New Terrace System 2017 r Fire, Security& Sound Systems, Inc. 4 Avis Drive—Suite 110 Latham,NY 12110 P:518-250-4364 F: 518-250-4365 u 1i x.fireecui•it�saund.com March 30, 2017 Glen at Hiland Meadows 39 Longview Drive Queensbury, NY 12804 RE:Terrace Fire Alarm Addition This is to certify that the final inspection test has been completed on the Siemens XLS Fire Alarm System at the above referenced project on 3/28/2017.The equipment supplied by Fire,Security& Sound Systems has been tested, meets NFPA 72 and the contract requirements and is working properly. These inspections and test conducted by our service technician fulfills our obligation on this job, and the warranty of one (1) year on this equipment is considered effective as of 3/28/17. If we can be of further service to you, please do not hesitate to call. Sincerely, gD Phil Conti Project Coordinator SO# 102488 �w`v 3Q Fire Security&Sound Systems—4 Avis Drive-Suite 110—Latham,NY 12110 Alarm License# 12000286670 FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed b},the system installation contractor at the time of sj stem acceptance and approval. It shall be permitted to mode this form as needed to provide a more complete and/or clear record. Insert AT/A in all unused lines. Attach additional sheets, data, or calculations as necessary to provide a complete record. 1. PROPERTY INFORMATION Name of property: GLEN AT HIGHLAND MEADOWS Address: 39 LONGVIEW DR QUEENSBURY,N.Y.12804 Description of property: RESIDENTAL Occupancy type: RESIDENTAL Name of property representative: NICK NORTON Address: 39 LONGVIEW DR QUEENSBURY N.Y.12804 Phone: 518-832-7800 Fax: N/A E-mail: NICK.NORTON@SPHP.COM Authority having jurisdiction over this property: NIA Phone: NIA Fax: NIA E-mail: N/A 2. INSTALLATION,SERVICE,AND TESTING CONTRACTOR INFORMATION Installation contractor for this equipment: FIRE,SECURITY&SOUND SYSTEMS,INC. Address: 4 AVIS DR-SUITE 110,LATHAM N.Y.12110 License or certification number: 12000286670 Phone: 518-250-4364 Fax: 518-260-4365 E-mail: N/A Service organization for this equipment: FIRE,SECURITY&SOUND SYSTEMS,INC. Address: 4 AVIS DR- SUITE 110,LATHAM, NY 12110 License or certification number: 12000286670 Phone: (518)250-4364 Fax: (518)250-4365 E-mail: N/A A contract for test and inspection in accordance with NFPA standards is in effect as of: Contracted testing company: FIRE SECURITY&SOUND SYSTEMS, INC. Address: 4 AVIS DRIVE-SUITE 110,LATHAM,NY 12110 Phone: 518-250-4364 Fax: 518-250-4365 E-mail: N/A Contract expires: NIA Contract number: NIA Frequency of routine inspections: YEARLY 3. DESCRIPTION OF SYSTEM OR SERVICE ®Fire alarm system(nonvoice) ❑Fire alarm with in-building fire emergency voice alarm communication system(EVACS) ❑Mass notification system(MNS) ❑Combination system,with the following components: ❑Fire alarm ❑EVACS ❑MNS ❑Two-way,in-building,emergency communication system ❑Other(specify): NIA NFPR 72, Fig. 10.18.2.1.1 (p. 1 of 12) Copyright®2009 National Fire Protection Association.This form may be copied for individual use other than for resale.it may riot be copied for commercial sale or dsbibution. 3. DESCRIPTION OF SYSTEM OR SERVICE (continued) AT-PA 72 edition: 2013 Additional description of system(s): N/A 3.1 Control Unit Manufacturer: SIEMENS Model number: XLS 3.2 Mass Notification System ®This system does not incorporate an MNS 3.2.1 System Type: ❑In-building MNS—combination ❑In-building NfNS—stand-alone ❑Wide-area MNS ❑Distributed recipient MNS ❑Other(specify): NIA 3.2.2 System Features: ❑Combination fire alarn>!/!i INS ❑N1NTS autonomous control unit ❑Wide-area MNS to regional national alerting interface ❑Local operating console(LOC) ❑Direct recipient MNS(DRMNS) ❑!Vide-area MNS to DRDINS interface ❑Wide-area MNTS to high-power speaker array(HPSA)interface ❑In-building MNS to wide-area NINS interface ❑Other(specify): N/A 3.3 System Documentation ®Ali owner's manual,a copy of the manufacturer's instructions,a written sequence of operation,and a copy of the numbered record drawings are stored on site. Location: MAINTENANCE 3.4 System Software ❑This system does not have alterable site-specific software. Operating system(executive)software revision level: ZEUS 12 Site-specific software revision date: 3/6117 Revision completed by: J.S.VAN WINKLE ®A copy of the site-specific software is stored on site. Location: IN PANEL 3.5 Off-Premises Signal Transmission ❑This system does not have off-premises transmission. Name of organization receiving alarm signals with phone numbers: Alarm: USA MONITORING Phone: 1-800-422-2300 Supervisory: USA MONITORING Phone: 1-800-422-2300 Trouble: USA MONITORING Phone: 1-800-422-2300 Entity to which alarms are retransmitted: N/A Phone: N/A Method of retransmission: NIA If Chapter 26,specify the means of transmission from the protected premises to the supervising station: DIGITAL DIALER If Chapter 27,specify the type of auxiliary alarm system: ❑Local energy ❑Shunt ❑Wired ❑ Wireless NFPA 72,Fig. 10.18.2.1.1 (p.2 of 12) Copyright®2009 National Fire Protection Association.This form maybe copied for individual use other than for resa:e.It may not be copied for commercial sale or distribution. 4. CIRCUITS AND PATHWAYS 4.1 Signaling Line Pathways 4.1.1 Pathways Class Designations and Survivability Pathways class: B Survivability level: 1 Quantity: 1 (See NFPA 72,Sections 12.3 and 12.4) 4.1.2 Pathways Utilizing Two or More Media Quantity: NIA Description: NIA 4.1.3 Device Power Pathways ❑No separate power pathways from the signaling line pathway ®Power pathways are separate but of the same pathway classification as the signaling line pathway ❑Power pathways are separate and different classification from the signaling line pathway 4.1.4 Isolation Modules Quantity: 0 4.2 Alarm Initiating Device Pathways 4.2.1 Pathways Class Designations and Survivability Pathways class: B Survivability level: i Quantity: 1 (See rlrFPA 72,Sections 12.3 and 12.4) 4.2.2 Pathways Utilizing Two or More Media Quantity: 0 Description: NIA 4.2.3 Device Power Pathways ❑No separate power pathways from the initiating device pathway ®Power pathways are separate but of the same pathway classification as the initiating device pathway ❑Power pathways are separate and different classification from the initiating device pathway 4.3 Non-Voice Audible System Pathways 4.3.1 Pathways Class Designations and Survivability Pathways class: NIA Survivability level: NIA _ Quantity: NIA (See 1VFPA 72,Sections 12.3 and 12.4) 4.3.2 Pathways Utilizing Two or More]Media Quantity: N/A Description: N/A 4.3.3 Appliance Power Pathways ❑No separate power pathways from the notification appliance pathway ❑Power pathways are separate but of the same pathway classification as the notification appliance pathway ❑Power pathways are separate and different classification from the notification appliance pathway NFPA 72, Fig. 10.18.2.1.1 (p.3 of 12) Copyright®2009 National Fire Protection Association.This form maybe copied for individual use other than for iesa:e.It may not be copied for commercial sale or disN-hution. 5. ALARM INITIATING DEVICES 5.1111anual Initiating Devices 5.1.1 Manual Fire Alarm Boxes ❑This system does not have manual fire alarm boxes. Type and number of devices: Addressable: 0 Conventional: 0 Coded: 0 Transmitter: 0 Other(specify): N/A 5.1.2 Other Alarm Boxes ®This system does not have other alarm boxes. Description: N/A Type and number of devices: Addressable: 0 Conventional: 0 Coded: 0 Transmitter: 0 Other(specify): N/A 5.2 Automatic Initiating Devices 5.2.1 Smoke Detectors ❑This system does not have smoke detectors. Type and number of devices: Addressable: 140 Conventional: 0 Other(specify): N/A Type of coverage: ®Complete area ❑Partial area ❑Nonreduired partial area Other(spccify): N/A Type of smoke detector sensing technology: ❑Ionization ®Photoelectric, ®Multicritcria []Aspirating ❑Beam Other(specify): N/A 5.2.2 Duet Smoke Detectors ❑This system does not have alarm-causing duct smoke detectors. Type and number of devices: Addressable: 0 Conventional: 0 Other(specify): N/A Type of coverage: N/A Type of smoke detector sensing technology: ❑Ionization ®Photoelectric ❑Aspirating ❑Beam 5.2.3 Radiant Energy(flame)Detectors ®This system does not have radiant energy detectors. Type and number of devices: Addressable: 0 Conventional: 0 Other(specify): N/A Type of coverage: N/A 5.2.4 Gas Detectors ®This system does not have gas detectors. Type of detector(s): N/A Number of devices: Addressable: 0 Conventional: 0 Type of coverage: NIA 5.2.5 Heat Detectors ❑This system does not have heat detectors. Type and number of devices: Addressable: 0 Conventional: 44 Type of coverage: (D Complete area ❑Partial area ❑Nonrequired partial area ❑Linear ❑Spot Type of heat detector sensing technology: ®Fixed temperature ❑Rate-of-rise ❑Rate compensated NFPA 72, Fig. 10.18,2.1.1 (p.4 of 12) Copyright 9 2009 National Fire Protection Association.This form maybe copied for individual use other than for resale.It may not be copied for commercial sae or distribution. 5. ALARM INITIATING DEVICES (continued) 5.2.6 Addressable Monitoring Modules ❑This system does not have monitoring modules. Number of devices: 44 5.2.7 Waterflow Alarm Devices ®This system does not have waterflow alarm devices. Type and number of devices: Addressable: 0 Conventional: 0 Coded: 0 Transmitter: 0 5.2.8 Alarm Verification ®This system does not incorporate alarm verification. Number of devices subject to alarm verification: N/A Alarm verification set for NIA I seconds 5.2.9 Pre-signal ®This system does not incorporate pre-signal. Number of devices subject to presignal: 0 Describe presignal functions: NIA 5.2.10 Positive Alarm Sequence(PAS) ®This system does not incorporate PAS. Describe PAS: N/A 5.2.11 Other Initiating Devices ®This system does not have other initiating devices. Describe: NIA 6. SUPERVISORY SIGNAL-INITIATING DEVICES 6.1 Sprinkler System Supervisory Devices ®This system does not have sprinkler supervisory devices. Type and number of devices: Addressable: 0 Conventional: 0 Coded: 0 Transmitter: 0 Other(spccify): N/A 6.2 Fire Pump Description and Supervisory Devices ®This system does not have a fire pump. Type fire pump: ❑Electric pump ❑Engine Type and number of devices: Addressable: 0 Conventional: 0 Coded: 0 Transmitter: 0 Other(specify): N/A 6.2.1 Fire Puntp Functions Supervised ❑Power ❑Running ❑Phase reversal ❑Selector switch not in auto ❑Engine or control panel trouble ❑Low fuel Other(specify): N/A 6.3 Duct Smoke Detectors(DSDs) ®This system does not have DSDs causing supervisory signals. Type and number of devices: Addressable: 0 Conventional: 0 Other(specify): NIA Type of coverage: NIA Type of smoke detector sensing technology: ❑Ionization ❑Photoelectric ❑Aspirating ❑Beam 6.4 Other Supervisory Devices ®This system does not have other supervisory devices. Describe: NIA NFPA 72, Fig. 10.18.2.1.1 (p.5 of 12) Copyright®2009 National Fire Protection Association.This fam may be copied for individual use other than for resale.It may not be copied for commercial sale or distn'bution. 10. MASS NOTIFICATION CONTROLS,APPLIANCES, AND CIRCUITS ®This system does not have an MNS. 10.1 AINS Local Operating Consoles Location 1: N/A Location 2: N/A Location 3: NIA 10.2 High-Power Speaker Arrays Number of HPSA speaker initiation zones: NIA Location 1: NIA Location 2: N/A Location 3: N/A 10.3 Klass Notification Devices Combination fire alarin/NMS visible appliances: N/A MNIS-only visible appliances: NIA Textual signs: N/A Other(describe): NIA Supervision class: NIA 10.3.1 Special Hazard Notification ®This system does not have special suppression predischarge notification. ®NTNTS systems DO NOT override notification appliances required to provide special suppression predischarge notification. 11. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS 11.1 Telephoiie System ®This system does not have a two-way telephone system. Number of telephone jacks installed: NIA Number of warden stations installed: N/A Number of telephone handsets stored on site: N/A Type of telephone system installed: ❑Electrically powered ❑Sound powered 11.2 Two-jVayRadio CommunicationsEnhaiicementSystem ®This system does not have a hvo-way radio communications enhancement system. Percentage of area covered by two-way radio service: Critical areas: NIA % General building areas: NIA % Amplification component locations: N/A Inbound signal strength: N/A dBm Outbound signal strength: N/A dBm Donor antenna isolation is: NIA dB above the signal booster gain Radio frequencies covered: NIA Radio system monitor panel location: N/A NFPA 72, Fig. 10.18.2.1.1 (p.7 of 12) Copyright 6 2009 National Fire Protection Association.This form may be copied for individual use other than for resale.it may not be copied for commercial sale or distribution. 11. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS (continued) 11.3 Area of Refuge(Area of Rescue Assistance)Emergency Communications Systems ®This system does not have an area of refuge(area of rescue assistance)emergency communications system. Number of stations: NIA Location of central control point: N/A Days and hours when central control point is attended: N/A Location of alternate control point: N/A Days and hours when alternate control point is attended: N/A 11.4 Elevator Emergency Communications Systems ®This system does not have an elevator emergency communications system. Number of elevators with stations: N/A Location of central control point: NIA Days and hours when central control point is attended: N/A Location of alternate control point: N/A Days and hours when alternate control point is attended: N/A 11.5 Other Two-'Nay Conunuttiention Systems Describe: N/A 12. CONTROL FUNCTIONS This system activates the following control factions: ❑Hold-open door releasing devices ❑Smoke management ❑HVAC shutdown ❑F/S dampers ❑Door unlocking ❑Elevator recall ❑Fuel source shutdown ❑Extinguishing agent release ❑Elevator shunt trip ❑Mass notification system override of fire alarm notification appliances Other(specify): N/A 12.1 Addressable Control Modules ❑This system does not have control modules. Number of devices: 1 Other(specify): N/A 13. SYSTEM POWER 13.1 Control Unit 13.1.1 Primary Power Input voltage of control pwiei: 120 Control panel amps: 12 Overcurrent protection: 'Type: BREAKER Amps: 20 Location(of primary supply panel board): EP-1 E Disconnecting means location: CIRCUIT#25 13.1.2 Engine-Driven Generator ®This system does not have a generator. Location of generator: NIA Location of fuel storage: NIA Type of fuel: N/A NFPA 72, Fig. 10.18.2.1.1 (p.8 of 12) Copyright 0 2009 National Fire Protection Association.This form maybe copied for individual use other than forressle.It may not be copied for commercial sale or distribution. 13. SYSTEM POWER(continued) 13.1.3 Uninterruptible Power System ®This system does not have a UPS. Equipment powered by a UPS system: N/A Location of UPS system: N/A Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode(hours): N/A In alarm mode(minutes): NIA 13.1.4 Batteries Location: MAIN PANEL Type: LEAD Nominal voltage: 24 Anip/hour rating: 28 Calculated capacity of batteries to drive the system: In standby mode(hours): 24 In alarm mode(minutes): 5 ®Batteries are marked with date of manufacture ❑Battery calculations are attached 13.2 In-Building Fire Emergency Voice Alai-in Communication System or Mass Notification System ®This system does not have an EVACS or MNS system. 13.2.1 Primary Power Input voltage of EVACS or MNS panel: N/A EVACS or MNS panel amps: NIA Overcurrent protection: Type: NIA Amps: NIA Location(of primary supply panel board): N/A Disconnecting means location: N/A 13.2.2 Engine-Driven Generator ®This system does not have a generator. Location of generator: N/A Location of fuel storage: NIA Type of fuel: N/A 13.2.3 Uninterruptible Power System ®This system does not have a UPS. Equipment powered by a UPS system: NIA Location of UPS system: N/A Calculated capacity of UPS batteries to drive the system*components connected to it: In standby mode(hours): N/A In alarm mode(minutes): N/A 13.2,4 Batteries Location: NIA Type: NIA Nominal voltage: N/A Amp/hour rating: N/A Calculated capacity of batteries to drive the system: In standby mode(hours): N/A In alarm mode(minutes): NIA ❑Batteries are marked with date of manufacture [J Battery calculations are attached NFPA 72, Fig. 10.18.2.1.1 (p.9 of 12) Copyright 0 2009 National Fire Protection Association'this form may be copied for irKliMdual use other than for resale.It may riot be copied for commercial sale or distnbutiom 13. SYSTEM POWER(continued) 13.3 Notification Appliance Power Extender Panels ®This system does not have power extender panels. 13.3.1 Primary Power Input voltage of power extender panel(s): NIA Power extender panel amps: NIA Overcurrent protection: Type: NIA Amps: NIA Location(of primary supply panel board): NIA Disconnecting means location: NIA 13.3.2 Engine-Driven Generator This system does not have a generator. Location of generator: NIA Location of fuel storage: NIA Type of fuel: NIA 13.3.3 Uninterruptible Power System ®This system does not have a UPS. Equipment powered by a UPS system: NIA Location of UPS system: NIA Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode(hours): NIA In alarm mode(minutes): NIA 13.3.4 Batteries Location: NIA Type: NIA Nominal voltage: NIA Amp/hour rating: NIA Calculated capacity of batteries to drive the system: In standby anode(hours): N/A In alarm mode(minutes): NIA ❑Batteries are marked with date of manufacture ❑Battery calculations are attached 14. RECORD OF SYSTEM INSTALLATION Fill out after all installation is complete and tinting has been checked for opens,shorts,ground faults, and improper branching,but before conducting operational acceptance tests. This is a: ❑New system ®Modification to an existing system Permit number: NIA The system has been installed in accordance with the following requirements:(Note any or all that apply.) ®A'FPA 72,Edition: 2013 ®NFPA 70,National Electrical Code,Article 760,Edition: 2013 ®Manufacturer's published instructions Other(specify): NIA h System deviations from referenced NFPA stwidards: NIA t 1 tf. Signed: i s t v` l J u7� Printed name: J.S.VAN WINKLE Date: 3/6/17 Organization: F.S.&S_ Title: TECH Phone: 250-4364 NFPA 72, Fig. 10.18.2.1.1 (p.10 of 12) Copymght®2009 National Fire Protection Association.This form may be copied for irzd"rvidual use other than for resale.It may not be copied for commercial safe or dstnbulion. 15, RECORD OF SYSTEM OPERATIONAL ACCEPTANCE TEST ❑New system All operational features and functio s of this system were tested by,or in the presence of,lire signer shown below, on the date shown below,and were found to be operating properly in accordance with the requirements for the following: ®Modifications to an existing system III newly modified operational features and f unctions of the system were tested bp, or in the presence of,tine signer shown below,on the date shown below,and were found to be operating properly in accordance with the requirements of the following: ®A'FPA 72,Edition: Z013 ®A'FPA 70,National Electrical Code, Article 760,Edition: 2013 ®Manufacturer's published instructions Other(specify): NIA ❑Individual device testing documentation[Inspection and Testing Form(Figure 14.6.2.4)is attached] Signed: Printed name: Date: Organization: Title: Phone: 16. CERTIFICATIONS AND APPROVALS 16.1 Syste►n Installation Contractor: This system,as specified herein,has been installed and tested according to all NFPA standards cited herein. Signed: Printed name: Date: Organization: Title: Phone: 16.2 System Service Contractor: The undersigned has a service contract for this system in effect as of the date shown below. Signed: Printed name: Date: Organization: Title: Phone: 16.3 Supervising Station: This system,as specified herein,will be monitored according to all NFPA standards cited herein. Signed: Printed name: Date: Organization: Title: Phone: NFPA 72, Fig. 10.18.2.1.1 (p. 11 of 12) Copyright 9 2009 National Fire Protection Association.This form maybe,copied for individual use other than for resate.It may not be copied for commercial save or distriWtion. 16. CERTIFICATIONS AND APPROVALS (continued) 16.4 Property or Owner Representative: I accept this system as having been installed and tested to its specifications and all NTFPA standards cited herein. Signed: Printed name: Date: Organization: Title: Phone: 16.5 Antlioi•ity Having Jttrisdiction: 1 have witnessed a satisfactory acceptance test of this system and find it to be installed and operating properly in accordance with its approved plans and specifications,with its approved sequence of operations,and with all NFPA standards cited herein. Signed: Printed name: Date: Organization: Title: Phone: NFPA 72, Fig. 10.18.2.1.1 (p. 12 of 12) Copyright®2009 National Fire Protection Association.This form maybe copied for individual use other than for resale.It may not be copied for commercial sale or dislrlbutlom FS&S FIRE SECURITYAND SOUND, INC. SALES AND SERVICE OF FIRE ALARM, SECURITY, CCTV, COMMUNICATIONS SYSTEMS Submittal #102488 November 08, 2016 Project: Glen at Hiland Meadows 39 Longview Drive Queensbury,NY 12804 Contractor: Trinity Health East PO Box 7052 Troy, MI 48007-7052 Submitted by: Jeremy Riel Salesmen: Phil Conti 4 Avis Drive - Suite 110, Latham, NY 12110 Website—WWW.FIRESECURITYSOUND.COM Phone: (518)250-4364 Fax: (518)250-4365 FS&S FIRE SECURITY AND SOUND, INC. SALES AND SERVICE OF FIRE ALARM,SECURITY, SPECIFICATION SECTION: DIGITAL, ADDRESSABLE FIRE-ALARM SYS. QUANTITY MODEL# DESCRIPTION PAGE XLS FIRE ALARM SYSTEM 1.1-12 1 XLS-250-CAB2-BD INCLUDES: (1) PMI-2, (1)PSC-12, 1.13-18 (1)CC-5, (1)DLC,(1) ID-SP, (1)BCL (1)ZIC-4A, (1)CAB2-BD,(1)OD-LP CAB2-BD TWO-ROW INNER&OUTER DOOR SET 1.13-18 1 CAB2-BB TWO-ROW BACKBOX 1.13-18 1 CAB-MP BACK BOX MODULE MOUNTING PLATE 1.13-18 1 OD-BP OUTER DOOR BLANK PLATE 1.13-18 1 ID-MP INNER DOOR MODULE MOUNTING PLATE 1.13-18 1 BCM (4) BLANK MODULE PLATES 1.13-18 - ID-SP INNER DOOR SINGLE MODULE BLANK 1.13-18 - OD-LP OUTER DOOR LENS PLATE 1.13-18 1 OD-BP OUTER DOOR BLANK PLATE 1.13-18 - PMI-2 PERSON MACHINE INTERFACE 2 1.19-22 - PSC-12 POWER SUPPLY&BATTERY CHARGER 1.23-26 - CC-5 CARD CAGE 5 SLOTS 1.27-28 - DLC DEVICE LOOP CARD 1.29-30 - BCL 60 PIN CABLE FOR ROW TO ROW CONN. - - ZIC-4A ZONE INDICATING CARD 1.31-34 1 NIC-C NETWORK INTERFACE CARD 1.35-36 1 SCM-8 8 SWITCH MODULE 1.37-40 1 CAB-BATT BATTERY CABINET 1.41-44 1 HTRI-R INTELLIGENT RELAY MOD. 1.45-46 1 TRI-S MXL LOOP INPUT MODULE 1.47-48 44 HTRI-M MINI INPUT MODULE 1.49-50 44 284B-PL CONV. 194 DEGREE HEAT DET. 1.51-52 134 OP921 INTELLIGENT PHOTO SMOKE DET. 1.53-56 134 DB-11 BASE 1.53-56 2 PS-12280 12V 28A/HR BATTERY(FACP) 1.57-58 PROJECT COMPLIANCE: PAGE FACP BATTERY CALCULATIONS Al-2 INSTALLER'S LICENSE B1 RISER DRAWING D-102488A1 SIEMENS Data Sheet Fire Safety Products FireFinderl XLS Advanced Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS • Standard 12500-point-capacity addressable fire-alarm control y` • Multiple command stations panel(FACP) • Menu-driven operator commands • Ability to network with other <h • 5000-event,history-logging capability FireFinder XLS systems J . . . , with on-line and off-line reports • Powerful,easy-to-use programming .. $ • Multiple levels of password protection capabilities R • • Automatic environmental compensation • Fully field programmable,via - for smoke detectors Windowsz'laptop PC • Alarm verification • 6",backlit LCD display • bydeviceorzone • User-friendly system interface • Pre-alarm operation • Touch screen for maintenance • Logic-controlled output functions operations and function keys • Time-based-controlled output functions • Global annunciation and control • Holiday schedule capability • Muitl-language display • City tie I leased line • Universal AC power input: •Modular assembly • 200notification-appliance-circuits 120VAC—240VAC @ 50160Hz •Supervised remote printer (NACs)capacity • 12 amps of system power • ar • Up to 3.0 amps(24VDC)per NAC •Thermal(expandable to 48 amps) Ther l strip custom messages synchronization protocol • Numerous Relays: Alarm,Trouble, ma sp printer • Built-in strobe• Supports pre-action,deluge and agent Programmable,etc. •Security-device monitoring releasin • (OUL 1076 Listed) g • sureWire-addressable-loop technology • Voice evacuation system(optional) • Polarity-insensitive detection circuits •Sprinkler Supervision • NEC 760powerlimited circuits (patented) •Degrade-mode operation . (®UL 864 Compliant) • Useful diagnostic LEDs on all cards •User help screens • Intelligent interface to building/process • supports FirePrintwapplication-specific •Coded outputs management systems detection •Supported by all Fire Safety • Operates as interactive peer with other • Intelligent/analog detection circuits: Management Stations XLS or XLSV units In a XNET network 'Class A'or'Class B' •UUKL Listed for smoke control • Distributed processing • Supports single-person'Walk Test' •AUL 864 9+h Edition Listed&®ULC Listed; • Detector Sensitivity Readout 1 Printout • Seismic certified FM,CSFM&NYC Fire Dept.Approved . per NFPA 72 System Overview FireFinder XLS is a microprocessor-based,advanced FireFinder XLS is Factory Mutual(FM 93010)Approved;as life-safety system that has a 6 display and large,lighted well as California State Fire Marshals(CSFM'7165- buttons;making it a highly intuitive fire-alarm user interface. 0067.0222)and NYC Fire Department(16160)Approved. Through the use of the unique muitiprocessor'Network' Additionally,FireFinder XLS is®UL Listed under the category design—along with the ability to utilize analog and UUKL for smoke control. conventional detection devices--FireFinder XLS FireFinder XLS is also®UL Listed and FM Approved for exemplifies a flexible and configurable life-safety system. Sinorixe dean-agent systems and pre-action or deluge FireFinder XLS is ideally suited for commercial,institutional sprinkler systems,which include foam or water applications. and industrial fire detection and notification applications. FireFinder XLS operates on the releasing requirements This FACP complies with the requirements of NFPA Standard specified in NFPA 13 and 2001. 