001733-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 3/19/19 Firestopping Partial Approval - 2nd Floor Walls
Approved except plumbing chases common with corridor
walls & gaps at top plates of double walls at bathrooms and
mechanical rooms.
3/27/19 Firestopping Partial Approval - 2nd Floor Bathrooms
- Plumbing chases firestopping approved 2nd Floor
Bathrooms except for rooms 201, 203, & 207.
3/29/19 Firestopping Partial Approval- 2nd Floor only!
-Plumbing chases at 201, 203 and 207 approved
-Partial approval of dead space shaft at south side of main
canopy. Firestop between 2nd& 3rd floor approved. Top of
Shaft at Roof needs to be firestopped will recheck on
Monday.
4/1/19 Firestopping & Draftstopping Partial Approval - 3rd
floor only!
- Draftstops between rooms & bathrooms
- Firestopping at exterior walls, bathroom walls. room walls,
tub traps and corridor walls.
- Completed Firestopping the lid of the dead space shaft at
the south side of the front canopy.
Remaining Items:
- Floor and Ceiling Firestops for HVAC rated shafts.
- Draftstops In floor above plumbing chases at room divider
walls.
Fire separation 1, 2, 3 hour NO
Fire wall 2, 3, 4 hour NO
Fireproofing NO
Apr 01, 2019 Page (2)
INSPECTION WORKSHEET (FIST-001733-2019)
Checklist Item Passed Comments
Firestopping NO 3/12/19 Complete sealing all penetrations between rooms in
draft stops on all floors
3/19/19 Firestopping Partial Approval - 2nd Floor Walls
Approved except plumbing chases common with corridor
walls & gaps at top plates of double walls at bathrooms and
mechanical rooms.
3/27/19 Firestopping Partial Approval - 2nd Floor Bathrooms
- Plumbing chases firestopping approved 2nd Floor
Bathrooms except for rooms 201, 203, & 207.
3/29/19 Firestopping Partial Approval- 2nd Floor only!
-Plumbing chases at 201, 203 and 207 and chase behind
elevator approved.
-Partial approval of dead space shaft at south side of main
canopy. Firestop between 2nd& 3rd floor approved. Top of
Shaft at Roof needs to be firestopped will recheck on
Monday.
4/1/19 Firestopping & Draftstopping Partial Approval - 3rd
floor only!
- Draftstops between rooms & bathrooms
- Firestopping at exterior walls, bathroom walls. room walls,
tub traps and corridor walls.
- Completed Firestopping the lid of the dead space shaft at
the south side of the front canopy.
Remaining Items:
- Floor and Ceiling Firestops for HVAC rated shafts.
- Draftstops In floor above plumbing chases at room divider
walls.
Draft stopping 1,000 sq. ft. floor trusses NO 4/1/19 Firestopping & Draftstopping Partial Approval - 3rd
floor only!
- Draftstops between rooms & bathrooms
- Firestopping at exterior walls, bathroom walls. room walls,
tub traps and corridor walls.
- Completed Firestopping the lid of the dead space shaft at
the south side of the front canopy.
Remaining Items:
- Floor and Ceiling Firestops for HVAC rated shafts.
- Draftstops In floor above plumbing chases at room divider
walls.
Penetration sealed NO
Apr 01, 2019 Page (3)
INSPECTION WORKSHEET (FIST-001733-2019)
Checklist Item Passed Comments
16 inch insulation in cavity min.NO
Garage Fire Separation NO
House side ½ inch or 58 inch Type X NO
Garage side 5/8 inch Type X NO
Ceilingwall NO
Apr 01, 2019 Page (4)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (FIST-001669-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Fri Mar 29, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Firestopping
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Primary Owner Ed & Ed T Enterprises, LLC
Primary Owner Exit 18 Development LLC
Architect Silvestri Architects, PC
Applicant Bette & Cring, LLC
Engineer Hutchins Engineering
Contractor Bette & Cring, LLC
Granted Permission Bette & Cring, LLC
Agent White, Richard
Checklist Item Passed Comments
Building Inspector Notes NO 3/19/19 Firestopping Partial Approval - 2nd Floor Walls
Approved except plumbing chases common with corridor
walls & gaps at top plates of double walls at bathrooms and
mechanical rooms.
3/27/19 Firestopping Partial Approval - 2nd Floor Bathrooms
- Plumbing chases firestopping approved 2nd Floor
Bathrooms except for rooms 201, 203, & 207.
3/29/19 Firestopping Partial Approval- 2nd Floor only!
-Plumbing chases at 201, 203 and 207 approved
-Partial approval of dead space shaft at south side of main
canopy. Firestop between 2nd& 3rd floor approved. Top of
Shaft at Roof needs to be firestopped will recheck on
Monday.
Mar 29, 2019 Page (1)
INSPECTION WORKSHEET (FIST-001669-2019)
Checklist Item Passed Comments
Fire separation 1, 2, 3 hour NO
Fire wall 2, 3, 4 hour NO
Fireproofing NO
Firestopping NO 3/12/19 Complete sealing all penetrations between rooms in
draft stops on all floors
3/19/19 Firestopping Partial Approval - 2nd Floor Walls
Approved except plumbing chases common with corridor
walls & gaps at top plates of double walls at bathrooms and
mechanical rooms.
3/27/19 Firestopping Partial Approval - 2nd Floor Bathrooms
- Plumbing chases firestopping approved 2nd Floor
Bathrooms except for rooms 201, 203, & 207.
3/29/19 Firestopping Partial Approval- 2nd Floor only!
-Plumbing chases at 201, 203 and 207 and chase behind
elevator approved.
