ResCheck 289.18-1-35.2 RC-000115-2017
Generated by REScheck-Web E Wild, Ryan
14 Blackberry Ln
Compliance Certif SFD w/wood FP 2502 s.f., Gar. 642 s.f.
Project PLAN NO. 2502-17-LOT 2 BLACKBERRY LN
Energy Code: 2015 IECC
Location: Warren County, New York D fL (gyp 0
Construction Type: Single-family E C J'
Project Type: New Construction D
Orientation: Bldg. faces 315 deg. from North MAR 2 3
Conditioned Floor Area: 2,502 ft2 2 1/
Glazing Area 23%
Climate Zone: 6 (8499 HDD) TOM BUILDING Permit Date: CODES
Permit Number:
Construction Site: Owner/Agent: Designer/Contractor:
LOT 2 BLACKBERRY LANE CREATIVE SPACES WILLIAMS&WILLIAMS DESIGNERS
QUEENSBURY, New York 12804 509 GLEN STREET
GLENS FALLS, New York 12801
518-798-4687
W ILLIAMSAND WILLIAMSDESIGNERS.
COM
Compliance: Passes using UA trade-off
Compliance: 0.6%Better Than Code Maximum ILA: 504 Your UA: 501
The%Better or worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a mmimummode home.
Envelope Assemblies
Gross Area Cavity Cont.
Per meter
Ceiling: Cathedral 1,846 38.0 10.0 0.021 39
Ceiling: Flat or Scissor Truss 697 49.0 0.0 0.026 18
Floor: All-Wood Joistfrruss Over Uncond. Space 624 38.0 0.0 0.026 16
Floor: Heated Slab-On-Grade 76 10.0 0.684 52
Insulation depth: 4.0'
Wall: Wood Frame, 16in.D.C. 573 21.0 0.0 0.057 28
Orientation: Front
Window: Wood Frame, 2 Pane w/Low-E 49 0.300 15
Orientation: Front
Door: Solid 20 0.140 3
Orientation: Front
Door: Glass 20 0.320 6
Orientation: Front
Wall: Wood Frame, 16in.D.C. 736 21.0 0.0 0.057 32
Orientation: Right side
Window: Wood Frame, 2 Pane w/Low-E 86 0.300 26
Orientation: Right side
Window: Wood Frame, 2 Pane w/Low-E 43 0.290 12
Orientation: Right side
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 1 of 11
Gross Area Cavity Cont.
Assembly or U-Factor UA
Door:Glass 37 0.320 12
Orientation: Right side
Wall:Wood Frame, 16in.o.c. 489 21.0 0.0 0.057 22
Orientation: Back
Window:Wood Frame, 2 Pane w/Low-E 103 0.300 31
Orientation: Back
Wall:Wood Frame, 16in.o.c. 349 21.0 0.0 0.057 19
Orientation: Left side
Window:Wood Frame, 2 Pane w/Low-E 13 0.300 4
Orientation: Left side
Wall:Wood Frame, 16in.o.c. 246 21.0 0.0 0.057 12
Orientation: Right side
Window:Wood Frame, 2 Pane w/Low-E 15 0.300 5
Orientation: Right side
Window:Wood Frame, 2 Pane w/Low-E 18 0.270 5
Orientation: Right side
Wall:Wood Frame, 16in.o.c. 275 21.0 0.0 0.057 12
Orientation: Left side
Window:Wood Frame,2 Pane w/Low-E 60 0.300 18
Orientation: Left side
Basement:Solid Concrete or Masonry 412 0.0 15.0 0.044 18
Orientation: Front
Wall height:9.0'
Depth below grade:8.0'
Insulation depth:9.0'
Basement: Solid Concrete or Masonry 167 0.0 15.0 0.044 7
Orientation: Right side
Wall height: 9.0'
Depth below grade:8.0'
Insulation depth: 9.0'
Basement: Solid Concrete or Masonry 209 21.0 0.0 0.056 8
Orientation: Right side
Wall height: 9.0'
Depth below grade:0.0'
Insulation depth:9.0'
Window:Wood Frame,2 Pane w/Low-E 60 0.300 18
Orientation: Right side
Basement:Wood Frame 35 21.0 0.0 0.060 2
Orientation: Right side
Wall height:9.0'
Depth below grade: 0.0'
Insulation depth:9.0'
Basement:Wood Frame 382 21.0 0.0 0.060 17
Orientation: Back
Wall height:9.0'
Depth below grade: 0.0'
Insulation depth:9.0'
Window:Wood Frame, 2 Pane w/Low-E 60 0.300 18
Orientation: Back
Door:Glass 40 0.320 13
Orientation: Back
Basement:Solid Concrete or Masonry 35 21.0 0.0 0.056 2
Orientation: Left side
Wall height:9.0'
Depth below grade: 0.0'
Insulation depth:9.0'
Basement: Solid Concrete or Masonry 100 21.0 0.0 0.042 4
Orientation: Left side
Wall height: 9.0'
Depth below grade: 8.0'
Insulation depth:9.0'
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 2 ofll
Gross Area Cavity Cont.