72,and is listed by Underwriters Laboratories under their FireFinder XLS is listed as a Fireman's Smoke Control Station eUL 864 standard. Underwriters laboratories of Canada in high-rise office buildings,malis and other large structures. also lists FireFinder XLS FACPs under 4DULC-S527. FireFinder®XLS System Overview 63OO SIEMENS Industry,Inc. Building Technologies Division System Overview—(continued) The FireFinder XLS system has been seismic qualified —- in accordance with: ■ International Building Code,2006 Edition • California Building Code,2007 Edition '' 0. • ASCE Standard 7,2005 Edition ■ OSHPD,OSP-0057-10 • OSHPD CAN 2-1708A.5,Rev.3 • ICC-ES AC 156,effective 1/1/2007 PM I-2- Person Machine Interface 2 System Components PMI-2-4 Person Machine Interface 2 A basic FireFinderXLS FACP consists of the following sub- The Person Machine Interface 2(Model PMI-2)is the assemblies: Person Machine Interface(Model PMI-2);Power primary user interface and central microprocessor for the Supply(Model PSC-12);Device Loop Card(Model DLC);Zone FireFinder FACP. Indicating Card(Model ZIC-4A);Card cage(Model CC-5), Model PMI-2 uses large,lighted buttons to prompt users as Inner Door Blank Single Plate(Model ID-SP);CAB-1,CAB-2 or to the next correct system operation that is available CAB-3 enclosures. (Acknowledge,Silence,Unsiience,Audible or Reset). From Optional modules that can be installed with this FACP each Model PMI-2 interface,the end-user can Acknowledge include: Card Cage(Model CC-2);Network Interface Card events;control the system notification appliance circuits (Model NIC C);8-Circuit zone Indicating Card(Models ZIC- (NACs),and reset the system. Detailed information about 88 l ZIC-2C);Control Relay Card(Model CRC-6);Output the nature and location of the events can also be displayed. Control Module(Model OCM-16),Switch Control Module The controller in Model PMI-2 provides all system logic and (Model SCM-8);LED Control Module(Model LCM-8);Fan supervision. Model PMI-2 contains a large(1l4 VGA),6" Control Module(Model FCM-6);Supervised Input Module 05.2 cm.),1200-x 800 pixel full-color liquid-crystal(LCD) (Model SIM-16);Power Supply Extender(Model PSX 12), display,touch screen and LEDs for displaying system status. Remote Network Interface(Model RNI);Remote Printer A sound is made when there is any unacknowledged event Module(Model RPM);System Status Display(Model SSD); from Model PMI-2. The display is surrounded by keys that are Multi-Point Digital Alarm Communicator(Model MDACi); used to control the displayed information and to navigate Two-Module Remote Enclosure(Model REMBOX2);Four- through these screens. Keys are also provided to obtain and Module Remote Enclosure(Model REMBOX4). enter•Help"into the menu features of Model PMI-2. FireFinder XLS is compatible with a full line of intelligent Overlays--available in Spanish,Portuguese and French-- initiating devices,highlighted by the FirePrint application- provide name in alternate languages for the text found on specified detectors: Models HFP-11 and HFPT-11. XLS the front of each Model PMI-2. Each overlay is assigned on functions with the Siemens Fire Safety portfolio of graphics the outer assembly,respectively,when affixed to the command centers. display on the user interface. Each overlay assignment is intended for use in combination with the run-time,alternate-language files found in the custom-configuration software tool,Zeus. Fire Safety Management Stations-XLS Compatible FireFinder XLS Compatibility with Siemens Fire Safety Management Stations - FireFinder XLS panels are compatible with Siemens Fire Safety Management Stations,which provide integrated ZIC-4A- Zone Indicating Card and reliable FACP monitoring and control of XLS system ZIC-4A Zone Indicating Card events—including: Alarm,Trouble,Security and The Zone Indicating Card(Model ZIC 4A)provides four(4) Supervisory commands. fully supervised,programmable output circuits for use Each management station includes PC-based,color- on each FireFinder XLS. Model ZIC-4A supplies four(4) graphics software designed for use with the XNET 'Class B'(Style`)or'Class A'(Style Z)type output circuits, network,offering full control and annunciation. power limited to 3.0 amps maximum per circuit. An extensive history log of all XLS-FACP events,as well as extensive report-generation capabilities,is easily maintained. Additionally,user-programmable function buttons allow site-specific control functions. SIEMENS Industry,Inc. 1 . 2 • 2 Building Technologies Divlsion FireFinder XLS Components--(cont.`d) Each circuit for Model ZIC 4A can be independently programmed for use with listed audible or visual notification appliances;listed emergency audio speakers; municipal tie boxes;leased lines,or as releasing circuits. Model ZIC-4A plugs into one(1)slot in the Model CC-5 or Model CC-2 card cage,and has on-board LEDs for system status and troubleshooting. Indication of power,communication,internal operation, and ground-fault conditions are provided,as well as NIC-C—3, Network Interface Card indication of circuit activation or Trouble conditions. NIC-C Network Interface Card The Network interface Card(Model NIC-Q provides HNET or } XNET network communications between enclosures. In � addition to the HNET or XNET'communication,Model NIC{ I<y; provides CAN network communication within an enclosure or external to the enclosure. HNET orXNET communication is can be wired Style 4 or Style 7,but the CAN network can be wired Style 4 only. When used for HNET communications,Model NICC ZIC-88 I ZiC-2C-3.zone Indicating Cards provides communication between enclosures on a single ZIC-8B/ZIC-2C system. The Zone Indicating Card(Model ZI086)provides eight(8) When Model NIC-C is used for XNET communications, fully supervised,programmable output circuits for use on Model NiC C provides communication between systems. FireFinder XLS. Model ZIC-813 supplies eight(8)`Class B' The maximum of XNET Model NIC-C cards on a single (Style Y)type output circuits,power limited to 2.0 amps system(single node)is one(1),for a total of 64 XNET maximum per circuit.Each circuit can be independently Model NIC-C cards on a peer-to-peer networked system. programmed for use with listed audible or visual notification Model NIC-C has diagnostic LEDs that indicate: Card Fail, appliances,or listed emergency audio speakers. Model ZIC CAN Fail,HNET Fail,XNET Fail,Ground Fault,Loop'A`Fail and 8B plugs into one(1)slot in the Model CC-5 or Model CC-2 Loop'B Fail. Model NIC C Card also has LEDs to indicate card cage,and has on-board LEDs for system status. Power,Style and Active Networks. Model ZIC2C mounts directly on Model ZIC813,and allows each of the Model ZIC-8B output circuits to be used for two-channel voice applications. Indication of power, communication,internal operation,and ground-fault conditions are provided,as well as indication of circuit activation or Trouble conditions. ', HCP—r Control Point Module HCP Control Point Module �s Model HCP provides an intelligent control point for the FireFindei-XLS. Model HCP can be programmed as an independent,remotely located telephone zone, speaker zone or notification appliance circuit. Model DLC--)Device Loop Card HCP is designed to be used with the Siemens—Fire Safety Alarm Signaling Devices product line. DLC Device Loop Card The Device Loop Card(Model DLC)is the interface for Model HCP communicates through the Model DLC analog loop,and can be wired either`Class A`(Style Z) connection with FireFinder XLSdetectors and initiating or'Class B'(Style Y). The 24 VDC power input comes devices---including manual stations,control and input from either the control panel or from any WL Listed devices. Model DLC plugs into one(1)slot of the CC-2 or CG power-limited,auxiliary power supply. 5 card cage. Programming Model DLC is accomplished using the Fi vFinderXLS system-programming tool,Zeus. Model DLC takes one(1)address on the network,and communicates with two(2)device circuits for a total of 252 detectors and devices. Model DLC has 12 LEDs for diagnostic purposes,and provides ground-faultdetection and zone- isolation circuitry. SIEMENS Industry,Inc. Building Technologies Division 1 . 3 FireFinder XLS Components—(cont,'d) i 1 t t �- CRC-6-+Controllable Relay Card CRC-6 Controllable Relay Card MLC-4 MXL Line Card[for rirerinder XLSI The Controllable Relay Card(Model CRC-6)is used with MLC-MXL Line Card [for FireFinder XLS] the FireFinder XLS FACP. Model CRC-6 is designed to The MXL Line Card(Model MLC)is an optional card for provide auxiliary control of building functions,such as: the FireFinder XLS panel that supplies two(2) door-holder release,elevator capture,smoke control,lock intelligent analog circuits,utilizing the Model'I'series; release,etc. Model CRC-6 plugs into one(1)slot in the Model'ID'series;Model'IL'series or Model'FP'series- Model CC-5 or Model CC-2 card cage. Model CRG6 type intelligent devices.Model MLC occupies two(2) provides six(6),fully programmable relays. Each relay addresses on the HNET network,and devices connected contains one(1)set of SPDT contacts rated at 4 Amps 30VDC to the Model MLC circuits are dynamically supervised by 1120VACresistiveand 3.5amps 120VACinductive(0.6 P.F.) FireFinder XLS through the use of a unique communications protocol. vi Kz Xy: SIM-16.4 Supervised Input Module NRC Network Ring Card SIM-16 Supervised Input Module NRC Network Ring Card--Second Generation The Supervised input Module(Model SIM-16)is a Model NRC,which is the 2nd generation of Model NRC,is a remotely located,general-purpose input module. Model networking ring card that transmits single-mode or multi- SIM-16 provides 16 input circuits for remote system mode network communication via fiber-optic or copper monitoring. Each input can be individually programmed lines. Each card uses a'Class A'(Style 7)ring configuration as supervised(dry-contact only)or unsupervised(general- for connection with each FireFinder XLS FACP. purpose input.) Model SIM-16 has two(2)'Form C relays.The relays and inputs are programmed using the One(1)Model NRC(per system node)provides XNET,peer- Zeus system software-programming tool. to-peer communication between FireFinder XLS FACPs, allowing a max,64,XLS FACPs to be networked together. '4'a t. FCM-6 Fan,Motor,Dampers Control Module CDC-4-+Conventional Detector Card FCM-6 Fan,Motor,Dampers Control Module CDC-4 Conventional Detector Card The Fan,Motor,Dampers Control Module(Model FCM-6)is a The Conventional Detector Card(Model CDC-4)is used FhvRnderXLS command-console option module that to monitor Siemens Fire Safety conventional detectors provides manual control of building HVAC system fans, on the FireFinder XLS system. Model CDC-4 can be motors,and dampers. Each Model FCM-6 module provides used in applications where conventional detectors are six(6)sets of three(3)push-button switches for manual- more suited than addressable detectors,such as system control. Each switch has three(3),associated hallways or large meeting rooms. Also,Model CDC-4 LEDs to indicate Fan 1 Damper 1 Motor status:OFF(RED LED), can be used to upgrade Siemens conventional fire-alarm ON(GREEN LED),Trouble(YELLOW LED). panels to the FireFinder XLS system without requiring detector replacement. SIEMENS Industry,Inc. Building Technologies Division 1 . 