-Partial approval of dead space shaft at south side of main
canopy. Firestop between 2nd& 3rd floor approved. Top of
Shaft at Roof needs to be firestopped will recheck on
Monday.
Penetration sealed NO
16 inch insulation in cavity min.NO
Garage Fire Separation NO
House side ½ inch or 58 inch Type X NO
Garage side 5/8 inch Type X NO
Ceilingwall NO
Mar 29, 2019 Page (2)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001670-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Fri Mar 29, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Insulation
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Primary Owner Exit 18 Development LLC
Applicant Bette & Cring, LLC
Architect Silvestri Architects, PC
Primary Owner Ed & Ed T Enterprises, LLC
Granted Permission Bette & Cring, LLC
Contractor Bette & Cring, LLC
Agent White, Richard
Engineer Hutchins Engineering
Checklist Item Passed Comments
Mar 29, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001670-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
- 3rd Floor Corridor return Ductwork at south end corridor.
3/22/19 Insulation Partial Approval-2nd Floor South Wing
- 3 1/2" Sound batts in ceilings of rooms except bathrooms.
- R19 fiberglass insulation and poly vapor barrier exterior
walls.
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
3/29/19 Insulation Partial Approval
- 2nd Floor window sealing with sprayfoam approved.
- Sound vinyl between rooms approved south wing 2nd floor.
Window Sealing NO
U Factors = .3 cfm for windows, .5 cfm for doors NO
Tyvek or Similar Exterior Sealant NO
Proper Vent, Attic Vent NO
Mar 29, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001670-2019)
Checklist Item Passed Comments
Insulation Residential Check Commercial Check NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/22/19 Insulation Partial Approval-2nd Floor South Wing
- 3 1/2" Sound batts in ceilings of rooms except bathrooms.
- R19 fiberglass insulation and poly vapor barrier exterior
walls.
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
3/29/19 Insulation Partial Approval
- 2nd Floor window sealing with sprayfoam approved.
- Sound vinyl between rooms approved south wing 2nd floor.
Blower Door Test NO
Combustion Air Supply for Furnace NO
Fresh air supply 3' from grade NO
Duct Insulation - if required in unheated spaces NO
Door / Window Sealed (No Insulation)NO 3/22/19
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
3/29/19 Insulation Partial Approval
- 2nd Floor window sealing with sprayfoam approved.
- Sound vinyl between rooms approved south wing 2nd floor.
Tub Shower R-20 with Vapor Barrier NO
Air Barrier behind Knee Walls NO
Mar 29, 2019 Page (3)
INSPECTION WORKSHEET (BINS-001670-2019)
Checklist Item Passed Comments
All Ductwork Sealed Return and Supply NO 3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
- 3rd Floor Corridor except return ductwork at south end
corridor.
Duct Blaster Test for duct work, R-8 NO
All Return Air Hard Duct Work NO
House Wrap Taped at all Seams NO
Mar 29, 2019 Page (4)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001531-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Fri Mar 22, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Insulation
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Primary Owner Exit 18 Development LLC
Architect Silvestri Architects, PC
Agent White, Richard
Engineer Hutchins Engineering
Applicant Bette & Cring, LLC
Granted Permission Bette & Cring, LLC
Contractor Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Checklist Item Passed Comments
Mar 22, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001531-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
- 3rd Floor Corridor return Ductwork at south end corridor.
3/22/19 Insulation Partial Approval-2nd Floor South Wing
- 3 1/2" Sound batts in ceilings of rooms except bathrooms.
- R19 fiberglass insulation and poly vapor barrier exterior
walls.
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
Window Sealing NO
U Factors = .3 cfm for windows, .5 cfm for doors NO
Tyvek or Similar Exterior Sealant NO
Proper Vent, Attic Vent NO
Mar 22, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001531-2019)
Checklist Item Passed Comments
Insulation Residential Check Commercial Check NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/22/19 Insulation Partial Approval-2nd Floor South Wing
- 3 1/2" Sound batts in ceilings of rooms except bathrooms.
- R19 fiberglass insulation and poly vapor barrier exterior
walls.
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
Blower Door Test NO
Combustion Air Supply for Furnace NO
Fresh air supply 3' from grade NO
Duct Insulation - if required in unheated spaces NO
Door / Window Sealed (No Insulation)NO 3/22/19
Note: Remove fiberglass insulation at perimeter of windows
and install window and door spray foam.
Tub Shower R-20 with Vapor Barrier NO
Air Barrier behind Knee Walls NO
All Ductwork Sealed Return and Supply NO 3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
- 3rd Floor Corridor except return ductwork at south end
corridor.
Mar 22, 2019 Page (3)
INSPECTION WORKSHEET (BINS-001531-2019)
Checklist Item Passed Comments
Duct Blaster Test for duct work, R-8 NO
All Return Air Hard Duct Work NO
House Wrap Taped at all Seams NO
Mar 22, 2019 Page (4)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001565-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Fri Mar 22, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Framing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Contractor Bette & Cring, LLC
Granted Permission Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Engineer Hutchins Engineering
Primary Owner Exit 18 Development LLC
Agent White, Richard
Applicant Bette & Cring, LLC
Architect Silvestri Architects, PC
Checklist Item Passed Comments
Mar 22, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001565-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/11/19 Framing Not Approved - Preliminary Framing
- Provide Dan Ryan's Inspection Report for the first floor
framing inspection for walls and ceiling.
- Provide floor and roof truss diagrams for framing
inspections.
