Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: MO-0429-2018 Case Module: Permit
Inspection Date: 07/05/2018 Inspection Status: Failed
Inspector: Gary Stillman Inspection Type: OCC-Inspections
Job Address: 524 AVIATION RD Parcel Number: 302.5-1-96.1
Queensbury,NY 12804
Contact Type Company Name Name �I+�
Primary Owner [Aviation Hospitality,LLC] Jariwala,Bhavik ) 1
iw
Business Name Home2 Suites by Hilton Collura,Kristen � ( ' ' W
Checklist Item Passed Comments ^�i
Fire Marshal NO PROVIDE PERMENANT FIRE DEPT.SIGNAGE
EMERGENCY CONTACT FORM
Exit Access YES
Exit Enclosure YES
Exit Discharge YES
Locks and Latches YES
Sign:Normal YES
Sign:Backup YES
Main Aisle Width YES
Secondary Aisle Width YES
Fire Extinguisher Hung YES
Inspection of Extinguisher YES
Evac Plan YES
Truss ID Signage YES
Emergency Lighting Interior YES
Emergency Lighting Exterior YES
Clearance to Electrical YES
Electrical Wiring Enclosed/Labeled YES
Combustibles in Equipment Rooms YES
F.D.Signage YES
Storage YES
Interior Finishes YES
CO Detectors YES
Clearance to Sprinkler/Ceiling YES
EVAC SIGNS IN Rooms YES
Exterior Storage YES
Elevator Semi Annual YES 6/2018
FIRE ALARM Annual YES FS&S 7/2018
Sprinkler System Annual YES FireTek 6/2018
Sprinkler FDC YES
Knox Box:installed/checked NO PROVIDE MASTER KEY AND(3)MASTER SWIPE,/"
CARDS FOR KNOX BOX l�"
Jul 05,2018 Page(1)
Checklist Item Passed Comments
Occupancy Cycle YES R1
Stillman,Gary(Inspector)
Jul 05,2018 � �� Page(2)
i
r
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: CC-000480-2017 Case Module: Permit
Inspection Date: 07/05/2018 Inspection Status: Passed
Inspector: Gary Stillman Inspection Type: OCC-Inspections
Job Address: 524 AVIATION RD Parcel Number: 302.5-1-96.1
Queensbury,NY 12804
Contact Type Company Name Name
Contractor [Bast Hatfield Construction LLC] Fretto,John
Primary Owner [Aviation Hospitality,LLC] Jariwala,Bhavik
Granted Permission [Aviation Hospitality,LLC] Jariwala,Bhavik
Architect [AIA Architect] ,
Applicant [Bast Hatfield Construction LLC] Fretto,John
Checklist Item Passed Comments
Fire Marshal YES 6/21/18 FireMarshal to research carport(sprinkler)
6/22/18 Fire Marshal researched carport-ok
Exit Access YES
Exit Enclosure YES
Exit Discharge YES
Locks and Latches YES 6/28/18 OK
Sign:Normal YES 6/28/18 OK
Sign:Backup YES 6/28/18 OK
Main Aisle Width YES
Ok 7/3/18
Secondary Aisle Width YES
Ok 7/3/18
Fire Extinguisher Hung YES PBX room
7/5/18 ok-passed
Inspection of Extinguisher YES 6/21/18 Fire extingushers require inspection
6/28/18 ALL FIRE EXTINGUISHERS INSPECTED
FEs floor 1 need current inp tags:laundry,pbx,pantry
7/5/18 COMPLETE/PASSED
Truss ID Signage YES 6/21/18 Add TRUSS ID AT ALL EXTERIOR DOORS
AND ABOVE FDC
6/29/18 ADD TRUSS ID SIGN REAR MECHANICAL
ROOM DOOR
Ok 7/3/18
Emergency Lighting Interior YES 6/21/18 Fire Marshal to witness test
6/28/18 PASSED ALL OK
Jul 05,2018 Page(1)
Checklist Item Passed Comments