4 FireFinder XLS Components--(cont.'d) Ft Each Model SCM-8 switch is fully programmable,and may be used to control speaker circuits and a wide range of general-system functions such as: Ali Call,All Evac, Warden's Page,Speaker,etc. Any number of circuits may be grouped and controlled by a single switch. Switch usages and zone groupings are assigned using the CC-2-3Card Cage-2 Slots CC-S-4Card Cage-5 Slots Zeus system software-programming software. Model CC-51 CC-2 Card Cages SCM-8 modules are mounted on a hinged panel,as a part The Models CC-51 CC-2 card cages provide the physical of the FueFinderXLS Command Console enclosure. mounting location and all wiring connection points for all fire-and-voice system options cards for the FireFinder XLS system. Model CC-5 has five(5)slots,while Model CC-2 has two(2)slots. All cards plugged into the CC-51 CC-2 card cage communicate with other FireFinder XLSmodulesviaa LCM-8-),LED Control Module common data bus.Connectors are provided on the left and LCM-8 LED Control Module right side of the CC-5 to connect a 60-pin cable for communications with the FireFinder XLS operator interface, The LED Control Module(Model LCM-8)is a FireFinder power supplies and amplifiers modules. XLS-option module that provides LED annunciation for Field wiring to devices and circuits terminates on the FireFinder XLS system activity. Each Model LCM-8 Models CC-51 CC-2 card cages.All cards designed for use contains eight(8)groups of two(2)LEDs-each of which with the Models CC-51 CC-2 route their field wiring can be assigned to desired outputs using the Zeus terminations to the'top'of the Model CC-51 CC-2 card system software-programming tool. cages. These connections are all power limited. Internal Eight(8)LEDs are dual-color capable(Red or Green 1 wiring connections distribute 24VDC to cards or high-level flashing or steady). The remaining LEDs are Amber audio signals(depending on application used)connect to flashing or steady. A space is provided for labeling of LED the bottom'of the Model CC-51 CC-2 card cages.These functions. The label slides behind a dear,protective connections are all non-power limited. membrane. Model LCM-8 dimensions are identical to Model SCM-8,and Model LCM-8 is mounted on the same All wiring connections to the Model CC-51 CC-2 card cages hinged panel,as a part of the FireFinder XLS Command are to removable terminal blocks. Terminal blocks are Console enclosure. rated for use with wire sized 12 American Wire Gauge WG)to 24AWG. Each is numbered to wiring terminations to the correct t position make on on the terminal block simple in order to reduce potential wiring errors. -ems RNI--)Remote Network Interface RNI Remote Network Interface The Remote Network Interface(Model RNI)provides a connection point for use with equipment mounted in a remote-lobby enclosure on the FireFinder XLS FACP. Model SCM-8-�Switch Control Module RNI is used to provide additional input,outputand control SCM-8 Switch Control Module features to the system remotely,via the main FACP. The Switch Control Module(Model SCM-8)is a FireFinder These additional features may include control switches XLS-option module that provides manual control to the and indicators:(Models SCM-8,LCM-8 and FCM-6), Emergency Voice Evacuation System(EVAC)or manual remote-emergency paging microphones or telephones: fire-system control. Each Model SCM-8 module provides (Models LVM,FMT),or controls used in graphic annunciators eight(8)momentary push-button switches and 16 (Models S[M16,OCM-16)or system-status display with the light-emitting diodes(LEDs)to indicate their status. ability to acknowledge alarms,silence audibles and Each switch is assigned two(2)LEDs,as well as a label reset the system(Model SSD-C REM). to indicate the switch`s programmed usage. The label Model RNI allows The Person Machine Interface to be slides behind a clear protective membrane. One set of mounted in the Model REMBOX2 or Model REMBOX4 LEDs assigned to each switch is a dual-colored LED, remote lobby enclosure. which is used to indicate what type of signal is active. SIEMENS Industry,Inc. Building Technologies Division 1 . 5 FireFinder XLS Components—(cont.'d) lkplll -...Itflltt, 1'.11111111 ' ip Ittl11 1 - - •E 117j1111 •Il 1! 1 11 Ifl• •11 Il,/8'11 PSG-12 Power Supply Charger Module PTB ►Power Termination Board PSC-12 Power Supply Charger Module PTB Power Termination Board The Power Supply Charger Module(Model PSC-12)is a Model PSC-12 comes packaged with a module called the high-current power supply that provides the FireFinder Power Termination Board(Model PTB). Model PTB is XLS primary-regulated 24VDC power to operate. Model required for operation with Model PSG12. Model PTB filters PSC-12 is rated at 12Amps(Alarm)l 5Amps(Standby),and the power from the incoming AC mains,and distributes has a built-in battery charger,capable of charging up to 100 it to the Model PSC-12 power supply and the optional Model AN batteries. Model PSC-12 is an addressable-intelligent, PSX-12 power-supply extender. microprocessor-controlled module that communicates its Model PTB has an optional connector that can be used during status to the system-operator interface. system installation,commissioning and service to provide Each Person Machine interface is then able to query the the technician with a place to plug in their laptop PC,if status of the power supply to obtain data regarding required. Model AC ADPT is an optional accessory cable system-charging current,terminal-loading information, that allows connection on one side to Model PTB,via a ground-fault conditions and more. keyed connector and on the other end directly into to the laptop's transformer. � ;,,;,,, Most laptop-computer external power transformers have removable AC power cords,which can be replaced by the optional Model AGADPT to temporarily provide an AC .q;hUSnFI ;; power source for laptop-PC usage during system ,j ii �; ji, installation,service and maintenance calls when needed. sl n: n, u..,n •11, till u Ile .n, PSX-12-4 Power Supply Extender PSX-12 Power Supply Extender The Power Supply Extender(Model PSX-12)is a high-current, auxiliary power supply that expands the main Model PSC-12 power supply and battery charger of the FireFinder XLS system with an additional 24VDC power. Model PSX-12 TSP-40A Thermal Strip Printer is rated at 12 Amps. TSP-40A Thermal Strip Printer The Thermal Strip Printer(Model TSP-40A)is designed for use with the FireFinder XLS system. Model TSP-40A acts as an event-logging device,providing a permanent 40 history report of all system activity. Model TSP-40A mounts in the FireFinder XLS Model CAB 1,Model CAB2 or Model CABS enclosure,and its printout is RPM--) Remote Printer Module visible through a window in the locked-door enclosure. RPM Remote Printer Module Printouts are automatically spooled onto take-up reel for The Remote Printer Module(Model RPM)provides a tidy,uniformed records storage. means of connecting the FireFinder XLS system to a printer,such as Model PAL-1,for creating a hard copy of system status and configuration reports. Concurrently, Model RPM provides an output port that can be configured to communicate with external systems. SIEMENS Industry,Inc. Building Technologies Division 1 . 6 FireFinderXLS Components---(cont.'d) RNI Remote Network Interface .- i t, System-Status Display MDACT Multi-Point Digital Alarm Communicator Transmitter SSD-Series System-Status Display MDACT-Multi-Point Digital Alarm The System Status Display(SSD-series model displays) Communicator Transmitter is a remote LED I LCD display that shows the local status of a FYreFinderXLS system. An LED illuminates when The Mufti-Point Digital Alarm Communicator Transmitter Alarm,Supervisory,Trouble,and Securityevents occur (Mode!MDACT)is used in FireFinderXL5 systems where point identification on the system. A(4)four-line liquid-crystal display Trouble of Alarm,Supervisory,Security and (LCD)will give details of the event in alphanumeric Trouble events is required at Central or Remote Receiving form. Stations. An intelligent RS-485 communications protocol transmits all system information to Model MDACT. The display can be toggled to display additional events. The installer selects the specific event or groups of Optional remote system control capabilities are events that are set to transmit from Model MDACT over available. phone lines to listed receiving station equipment.In Models SSD-C,SSD-GINT,and Model SSD-GREM have turn,Model MDACT can transmit point information,via three(3)additional control buttons to acknowledge the Ademco Contact ID and the SIA protocol. A mounting events,silence audible circuits,and reset the system. plate(Model MOM2-XMP),MOM-2 card cage,and an XMI Interface Card are required for installation. IIC Interface Isolation Card IIC--Interface Isolation Card The Interface Isolation Card(Model IIC)is designed to isolate network signals when used with a Model NCC ring configuration,via Model NRC. Model IIC executes CA01 3 Single Row Enclosure the aforementioned isolation by removing the backpiane network signals from each Model CC-2 card CAB7 Single Row Enclosure cage. Model IIC also provides one(1)end of CAN Model CAB 1,the smallest of the FireFinder XLS termination on each side of Model CC-2. enclosures,can house a single Model CAB-MP cabinet Models SSD-C and SSD-C INT have an integral keyswitch mounting plate for mounting card cages,power supplies that enables these control buttons to operate. Model and bulk amplifiers. Model CAB1 also has four(4) SSD-C-REM is located within a locked cabinet. mounting slots on the inner door for mounting The Person Therefore,no additional keyswitch is required for Machine Interface and Model ID-MPswitch module manual activation of the control buttons. brackets. Model CAB1 comes complete with a black back box,black inner and outer doors,a single lock and key set on the outer door,a single,installed cabinet mounting plate(Model CAB-MP),and a single,installed outer door lens plate (Model OD-LP). A red version(Model CAB1-R)is also available. Approximate size: 27"(68.6cm.)high,26"(66cm.)wide, and 8"(20.3cm.)deep. SIEMENS Industry,Inc. Building Technologies Division 1 . 7 FireFinder XLS Com pone nts—(cont.'d) CAB-MP Cabinet Mounting Plate The Model CAB-MP cabinet mounting plate provides mounting for a single row of modules in a FireFinder XLS cabinet. Four(4)module spaces are available on Model CAB-MP,which is used to mount the Model CC-5 card cage;the Model CC-2 card cage;the Model PSC 12 power supply;the Model PSX-12 power-supply extender, 3 and the Model ZAM-801180-zone amplifiers. CAB2 aTwo-Row Enclosure Enclosure Trim Kits CAB2 Two-Row Enclosure Trim kits are available for all system enclosures for semi- flush mounting applications. Model CAB1-TIC(for black The Two-Row Enclosure(Model CAB2)is the mid-sized enclosures)and the Model CAB R-TK(for red enclosures) FireFinder XLS enclosure capable of housing up to two fit inside the Models CAB1 and CAB1-R enclosures. (2)Model CAB-MP cabinet mounting plates.The inner Similarly,Models CAB2-TKand CAB-2R-TK fit inside the door has two(2)rows of four(4)mounting slots. Model CAB-2 enclosure,while Models CAB3-TK and CAR3R- The outer door has space for mounting two(2)outer door TK fit the Model CAB-3 enclosure. plates(Models OD-LP,OD-BP or OD-GP),and can be configured to open from either side. Model CAB2 consists Remote Transponders of the black Model CAB2-BB back box,the Model CAB2-BD The FireFinder XLS system can use remote transponders black inner and outer door package,and one(1)Model OD- for mounting additional modules such as amplifiers LP lens plate. The outer door has a single lock and key set without requiring a Person Machine Interface or any installed.A red version(Model CA6211)is also available,and control switches. Special doors are available for systems a CAB2-RB back box is used with Model CAB2R. using Model CAB-2 or Model CAB-3 remote transponders. Approximate size is 45"(114.3cm.) high,26"(66cm.) These doors(Models CAB2-XBD and CAB3-XBD)omit the wide,and 8"(20.3cm.)deep. unused inner door,and come complete with ventilation louvers built into the door. Model CAB2-XBD fits into Model CAB2-BB,and Model CAB3- XBD fits into Model CAB3-BB. Model CAB2-XBD and CAB3- XBD are supplied in black. Red versions(Models CAB2-XRD and CAB3-XRD)are also available. Complete box and door kits are available,Models CAB2-X and CAB3-X. CABS--�Three-Row Enclosure CAB3 Three-Row Enclosure Model CAB3,the single largest FireFinder XLS enclosure available,can house a maximum three(3) Model CAB-MP cabinet mounting plates in the enclosure, and three(3)rows of inner-door mounting slots. The outer door can be configured to open from either ID-MP-).Inner Door Mounting Plate side.Model CAB3 consists of the Model CA83-BB back ID-MP Inner Door Mounting Plate box,the Model CAB3-BD black inner and outer door The inner door mounting plate(Model ID-MP)is mounted package,and one(1)Model OD-LP lens plate. The outer on the inner door of any given model CAB enclosure. door has two(2)locks and key sets installed. A red Model ID-MP plates are used to mount switch-control version(Model CAB311)is also available. modules(Model SCM-8);LED control modules(Model Approximate size is 63"(160cm.)high,26'(66.4cm.) LCM-8),or fan-control modules(Model FCM-6). wide,and 8°(20.3cm.)deep. Four(4)mounting plates are included with each order of Model ID-MP. Each mounting plate has four(4)spaces for i is ti,: a control modules,and can hold either four(4)Model ' SCM-8 modules(one[1]control module space for each module);four(4) LCM-8(one(1]control module space f >! t t 1 r l for each module),or two(2)Model FCM-6 modules(two .s [2]module spaces for each module). ' 3 CAB-MP Cabinet Mounting Plate SIEMENS Industry,Inc. Building Technologies Division 1 . 