- Engineer's approval on fastening of interior walls, corridor
walls, and shear walls. Framer has used power actuated
nails at all locations which is different from the approved
plans. I spoke with Dan Ryan the engineer today while on
site performing my inspection.
2/15/19 Framing for first and second floor main hall ceiling
approved. Third floor main hall ceiling not approved, it is still
missing joist hangers.sound proofing insulation must be
verified before sheet rock is installed.
3/22/19 Framing Partial Approval - 2nd Floor Only!
Note: Received Dan Ryan's Structural Inspection Report for
floors 1,2 & 3 (Special Inspection). I will perform my final
framing inspections on the 1st & 3rd floor next week.
Framing NO 2/11/19 Framing Not Approved - Preliminary Framing
- Provide Dan Ryan's Inspection Report for the first floor
framing inspection for walls and ceiling.
- Provide floor and roof truss diagrams for framing
inspections.
- Engineer's approval on fastening of interior walls, corridor
walls, and shear walls. Framer has used power actuated
nails at all locations which is different from the approved
plans. I spoke with Dan Ryan the engineer today while on
site performing my inspection.
2/15/19 first and second floor main hall ceiling only approved.
Third floor is missing joist hangers. Sound proofing insulation
must be verified before Sheetrock is installed.
3/22/19 Framing Partial Approval - 2nd Floor Only!
Note: Received Dan Ryan's Structural Inspection Report for
floors 1,2 & 3 (Special Inspection). I will perform my final
framing inspections on the 1st & 3rd floor next week.
Bracing Bridging NO
Hurricane Clips/Uplift Screws/Nail Holes Filled NO
Joist hangers NO
Mar 22, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001565-2019)
Checklist Item Passed Comments
Jack Posts Main Beams NO
Headroom 6 ft. 8 in.NO
Notches Holes Bearing Walls NO
Metal Strapping for Notches Top Plate NO
Draft stopping 1,000 sq. ft. floor trusses NO 2nd floor only completed.
Anchor Bolts 6 ft. or less on center NO
Design Professional Sign-off, if required YES 3/22/19
Note: Received Dan Ryan's Structural Inspection Report for
floors 1,2 & 3 (Special Inspection). I will perform my final
framing inspections on the 1st & 3rd floor next week.
Mar 22, 2019 Page (3)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (RPLUM-001567-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Fri Mar 22, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Contractor Bette & Cring, LLC
Granted Permission Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Engineer Hutchins Engineering
Primary Owner Exit 18 Development LLC
Agent White, Richard
Applicant Bette & Cring, LLC
Architect Silvestri Architects, PC
Checklist Item Passed Comments
Mar 22, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001567-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
3/19/19 Sealed Ductwork Partial Approval - 2nd Floor
Mechanical Chases
3/22/19 Plumbing Partial Approval - 2nd Floor Only!
- Nail Plates Approved
Plumbing Under Slab YES 11/2/18. Underslab for north half of building
Mar 22, 2019 Page (2)
INSPECTION WORKSHEET (RPLUM-001567-2019)
Checklist Item Passed Comments
Rough Plumbing / Nail Plates NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
3/22/19 Plumbing Partial Approval - 2nd Floor Only!
- Nail Plates Approved
Plumbing Vent Vents in Place NO
3" Vent Through Roof NO
1 ½ inch minimum Drain Size NO
Washing Machine Drain 2 inch minimum NO
Washing Machine Trap: 18"-24" discharge NO
Cleanout every 100 feet change of direction NO
Mar 22, 2019 Page (3)
INSPECTION WORKSHEET (RPLUM-001567-2019)
Checklist Item Passed Comments
Pressure Test NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Drain Vent YES 11/2/18 north half of building water head test ok
Mar 22, 2019 Page (4)
INSPECTION WORKSHEET (RPLUM-001567-2019)
Checklist Item Passed Comments
Air Head NO Air Test
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Mar 22, 2019 Page (5)
INSPECTION WORKSHEET (RPLUM-001567-2019)
Checklist Item Passed Comments
5 psi or 10 ft. above highest conn. for 15 minutes NO 5 PSI
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Pressure Test NO
Water Supply Piping NO
Air Head NO
50 P.S.I for 15 minutes NO
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Mar 22, 2019 Page (6)
INSPECTION WORKSHEET (RPLUM-001567-2019)
Checklist Item Passed Comments
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO 3/19/19 Sealed Ductwork Partial Approval - 2nd Floor
Mechanical Chases
Mar 22, 2019 Page (7)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (RPLUM-001582-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Mon Mar 25, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Contractor Bette & Cring, LLC
Granted Permission Bette & Cring, LLC
Agent White, Richard
Applicant Bette & Cring, LLC
Primary Owner Exit 18 Development LLC
Engineer Hutchins Engineering
Primary Owner Ed & Ed T Enterprises, LLC
Architect Silvestri Architects, PC
Checklist Item Passed Comments
Mar 25, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001582-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
3/19/19 Sealed Ductwork Partial Approval - 2nd Floor
Mechanical Chases
3/22/19 Plumbing Partial Approval - 2nd Floor Only!
- Nail Plates Approved
3/25/19 Plumbing Partial Approval
- Pressure Test Approved waterlines in rooms for 1st, 2nd,
and 3rd Floor. 80 PSI !
- Seal Ductwork Partial Approval north and south wings of 1st
floor.
Plumbing Under Slab YES 11/2/18. Underslab for north half of building
Mar 25, 2019 Page (2)
INSPECTION WORKSHEET (RPLUM-001582-2019)
Checklist Item Passed Comments
Rough Plumbing / Nail Plates NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
3/22/19 Plumbing Partial Approval - 2nd Floor Only!