Emergency Lighting Exterior YES 6/21/18 Fire Marshal to witness test
6/28/18 verified ok
Clearance to Electrical YES
Electrical Wiring Enclosed/Labeled YES
6/21/18 LABEL ALL ELECTRIC PANELS,CLOSE UP
ALL ELECTRICAL
7/3/18 still open
7/5/18 ok
Combustibles in Equipment Rooms YES 6/28/18 return to verify
7/3/18 clean out construction trade equipment
7/5/2018 ok
F.D.Signage YES 6/21/18 Fire Marshal to provide blue signage
6/28/18 ALL ELECTRIC ROOM/MECHANICAL ROOMS
REQUIRE BLUE SIGNAGE SUPPLIED BT FIRE
MARSHAL OR EQUIVILANT
7/3/18 still open
7/5/2018 OK/COMPLETE TEMPORARY SIGNAGE
PROVIDED
Storage YES 7/3/18 several areas storage heights non compliant
7/5/2018 OK/COMPLETE
Interior Finishes YES 6/26/18 Proper closure fire door-stair 2,4th floor
6/28/18 CORRECTED OK
CO Detectors YES Verify CO detection throughout
6/22/18 CArbon dioxide detectors(various)1st floor
business area are not combo units,detects CO2 only
not carbon monoxide.Still need to verify cardon
monixide detection throughout
7/3/18 need compliance letter for guest laundry
6/28/18 add CO DETECTION AT GUEST LAUndry
6/29/18 PROVIDE FINAL INSPECTION REPORT
7/5/18 COMPLETE/PASSED,RECEIVED
PAPERWORK FROM FS&S
Clearance to Sprinkler/Ceiling YES
Page(2)
Jul 05,2018
Checklist Item Passed Comments
EVAC SIGNS IN Rooms YES 6/21/18/PROVIDE EVAC SIGNS IN ALL ROOMS
6/26/18 verified EVAC signs on all room doors 3rd&4th
floor
6/28/18 All rooms ok
Exterior Storage YES 7/3/18 ok
Elevator Semi Annual YES 6/21/18 Schedule elevator testing with Fire Marshal
office
Properly mark elevator shutoffs
6/28/18,PROVIDE ELEVATOR INSPECTION
REPORTS
6/29/18 PASSED-ALL ITEMS COMPLETE
FIRE ALARM Annual YES 6/21/18 Schedule fire alarm testing with Fire Marshal's
office
6/28/18 reprogram sounder bases on 4th floor room 421
up,PROVIDE ALL PAPERWORK AND INSPECTION
REPORTS,provide signals received at central station
for todays test
7/3/18 still need complince letter for 4th floor sounder
bases
6/29/18 REPAIR ALL SOUNDER BASES 4TH FLOOR,
PROVIDE PAPERWORK WHEN COMPLETE
7/5/2018 complete/passed,received all paperwork
from FS&S
HVAC Shutdown YES 6/21/18 Fire Marshal to witness with fire alarm
contractor
6/28/18 verified ok
Sprinkler System Annual YES 6/21/18 recieved NFPA LETTER FROM FIRETEK
DATED 6/21/18
Install all eschuteon plates-missing 2nd,3rd&4th floor
elevator lobby,1 st floor rest room,storeroom by
elevators 1st floor
6/26/18 repair openings around eschteon plates,verified
missing eschuteon plates on 3rd&4th floor.
6/28/18 all eschuteon plates installed noted in 6/21/18
inspection,openings repaired
Jul 05,2018 ✓<�, �¢ Page(3)
Checklist Item Passed Comments
Sprinkler FDC YES
6/22/18 36 inch clearance required to sides and front of
FDC,AC units must be relocated
Provide SIGN above FDC(6 INCH
LETTERS))
6/26/18 FDC CLEARANCE OK,WAS MOVED TO
SOUTH SIDE OF BLDG,STILL NEED ALL SIGNAGE
AS DISCUSSED.Also STROBE NEEDS TO BE
MOVED TO NEW LOCATION(FIRE ALARM)
6/28/18 STROBE MOVED,VERIFIED OPERATION.