Assembly or U-Factor UA
Basement: Solid Concrete or Masonry 79 21.0 0.0 0.050 4
Orientation: Unspecified
Wall height:9.0'
Depth below grade: 5.0'
Insulation depth:9.0'
Basement:Solid Concrete or Masonry 71 0.0 15.0 0.044 3
Orientation: Left side
Wall height: 9.0'
Depth below grade: 8.0'
Insulation depth: 9.0'
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application.The proposed building has been designed to meet the 2015 IECC requirements in
REScheck Version 5.5.0 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Jessica Chenier Bulman 3essica Chewt FdwRH 03/21/17
Name-Title Signature � NEIN Date
54P �pKEII Jr ,
�P S
r
r-
I P/
� (23117
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 3 of 11
REScheck Software Version 5.5.0
C�(J Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed.Where compliance is itemized in a separate table, a reference to that table is provided.
Section Plans Verified Field Verified
# Pre-Inspection/Plan Review Value Value Complies? Comments/Assumptions
& Req.ID
103.1, !Construction drawings and ❑Complies
103.2 documentation demonstrate ❑Does Not
[PR111 energy code compliance for the
.� building envelope.Thermal []Not Observable
envelope represented on ❑Not Applicable
construction documents.
103.1, Construction drawings and ❑Complies
103.2, documentation demonstrate ❑Does Not
403.7 -energy code compliance for
[PR3)1 lighting and mechanical systems. ❑Not Observable
Systems serving multiple ❑Not Applicable
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
302.1, !Heating and cooling equipment is Heating: Heating: ❑Complies
403.7 sized per ACCA Manual S based Btu/hr— Btu/hr ❑Does Not
[PR212 on loads calculated per ACCA Cooling: Cooling: ❑Not Observable
Manual J or other methods . Btu/hr_ Btu/hr_ ❑Not Applicable
approved by the code official.
Additional Comments/Assumptions:
1 1 High Impact(Tier 1) 12 1 Medium Impact(Tier 2) 1 3 1 Low Impact(Tier 3)
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Reportdate: 03/21/17
Data filename: Page 4 of 11
Section Plans Verified Field Verified
# Foundation Inspection Value Value Complies? Comments/Assumptions
& Re .ID
402.1.2 Slab edge insulation R-value. R- R- ❑Complies See the Envelope Assemblies
[F0111 ❑ Unheated ❑ Unheated ❑Does Not table for values.
0 ❑ Heated ❑ Heated []Not Observable
❑Not Applicable
402.1.2 Slab edge insulation _ft - _ft ❑Complies ,See the Envelope Assemblies
[F0311 depth/length. j ❑Does Not ,'table for values.
0 ❑Not Observable
[]Not Applicable
402.1.1 Conditioned basement wall R- R-_ ❑Complies See the Envelope Assemblies
[F0411 insulation R-value.Where interiorR- R- ❑Does Not ;table for values.