8 FireFinder XLS Components—(cont.'d) ID-MP Inner Door Mounting Plate p Combinations are also allowed. Blanks aces in Model ID- MP can be covered using the blank-control-module plate(Model BCM). Up to four(4) Model ID-MP modules can be mounted in a single row on the inner door. OD-BP->Outer Door Blank Plate OD-BP Outer Door Blank Plate The Outer Door Blank Plate(Model OD-BP)entirely covers an unused row of a XLS system cabinet,and is mounted on the outer door. One(1)blank plate is included with each order of Model OD-BP. ID-SP-4 Inner Door Blank Single Plate ID-SP Inner Door, Blank Single Plate The inner door,blank single plate(Model ID-SP)is used to cover any single-module blank spaces within the inner OD-GP->Outer Door Grill Plate door where no Person Machine Interface or Model ID- OD-GP Outer Door Grill Plate MP is being used. Up to four(4)Model ID-SP modules The Outer Door Grill Plate(Model OD-GP)also covers an can be mounted in a single row on the inner door. Two entire row on the outer door of a system cabinet,but has (2)blank plates are included with each order of Model 113- four(4)rows of ventilation louvers on it. Model OD-GP is SP. mounted in front of system bulk amplifiers,card amplifiers,or other modules that generate heat. Using Model OD-GP will permit airflow across these modules to aid in heat dissipation. One(1)grill plate is included with each order of Model OG-GP. Remote System Enclosures Models REMBOX2 and REMBOX4 are FireFinder AS BCM->Blank Control Module Plate system enclosures that are used for remotely mounting BCM Blank Control-Module Plate inner-door modules,such as: Person Machine Interfaces; Model BCM plates can be mounted on a single ID-MP. switch modules(Model SCM series);Live Voice Modules Four(4)blank module plates are included with each (Model LVM),and Firefighters'Master Telephone(Model order of Model BCM. FMT)modules. Models REMBOX2 and REMBOX4 are thinner than regular Model CAB-series of enclosures—just 5"(12.7cm.)deep overall,and are perfect for mounting in limited-space areas (e.g.—office-complex lobbies or behind a receptionists •yam - ,:3`:,..L desk). No card cages,power supplies or bulk amplifiers can be OD-LP Outer Door Lens Plate mounted in a given Model REMBOX-series enclosure due OD-LP Outer Door Lens Plate to their smaller depth. However,Person Machine Interfaces and some modules(e.g. --the remote network The Outer Door Lens Plate(Model OD-LP)is a clear plastic interface module[Model RNI];the output control module lens plate mounted on the outer door of a system [Model OCM-161,and the supervised input module cabinet. Model OD-LP is used to allow operators to see [Mode[SIM-161)can be mounted in a given Model the system interface and controls mounted on the inner REMBOX-series enclosure. door,but restricts access to unauthorized users. The plate covers an entire row on the outer door.A single lens Due to the depth of Models LVM and FMT,no Model OCM- plate is included with each order of Model OD-LP. 16 or Model SIM-16 modules can be used simultaneously with Model LVM or Model FMT. Model REMBOX2 and Model REMBOX4 are designed for flush mounting with no trim kit required. Both enclosures also come with a clear lens plate on the cover. SIEMENS Industry,Inc. Building Technologies Division 1 . 9 FireFinder XLS Components—(cont.'d) Ll REMBOX2>Two-Module Remote Enclosures XLS-MSE2-ADPT Enclosure Adapter REMBOX2 Two Module Remote Enclosures XLS-MSE2/R-ADPT—XIS MSE-2/11 Enclosure Adapter Model REMBOX2 has two(2)inner-door module spaces, Model XLS-MSE2-ADPT,which must be used in conjunction with Model CAB-MP,is an adapter that allows FireFinder and can hold a single Person Machine Interface,up to two XLS cards to be mounted in older-generation MXL Model (2)switch module brackets and one(1)Model LVM. MSE-2 small black enclosures. Combinations are also allowed. Model XLS-MSE2R-ADPT,which must be used in Model REMBOX2 can also mount a single RNI remote conjunction with Model CAB-MP,is an adapter that allows network interface on a bracket included in the backbox. A FireFinder XLS cards to be mounted in older-generation bracket,known as Model REMBOX2-MP,can be used to MXL Model MSE-211 small red enclosures. mount up to four(4) Model OCM-16 output control modules or SIM-16 supervised input modules. Model REMBOX2-MP must be purchased separately. _ Approximate size of Model REMBOX2 is 14-112"(36.8cm.) wide, 18-112"(47cm.)high and 5"(12.7cm.)deep. XLS-MME3-ADPT-4Enclosure Adapters XLS-MME3/R-ADPT—XLS MME-3/R or MBR-2 Enclosure Adapters Model XLS-MME3-ADPT,which must be used in conjunction with Model CAB-MP,is an adapter that allows FireFinder XLS cards to be mounted in older-generation REMBOX4-4 Four-Module Remote Enclosures MXL Model MME-3 or Model MBR-2 medium black REMBOX4 Four-Module Remote Enclosures enclosures. Model REMBOX4 has space for mounting four(4)inner-door Model XLS-MME3R-ADPT,which must be used in modules. Any combination of A Person Machine Interface conjunction with Model CAB-MP,is an adapter that allows (two-module spaces);switch module brackets;Model FireFinder XLS cards to be mounted in older-generation LVM,or Model FMT(one-module space each)can be MXL Model MME-3R medium red enclosures. used. Unused module spaces can be covered with Model - ID-SP blank plates. Model REMBOX4 can also mount a , single,remote network interface(Model RNI)on aJ bracket included in the backbox. - A bracket known as Model REMBOX4-MP can be used to mount up to eight(8)output control modules(Model OCM- - 16)or supervised input modules(SIM-16). Approximate size of Model REMBOX4 is 24"(61cm.) XLS-MLE6-ADPT-aEnclosureAdapter wide, 18-112"(47cm.) high and 5"(12.7cm.)deep. XLS-MLE6/R-ADPT—XLS MLE-6111 Enclosure Adapter Model REMBOX4-MP must be purchased separately. Model XLS-MLE6-ADPT,which must be used in conjunction with Model CAB-MP,is an adapter that allows FireFinder XLS cards to be mounted in older- generation MXL Model MLE-6 large black enclosures. Model XLS-MLE6R-ADPT,which must be used in conjunction with Model CAB-MP,is an adapter that allows FireFinder XLS cards to be mounted in older- generation MXL MLE-611 large red enclosures. SIEMENS Industry,Inc. Building Technologies Division 1 . 10 FireFinder XLS Com pone nts-(cont.'d) art M 1: XLS-MSE3-AlPT),Enclosure Adapters XLS-MSE3/R-ADPT—XLS MSE-3L/R or MSE-3M/R VPM-MP-4 VESDA Mounting Plate Enclosure Adapters VPM,VESDA-HLI-KIT and VMP-MP— Model XLS-MSE3-ADPT is an adapter that allows VESDA Interface Equipment FireFinder XLS cards to be mounted in older- The Very Early Smoke Detection Aspiration(VESDA) generation MXL-IQ Model MSE-3L or Model MSE-3M Peripheral Module(Model VPM)and the VESDA High- black enclosure. Level Interface Kit(Model VESDAHLI-KIT)are optional Model XLS-MSE3R-ADPT is an adapter that allows FireFinder XLS modules that work in conjunction to FireFinder XLS cards to be mounted in older- provide bi-directional communication between the generation MXL-IQ Model MSE-3LR or Model MSE- FireFinder XLS FACP and multiple VESDA detection 3MR red enclosure. networks for the following types of VESDA detectors: ■ LaserCOMPACr • LaserFoCUS • LaserPLUS • LaserSCANNER Model VPM allows each FireFinder XLS FACP to XLS-RCCI-ADPT—rEnclosureAdapter annunciate'Alert,'Action;'Fire 1,'and'Fire X levels, as well as provide'fa u Its'from any zone on a XLS-RCC-1-ADPT—XLS RCC-1 Enclosure Adapter connected VESDA network. Model XLS-RCC1-ADPT is an adapter that allows the The VPM Mounting plate(Model VPM-MP)allows FireFinder XLS Model SSDI-C series remote annunciator mounting one(1)Model VPM and two(2)of Model to be mounted in older-generation Model RCC-1 surface- VESDAHLi-KIT inside a standard FireFinder XLS Model mount enclosure. CAB1,Model CAB2 or Model CA63 enclosure. Model VPM-MP utilizes two(2)module spaces on a single row of each enclosure. XLS-RCCI3F-ADPT Enclosure Adapters limit XLS-RCC13F/R-ADPT—XLS RCC-1 FIR or RCC-3F >DiIR C900V2— aler-Capture Ethernet Module Enclosure Adapters Model XLS-RCCI3F-ADPT is an adapter that allows the C900V2—Dialer-Capture Ethernet Module FireFinder XLS Model SSDI-C series remote annunciator The Dialer-Capture Ethernet Module(Model C900V2) to be mounted in older-generation Model RCC-1 F or links the data output of Model MDACT from the Model RCC-3F black,flush-mount enclosure. FireFinder XLS FACP to an Ethernet connection—on a Model XLS-RCCI3FR-ADPT is an adapter that allows the local-area network(LAN)or wide-area network(WAN)— Model SSDI-C series to be mounted in older-generation for communication to a central station over the Internet. RCC-1FR and RCC-3FR,red flush-mount enclosure. Model C900V2 also allows Model MDACT to be optionally linked to the public switched telephone network(PSTN)for communication to a central station over telephone lines. 4P ............. Temperature and Humidity Range VPM-+VESDA VESDA-HLr-KIT-3 VESDA High- FireFinder XLS components are®U L 864 9"'Edition Interface Equipment Level Interface Kit Listed for indoor dry locations within a temperature range of 120+I-3°F(49+1-2°C)to 32+1-30F(0+1- 2°C)and a relative-humidity range of 93+1-2%at a temperature of 90+1-3°F(32+1-20C). SIEMENS Industry,Inc. Building Technologies Division 1 . 1 Details for Ordering Details for Ordering -- (continued) Part Model Description Model part` ;Descnption. 0. Nuinber Number AC-ADPT 500-633992 Technician La to Power connector NIC-C 500-033240 Network interface Card BCM 500-033320 Blank control module plate, NRC S54430-A2-A1 Network Ring Card: 2^d Generation four(4per package] OD-BP 500.633017 Outer Door Blank Plate C900V2 S54430-C13-A2 Dialer-Ca tore Ethemet Module OD-BP-R 5OD-634919 Outer Door Blank Plate,red CAB-1 500-633007 Complete Sin le-RowCabinet,black OD-GP-R 500-634920 Outer DoorGd1l Plate,red CAB-1R 500-633728 Complete Sin le-RowCabinet,red OD-GP 500-633018 Outer Door Grill Plate CA81-TK 500-633013 Single-Row Trim-kit Cabinet,black OD-LP 500-633016 Outer Door Lens Plate CAB R-TK 500-633729 Sin le-Row Trim-kit Cabinet,red PAL-i 500-692407 VUL Listed Parallel Printer CA132-BB 500-633009 (2)Two-Rote Back Box,black — 599-050092 PMI and GPMI CA92-AB 500-634941 2 Tivo-Row Back Box,red PMI-2 554430-Cl-Al Person Machine Interface 2 CAB2-BD 500.633008 2 Two-Row Inner&Outer Door set,black PMI-Z-SPAWAR S54430L10-Al Spanish Overlay for Model PM 1-2 CA82-RD 500-633755 2 Two-Row inner&Outer Door set,red PMI.2-PORT-LAB 554430-C11-Al Portuguese Overlay for Model PMI-2 CAB2-TK 500-633014 (2)Two-Row Trim-kit Cabinet,black Phu -FRENCH-L 554430 C12-A7 Canadian[French]Overlayfor Mode}PMi-2 CAB2R-TK 500-633753 2 Two Row Trim Idt Cabinet red Power supply with battery charger CAB2-XBD 500-633768 CAB2 Transponder Door PSC-12 500-033340 12A@ 24VDC Complete CA82 tvl Transponder Door CAB2-X 599-034252 no inner door PSX-12 500-034120 Power supply extender Medium-Enclosure Transponder Door,red Power termination CAB2-XRD 500-633792 PTB 500-033390 Power termination board mounts to Model CA92-RBIREMBOX2 500-633772 (2)Ttvo-module remote lobby enclosure,black CAB3-BB 500-633011 (3)Alree-Row Back Box,black (2)Ttvo-module remote CABS-RB 500-634942 3 Three-Row Back Box,red REMBOUR 500-650612 lobby enclosure,red CABS-BD 500.633010 3)Three-Row Inner&Outer Doorset black Mounting plate for Models CA83-RD 500-633757 3 Three-row Inner&Outer Door set,red REMBOX2-MP 500-634211 OCM-1 6 1 SIM-1 6 in Model REMBOX2 CABS-TK 500-633015 (3)Three-Row Trim-kit Cabinet,black REMBOX4 500.633914 4 Four-module remote lobb enclosure,black CAB3R-TK 500-633754 3 Three-Row Trim-kit Cabinet,red Mounting plate for Models OCM-161 CABS-XBD 500-633769 CABS Transponder Door REMBOX4-MP 500-634212 SIM-16 in Model REMBOX4 CABS-X 599-034253 Complete CA93 wl Transponder Door REMBOX411 500-650613 (4)Four-module remote lobby enclosure,red noinnerdoor) RNI 5OD-033420 Remote network interface module CA83-XRD 500 633793 Large-Enclosure Transponder Door,red RPM 5OD-033270 Remote printer module [mounts to Model CA133-118] SCM-8 500-033040 Switch module,eight(8)switches CAB-MP 500.633012 Back Box Module Mounting Plate SIM-16 1 500-034060 Supervised in utmodule CAN Cable SSD 500-034740 System-status display 3 t.L$cm.)LeLgth required for CCL 599-634214 SCMILCMIFOA modules from Models CC-5ICC-2 SSD-C 500-648733 System-status dis to with control Inner Doors and from Roty-to-Rotvon#.Wei CAB-series SSD INT 500-034740 System-statusdisplaywith n Inner Doors muld-lingual overlays CC-2 500-633440 Two(2)Slot Card Cage SSD-C-INT 500-034750 System-status display with control CC-5 500-633037 Five(5)slot Card Cage- and multi-lin ual overlays CDC-4 500-034200 Conventional Detector Card SSD-C-REM 500.634773 System-status displaywith control for COM-BRK S54430-B7-A1 Communications Bracket I remote lobby enclosure CRCA 500-033250 Controllable Relay Card TSP-40A 500-634933 Thermal-strip printer C58 500-033130 CAN Sounder Board TSP-X8 500-849949 Brackets for thermal-strip inter DCT-P 500-699291 MDACTPro rammer TSP XC 500-849950 Cables for thermal-strip printer DLC 500-033090 Device Loop Card VPM S54430-F93-A2 VESDA Peripheral Module FCM-6 500-033140 Fan-Control-Module Switches VPM-MP S54430-F95-A2 Mounting Plate for VESDA (oil,OFF,AUTO) Peripheral Module GPM[-UK 500 650066 Software-Upgrade Kit for PMI(vers.1) VESDA-HLFIaT S54430-F99-A2 VESDA High-Level Interface Kit /oallw iobalfunctionaG XLS-MLE6-ADPT S54430-C9-Al MLE-6 enclosure adapter for XLS,black GPMI-2 554430-C3-Al Model PMI-2(with GPlft-HPI-KEY) Xt_sMLE6R-ADPT S54430-C9-A2 MLE-6R enclosure adapter for XLS,red HCP 500-034860 Intelligent Control Point Module MME-3 and MBA-2 enclosure adapters for HUM 500-033170 Line-Isolator Module XLSMME3-ADPT 554430-C8-Al PfrePinder XLS,black ID-MP 500-633027 Inner-Door Enclosure Mounting Plate, XLS-MME311-ADPT 554430-Ce-A2 MME-3R enclosure adapter for XLS,red [four(4)per package] XIS-MSE2-ADPT S54430-C7-A1 MSE-2 enclosure adapter for XLS,black ID-SP 500-633028 Single-Module Inner-Door Enclosu re XL5415E211-ADPT S54430-C7-A2 MSE-2R enclosure adapter for XLS,red Mounting Plate,[tn-o(2)perpackage] MXL-IQ MSE-3L and MSE-3M enclosure adapters IIC 500-850328 Interface isolation Card XLSMSF3-ADPT S54430-C14-Al for XLS,black LCM 8 500-033100 LED Annunciator Module XLS -ADPT 554430-C14-A2 MXL-IQ MSE-3LR&MSE-3MR enclosure [eight(8)LED sets adapters for XLS,red MDACT 500-699254 Multi-Point Digital-Alarm XLS-RCCl-ADPT SS4430-Z14-A1 RCC-tenclosureadapter for XLS-SSD black Communication Transmitter xiSRCC13F-ADPT 554430-713-Al RCC-1F&RCC-3F enclosure adapters,black MLC S54431-B4-A1 MXLAddressable-Device Line Card LSRCC13FR-ADP 554430-Z13-A2 RCC-1FR&RCC-3FRendosureadapters,red MOM2-XMP 500-634822 Mountinq Plate for Model MOM-2 ZIC-2C 500-648671 (2)Two-channel adaptercard, MOM-2 500 892766 MXL Module Card Cage via Model ZIC-88) [one(1)full slot] ZiCAA 500-033050 (4)Four-circuit zone indicating card ZIC-8B 500-648670 (8)Eight-circuit zone Indicating card No•tics: This marketing data street is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 1577 North Service Road SIEMENS Industry,Inc. Florham Park,Ni 07932 East Oakville,Ontario April 2015 Building Technologies Division Tel:(973)593-2600 Isis-fs► L6H OH61 Canada supersedes sheet dated 112015 FAX:(908)547-6877 Printed In U.S A. Tel:[9051465-8000 Lae..1s1 1 . 