STILL NEED ALL SIGNAGE AT FDC
6/29/18 PASSED-ALL ITEMS CORRECTED
Knox Box:installed/checked YES 6/21/18 Install elevator Knox Box
6/28/18 INSTALLED-PROVIDE MASTER KEYS AND
CARDS FOR ROOMS
7/3/18 need master keys and fa keys
7/5/2018 RECEIVED FIRE ALARM PANEL KEY&(1)
MASTER SWIPE CARD.STILL NEED MASTER KEY
AND(3)MASTER SWIPE CARDS
Occupancy Cycle YES R1
Stillman,Gary(Inspector)
Jul 06,2018 Page(4)
A
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: CC-000480-2017 Case Module: Permit
Inspection Date: 07/03/2018 Inspection Status: Partial Pass
Inspector: Mike Palmer Inspection Type: OCC-Inspections
Job Address: 524 AVIATION RD Parcel Number: 302.5-1-96.1
Queensbury,NY 12804
Contact Type Company Name Name
Applicant [Bast Hatfield Construction LLC] Fretto,John
Primary Owner [Aviation Hospitality,LLC] Jariwala,Bhavik
Architect [AIA Architect] ,
Contractor [Bast Hatfield Construction LLC] Fretto,John
Granted Permission [Aviation Hospitality,LLC] Jariwala,Bhavik
Checklist Item Passed Comments
Fire Marshal YES 6/21/18 FireMarshal to research carport(sprinkler)
6/22/18 Fire Marshal researched carport-ok
Exit Access YES
Exit Enclosure YES
Exit Discharge YES
Locks and Latches YES 6/28/18 OK
Sign:Normal YES 6/28/18 OK
Sign:Backup YES 6/28/18 OK
Main Aisle Width YES
Ok 7/3/18
Secondary Aisle Width YES
Ok 7/3/18
Fire Extinguisher Hung NO PBX room
Inspection of Extinguisher NO 6/21/18 Fire extingushers require inspection
6/28/18 ALL FIRE EXTINGUISHERS INSPECTED
FEs floor 1 need current inp tags:laundry,pbx,pantry
Truss ID Signage YES 6/21/18 Add TRUSS ID AT ALL EXTERIOR DOORS
AND ABOVE FDC
6/29/18 ADD TRUSS ID SIGN REAR MECHANICAL
ROOM DOOR
Ok 7/3/18
Emergency Lighting Interior YES 6/21/18 Fire Marshal to witness test
6/28/18 PASSED ALL OK
Emergency Lighting Exterior YES 6/21/18 Fire Marshal to witness test
6/28/18 verified ok
Jul 03,2018 Page(4)
Checklist Item Passed Comments
Clearance to Electrical YES
Electrical Wiring Enclosed/Labeled NO
6/21/18 LABEL ALL ELECTRIC PANELS,CLOSE UP
ALL ELECTRICAL
7/3/18 still open
Combustibles in Equipment Rooms NO 6/28/18 return to verify
7/3/18 clean out construction trade equipment
F.D.Signage NO 6/21/18 Fire Marshal to provide blue signage
6/28/18 ALL ELECTRIC ROOM/MECHANICAL ROOMS
REQUIRE BLUE SIGNAGE SUPPLIED BT FIRE
MARSHAL OR EQUIVILANT
7/3/18 still open
Storage NO 7/3/18 several areas storage heights non compliant
Interior Finishes YES 6/26/18 Proper closure fire door-stair 2,4th floor
6/28/18 CORRECTED OK
CO Detectors NO Verify CO detection throughout
6/22/18 CArbon dioxide detectors(various)1 st floor
business area are not combo units,detects CO2 only
not carbon monoxide.Still need to verify cardon
monixide detection throughout
7/3/18 need compliance letter for guest laundry
6/28/18 add CO DETECTION AT GUEST LAUndry
6/29/18 PROVIDE FINAL INSPECTION REPORT
Clearance to Sprinkler/Ceiling YES
EVAC SIGNS IN Rooms YES 6/21/18/PROVIDE EVAC SIGNS IN ALL ROOMS
6/26/18 verified EVAC signs on all room doors 3rd&4th
floor
6/28/18 All rooms ok
Exterior Storage YES 7/3/18 ok
Elevator Semi Annual YES 6/21/18 Schedule elevator testing with Fire Marshal
office
Properly mark elevator shutoffs
6/28/18,PROVIDE ELEVATOR INSPECTION
REPORTS
6/29/18 PASSED-ALL.ITEMS COMPLETE
Jul 03,2018 Page(5)
Checklist Item Passed Comments
FIRE ALARM Annual NO 6/21/18 Schedule fire alarm testing with Fire Marshal's
office
6/28/18 reprogram sounder bases on 4th floor room 421
up,PROVIDE ALL PAPERWORK AND INSPECTION
REPORTS,provide signals received at central station
for todays test
7/3/18 still need complince letter for 4th floor sounder
bases
6/29/18 REPAIR ALL SOUNDER BASES 4TH FLOOR,
PROVIDE PAPERWORK WHEN COMPLETE
HVAC Shutdown YES 6/21/18 Fire Marshal to witness with fire alarm
contractor
6/28/18 verified ok
Sprinkler System Annual YES 6/21/18 recieved NFPA LETTER FROM FIRETEK
DATED 6/21/18
Install all eschuteon plates-missing 2nd,3rd&4th floor
elevator lobby,1 st floor rest room,storeroom by
elevators 1 st floor
6/26/18 repair openings around eschteon plates,verified
missing eschuteon plates on 3rd&4th floor.