- Nail Plates Approved
3/25/19 Plumbing Partial Approval
- Pressure Test Approved waterlines in rooms for 1st, 2nd,
and 3rd Floor. 80 PSI !
- Seal Ductwork Partial Approval north and south wings of 1st
floor.
Plumbing Vent Vents in Place NO
3" Vent Through Roof NO
1 ½ inch minimum Drain Size NO
Washing Machine Drain 2 inch minimum NO
Washing Machine Trap: 18"-24" discharge NO
Mar 25, 2019 Page (3)
INSPECTION WORKSHEET (RPLUM-001582-2019)
Checklist Item Passed Comments
Cleanout every 100 feet change of direction NO
Pressure Test NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Drain Vent YES 11/2/18 north half of building water head test ok
Mar 25, 2019 Page (4)
INSPECTION WORKSHEET (RPLUM-001582-2019)
Checklist Item Passed Comments
Air Head NO Air Test
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Mar 25, 2019 Page (5)
INSPECTION WORKSHEET (RPLUM-001582-2019)
Checklist Item Passed Comments
5 psi or 10 ft. above highest conn. for 15 minutes NO 5 PSI
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Pressure Test NO
Water Supply Piping NO 3/25/19 Plumbing Partial Approval
- Pressure Test Approved waterlines in rooms for 1st, 2nd,
and 3rd Floor. 80 PSI !
- Seal Ductwork Partial Approval north and south wings of 1st
floor.
Air Head NO
50 P.S.I for 15 minutes NO
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Mar 25, 2019 Page (6)
INSPECTION WORKSHEET (RPLUM-001582-2019)
Checklist Item Passed Comments
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO 3/19/19 Sealed Ductwork Partial Approval - 2nd Floor
Mechanical Chases
3/25/19 Plumbing Partial Approval
- Pressure Test Approved waterlines in rooms for 1st, 2nd,
and 3rd Floor. 80 PSI !
- Seal Ductwork Partial Approval north and south wings of 1st
floor.
Mar 25, 2019 Page (7)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001611-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Mon Mar 25, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Framing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Contractor Bette & Cring, LLC
Granted Permission Bette & Cring, LLC
Agent White, Richard
Applicant Bette & Cring, LLC
Primary Owner Exit 18 Development LLC
Engineer Hutchins Engineering
Primary Owner Ed & Ed T Enterprises, LLC
Architect Silvestri Architects, PC
Checklist Item Passed Comments
Mar 25, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001611-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/11/19 Framing Not Approved - Preliminary Framing
- Provide Dan Ryan's Inspection Report for the first floor
framing inspection for walls and ceiling.
- Provide floor and roof truss diagrams for framing
inspections.
- Engineer's approval on fastening of interior walls, corridor
walls, and shear walls. Framer has used power actuated
nails at all locations which is different from the approved
plans. I spoke with Dan Ryan the engineer today while on
site performing my inspection.
2/15/19 Framing for first and second floor main hall ceiling
approved. Third floor main hall ceiling not approved, it is still
missing joist hangers.sound proofing insulation must be
verified before sheet rock is installed.
3/15/19 Draftstopping Partial Approval-2nd Floor Rooms
only!
-Draftstopping in rooms of 2nd floor Approved except for
bathrooms.
3/25/19 Framing Inspection Partial Approval
- Framing Approved for 1st and 3rd floor rooms and corridors
Framing NO 2/11/19 Framing Not Approved - Preliminary Framing
- Provide Dan Ryan's Inspection Report for the first floor
framing inspection for walls and ceiling.
- Provide floor and roof truss diagrams for framing
inspections.
- Engineer's approval on fastening of interior walls, corridor
walls, and shear walls. Framer has used power actuated
nails at all locations which is different from the approved
plans. I spoke with Dan Ryan the engineer today while on
site performing my inspection.
2/15/19 first and second floor main hall ceiling only approved.
Third floor is missing joist hangers. Sound proofing insulation
must be verified before Sheetrock is installed.
Air Seal all Plates and Sills NO
Air Seal All Registers at Floor NO
Air Sealing all Joints Before Insulation NO
Mar 25, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001611-2019)
Checklist Item Passed Comments
Notches Holes Bearing Walls NO
Metal Strapping for Notches Top Plate NO
Draft stopping 1,000 sq. ft. floor trusses NO 3/15/19 Draftstopping Partial Approval-2nd Floor Rooms
only!
-Draftstopping in rooms of 2nd floor Approved except for
bathrooms.
Design Professional Sign-off, if required NO
Mar 25, 2019 Page (3)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (FIST-001566-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Wed Mar 27, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Firestopping
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Engineer Hutchins Engineering
Contractor Bette & Cring, LLC
Applicant Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Granted Permission Bette & Cring, LLC
Architect Silvestri Architects, PC
Agent White, Richard
Primary Owner Exit 18 Development LLC
Checklist Item Passed Comments
Building Inspector Notes NO 3/19/19 Firestopping Partial Approval - 2nd Floor Walls
Approved except plumbing chases common with corridor
walls & gaps at top plates of double walls at bathrooms and
mechanical rooms.
3/27/19 Firestopping Partial Approval - 2nd Floor Bathrooms
- Plumbing chases firestopping approved 2nd Floor
Bathrooms except for rooms 201, 203, & 207.
