FM-007143-2019 10302019INSPECTION WORKSHEET (FM-007143-2019)
CC-0282-2019Permit Management
Case Number:Case Module:
10/30/2019Passed
Inspection Date:Inspection Status:
Mike PalmerOCC-Inspections
Inspector:Inspection Type:
296.19-1-42
Job Address:Parcel Number:
79 Glenwood Ave
Queensbury, NY 12804
Contact TypeCompany NameName
ApplicantBBL Construction Services
ArchitectHCP Architects, LLP
ContractorBBL Construction Services
Granted PermissionAddiction Care Center of AlbanyAshley Bowery
Primary OwnerAddiction Care Center of AlbanyAshley Bowery
Checklist ItemPassedComments
Sign: NormalTrue10/17/19 OK-PASS
Occupancy CycleTrueI1
Fire MarshalTrue
10/17/19 & 10/22/19
-PROVIDE ATTIC ACCESS SIGNAGE AS DISCUSSED
-FIRE MARSHAL TO PROVIDE EMERGENCY CONTACT FORM
10/30/19 OK-PASS
Interior FinishesTrue
Electrical Wiring Enclosed/LabeledTrue
Sign: BackupTrue10/17/19 OK-PASS
Emergency Lighting InteriorTrue10/17/19 OK-PASS
CO DetectorsTrue
10/17/19 FUNCTION TEST WITH FIRE ALARM CONTRACTOR
10/22/19 OK-PASS
Knox Box: installed/checkedTrue
10/17/19 FM TO TAG KEYS
10/22/19 ALL KEYS RECEIVED &TAGGED
Evac PlanTrue
10/17/19 PROVIDE EVAC PLAN
10/22/19 OK-PASS
10/30/19 HANG EVAC SIGNS- OK PASS
Exit AccessTrue
Elevator Semi AnnualTrue
10/17/19 & 10/22/19
-PROVIDE DOCUMENTATION OF VIOLATION REPAIRS FOR
LAST INSPECTION OF ELEVATOR - ok
10/30/19 OK-PASS
Exit DischargeTrue
FIRE ALARM AnnualTrue
10/17/19
PROVIDE NFPA 72 INSPECTION & COMPLETION REPORT
PROVIDE SPEC SHEETS FOR ALL DEVICES INSTALLED
FIRE MARSHAL TO WITNESS A FUNCTION TEST WITH FIRE
ALARM CONTRACTOR
10/22/19 OK-PASS
Exterior StorageTrue
December 23, 2019Page 1 of 2
INSPECTION WORKSHEET (FM-007143-2019)
Checklist ItemPassedComments
Clearance to ElectricalTrue
Inspection of ExtinguisherTrue
F.D. SignageTrue10/30/19 HANG BLUE SIGNAGE- OK PASS
Locks and LatchesTrue
Clearance to Sprinkler/CeilingTrue
Combustibles in Equipment RoomsTrue
Exit EnclosureTrue
StorageTrue
Sprinkler System AnnualTrue
10/17/19 & 10/22/19
-PROVIDE SPRINKLER PLANS & SPECS AS DISCUSSED -OK
10/22/19
-PROVIDE NFPA 13 LETTER & FINAL INSPECTION REPORT
FROM RBM- OK 10/22/19
-ADD ESCHTEON PLATE IN MECHANICAL ROOM-ok
1030/19 OK-PASS
Main Aisle WidthTrue
Sprinkler FDCTrue
Emergency Lighting ExteriorTrue10/17/19 OK-PASS
Secondary Aisle WidthTrue
Fire Extinguisher HungTrue
10/17/19 & 10/22/19
-HANG FIRE EXTINGUISHER IN ELEVATOR MACHINE ROOM &
K-EXTINGUISHER IN KITCHEN AS DISCUSSED
10/30/19 OK-PASS
December 23, 2019Page 2 of 2