6/28/18 all eschuteon plates installed noted in 6/21/18
inspection,openings repaired
Sprinkler FDC YES
6/22/18 36 inch clearance required to sides and front of
FDC,AC units must be relocated
Provide SIGN above FDC(6 INCH
LETTERS))
6/26/18 FDC CLEARANCE OK,WAS MOVED TO
SOUTH SIDE OF BLDG,STILL NEED ALL SIGNAGE
AS DISCUSSED.Also STROBE NEEDS TO BE
MOVED TO NEW LOCATION(FIRE ALARM)
6/28/18 STROBE MOVED,VERIFIED OPERATION.
STILL NEED ALL SIGNAGE AT FDC
6/29/18 PASSED-ALL ITEMS CORRECTED
Jul 03,2018 Page(6)
Checklist Item Passed Comments
Knox Box:installed/checked NO 6/21/18 Install elevator Knox Box
6/28/18 INSTALLED-PROVIDE MASTER KEYS AND
CARDS FOR ROOMS
7/3/18 need master kets and fa keys
Occupancy Cycle YES R1
John Palmer,Mike(Inspector)
Jul 03,2018 Page(7)
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: CC-000480-2017 Case Module: Permit
Inspection Date: 06/29/2018 Inspection Status: Failed
Inspector: Gary Stillman Inspection Type: OCC-Inspections
Job Address: 524 AVIATION RD Parcel Number: 302.5-1-96.1
Queensbury,NY 12804
Contact Type Company Name Name
Primary Owner [Aviation Hospitality,LLC] Jariwala,Bhavik
Architect [AIA Architect] ,
Applicant [Bast Hatfield Construction LLC] Fretto,John
Granted Permission [Aviation Hospitality,LLC] Jariwala,Bhavik
Contractor [Bast Hatfield Construction LLC] Fretto,John
Checklist Item Passed Comments
Fire Marshal YES 6/21/18 FireMarshal to research carport(sprinkler)
6/22/18 Fire Marshal researched carport-ok
Exit Access YES
Exit Enclosure YES
Exit Discharge YES
Locks and Latches YES 6/28/18 OK
Sign:Normal YES 6/28/18 OK
Sign:Backup YES 6/28/18 OK
Main Aisle Width (r/
Secondary Aisle Width
Fire Extinguisher Hung YES
Inspection of Extinguisher YES 6/21/18 Fire extingushers require inspection
6/28/18 ALL FIRE EXTINGUISHERS INSPECTED
Truss ID Signage &.N@1 6/21/18 Add TRUSS ID AT ALL EXTERIOR DOORS
AND ABOVE FDC
6/29/18 ADD TRUSS ID SIGN REAR MECHANICAL
ROOM DOOR
Emergency Lighting Interior YES 6/21/18 Fire Marshal to witness test
6/28/18 PASSED ALL OK
Emergency Lighting Exterior YES 6/21/18 Fire Marshal to witness test
6/28/18 verified ok
Clearance to Electrical lK b (—
Electrical Wiring Enclosed/Labeled NO
6/21/18 LABEL ALL ELECTRIC PANELS,CLOSE UP
ALL ELECTRICAL
Combustibles in Equipment Rooms 6/28/18 return to verifyjy�
Jun 29,2018 Page(12)
Checklist Item Passed Comments
F.D.Signage NO 6/21/18 Fire Marshal to provide blue signage
6/28/18 ALL ELECTRIC ROOM/MECHANICAL ROOMS
REQUIRE BLUE SIGNAGE SUPPLIED BT FIRE
MARSHAL OR EQUIVILANT
Storage NO
Interior Finishes YES 6/26/18 Proper closure fire door-stair 2,4th floor
6/28/18 CORRECTED OK
CO Detectors NO Verify CO detection throughout
6/22/18 CArbon dioxide detectors(various)1 st floor
business area are not combo units,detects CO2 only
not carbon monoxide.Still need to verify cardon
monixide detection throughout
6/28/18 add CO DETECTION AT GUEST LAUndry
6/29/18 PROVIDE FINAL INSPECTION REPORT
Clearance to Sprinkler/Ceiling YES
EVAC SIGNS IN Rooms YES 6/21/18/PROVIDE EVAC SIGNS IN ALL ROOMS
6/26/18 verified EVAC signs on all room doors 3rd&4th
floor
6/28/18 All rooms ok
Exterior Storage
Elevator Semi Annual YES 6/21/18 Schedule elevator testing with Fire Marshal
office
Properly mark elevator shutoffs
6/28/18,PROVIDE ELEVATOR INSPECTION
REPORTS
6/29/18 PASSED-ALL ITEMS COMPLETE
FIRE ALARM Annual NO 6/21/18 Schedule fire alarm testing with Fire Marshal's
office
6/28/18 reprogram sounder bases on 4th floor room 421
up,PROVIDE ALL PAPERWORK AND INSPECTION
REPORTS,provide signals received at central station
for todays test
6/29/18 REPAIR ALL SOUNDER BASES 4TH FLOOR,
PROVIDE PAPERWORK WHEN COMPLETE
Jun 29,2018 Page(13)
Checklist Item Passed Comments
HVAC Shutdown YES 6/21/18 Fire Marshal to witness with fire alarm
contractor
6/28/18 verified ok
Sprinkler System Annual YES 6/21/18 recieved NFPA LETTER FROM FIRETEK
DATED 6/21/18
Install all eschuteon plates-missing 2nd,3rd&4th floor
elevator lobby,1 st floor rest room,storeroom by
elevators 1st floor
6/26/18 repair openings around eschteon plates,verified
missing eschuteon plates on 3rd&4th floor.