J insulation is used,verification []Not Observable
may need to occur during
Insulation Inspection. Not ❑Not Applicable j
required in warm-humid locations
in Climate Zone 3.
303.2 Conditioned basement wall [ Complies
[F0511 insulation installed per []Does Not
U manufacturer's instructions. ❑Not Observable
❑Not Applicable
402.2.9 Conditioned basement wall _ft _ft ❑Complies See the Envelope Assemblies
[F06)1 insulation depth of burial or ❑Does Not (table for values.
4 distance from top of wall. ❑Not Observable
❑Not Applicable
303.2.1 A protective covering is installed ❑Complies
[FO 1112 to protect exposed exterior ❑Does Not
insulation and extends a ❑Not Observable
minimum of 6 in. below grade.
❑Not Applicable
403.9 Snow-and ice-melting system ❑Complies
[F012)2 controls installed. ❑Does Not
❑Nat Observable
❑Not Applicable
Additional Comments/Assumptions:
111 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 5 of 11
Section Plans Verified Field Verified
# Framing/Rough-In Inspection Value Value Complies? Comments/Assumptions
& Re .ID
402.1.1, (Door U-factor. U-_ U-_ ❑Complies See the Envelope Assemblies
402.3.4 ❑Does Not table for values.
[FR111 ❑Not Observable
I' ❑Not Applicable
402.1.1, Glazing U-factor(area-weighted U-_ U-_ ❑Complies !See the Envelope Assemblies
402.3.1, average). ❑Does Not table for values.
402.3.3,
[]Not402.3.6, Not Observable
402.5 ❑Not Applicable
[FR2]1
M,
303.13 U-factors of fenestration products ❑Complies
[FR411 are determined in accordance i❑Does Not
V, with the NFRC test procedure or ❑Not Observable
taken from the default table.
UNot Applicable
402.4.1.1 Air barrier and thermal barrier I❑Complies
[FR23]1 installed per manufacturer's ❑Does Not
instructions. j❑Not Observable
❑Not Applicable
402.4.3 Fenestration that is not site built ;❑Complies
[FR20]1 is listed and labeled as meeting ;❑Does Not j
AAMA/WDMA/CSA 101/1.S.2/A440 j❑No[Observable
or has infiltration rates per NFRC
400 that do not exceed code ;❑Not Applicable
limits.
402.4.5 IC-rated recessed lighting fixtures J❑Complies
[FR16]2 sealed at housing/interior finish '❑Does Not
and labeled to indicate <_2.0 cfm ![]Not Observable
leakage at 75 Pa.
❑Not Applicable
403.2.1 Supply and return ducts in attics ;❑Complies
[FR1211 insulated >= R-8 where duct is t❑Does Not
>= 3 inches in diameter and >_ ❑Not Observable
R-6 where< 3 inches.Supply and
return ducts in other portions of j❑Not Applicable
the building insulated >= R-6 for
diameter>= 3 inches and R-4.2
for<3 inches in diameter.
403.3.3.5 Building cavities are not used as ❑Complies
[FR15]3 ducts or plenums. ❑Does Not
❑Not Observabie
❑Not Applicable j
403.4 HVAC piping conveying fluids R- R-_ ❑Complies
[FR17]2 above 105 2F or chilled fluids ❑Does Not
3elow 55 QF are insulated to aR- : ❑Not Observable .
❑Not Applicable
403.4.1 Protection of Insulation on HVAC ❑Complies
(FR2411 piping. ❑Does Not
❑Not Observable
❑Not Applicable !
403.5.3 Hot water pipes are insulated to R- R-_ ❑Complies
IFR1812 IaR-3. ❑Does Not
ll� ❑Not Observable
❑Not Applicable
403.6 Automatic or gravity dampers are ❑Complies
IFR1912 :installed on all outdoor air ❑Does Not
:intakes and exhausts.