Fire separation 1, 2, 3 hour NO
Mar 27, 2019 Page (1)
INSPECTION WORKSHEET (FIST-001566-2019)
Checklist Item Passed Comments
Fire wall 2, 3, 4 hour NO
Fireproofing NO
Firestopping NO 3/12/19 Complete sealing all penetrations between rooms in
draft stops on all floors
3/19/19 Firestopping Partial Approval - 2nd Floor Walls
Approved except plumbing chases common with corridor
walls & gaps at top plates of double walls at bathrooms and
mechanical rooms.
3/27/19 Firestopping Partial Approval - 2nd Floor Bathrooms
- Plumbing chases firestopping approved 2nd Floor
Bathrooms except for rooms 201, 203, & 207.
Penetration sealed NO
16 inch insulation in cavity min.NO
Garage Fire Separation NO
House side ½ inch or 58 inch Type X NO
Garage side 5/8 inch Type X NO
Ceilingwall NO
Mar 27, 2019 Page (2)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001475-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Fri Mar 15, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Framing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Contractor Bette & Cring, LLC
Architect Silvestri Architects, PC
Primary Owner Exit 18 Development LLC
Agent White, Richard
Granted Permission Bette & Cring, LLC
Engineer Hutchins Engineering
Primary Owner Ed & Ed T Enterprises, LLC
Applicant Bette & Cring, LLC
Checklist Item Passed Comments
Mar 15, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001475-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/11/19 Framing Not Approved - Preliminary Framing
- Provide Dan Ryan's Inspection Report for the first floor
framing inspection for walls and ceiling.
- Provide floor and roof truss diagrams for framing
inspections.
- Engineer's approval on fastening of interior walls, corridor
walls, and shear walls. Framer has used power actuated
nails at all locations which is different from the approved
plans. I spoke with Dan Ryan the engineer today while on
site performing my inspection.
2/15/19 Framing for first and second floor main hall ceiling
approved. Third floor main hall ceiling not approved, it is still
missing joist hangers.sound proofing insulation must be
verified before sheet rock is installed.
3/15/19 Draftstopping Partial Approval-2nd Floor Rooms
only!
-Draftstopping in rooms of 2nd floor Approved except for
bathrooms.
Framing NO 2/11/19 Framing Not Approved - Preliminary Framing
- Provide Dan Ryan's Inspection Report for the first floor
framing inspection for walls and ceiling.
- Provide floor and roof truss diagrams for framing
inspections.
- Engineer's approval on fastening of interior walls, corridor
walls, and shear walls. Framer has used power actuated
nails at all locations which is different from the approved
plans. I spoke with Dan Ryan the engineer today while on
site performing my inspection.
2/15/19 first and second floor main hall ceiling only approved.
Third floor is missing joist hangers. Sound proofing insulation
must be verified before Sheetrock is installed.
Truss Specification Provided NO
Bracing Bridging NO
Hurricane Clips/Uplift Screws/Nail Holes Filled NO
Air Seal all Plates and Sills NO
Mar 15, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001475-2019)
Checklist Item Passed Comments
Air Seal All Registers at Floor NO
Air Sealing all Joints Before Insulation NO
Joist hangers NO
Jack Posts Main Beams NO
Exterior sheeting nailed properly NO
12 O.C.NO
Headroom 6 ft. 8 in.NO
Notches Holes Bearing Walls NO
Metal Strapping for Notches Top Plate NO
Draft stopping 1,000 sq. ft. floor trusses NO 3/15/19 Draftstopping Partial Approval-2nd Floor Rooms
only!
-Draftstopping in rooms of 2nd floor Approved except for
bathrooms.
Anchor Bolts 6 ft. or less on center NO
Ice and water shield 24 inches from wall NO
Soffits-Insulation Baffel NO
Windows Habitable Space Bedrooms NO
24 in. (H)NO
Mar 15, 2019 Page (3)
INSPECTION WORKSHEET (BINS-001475-2019)
Checklist Item Passed Comments
20 in. (W)NO
5.7 sf above below grade NO
5.0 sf grade NO
Design Professional Sign-off, if required NO
Mar 15, 2019 Page (4)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001448-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Fri Mar 15, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Insulation
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Agent White, Richard
Primary Owner Exit 18 Development LLC
Primary Owner Ed & Ed T Enterprises, LLC
Contractor Bette & Cring, LLC
Architect Silvestri Architects, PC
Engineer Hutchins Engineering
Granted Permission Bette & Cring, LLC
Applicant Bette & Cring, LLC
Checklist Item Passed Comments
Building Inspector Notes NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
Mar 15, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001448-2019)
Checklist Item Passed Comments
- 3rd Floor Corridor return Ductwork at south end corridor.
Window Sealing NO
U Factors = .3 cfm for windows, .5 cfm for doors NO
Tyvek or Similar Exterior Sealant NO
Proper Vent, Attic Vent NO
Insulation Residential Check Commercial Check NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
Blower Door Test NO
Combustion Air Supply for Furnace NO
Fresh air supply 3' from grade NO
Duct Insulation - if required in unheated spaces NO
Door / Window Sealed (No Insulation)NO
Air Barrier behind Knee Walls NO
Tub Shower R-20 with Vapor Barrier NO
Mar 15, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001448-2019)
Checklist Item Passed Comments
All Ductwork Sealed Return and Supply NO 3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
3/15/19 Ductwork Sealing Partial Approval
- 3rd Floor Corridor except return ductwork at south end
corridor.