12 URL•rnvtv.usa.Slemens.contfFire URL:vmnv.Siemens.CA SIEMENS Data Sheet Fire Safety Products FireFinder" XLS Fire Alarm Enclosures & Equipment Models: CAB1,CAB-BATT,CAB-BATT-R,CAB2-BB,CAB2-BD,CAB2-X, CAB2-XBD,CAB2-XRD, CAB3-BB, CAB3-BD,CAB3-X,CAB3-XBD,CAB3-XRD,CAB-MP,ID-MP,ID-SP, BCM,OD-LP, OD-BP,OD-GP, REMBOX2, REMBOX4,XLS-MLE6-ADPT,XLS-MME3-ADPT,XLS-MSE2-ADPT, XLS-MSE3-ADPT and XLS-RCC13F-ADPT ARCHITECT AND ENGINEER SPECIFICATIONS • One(1),two(2),and(3)three-row enclosures for the FireFinder XLS system • Blank plates for inner and outer doors x • Lens and grill plates for outer door • SUL 864 gth Edition Listed and GULC Listed; FM (9010),CSFM (w7165-0067:0222)& NYCFD ("6160)Approved CAB1 CAB2 CA133 Product Overview Enclosures, Doors & Plates The FireFinder XLS fire alarm enclosures (Models CAB1 —Single-Row Enclosure CAB1, CAB2, and CAB3) and their accessories Model CAB1, the smallest of the FireFinder XLS provide a complete set of hardware for mounting enclosures, can house a single Model CAB-MP all FireFinder XLS main system and remote cabinet mounting plate for mounting card cages, transponder cards and modules. power supplies and bulk amplifiers. Model CAB1 The hardware allows the FireFinder XLS system to also has four (4) mounting slots on the inner door for be configured for a wide variety of applications, mounting a Person Machine Interface and Model ID- and allows for future system upgrades. Included in MP switch module brackets. the enclosure series are backbox and door sets, Model CAB1 comes complete with a black back box, removable mounting plates and clear lenses, with black inner and outer doors, a single lock and louvered ventilation grill plates, and blank plates for key set on the outer door, and a single OD-LP outer use with the enclosure doors. door lens plate (installed). A red version (Model All enclosures come with ground straps for the inner CA131-R) is also available. Approximate size is 27" and outer doors, shield termination lugs, (68.6cm.) high, 26" (66cm.) wide, and 8" (20.3cm.) grounding lugs, and tie wrap lances for securing deep. wire. All enclosures can also mount system backup batteries up to 31 AH in capacity. FireFinder® XLS Enclosures 6327 SIEMENS Industry,Inc. 1 . 13 Building Technologies Division Enclosures, Doors & Plates —(cont.'d) Enclosure Trim Kits Trim kits are available for all system enclosures for semi-flush mounting applications. Model CAB1-TK(for black enclosures) and Model CAB1 R-TK (for red enclosures) fit Models CA131 and CA61-11 enclosures. Similarly, Models CAB2-TK and CAB2R-TK fit the Model CA132 enclosure, and Models CAB3-TK and CAB3R-TK CA61 Enclosure fit the Model CAB-3 enclosure. CAB2—Two-Row Enclosure Remote Transponder Doors Model CAB2 is the mid-sized FireFinder XLS enclosure The FireFinder XLS system can use remote transpon- ders for mounting additional modules such as capable of housing a maximum two (2) Model CAB-MP cabinet mounting plates. The inner door has two (2) amplifiers without requiring a Person Machine rows of four (4) mounting slots. The outer door has Interface or any control switches. Special doors are space for mounting two(2)outer door plates(Models OD- available for systems using Model CAB2 or Model CAB3 LP, OD-BP or OD-GP). The outer door can be configured remote transponders. Models CAB2-XBD and CA63- to open from either side. Model CA132 consists of the XBD omit the unused inner door and come complete Model CA132-13113 back box;the Model CAB2-BD black inner with ventilation louvers built into the door. Model and outer door package, and one (1) Model OD-LP lens CAB2-XBD comes in black, and fits on Model CAB2-13B. plate. The outer door has a single lock and key set Model CAB3-XBD also comes in black, and fits on installed. Red doors are available in Model CA132-RD. Model CA133-1313. Additional door mounting plates must be ordered Remote transponder door are also orderable in red: separately. Approximate size is 45" (114.3cm.) high, 26" Models CAB2-XRD and CAB3-XRD. Complete box and (66cm.)wide,and 8"(20.3cm.)deep. door kits are available as Models CA132-X and CAB3-X. CAB2 Enclosure CAB3 —Three-Row Enclosure Model CAB3, the largest single FireFinder XLS enclosure CAB2-XBD Door CA83-XBD Door available, can house a maximum three (3) Model CAB-MP OD-GP—Outer-Door Grill Plate cabinet mounting plates in the enclosure, and three (3) Model OD-GP also covers an entire row on the outer rows of inner door mounting slots. The outer door can door of a system cabinet, but has four rows of be configured to open from either side. Model CA133 ventilation louvers on it. Model OD-GP is mounted consists of the Model CAB3-1313 back box; the Model CA133- in front of system bulk amplifiers, card amplifiers, BD black inner and outer door package, and one(1) Model or other modules that generate heat. Using Model OD-LP lens plate. The outer door has two (2) locks and OD-GP will permit airflow across these modules to aid key sets installed. Red doors are available via Model in heat dissipation. A single grill plate is included with CA133-RD. each Model OG-GP. Additional door mounting plates must be ordered separately. Approximate size is 63" (160cm.) high, 26" (66cm.)wide,and 8"(20.3cm.)deep. OD-GP Remote System Enclosures Models REMBOX2 and REMBOX4 are FireFinder XLS system enclosures that are used for remotely mounting inner-door modules, such as the Person Machine Interface, switch modules, live-voice CAB3 Enclosure modules, and Model FMTs. SIEMENS Industry, Inc. 1 . 14 Building Technologies Division Enclosures, Doors & Plates —(cont.°d) II REMBOX4 are FireFinder XLS system are thinner than the regular CAB enclosures Qust 5" deep overall), and are perfect for mounting in places where space is limited(such as lobbies or behind a receptionist's desk). Due to their smaller depth, no card cages, power supplies or bulk amplifiers can be mounted in a REMBOX. However, modules such as the Remote Network Interface Module REMBOX4 REMBOX4 (Model RNI); the Output-Control Module (Model OC -16) (with doors closed) (with doors open) and the Supervised Input Module (Model SIM-16) can a Note:A red,(4)four-module remote lobby enclosure mounted in a REMBOX. Due to the depth of the live-voic (Model REMBOX4R)is also available. module and the firefighters' master telephone, no Model CAB-MP—Cabinet Mounting Plate OCM-16 or Model SIM-16 modules can be used The cabinet mounting plate (Model CAB-MP) provides simultaneously with Model LVM or Model FMT. mounting for a single row of modules in a FireFinder Both Models REMBOX2 and REMBOX4 are designed for XLS cabinet. Four (4)-module spaces are available on flush mounting with no trim kit required. Both enclosures Model CAB-MP. Model CAB-MP is used to mount the Model also come with a clear lens plate on the cover. CC-5 card cage, the Model CC-2 card cage, the Model PSC- 12 power supply, the Model PSX-12 power supply REMBOX2—Two-Module Remote Enclosure extender,and the Model ZAM-801 180 zone amplifiers. Model REMBOX2 has two (2) inner door module spaces, and can hold a single Model PMI-2, up to two (2) s " switch module brackets, one (1) Model LVM live voice ram , R module. Combinations are also allowed. Model}" REMBOX2 can also mount a single Model RNI on a t bracket included in the backbox. A bracket (Model REMBOX2-MP) can be used to mount up to four (4) Model .x. OCM-16s or Model SIM-16 enclosures. Model REMBOX2- MP must be purchased separately. Approximate size of CAB-MP Model REMBOX2 is 14-112" (36.8cm.) wide, 18-112" ID-MP—Inner Door Mounting Plate (47cm.) high and 5"(12.7cm.)deep. The inner door mounting plate(Model ID-MP) is mounted on the inner door of a CAB enclosure. Model ID-MP plates are used to mount Model SCM-8 switch control modules; Model LCM-8 LED control modules,or with Model FCM-6. Four (4) mounting plates are included in each Model ID- MP. Each mounting plate has four (4) spaces for control modules, and can hold either four (4) Model SCM-8 modules {one [1] control module space each}; four (4) 10 REMBOX2 REMBOX2 Model LCM-8 modules {one [1] control module space (with doors closed) (with doors open) each); or two (2) Model FCM-6 modules {two [2] module Note:A red,(2)two-module remote lobby enclosure spaces each}. (Model REMBOX211)is also available. Combinations are also allowed. Blank spaces in Model REMBOX4— Four-Module Remote Enclosures ID-MP can be covered using the Model BCM blank Model REMBOX4 has space for mounting four(4)inner door control module plate. A maximum four(4) Model modules. Any combination of Model PMI-2 (two- ID-MP plates can be mounted in a single row on the inner door. module spaces),switch module brackets, Model LVM or Model FMT(one-module space each) can be used. Unused module spaces can be covered with Model ID-SP blank plates. Model REMBOX4 can also mount to a single Model RNI on a bracket included in the backbox. A bracket known as Model REMBOX4-MP can be used to mount a maximum eight(8) Model OCM-16s or Model SIM-16s. Model REMBOX4-MP must be purchased separately. Approximate size of Model REMBOX4 is 24" (61cm.) wide, 18-112" (47cm.) high and 5" (12.7cm.) deep. ID-MP SIEMENS Industry,Inc. Building Technologies Division 1 . 15 Enclosures, Doors & Plates —(cont.'d) OD-BP—Outer-Door Blank Plate ID-SP—Inner-Door Single Blank Plate The Outer Door Blank Plate (Model OD-BP) is used to Model ID-SP is used to cover any single module blank cover an entire row of a XLS system cabinet. Model spaces on the inner door not used to mount the Person OD-BP is mounted when no module is used in that Machine Interface or one (1) Model ID-MP. Up to four location. Model OD-BP is mounted on the outer door, (4) Model ID-SP plates can be mounted in a single row and one (1) blank plate is included with each order. on the inner door.Two(2) blank plates are included in each Model ID-SP. OD-BP XLS-MSE2/R-ADPT—XLS MSE-2/11 Enclosure Adapter Model XLS-MSE2-ADPT, which must be used in conjunction with Model CAB-MP, is an adapter that ID-SP allows FireFinder XLS cards to be mounted in older- XDACT-ASSY—XDACT Assembly generation MXL Model MSE-2 small black enclosures. The XDACT Assembly (Model XDACT-ASSY) is the blank Model XLS-MSE2R-ADPT, which must be used in plate used for holding the optional Digital Alarm conjunction with Model CAB-MP, is an adapter that Communication Transmitter (DACT), Model FCA2015- allows FireFinder XLS cards to be mounted in older- U1. The XDACT assembly vertically mounts on the back, generation MXL Model MSE-2R small red enclosures. left-hand side of an inner door of any type of FireFinder panel, adjacent to a Person Machine Interface(PMI). [J 0 IR XLS-MSE2-ADPT XLS-MME3/R-ADPT—XLS MME-3/11 or MBR-2 Enclosure Adapters XDACT-ASSY Model XLS-MME3-ADPT, which must be used in BCM —Blank Control Module plate conjunction with Model CAB-MP, is an adapter that Model BCM is used on Model ID-MP to cover any allows FireFinder XLS cards to be mounted in older- blank areas where control modules are not used. A generation MXL Model MME-3 or Model MBR-2 medium maximum four(4)Model BCM plates can be mounted on black enclosures. a single Model ID-MP. Four(4),blank-module plates are Model XLS-MME3R-ADPT, which must be used in included in each Model BCM. conjunction with Model CAB-MP, is an adapter that allows FireFinder XLS cards to be mounted in older- generation MXL Model MME-311 medium red enclosures. BCM OD-LP—Outer Door Lens Plate Model OD-LP is a clear plastic lens plate mounted on the outer door of a system cabinet. Model OD-LP is used to allow operators to see the system interface and controls XLS-MME3-ADPT mounted on the inner door, but restricts access to unauthorized users. Model OD-LP covers an entire row on the outer door. A single lens plate is included with each Model OD-LP. SIEMENS Industry,Inc.