❑Not Observable ,
❑Not Applicable
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 6 of 11
Additional Comments/Assumptions:
----------
11 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 37)
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 7 of 11
Section Plans Verified Field Verified
# Insulation inspection Value Value Complies? Comments/Assumptions
& Req.ID
303.1 All installed insulation is labeled '..❑Complies
[IN13]2 or the installed R-values ❑Does Not
,� provided. ;❑Not Observable
❑Not Applicable
402.1.1, Floor insulation R-value. R- R- ❑Complies See the Envelope assemblies
402.2,6 ❑ Wood El Wood ❑Does Not table for values.
[IN111 ❑ Steel -❑ Steel ❑Not Observable
0 ❑Not Applicable
303.2, Floor insulation installed per ❑Complies
402.2.7 manufacturer's instructions and ❑Does Not
[IN211 in substantial contact with the ❑No[Observable
_ underside of the subfloor, or floor
framing cavity insulation is in ❑Not Applicable
contact with the top side of
sheathing, or continuous
insulation is installed on the
underside of floor framing and
extends from the bottom to the
top of all perimeter floor framing
members.
402.1.1, Wall insulation R-value.If this is a R- R-_ ❑Complies See the Envelope Assemblies
402.2.5, mass wall with at least 1/2 of the ❑ Wood ❑ Wood ❑Does Not 'table for values.
402.2.6 wall insulation on the wall ❑ Mass ❑ Mass ❑Not Observable
[IN311 exterior,the exterior insulation
requirement applies(FR10). ❑ Steel ❑ Steel ❑Not Applicable
303.2 Wall insulation is installed per []Complies
[IN4]1 manufacturer's instructions. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
-------------
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 8 of 11
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Re .ID
402.1.1, Ceiling insulation R-value. R- R- ❑Complies See the Envelope Assemblies
402.2.1, E] Wood ❑ Wood ❑Does Not table for values.
402.2.2, ❑ Steel ❑ Steel [-]Not Observable
F1111 6
[ ❑Not Applicable
FIl]
303.1.1.1, Ceiling insulation installed per ❑Complies
303.2 manufacturer's instructions. ❑Does Not
[FI211 Blown insulation marked every ❑Not Observable
300 ft2. ❑Not Applicable
402.2.3 Vented attics with air permeable ❑Complies
[FI22]2 insulation include baffle adjacent ❑Does Not
to soffit and eave vents that ❑Not Observable
,extends over insulation.
[]Not Applicable
402.2.4 Attic access hatch and door R- R-_ ❑Complies
[FI311 insulation>R-value of the ❑Does Not
.adjacent assembly. []Not Observable
❑Not Applicable
402.4.1.2 Blower door test @ 50 Pa.<=5 ACH 50=_ ACH 50=_ ❑Complies
[FI1711 ach in Climate Zones 1-2,and ❑Does Not
<=3 ach in Climate Zones 3-8. []Not Observable
[]Not Applicable
403.2.3 Duct tightness test result of<=4 cfm/100 cfm/100 '❑Complies
[1`I411 cfm/100 ft2 across the system or ft2 ftz ❑Does Not
<=3 cfm/100 ft2 without air ❑Nat Observable
handler @ 25 Pa. For rough-in
tests,verification may need to ❑Not Applicable
occur during Framing Inspection.