Duct Blaster Test for duct work, R-8 NO
All Return Air Hard Duct Work NO
House Wrap Taped at all Seams NO
Mar 15, 2019 Page (3)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (RPLUM-001500-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Wed Mar 20, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Agent White, Richard
Engineer Hutchins Engineering
Architect Silvestri Architects, PC
Contractor Bette & Cring, LLC
Applicant Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Primary Owner Exit 18 Development LLC
Granted Permission Bette & Cring, LLC
Checklist Item Passed Comments
Mar 20, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001500-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
3/19/19 Sealed Ductwork Partial Approval - 2nd Floor
Mechanical Chases
Plumbing Under Slab YES 11/2/18. Underslab for north half of building
Mar 20, 2019 Page (2)
INSPECTION WORKSHEET (RPLUM-001500-2019)
Checklist Item Passed Comments
Rough Plumbing / Nail Plates NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Plumbing Vent Vents in Place NO
3" Vent Through Roof NO
1 ½ inch minimum Drain Size NO
Washing Machine Drain 2 inch minimum NO
Washing Machine Trap: 18"-24" discharge NO
Cleanout every 100 feet change of direction NO
Mar 20, 2019 Page (3)
INSPECTION WORKSHEET (RPLUM-001500-2019)
Checklist Item Passed Comments
Pressure Test NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Drain Vent YES 11/2/18 north half of building water head test ok
Mar 20, 2019 Page (4)
INSPECTION WORKSHEET (RPLUM-001500-2019)
Checklist Item Passed Comments
Air Head NO Air Test
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Mar 20, 2019 Page (5)
INSPECTION WORKSHEET (RPLUM-001500-2019)
Checklist Item Passed Comments
5 psi or 10 ft. above highest conn. for 15 minutes NO 5 PSI
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Pressure Test NO
Water Supply Piping NO
Air Head NO
50 P.S.I for 15 minutes NO
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Mar 20, 2019 Page (6)
INSPECTION WORKSHEET (RPLUM-001500-2019)
Checklist Item Passed Comments
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO 3/19/19 Sealed Ductwork Partial Approval - 2nd Floor
Mechanical Chases
Mar 20, 2019 Page (7)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (FIST-001519-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Wed Mar 20, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Firestopping
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-86.11
Contact Type Company Name Name
Agent White, Richard
Engineer Hutchins Engineering
Architect Silvestri Architects, PC
Contractor Bette & Cring, LLC
Applicant Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Primary Owner Exit 18 Development LLC
Granted Permission Bette & Cring, LLC
Checklist Item Passed Comments
Building Inspector Notes NO 3/19/19 Firestopping Partial Approval - 2nd Floor Walls
Approved except plumbing chases common with corridor
walls & gaps at top plates of double walls at bathrooms and
mechanical rooms.
Fire separation 1, 2, 3 hour NO
Fire wall 2, 3, 4 hour NO
Fireproofing NO
Mar 20, 2019 Page (1)
INSPECTION WORKSHEET (FIST-001519-2019)
Checklist Item Passed Comments
Firestopping NO 3/12/19 Complete sealing all penetrations between rooms in
draft stops on all floors
3/19/19 Firestopping Partial Approval - 2nd Floor Walls
Approved except plumbing chases common with corridor
walls & gaps at top plates of double walls at bathrooms and
mechanical rooms.
Penetration sealed NO
16 inch insulation in cavity min.NO
Garage Fire Separation NO
House side ½ inch or 58 inch Type X NO
Garage side 5/8 inch Type X NO
Ceilingwall NO
Mar 20, 2019 Page (2)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001320-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Wed Mar 6, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Insulation
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-89.1
Contact Type Company Name Name
Granted Permission Bette & Cring, LLC
Engineer Hutchins Engineering
Primary Owner Ed & Ed T Enterprises, LLC
Primary Owner Exit 18 Development LLC
Architect Silvestri Architects, PC
Contractor Bette & Cring, LLC
Agent White, Richard
Applicant Bette & Cring, LLC
Checklist Item Passed Comments
Building Inspector Notes NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
Window Sealing NO
Mar 06, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001320-2019)
Checklist Item Passed Comments
U Factors = .3 cfm for windows, .5 cfm for doors NO
Tyvek or Similar Exterior Sealant NO
Proper Vent, Attic Vent NO
Insulation Residential Check Commercial Check NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
Blower Door Test NO
Combustion Air Supply for Furnace NO
Fresh air supply 3' from grade NO
Duct Insulation - if required in unheated spaces NO
Door / Window Sealed (No Insulation)NO
Air Barrier behind Knee Walls NO
Tub Shower R-20 with Vapor Barrier NO
All Ductwork Sealed Return and Supply NO
Duct Blaster Test for duct work, R-8 NO
Mar 06, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001320-2019)
Checklist Item Passed Comments
All Return Air Hard Duct Work NO
House Wrap Taped at all Seams NO
Mar 06, 2019 Page (3)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-001360-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Fri Mar 8, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Insulation
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-89.1
Contact Type Company Name Name
Agent White, Richard
Granted Permission Bette & Cring, LLC
Primary Owner Exit 18 Development LLC
Contractor Bette & Cring, LLC
Engineer Hutchins Engineering
Architect Silvestri Architects, PC
Primary Owner Ed & Ed T Enterprises, LLC
Applicant Bette & Cring, LLC
Checklist Item Passed Comments
Building Inspector Notes NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
Mar 08, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001360-2019)
Checklist Item Passed Comments
Window Sealing NO
U Factors = .3 cfm for windows, .5 cfm for doors NO
Tyvek or Similar Exterior Sealant NO
Proper Vent, Attic Vent NO
Insulation Residential Check Commercial Check NO 2/19/19 Insulation Partial Approval- 3 1/2" Sound batts in
corridor floors.
- 1st Floor Corridor Ceiling North Wing only where 3 1/2"
Sound Insulation is Installed before elevator.