• 16 Building Technologies Division Enclosures, Doors & Plates— (cont.'d) XLS-MLE6/R-ADPT—XLS MLE-6/11 Enclosure Adapter XLS-RCC-1-ADPT—XLS RCC-1 Enclosure Adapter Model XLS-MLE6-ADPT, which must be used in Model XLS-RCC1-ADPT is an adapter that allows the conjunction with Model CAB-MP, is an adapter that FireFinder XLS Model SSD/-C series remote annunciator allows FireFinder XLS cards to be mounted in older- to be mounted in the older generation Model RCC-1 generation MXL Model MLE-6 large black enclosures. surface-mount enclosure. Model XLS-MLE6R-ADPT, which must be used in 1:39 conjunction with Model CAB-MP, is an adapter that allows FireFinder XLS cards to be mounted in older- generation MXL MLE-6R large red enclosures. XLS-RCCI-ADPT XLS-RCC13F/R-ADPT—XLS RCC-1 F/R or RCC-3F/R Enclosure Adapters Model XLS-RCC13F-ADPT is an adapter that allows the FireFinder XLS Model SSDI-C series remote annunciator XLS-MLE6-ADPT to be mounted in the older generation Model RCC-1 F or XLS-MSE3/R-ADPT—XLS MSE-31JR or MSE-3M/R Model RCC-3F black,flush-mount enclosure. Enclosure Adapters Model XLS-RCC13FR-ADPT is an adapter that allows the Model XLS-MSE3-ADPT is an adapter that allows Model SSDI-C series to be mounted in the older FireFinder XLS cards to be mounted in the older generation RCC-1 FR(red)and RCC-3FR(red)flush-mount generation MXL-IQ Model MSE-3L or Model MSE-3M enclosure. black enclosure. Model XLS-MSE3R-ADPT is an adapter that allows FireFinder XLS cards to be mounted in the older generation MXL-IQ Model MSE-3LR or Model MSE-3MR red enclosure. 1:3: XLS-RCC13F-ADPT Q1J1q Temperature and Humidity Range XLS-MSE3-ADPT Products are®UL 864 9th Edition listed for indoor/dry locations within a temperature range of 120+1-3°F (49+/_2°C)to 32+/-30F(0+/_2°C)and a relative humidity of 93+/_2%at a temperature of 90+/_30F(32+/_20C). SIEMENS Industry,Inc. Building Technologies Division 1 . 17 Details for Ordering Model Part Number Description Model Number Part Description Blank control module plate, Inner-door enclosure mounting plate, BCM 500-033320 four[4]per package ID MP 500-633027 four[4]per package CAB-1 500-633007 Complete single-row cabinet,black ID-SP 500-633028 Single-module inner-door enclosure CAB-1 R 500-633728 Complete single-row cabinet,red mounting plate[two(2)per package] CAB1-TK 500-633013 Single-row trim-kit cabinet,black OD-BP 500-633017 Outer door blank plate CA81 R-TK 500-633729 Single-row trim-kit cabinet,red OD-BP-R 500-634919 Outer door blank plate,red CAB2-BB 500-633009 (2)Two-row back box,black OD-GP 500-633018 Outer door grill plate CAB2-RB 500-634941 (2)Two-row back box,red OD-GP-R 500-634920 Outer door grill plate,red CAB2-BD 500-633008 2)Two-row inner&outer door set,black OD-LP 500-633016 Outer door lens plate CAB2-RD 500-633755 (2)Two-row inner&outer door set,red REMBOX2 500-633772 (2)Two-module remote lobby enclosure,black CAB2-TK 500-633014 (2)Two-row trim-kit cabinet,black REMBOX2R 500-650612 (2)Two-module remote lobby enclosure,red CAB2R-TK 500-633753 (2)Two-row trim-kit cabinet,red REMBOX2 MP 500 634211 Mounting plate for Models OCM-16/ CAB2-XBD 500-633768 CAB2 transponder door,black SIM-16 in Model REMBOX2 CAB2-XRD 500-633792 CAB2 transponder door,red REMBOX4 500-633914 (4)Four-module remote lobby enclosure,black Complete CAB2 w/transponder door REMBOX4R 500-650613 (4)Four-module remote lobby enclosure,red CAB2-X 599-034252 [no inner door] REMBOX4-MP 500-634212 Mounting plate for Models OCM-16 - 1 CAB3-BB 500-633011 (3)Three-row back box,black SIM-16 in Model REMBOX4 CAB3-RB 500-634942 (3)Three-row back box,red XDACT-ASSY 554430-A5-A7 XDACT Assembly(mounts to Inner-door) CAB3-BD 500-633010 (3)Three-row inner&outer door set,black XLS-MLE6-ADPT 554430-C9-A1 MLE-6 enclosure adapter for XLS,black CAB3-RD 500-633757 (3)Three-row inner&outer door set,red XLS-MLE6R-ADPT 554430-C9-A2 MLE-6R enclosure adapter for XLS,red CAB3-TK 500-633015 (3)Three-row trim-kit cabinet,black MME-3 and MBR-2 enclosure adapters for CAB3R-TK 500-633754 (3)Three-row trim-kit cabinet,red XIS-MME3-ADPT 554430-C8-A1 FireFinder XLS,black CAB3-XBD 500-633769 CAB3 transponder door,black XLS-MME3R-ADPT 554430-C8-A2 MME-3R enclosure adapter for XLS,red CAB3-XRD 500-633793 CAB3 transponder door,red XIS-MSE2-ADPT 554430-0-A1 MSE-2 enclosure adapter for XLS,black Complete CAB3 w/transponder door XLS-MSE2R-ADPT 554430-0-A2 MSE-2R enclosure adapter for XLS,red CAB3-X 599-034253 [no inner door] Field-mounted enclosure for 100AH XLS-MSE3-ADPT 554430-C14-A1 MXL-IQ MSE-3L and MSE-3M enclosure CAB-BATT 500-633917 batteries,black adapters for XLS,black Field-mounted enclosure for 100AH XLS-MSE3R-ADPT 554430-C14-A MXL-IQ MSE-3LR&MSE-3MR enclosure CAB-BATT-R 500-634925 batteries,red I adapters for XLS,red XLS-RCCI-ADPT 554430-Z14-A1 RCC-1 enclosure adapter,black XLS-RCCI3F-ADPT I S54430-Z13-At RCC-1 F&RCC-3F enclosure adapters,black XLS-RCCI3FR-ADPT S54430-Z13-A2 RCC-1 FR&RCC-3FR enclosure adapters,red Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each products installation instructions. Fire Safety Fire Safety 8 Fernwood Road 1577 North Service Road SIEMENS Industry,Inc. Florham Park,NJ 07932 East Oakville,Ontario October 2016 Building Technologies Division Tel:(973)593-2600 (SII-FS) L6H OH6/Canada supersedes sheet dated 1/2015 l l O FAX:(908)547-6877 Printed in U.S.A. Tel:[905]465-8000 (Rev.11) URL:www.USA.SIam*ns,com/FIRE URL:www.Siemens.CA SIEMENS Data Sheet Fire Safety&Security Products FireFindere XLS Person Machine Interface 2 Model PMI-2 ARCHITECT AND ENGINEER SPECIFICATIONS • Main-operator interface • User-prompted lighted, large buttons for system control,operating sequence • Global annunciation and control capability • Partial-system disable, light-emitting diode(LED) • Alarm, Trouble,Supervisory, and Security system-status LEDs • Audible Status LEDs(ON and Silenced) *, • Integrated slots for switch-control(Model SCM-8) fir. and LED-control(Model LCM-8) modules • Large, 6-inch(15.2 cm)color display • Co ntext-sensitive'Help'menu • Navigation buttons and'More Info' • Touch-screen driven,system-control menus XLS Person Machine Interface 2 • 40 software-prog ram mable'User Macro'switches (Model PMI-2) • ®UL 864 9th Edition Listed &OULC Listed; FM, CSFM and NYCFD Approved Product Overview Specifications The Person Machine Interface(Model PMI-2) is the Model PMI-2 contains a large,6"(15.2 cm)(1200—x— primary user interface for the FireFinder fire alarm 800 pixel)color liquid-crystal display(LCD), touch control panel(FACP). Model PMI-2 also serves as screen and LEDs for displaying system status. both operator interface and central microprocessor An audible sounds when there are for each XLS system. From each Model PMI-2,the end- 'unacknowledged'events on Model PMI-2. The user can Acknowledge events;control the system display is surrounded by keys that are used to control notification appliance circuits(NACs),and reset the the displayed information and to navigate through system. Detailed information about the nature these screens. Keys are also provided to obtain'Help' and location of the events can also be displayed. and to enter into the menu features of Model PMI-2. Model PMI-2 contains the site-specific program Every FireFinder XLS FACP is controlled and operated configuration created in the custom-configuration from Model PMI-2,which uses large,lighted buttons tool,Zeus. The controller in Model PMI-2 to prompt the end-user to the next available,correct provides all system logic and supervision. system operation (i.e.—Acknowledge,Silence, Unsilence Audible or Reset). FireFinder®XLS Person Machine Interface 2 6359 SIEMENS Industry,Inc. Building Technologies Division 1 . 19 Specifications — (continued) With the use of the software upgrade kit(Model The detail screen also provides the end-user with a GPMI2-HW-KEY)Model PMI-2 can provide global summary of the events—sorted by active type active functionality by annunciation and controlling multiple in the area. A building contact name and phone FireFinder XLS and MXL systems. number are also available. The display of Model PMI-2 categorizes events by In addition to the detail screen, the end-user can type, providing a separate event tab for Alarm, view a graphics map,which can show a simple Supervisory,Security and Trouble events. The building floor plan. On the map, the end-user will quantity of active events of each type is listed in see an icon indicating the location of the event in each event tab. The display provides two(2)full the building in addition to a'You-Are-Here'symbol lines of text message for each event. to tell the responding person exactly where they Each event can have a 32-character custom message are in the building in relation to the event. describing the event's location. In addition to the Model PMI-2 also provides a completed menu for text message,the system displays the category of running system status reports (via a print-preview the active event: (e.g.—Smoke,Heat, Water Flow, feature right on the screen before sending the report Manual,etc)—the category means more to to the printer). The menu system is designed to allow responding officials than model numbers. the user to scroll through the entire system in either the The LCD screen displays events in colors Physical or Geographic views to locate the area of the corresponding to the event type. Alarm events system desired—all without having to know module or appear in red; Trouble events appear in yellow; device addresses. All navigation is possible using custom Supervisory events in l;i,w,and Security events in messages. magenta. Maintenance menus also use colors to The Maintenance Menu is accessed by password. When highlight system features and capabilities,such as an end-user enters this mode,the touch screen of arming and disarming points,system testing,and Model PMI-2 will be enabled, prompting the end- system reports. user to enter a password. System control within the Up to five(5)events can be displayed at a time. maintenance menu uses large,easy-to-read touch For Canadian operation, 10 events are shown. buttons. When more than five(5)events are present,the Model PMI-2 also provides the end-user with 40 up-and-down-arrow keys allow the user to programmable macro or function buttons,which can vertically scroll the list of events. A progress be programmed for a variety of usages. Model PMI-2 meter on the side of the list indicates the size of mounts to the inner door in two(2)of four(4)available the list of events and the location in the list. New, module spaces in the Models CA131,CA62 or CA133 'unacknowledged'events are indicated by a flashing enclosures. exclamation point('!'). Once acknowledged,the Model PMI-2 communicates with the rest of the exclamation point changes to a check mark('d). FireFinder XLS system via the internal,60-pin data To the right of the display is a button that is bus. Each of these data buses contains all power and labeled 'More Info.' When an event occurs in data communications for Model PMI-2. the system (if additional information has been configured for this event),the'More Info' Language Overlays button will light green, prompting the end-user There are three(3)types of overlays that provide to press the'More Info' button. naming in alternate languages for visual indicators Once'More Info' is pressed,the end-user is found on the front of each Model PMI-2. Each overlay presented with a full screen of detailed is assigned, respectively,on Model PMI-2's outer information about that event, including over assembly when affixed to the display on the user 200 characters of additional text to describe the interface. Each overlay assignment is intended to be event, standard NFPA 170 Fire Safety symbols, used in combination with the run-time,alternate- Hazmat and other critical information concerning language files found in the Zeus tool. the event. This information can be invaluable to a Note: Refer to Details for Ordering section on the following page for fire official responding to an Alarm event. the three(3)types of language overlays available for Model PMI-2. SIEMENS Industry, Inc. Building Technologies Division 1 . 