403.3.2 Ducts are pressure tested to cfm/100 cfm/100 ❑Complies
[F12711 determine air leakage with ft2 ❑Does Not
either: Rough-in test:Total
leakage measured with a ❑Not Observable
pressure differential of 0.1 inch ❑Not Applicable
w.g.across the system including
the manufacturer's air handler
enclosure if installed at time of
test.Postconstruction test:Total
leakage measured with a
pressure differential of 0.1 inch
w.g.across the entire system
including the manufacturer's air
handler enclosure. _
403.3.2.1 Air handler leakage designated ❑Complies
[FI2411 by manufacturer at<=2%of ❑Does Not
design air flow. ❑Not Observable
❑Not Applicable ,
403.1.1 Programmable thermostats ❑Complies
[F[9]2 installed for control of primary ❑Does Not
heating and cooling systems and
;initially set by manufacturer to ❑Not Observable
code specifications. ❑Not Applicable
403.1.2 Heat pump thermostat installed ❑Complies
[F110]2 on heat pumps. ❑Does Not
❑Not Observable
❑Not Applicable
403.5.1 Circulating service hot water ❑Complies
[Flll]2 systems have automatic or ❑Does Not
accessible manual controls. ❑Not Observable
❑Not Applicable
11 High Impact(Tier 1) r Medium Impact(Tier 2) 13 JLow Impact(Tier 3)
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 9 of 11
Section Plans Verified Field Verif led
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
403.6.1 All mechanical ventilation system ❑Complies
[F125]2 fans not part of tested and listed ❑Does Not
HVAC equipment meet efficacy
and air flow limits. ❑Not Observable
❑Not Applicable
403.2 Hot water boilers supplying heat ❑Complies
[FI2617 through one-or two-pipe heating ❑Does Not
systems have outdoor setback
control to lower boiler water ❑Not Observable
temperature based on outdoor ❑Not Applicable
temperature.
403.5.1.1 Heated water circulation systems ❑Complies
[FI28]2 have a circulation pump.The ❑Does Not
system return pipe is a dedicated ❑Not Observable
return pipe or a cold water supply
pipe.Gravity and thermos- ❑Not Applicable
syphon circulation systems are
not present.Controls for
circulating hot water system -
pumps start the pump with signal
for hot water demand within the
occupancy.Controls
automatically turn off the pump
when water is in circulation loop
is at set-point temperature and
no demand for hot water exists.
403.5.1.2 Electric heat trace systems ❑Complies
[FI29]2 comply with IEEE 515.1 or UL ❑Does Not
515.Controls automatically
adjust the energy input to the ❑Not Observable
heat tracing to maintain the ❑Not Applicable
desired water temperature in the
piping.
403.5.2 Water distribution systems that ❑Complies
[F130]2 have recirculation pumps that ❑Does Not
pump water from a heated water ❑Not Observable
supply pipe back to the heated
water source through a cold ❑Not Applicable
water supply pipe have a
demand recirculation water
system. Pumps have controls
that manage operation of the
pump and limit the temperature
of the water entering the cold
water piping to 1049F.
403.5.4 Drain water heat recovery units ❑Complies
[F131]' tested in accordance with CSA ❑Does Not -
B55.1.Potable water-side
pressure loss of drain water heat ❑Not Observable
recovery units < 3 psi for ❑Not Applicable
individual units connected to one
or two showers.Potable water-
side pressure loss of drain water
heat recovery units<2 psi for
individual units connected to
three or more showers.
404.1 75%of lamps in permanent [ Complies
[FI611 fixtures or 75%of permanent ❑Does Not
fixtures have high efficacy lamps.
Does not apply to low-voltage ❑Not Observable
lighting. ❑Not Applicable
404.1.1 Fuel gas lighting systems have ❑Complies
[FI2313 no continuous pilot light. ❑Does Not
❑Not Observable
❑Not Applicable j
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 10 of 11
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.
401.3 Compliance certificate posted. ❑Complies
[1`I7]2 ❑Does Not
❑Not Observable
❑Not Applicable
303.3 Manufacturer manuals for ❑Complies
[FI18]3 mechanical and water heating []Does Not
systems have been provided. ❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: PLAN NO. 2502-17-LOT 2 BLACKBERRY LN Report date: 03/21/17
Data filename: Page 11 of 11
2015 IECC Energy
Efficiency Certificate
Insulation Rating R-Value
Above-Grade Wall 21.00
Below-Grade Wall 15.00
Floor 38.00
Ceiling / Roof 48.00
Ductwork (unconditioned spaces):
Glass&Door Rating U-Factor SHGC
Window 0.30
Door 0.32
Heating&Cooling Equipment Efficiency
Heating System•
Cooling System:
Water Heater:
Name• Date:
Comments