- 2nd Floor Corridor Ceiling at North & South Wings only
where 3 1/2" Sound Insulation is installed.
3/6/19 Insulation Partial Approval
- R38 fiberglass insulation 2nd floor overhangs.
- 1st floor elevator foyer ceiling 3 1/2" fiberglass sound batt
insulation
Blower Door Test NO
Combustion Air Supply for Furnace NO
Fresh air supply 3' from grade NO
Duct Insulation - if required in unheated spaces NO
Door / Window Sealed (No Insulation)NO
Tub Shower R-20 with Vapor Barrier NO
Air Barrier behind Knee Walls NO
Mar 08, 2019 Page (2)
INSPECTION WORKSHEET (BINS-001360-2019)
Checklist Item Passed Comments
All Ductwork Sealed Return and Supply NO 3/8/19 Ductwork Sealing Partial Approval
- 2nd Floor Corridor Only!
Duct Blaster Test for duct work, R-8 NO
All Return Air Hard Duct Work NO
House Wrap Taped at all Seams NO
Mar 08, 2019 Page (3)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (RPLUM-001177-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Wed Feb 27, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-89.1
Contact Type Company Name Name
Engineer Hutchins Engineering
Primary Owner Ed & Ed T Enterprises, LLC
Agent White, Richard
Contractor Bette & Cring, LLC
Architect Silvestri Architects, PC
Primary Owner Exit 18 Development LLC
Applicant Bette & Cring, LLC
Granted Permission Bette & Cring, LLC
Checklist Item Passed Comments
Building Inspector Notes NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
Plumbing Under Slab YES 11/2/18. Underslab for north half of building
Feb 27, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001177-2019)
Checklist Item Passed Comments
Rough Plumbing / Nail Plates NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
Plumbing Vent Vents in Place NO
3" Vent Through Roof NO
1 ½ inch minimum Drain Size NO
Washing Machine Drain 2 inch minimum NO
Washing Machine Trap: 18"-24" discharge NO
Cleanout every 100 feet change of direction NO
Pressure Test NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
Drain Vent YES 11/2/18 north half of building water head test ok
Feb 27, 2019 Page (2)
INSPECTION WORKSHEET (RPLUM-001177-2019)
Checklist Item Passed Comments
Air Head NO Air Test
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
5 psi or 10 ft. above highest conn. for 15 minutes NO 5 PSI
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
Pressure Test NO
Water Supply Piping NO
Air Head NO
50 P.S.I for 15 minutes NO
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO
Feb 27, 2019 Page (3)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (RPLUM-001202-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Thu Feb 28, 2019 Inspection Status:Passed
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-89.1
Contact Type Company Name Name
Engineer Hutchins Engineering
Contractor Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Granted Permission Bette & Cring, LLC
Agent White, Richard
Applicant Bette & Cring, LLC
Primary Owner Exit 18 Development LLC
Architect Silvestri Architects, PC
Checklist Item Passed Comments
Building Inspector Notes NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
Feb 28, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001202-2019)
Checklist Item Passed Comments
Plumbing Under Slab YES 11/2/18. Underslab for north half of building
Rough Plumbing / Nail Plates NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
Plumbing Vent Vents in Place NO
3" Vent Through Roof NO
1 ½ inch minimum Drain Size NO
Washing Machine Drain 2 inch minimum NO
Washing Machine Trap: 18"-24" discharge NO
Cleanout every 100 feet change of direction NO
Pressure Test NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
Feb 28, 2019 Page (2)
INSPECTION WORKSHEET (RPLUM-001202-2019)
Checklist Item Passed Comments
Drain Vent YES 11/2/18 north half of building water head test ok
Air Head NO Air Test
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
5 psi or 10 ft. above highest conn. for 15 minutes NO 5 PSI
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
Pressure Test NO
Water Supply Piping NO
Air Head NO
50 P.S.I for 15 minutes NO
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Feb 28, 2019 Page (3)
INSPECTION WORKSHEET (RPLUM-001202-2019)
Checklist Item Passed Comments
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO
Feb 28, 2019 Page (4)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (RPLUM-001223-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Fri Mar 1, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-89.1
Contact Type Company Name Name
Contractor Bette & Cring, LLC
Agent White, Richard
Architect Silvestri Architects, PC
Granted Permission Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Primary Owner Exit 18 Development LLC
Engineer Hutchins Engineering
Applicant Bette & Cring, LLC
Checklist Item Passed Comments
Mar 01, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001223-2019)
Checklist Item Passed Comments
Building Inspector Notes NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Plumbing Under Slab YES 11/2/18. Underslab for north half of building
Mar 01, 2019 Page (2)
INSPECTION WORKSHEET (RPLUM-001223-2019)
Checklist Item Passed Comments
Rough Plumbing / Nail Plates NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Plumbing Vent Vents in Place NO
3" Vent Through Roof NO
1 ½ inch minimum Drain Size NO
Washing Machine Drain 2 inch minimum NO
Washing Machine Trap: 18"-24" discharge NO
Cleanout every 100 feet change of direction NO
Mar 01, 2019 Page (3)
INSPECTION WORKSHEET (RPLUM-001223-2019)
Checklist Item Passed Comments
Pressure Test NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Drain Vent YES 11/2/18 north half of building water head test ok
Mar 01, 2019 Page (4)
INSPECTION WORKSHEET (RPLUM-001223-2019)
Checklist Item Passed Comments
Air Head NO Air Test
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Mar 01, 2019 Page (5)
INSPECTION WORKSHEET (RPLUM-001223-2019)
Checklist Item Passed Comments
5 psi or 10 ft. above highest conn. for 15 minutes NO 5 PSI
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
2/27/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 218-230, 232 & 318-330,
332 Approved
2/28/19 Plumbing Partial Approval
- Sanitary Pressure Test for Rooms 210-217 & 310-317
Approved.