6/28/18 all eschuteon plates installed noted in 6/21/18
inspection,openings repaired
Sprinkler FDC YES
6/22/18 36 inch clearance required to sides and front of
FDC,AC units must be relocated
Provide SIGN above FDC(6 INCH
LETTERS))
6/26/18 FDC CLEARANCE OK,WAS MOVED TO
SOUTH SIDE OF BLDG,STILL NEED ALL SIGNAGE
AS DISCUSSED.Also STROBE NEEDS TO BE
MOVED TO NEW LOCATION(FIRE ALARM)
6/28/18 STROBE MOVED,VERIFIED OPERATION.
STILL NEED ALL SIGNAGE AT FDC
6/29/18 PASSED-ALL ITEMS CORRECTED
Knox Box:installed/checked NO 6/21/18 Install elevator Knox Box
6/28/18 INSTALLED-PROVIDE MASTER KEYS AND
CARDS FOR ROOMS
Occupancy Cycle YES R1
Stillman,Gary(Inspector)
Jun 29,2018 Page(14)
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: CC-000480-2017 Case Module: Permit
Inspection Date: 06/28/2018 Inspection Status: Failed
Inspector: Gary Stillman Inspection Type: OCC-Inspections
Job Address: 524 AVIATION RD Parcel Number: 302.5-1-96.1
Queensbury,NY 12804
Contact Type Company Name Name
Architect [AIA Architect]
Granted Permission [Aviation Hospitality,LLC] Jariwala,Bhavik
Contractor [Bast Hatfield Construction LLC] Fretto,John
Primary Owner [Aviation Hospitality,LLC] Jariwala,Bhavik
Applicant [Bast Hatfield Construction LLC] Fretto,John
Checklist Item Passed Comments
Fire Marshal YES 6/21/18 FireMarshal to research carport(sprinkler)
6/22/18 Fire Marshal researched carport-ok
Exit Access YES
Exit Enclosure YES
Exit Discharge YES
Locks and Latches YES 6/28/18 OK
Sign:Normal YES 6/28/18 OK
Sign:Backup YES 6/28/18 OK
Main Aisle Width NO
Secondary Aisle Width NO
Fire Extinguisher Hung YES
Inspection of Extinguisher YES 6/21/18 Fire extingushers require inspection
6/28/18 ALL FIRE EXTINGUISHERS INSPECTED
Truss ID Signage NO 6/21/18 Add TRUSS ID AT ALL EXTERIOR DOORS
AND ABOVE FDC
Emergency Lighting Interior YES 6/21/18 Fire Marshal to witness test
6/28/18 PASSED ALL OK
Emergency Lighting Exterior YES 6/21/18 Fire Marshal to witness test
6/28/18 verified ok
Clearance to Electrical NO
Electrical Wiring Enclosed/Labeled NO
6/21/18 LABEL ALL ELECTRIC PANELS,CLOSE UP
ALL ELECTRICAL
Combustibles in Equipment Rooms NO 6/28/18 return to verify
Jun 28,2018 Page(5)
Checklist Item Passed Comments
F.D.Signage NO 6/21/18 Fire Marshal to provide blue signage
6/28/18 ALL ELECTRIC ROOM/MECHANICAL ROOMS
REQUIRE BLUE SIGNAGE SUPPLIED BT FIRE
MARSHAL OR EQUIVILANT
Storage NO
Interior Finishes YES 6/26/18 Proper closure fire door-stair 2,4th floor
6/28/18 CORRECTED OK
CO Detectors NO Verify CO detection throughout
6/22/18 CArbon dioxide detectors(various)1 st floor
business area are not combo units,detects CO2 only
not carbon monoxide.Still need to verify cardon
monixide detection throughout
6/28/18 add CO DETECTION AT GUEST LAUndry
Clearance to Sprinkler/Ceiling YES
EVAC SIGNS IN Rooms YES 6/21/18/PROVIDE EVAC SIGNS IN ALL ROOMS
6/26/18 verified EVAC signs on all room doors 3rd&4th
floor
6/28/18 All rooms ok
Exterior Storage NO
Elevator Semi Annual NO 6/21/18 Schedule elevator testing with Fire Marshal
office
Properly mark elevator shutoffs
6/28/18,PROVIDE ELEVATOR INSPECTION
REPORTS OK.
FIRE ALARM Annual NO 6/21/18 Schedule fire alarm testing with Fire Marshal's
office
6/28/18 reprogram sounder bases on 4th floor room 421
up,PROVIDE ALL PAPERWORK AND INSPECTION
REPORTS,provide signals received at central station
for todays test
HVAC Shutdown YES 6/21/18 Fire Marshal to witness with fire alarm
contractor
6/28/18 verified ok
Jun 28,2018 Page(6)
Checklist Item Passed Comments
Sprinkler System Annual �dt� 6/21/18 recieved NFPA LETTER FROM FIRETEK
DATED 6/21/18
Install all eschuteon plates-missing 2nd,3rd&4th floor
elevator lobby,1 st floor rest room,storeroom by
elevators 1 st floor
6/26/18 repair openings around eschteon plates,verified
missing eschuteon plates on 3rd&4th floor.
6/28/18 all eschuteon plates installed noted in 6/21/18
inspection,openings repaired
Sprinkler FDC NO
6/22/18 36 inch clearance required to sides and front of
FDC,AC units must be relocated
Provide SIGN above FDC(6 INCH
LETTERS))
6/26/18 FDC CLEARANCE OK,WAS MOVED TO
SOUTH SIDE OF BLDG,STILL NEED ALL SIGNAGE
AS DISCUSSED.Also STROBE NEEDS TO BE
MOVED TO NEW LOCATION(FIRE ALARM)
6/28/18 STROBE MOVED,VERIFIED OPERATION.
/ STILL NEED ALL SIGNAGE AT FDC
Knox Box:installed/checked �fy� 6/21/18 Install elevator Knox Box
6/28/18 INSTALLED 4
Occupancy Cycle NO R1
P Y Y
zzod
Stillman,Gary(Inspector)
Jun 28,2018 4 Page(7)
v
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: CC-000480-2017 Case Module: Permit
Inspection Date: 06/26/2018 Inspection Status: Failed
Inspector: Gary Stillman Inspection Type: OCC-Inspections
Job Address: 524 AVIATION RD Parcel Number: 302.5-1-96.1
Queensbury,NY 12804
Contact Type Company Name Name
Architect AIA Architect ,
Primary Owner Aviation Hospitality,LLC Jariwala,Bhavik
Applicant Bast Hatfield Construction LLC Fretto,John
Contractor Bast Hatfield Construction LLC Fretto,John
Granted Permission Aviation Hospitality,LLC Jariwala,Bhavik
Checklist Item Passed Comments
Fire Marshal YES 6/21/18 FireMarshal to research carport(sprinkler)
6/22/18 Fire Marshal researched carport-ok
Exit Access NO
Exit Enclosure NO
Exit Discharge NO
Locks and Latches NO
Sign:Normal NO
Sign:Backup NO
Main Aisle Width NO
Secondary Aisle Width NO
Fire Extinguisher Hung YES
Inspection of Extinguisher NO 6/21/18 Fire extingushers require inspection
Evac Plan NO
Truss ID Signage NO 6/21/18 Add TRUSS ID AT ALL EXTERIOR DOORS
AND ABOVE FDC
Emergency Lighting Interior NO 6/21/18 Fire Marshal to witness test
Emergency Lighting Exterior NO 6/21/18 Fire Marshal to witness test
Clearance to Electrical NO
Electrical Wiring Enclosed/Labeled NO
6/21/18 LABEL ALL ELECTRIC PANELS,CLOSE UP
ALL ELECTRICAL
Combustibles in Equipment Rooms NO
F.D.Signage NO 6/21/18 Fire Marshal to provide blue signage
No Smoking Signs NO
Storage NO
Interior Finishes NO 6/26/18 Proper closure fire door-stair 2,4th floor
Jun 26,2018 Page(2)
Checklist Item Passed Comments
CO Detectors NO Verify CO detection throughout
6/22/18 CArbon dioxide detectors(various)1 st floor
business area are not combo units,detects CO2 only
not carbon monoxide.Still need to verify cardon
monixide detection throughout
Clearance to Sprinkler/Ceiling NO
EVAC SIGNS IN Rooms NO 6/21/18/PROVIDE EVAC SIGNS IN ALL ROOMS
6/26/18 verified EVAC signs on all room doos 3rd&4th
floor
Exterior Storage NO
Elevator Semi Annual NO 6/21/18 Schedule elevator testing with Fire Marshal
office
Properly mark elevator shutoffs
FIRE ALARM Annual NO 6/21/18 Schedule fire alarm testing with Fire Marshal's
office
HVAC Shutdown NO 6/21/18 Fire Marshal to witness with fire alarm
contractor
Sprinkler System Annual NO 6/21/18 recieved NFPA LETTER FROM FIRETEK
DATED 6/21/18
Install all eschuteon plates-missing 2nd,3rd&4th floor
elevator lobby,1 st floor rest room,storeroom by
elevators 1 st floor
6/26/18 repair openings around eschteon plates,verified
missing eschuteon plates on 3rd&4th floor.