3/1/19 Plumbing Partial Approval
Sanitary Pressure Tests for Rooms 101-109, 201-209, &
301-309
Remaining Items:
-Vent stacks thru roof will need pressure tests.
-Bathtubs will need a water flow test
-Pressure Test for domestic water supplies.
-Pressure Test Storm & Overflow Drains
-Pressure Test Gas Lines
-Recheck all plumbing for stud guards, pipe hangers and
correct pitch of pipe.
-Inspect pipe insulation.
Pressure Test NO
Water Supply Piping NO
Air Head NO
50 P.S.I for 15 minutes NO
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Mar 01, 2019 Page (6)
INSPECTION WORKSHEET (RPLUM-001223-2019)
Checklist Item Passed Comments
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO
Mar 01, 2019 Page (7)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (RPLUM-001158-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Tue Feb 26, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-89.1
Contact Type Company Name Name
Primary Owner Exit 18 Development LLC
Architect Silvestri Architects, PC
Applicant Bette & Cring, LLC
Contractor Bette & Cring, LLC
Engineer Hutchins Engineering
Granted Permission Bette & Cring, LLC
Agent White, Richard
Primary Owner Ed & Ed T Enterprises, LLC
Checklist Item Passed Comments
Building Inspector Notes NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
Plumbing Under Slab YES 11/2/18. Underslab for north half of building
Rough Plumbing / Nail Plates NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
Feb 26, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001158-2019)
Checklist Item Passed Comments
Plumbing Vent Vents in Place NO
3" Vent Through Roof NO
1 ½ inch minimum Drain Size NO
Washing Machine Drain 2 inch minimum NO
Washing Machine Trap: 18"-24" discharge NO
Cleanout every 100 feet change of direction NO
Pressure Test NO 2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
Drain Vent YES 11/2/18 north half of building water head test ok
Air Head NO Air Test
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
5 psi or 10 ft. above highest conn. for 15 minutes NO 5 PSI
2/26/19 Plumbing Partial Approval-Pressure Test Only!
- Sanitary pressure test for rooms 112-115, 228-232, &
328-332 Approved
Pressure Test NO
Water Supply Piping NO
Air Head NO
Feb 26, 2019 Page (2)
INSPECTION WORKSHEET (RPLUM-001158-2019)
Checklist Item Passed Comments
50 P.S.I for 15 minutes NO
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO
Feb 26, 2019 Page (3)
O'Brien, John (Inspector)
INSPECTION WORKSHEET (BINS-000859-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000181-2017 Case Module:Permit
Inspection Date:Mon Feb 11, 2019 Inspection Status:Failed
Inspector:John O'Brien Inspection Type:Building Framing
Job Address:Parcel Number:21 Big Boom RD
Queensbury, NY 12804
309.14-1-89.1
Contact Type Company Name Name
Primary Owner Exit 18 Development LLC
Architect Silvestri Architects, PC
Engineer Hutchins Engineering
Applicant Bette & Cring, LLC
Agent White, Richard
Granted Permission Bette & Cring, LLC
Primary Owner Ed & Ed T Enterprises, LLC
Contractor Bette & Cring, LLC
Checklist Item Passed Comments
Building Inspector Notes NO 2/11/19 Framing Not Approved - Preliminary Framing
- Provide Dan Ryan's Inspection Report for the first floor
framing inspection for walls and ceiling.
- Provide floor and roof truss diagrams for framing
inspections.
- Engineer's approval on fastening of interior walls, corridor
walls, and shear walls. Framer has used power actuated
nails at all locations which is different from the approved
plans. I spoke with Dan Ryan the engineer today while on
site performing my inspection.
Feb 11, 2019 Page (1)
INSPECTION WORKSHEET (BINS-000859-2019)
Checklist Item Passed Comments
Framing NO 2/11/19 Framing Not Approved - Preliminary Framing
- Provide Dan Ryan's Inspection Report for the first floor
framing inspection for walls and ceiling.
- Provide floor and roof truss diagrams for framing
inspections.
- Engineer's approval on fastening of interior walls, corridor
walls, and shear walls. Framer has used power actuated
nails at all locations which is different from the approved
plans. I spoke with Dan Ryan the engineer today while on
site performing my inspection.
Truss Specification Provided NO
Bracing Bridging NO
Hurricane Clips/Uplift Screws/Nail Holes Filled NO
Air Seal all Plates and Sills NO
Air Seal All Registers at Floor NO
Air Sealing all Joints Before Insulation NO
Joist hangers NO
Jack Posts Main Beams NO
Exterior sheeting nailed properly NO
12 O.C.NO
Headroom 6 ft. 8 in.NO
Notches Holes Bearing Walls NO
Feb 11, 2019 Page (2)
INSPECTION WORKSHEET (BINS-000859-2019)
Checklist Item Passed Comments
Metal Strapping for Notches Top Plate NO
Draft stopping 1,000 sq. ft. floor trusses NO
Anchor Bolts 6 ft. or less on center NO
Ice and water shield 24 inches from wall NO
Soffits-Insulation Baffel NO
Windows Habitable Space Bedrooms NO
24 in. (H)NO
20 in. (W)NO
5.7 sf above below grade NO
5.0 sf grade NO
Design Professional Sign-off, if required NO
Feb 11, 2019 Page (3)
O'Brien, John (Inspector)