Sprinkler FDC NO
6/22/18 36 inch clearance required to sides and front of
FDC,AC units must be relocated
Provide SIGN above FDC(6 INCH
LETTERS))
6/26/18 FDC CLEARANCE OK,WAS MOVED TO
SOUTH SIDE OF BLDG,STILL NEED ALL SIGNAGE
AS DISCUSSED.Also STROBE NEEDS TO BE
MOVED TO NEW LOCATION(FIRE ALARM)
Knox Box:installed/checked NO 6/21/18 Install elevator Knox Box
Occupancy Cycle NO R1
Stillman,Gary(Inspector)
Jun 26,2018 Page(3)
saxza ma ;;
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8266 Building(518)761-8206 Fire Marshal
Case Number: CC-000480-2017 Case Module: Permit
Inspection Date: 06/22/2018 Inspection Status: Failed
Inspector: Gary Stillman Inspection Type: OCC-Inspections
Job Address: 524 AVIATION RD Parcel Number: 302.5-1-96.1
Queensbury,NY 12804
Contact Type Company Name Name
Primary Owner [Aviation Hospitality,LLC] Jariwala,Bhavik
Applicant [Bast Hatfield Construction LLC] Fretto,John
Granted Permission [Aviation Hospitality,LLC] Jariwala,Bhavik
Contractor [Bast Hatfield Construction LLC] Fretto,John
Architect [AIA Architect]
Checklist Item Passed Comments
Fire Marshal NO 6/21/18 FireMarshal to research carport(sprinkler)
6122/18 Fire Marshal researched carport-ok
Exit Access NO
Exit Enclosure NO
Exit Discharge NO
Locks and Latches NO
Sign:Normal NO
Sign:Backup NO
Main Aisle Width NO
Secondary Aisle Width NO
Fire Extinguisher Hung YES
Inspection of Extinguisher NO 6/21/18 Fire extingushers require inspection
Evac Plan NO
Truss ID Signage NO 6/21/18 Add TRUSS ID AT ALL EXTERIOR DOORS
AND ABOVE FDC
Emergency Lighting Interior NO 6/21/18 Fire Marshal to witness test
Emergency Lighting Exterior NO 6/21/18 Fire Marshal to witness test
Clearance to Electrical NO
Electrical Wiring Enclosed/Labeled NO
6/21/18 LABEL ALL ELECTRIC PANELS,CLOSE UP
ALL ELECTRICAL
Combustibles in Equipment Rooms NO
F.D.Signage NO 6/21/18 Fire Marshal to provide blue signage
No Smoking Signs NO
Storage NO
Vehicle Impact Protection NO
Interior Finishes NO
Jun 22,2018 Page(1)
A
w
T
Checklist Item Passed Comments
CO Detectors NO Verify CO detection throughout
6/22/18 CArbon dioxide detectors(various)1st floor
business area are not combo units,detects CO2 only
not carbon monoxide.Still need to verify cardon
monixide detection throughout
Clearance to Sprinkler/Ceiling NO
EVAC SIGNS IN Rooms NO 6/21/18/PROVIDE EVAC SIGNS IN ALL ROOMS
Exterior Storage NO
Elevator Semi Annual NO 6/21/18 Schedule elevator testing with Fire Marshal
office
Properly mark elevator shutoffs
FIRE ALARM Annual NO 6/21/18 Schedule fire alarm testing with Fire Marshal's
office
HVAC Shutdown NO 6/21/18 Fire Marshal to witness with fire alarm
contractor
Sprinkler System Annual NO 6/21/18 recieved NFPA LETTER FROM FIRETEK
DATED 6/21/18
Install all eschuteon plates-missing 2nd,3rd&4th floor
elevator lobby,1 st floor rest room,storeroom by
elevators 1 st floor
Sprinkler FDC NO
6/22/18 36 inch clearance required to sides and front of
FDC,AC units must be relocated
Provide SIGN above FDC(6 INCH LETTERS)
Knox Box:installed/checked NO 6/21/18 Install elevator Knox Box
Occupancy Cycle NO R1
Stillman,Gary(Inspector)
Jun 22,2018 Page(2)
Town of Queensbury-Building and Codes-Fire Marshal
742 Bay Road-(518)761-8256 Building(518)761-8206 Fire Marshal
Case Number: CC-000480-2017 Case Module: Permit
Inspection Date: 06/21/2018 Inspection Status: Failed
Inspector: Gary Stillman Inspection Type: OCC-Inspections
Job Address: 524 AVIATION RD Parcel Number: 302.5-1-96.1
Queensbury,NY 12804
Contact Type Company Name Name
Contractor Bast Hatfield Construction LLC Fretto,John
Primary Owner Aviation Hospitality,LLC Jariwala,Bhavik
Architect AIA Architect ,
Applicant Bast Hatfield Construction LLC Fretto,John
Granted Permission Aviation Hospitality,LLC Jariwala,Bhavik
Checklist Item Passed Comments
Fire Marshal NO FireMarshal to research carport(sprinkler)
Exit Access NO
Exit Enclosure NO
Exit Discharge NO
Locks and Latches NO
Sign:Normal NO
Sign:Backup NO
Main Aisle Width NO
Secondary Aisle Width NO
Fire Extinguisher Hung YES
Inspection of Extinguisher NO Fire extingushers require inspection
Evac Plan NO Add TRUSS ID AT ALL EXTERIOR DOORS AND FDC
Truss ID Signage NO
Emergency Lighting Interior NO Fire Marshal to witness test
Emergency Lighting Exterior NO Fire Marshal to verify
Clearance to Electrical NO
Electrical Wiring Enclosed/Labeled NO
LABEL ALL ELECTRIC PANELS,CLOSE UP ALL
ELECTRICAL
Combustibles in Equipment Rooms NO
F.D.Signage NO Fire Marshal to provide blue signage
No Smoking Signs NO
Storage NO
Vehicle Impact Protection NO
Interior Finishes NO
CO Detectors NO Verify CO detection throughout r
Clearance to Sprinkler/Ceiling NOJ t'!r
EVAC SIGNS IN Rooms NO PROVIDE EVAC SIGNS IN ALL ROOMS
Exterior Storage NO
Jun 21,2018 Page(1)
r'w a r
Checklist Item Passed Comments
Elevator Semi Annual NO Schedule elevator testing with Fire Marshal office
Properly mark elevator shutoffs
FIRE ALARM Annual NO Schedule fire alarm testing with Fire Marshal's office
HVAC Shutdown NO Fire Marshal to witness with fire alarm contractor
Sprinkler System Annual NO 6/21/18 recieved NFPA LETTER FROM FIRETEK
DATED 6/21/18
Install all eschuteon plates-missing 2nd,3rd&4th floor
elevator lobby,1 st floor rest room,storeroom by
elevators 1 st floor
Sprinkler FDC NO Fire marshal to research clearance to FDC
Knox Box:installed/checked NO Install elevator Knox Box
Occupancy Cycle NO R1
-?6
R f ,
rX
Stillman,Gary(Inspector)
Jun 21,2018 Page(2)
KNOX BOX KE IST
-> M.A: D00P,-ACCESS K.
LFIRE ALARM PANEL KEY
SPRINKLER ROOM KEY
SPRINKLER LOCK KEY
ELEVATOR MACHINE ROOM KEY
FIRE ALARM PULL STATION KEY
FIRE ALARM DUCT DETECTOR KEY
ROOF HATCH LOCK KEY
FIRE ALARM ROOM KEY
SECURITY GATE KEY
ELEVATOR FIREFIGHTER KEYS `s
ROOM M:OCKSET
STER KEY (HOTELS) ,� , N
p
MASTER KEY (interio
ELEVATOR DOOR DROP KEY ti e,1 f '`'`'r'"
KNOX BOX MISCELLANEOUS
EMERGENCY CONTACT LIST
HAZARDOUS CHEMICALS OR STORAGE
MSDS SHEETS OR 209u