20 Electrical Ratings Temperature and Humidity Range 24V Back Plane Current: 190mA Products are®UL 864 9th Edition Listed for indoor dry Screw Terminal 24V Current: 0 locations within a temperature range of 120+/-3°F 6.2V Back Plane Current: 0 (49+/-2°C)to 32+/-3°F(0+/-2°C)and relative humidity of 93+/-2/o at a temperature of 90+/-3 F(32+1-2 C). 24V Standby Current: 190mA Related Documentation Details for Ordering Product Data Sheet Number Model Part Description FireFinderaXLS 6300 Nurf�f Number S stem Overview Person Machine Interface 2 for PMI-2 S54430-C1-A1 FireFinder XLS GPMI-2 554430-C3-A1 Person Machine Interface 2 with GPMI2-HW-KEY PMI-2-SPAN-LAB S54430-C10-A1 Spanish Overlay for Person Machine Interface 2 PMI-2-PORT-LAB S54430-C71-A1 Portuguese Overlay for Person Machine Interface 2 PMI-2-FRENCH-L S54430-C12-A1 Canadian[French]Overlay for Person Machine Interface 2 GPMI2-HW-KEY 554430 C4 Al Software Upgrade Kit for Model PMI-2 Global Functionality SIEMENS Industry, Inc. Building Technologies Division 1 . 21 Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard SIEMENS Industry,Inc. Florham Park,NJ 07932 Brampton,Ontario August 2013 Building Technologies Division Tel:(973)593-2600 (sii) L6T 5E4/Canada Supersedes sheet need izizaiz FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 (R—1) URL:www.usa,Siemens.com/Fire FAX:(905)799-9858 1 . 22 S Data Sheet Fire Safety Products FireFinder' XLS Power-Supply Charger, Power-Termination Board Module & Power-Supply Extender Models PSC-12, PTB and PSX-12 ARCHITECT AND ENGINEER SPECIFICATIONS • Main-system power supply • Total power output 12 Amp cm 24VDC • Built-in charger for up to 100AH batteries • Universal AC power input: 120VAC- 240VAC @ 50/60Hz I I I • Off-line, switch-mode power converter • Filtered & regulated 24VDC i • Mounts on back box or optional CAB-MP in one(1) module space IIIII111 � • Common Alarm&common Trouble relays(Form 'C' rated ® 2A) I I • Two(2) Programmable relays (Form'C'rated 0 2A) I I I I I I CAUTM • Provides 12-Amp, non-power-limited 24 VDC output(internal use) =`` • Provides 24VDC and 6,2VDC power to all modules connected to a 60-pin bus • 4-Amp, power-limited 24VDC output(external use) I I I I • Supervised Intelligent Module with plain, decimal addressing • Communicates with PM1/CPC,via common 60-pin power/data bus • Ground-fault detection circuitry • Optional enclosure tamper switch connection point(Model HTSW-1) • Includes PTB Power Termination Board for AC field connections • Optional 24VDC system power expansion with the power-supply extender (Model PSX-12) , • Models PSC-12 and PSX-12 share common batteries • Up to three (3) Model PSX-12s connected to Model PSC-12 • ®UL 864 9th Edition Listed &®ULC Listed; Model FM, CSFM, NYC Fire Department Approved PSC-1 Product Overview— (Model PSC-12) The Model PSC-12 Power-Supply Charger is a Model PSC-12 is an addressable-intelligent, microprocessor- high-current power supply that provides controlled module that communicates its status to the FireFinder XLS with primary, regulated 24VDC system-operator interface(PMI). power to operate at 12 Amps(Alarm)/5 Amps Model PMI is able to query the status of the power supply (Standby). to obtain information regarding system charging current, Model PSC-12 has a built-in battery charger, terminal loading information, ground fault-conditions and capable of charging up to 100AH batteries. more. FireFinder XLS Power Components 6322 s Industry, Inc. Building Technologies Division 1 . 23 Product Overview— (continued) Model PSC-12 Two(2)additional relays are available to be programmed for activation based on system control logic. Model PSC-12 is a universal power supply;accepting When adoor-tamper switch is required in any of the CAB AC power-input levels from 120VAC—240VAC @ 50/60Hz. No special configuration is required enclosures,the Model HTSW-1 tamper switch can be— Model PSC-12 is designed to operate across these optionally connected to Model PSC-12 to provide this AC input ranges. functionality. Model PSC-12 has an off-line,switch-mode power Model PSC-12 has diagnostics LEDs to indicate'Power On', converter and a power-factor-correction circuit to 'Module Failure' (internal module failure), 'H-NET Failure' improve conductive RF emissions at low (network-communication failure),'Ground Fault'(internal to frequency. enclosure or on any 24VDC output circuits),'24VDC 12A Fail' Model PSC-12 communicates with the H-Net and'24VDC 4A Fail.' Model PSC-12 module is addressed protocol with other system cards and modules, using plain, decimal-address switches, which clearly state the address of the module. via the common 60-pin power/data bus. Model PSC-12 also provides the FireFinder XLS As an option,an extender cable (Model PSC-ISO-CBL)can system with 6.2VDC (2Amps) and 24VDC allow usage of two (2)XLS universal power supplies (2Amps)—via the 60-pin bus—to provide basic (Model PSC-12) in one(1) Model CAB-series enclosure. power to cards and modules. This 24VDC and 6.2VDC power is also referred to as 'back-plane Model PTB current.' Model PSC-12 Power-Termination Board comes packaged Combined with the'back-plane current,'the PSC- with a module known as Model PTB. Model PTB is the 12 provides 12Amps of power @ 24VDC. Two Power-Termination Board,and is required for operation (2) separate power-output terminals are with the PSC-12. Model PTB must be mounted in the available:one (1)power limited with 4A max @ lower-right corner of the CAB enclosures. Mounting studs 24VDC capacity and one(1) non-power limited with are provided in all enclosures to mount to Model PTB. 12A max @24VDC capacity (the total not to Model PTB contains screw terminals for AC input power to exceed 12A). Model PSC-12 also provides two (2) be connected. Model PTB contains an AC-line filter and connection points for the 60-pin power/data bus. AC-line power breaker rated at 5A. From another The 24 VDC outputs for Model PSC-12 provide auto- connector on Model PTB, AC power is connected directly resettable current protection circuits for overload to Model PSC-12,via a keyed-cable harness. Each Model PTB and short-circuit conditions. supports building AC-power-connection circuits for two (2) power supplies—either one(1) for Model PSC-12 and The battery sizes installed are entered in the one(1),optionally,for the Power Supply extender(Model software configuration tool. Model PSC-12 can PSX-12.) When more than one (1) Model PSX-12 Power charge 15AH,31AH, 75AH or 100AH batteries. The Supply extender is used, a second Model PTB is charger monitors and maintains the battery. The required, and must be ordered separately. charger has three (3)charge modes—depending on the state of the batteries: Bulk (full) Charge State,Trickle Charge State and Float IF10- (maintenance) State. The charger monitors the batteries and automatically determines which of the charging modes to activate. Model PSC-12 can charge lead-acid batteries Model PTB only. Model PTB has an optional connector that can be used Model PSC-12 mounts on one(1)of four(4)available during system installation, commissioning and service to provide the technician with a place to plug in their module spaces directly on the back box or laptop computer, if required. Model AC-ADPT is an optional Model CAB MP module mounting plate, optional accessory cable that allows connection on one which then mounts inside of Models CABA,CAB-2 or side to Model PTB,via a keyed connector,and on the CAB-3 system enclosures. other end directly into to the laptop's transformer. Most Model PSC-12 has four(4) Form'C'relays rated at PC external power transformers have removable AC 2 Amps each. A relay is dedicated to automatically power cords which can be replaced by Model AC-ADPT operate on"Any System Alarm"—this is the to temporarily provide an AC power source for PCs used Common Alarm Relay.Another is dedicated to during system installation, service and maintenance automatically operate on"Any System Trouble"- calls, when needed. this is the Common Trouble Relay. s Industry, Inc. 1 . 24 Building Technologies Division PSX-12 Power-Supply Extender • Auxiliary 24VDC Power Supply • Total power output 12 Amp @ 24VDC • Universal AC power input 120VAC—240VAC @ 50/60Hz I I! 1111 • Off-line Switch Mode Power Converter • Filtered &Regulated @ 24VDC 1 I 1! 1 I 1! ■ Provides 12A non-power limited @ 24 VDC output I 1! 11 (Internal use) 4 CAUTM ■ Provides 4-Amp, power-limited @ 24VDC output (external use) 11 1! I 1 • Mounts on CAB-MP one (1) module space 1 I » I! 11 • Supervised Intelligent Module—plain,decimal addressing I 1 A 1 I I I } • Communicates with PMI/CPC, via common 60-pin 11 I I I 1 power/data bus • Ground-fault detection circuit 1 I 11 • PTB Power Termination Board for AC field connections 4 1 ® I 1 • Models PSCA 2 and PSX-12 share common back-up batteries ■ Up to three (3) PSX-12s connected to a PSC-12 charger • SUL 864 gth Edition Listed &OULC Listed; Model FM, CSFM, NYC Fire Department Approved PSX 12 Product Overview — (Model PSX-12) The Model PSX-12 Power-Supply Extender is a Model PSX-12 communicates via H-Net protocol with high-current, auxiliary-power supply thatexpands other system cards and modules, via the system's the main Model PSC-12 power supply and battery common 60-pin power/data bus. Model PSX-12 charger for the FireFinder XLS system with an provides a full 12 Amps of power @ 24VDC. additional 24VDC power. Model PSX-12 is rated at Two (2)separate power-output terminals are available: 12Amps. one that is power limited with 4A max @24VDC Model PSX-12 is an addressable intelligent capacity and one non-power limited with 12A max microprocessor-controlled module that 924VDC capacity(total is not to exceed 12A). Model communicates its status to the system-operator PSX-12 also provides two(2)connection points for the interface (PMI) to report fault conditions. Model PMI 60-pin power/data bus. is able to query the status of the power supply to obtain information regarding terminal-loading Model PSX-12 mounts on one (1) of four (4), information, ground-fault conditions and more. available module spaces directly on the back box or optional Model CAB-MP module mounting plate, Model PSX-12 is a universal power supply;accepting AC which then mounts inside of Models CA131,CA62 or power-input levels from 120VAC—240VAC, and has CA63 system enclosures. an off-line,switch-mode power converter and power- factor-correction circuit to improve conductive RF Model PSX-12 has diagnostics LEDs to indicate'Power emissions at low frequency. No special configuration On',Module Failure(interna(module failure), H-NET is required. Failure (network communication failure), Ground Fault(internal to enclosure or on any 24VDC output circuits), 24VDC 12A fail and 24VDC 4A fail. Model PSX-12 is addressed using plain, decimal-address switches, which clearly state the address of the module. s Industry, Inc. 1 . 25 Building Technologies Division Details for Ordering Model Part :Description Number Number p AC-ADPT 500-633992 Technician Laptop-Power Connector BP-61 175-387194 24VDC,15AH Batter BTX-1 175-083897 Set of 12V,31 AH Batteries BTX-2 175-083898 Set of 12V,55AH Batteries BTX-3 599-034220 Set of 12V,100AH Batteries CAB-BATT 500-633917 Battery Enclosure for 75AH or 100AH Batteries HTSW-1 500-033350 Door Tamper Switch PSC-12 500-033340 Power Supply and Battery Charger,12A @ 24VDC PSC-ISO-CBL S54430-K4-A1 Optional Extender Cable(used for holding two[2]Model PSC-12 power supplies in one[1]Model CAB-series enclosure PSX-12 500-034120 Power Supply Extender,12A @ 24VDC PTB 500-033390 Power Termination Board [only required for applications with more than two(2)Model PSX-12 extenders] Temperature and Humidity Range Products are®UL 864 gth Edition Listed for indoor dry locations within a temperature range of 120+/-3°F (49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2%at a temperature of 90+/-3°F (32+/-2°C). Electrical Ratings Model Model P5G12` PSX-12 41 t 120VAC @ 50/60 Hz. 120VAC @ 50/60 Hz. 220VAC @ 50/60 Hz. 220VAC @ 50/60 Hz. 240VAC @ 50/60 Hz. 240VAC @ 50/60 Hz. 3.5A,max.@ 120VAC 3.5A,max.@ 120VAC Jut 2.5A,max.@ 220VAC 2.5A,max.@ 220VAC 2.OA,max.@ 240VAC 2.OA,max.@ 240VAC , :, FGklt 2A,max. Not Applicable - Power Limited: 4A,max. Power Limited: 4A,max. ------------------------------------ -------------------------------------- ., Non-Power Limited: 12A,max. Non-Power Limited: 12A,max. 2A,max. Not Applicable t: 150mA+20mA per active relay 150mA L *lt7i1iE'� " 8V peak-to-peak max. 8V peak-to-peak max. ------------------------------------- -------------------------------------- [Each t{E1WXAt�T_ Pairs 75m&max.durin ms .transmission 75mA,max.durin ms .transmission Model PTB __AC_Mains Rating {Each Model PSC-_12/Model PSX_12} ------------- ---- 120VAC @ 50/60 Hz. 3.5A,max. ............................................................................................................................................._............................................................................................................................................................. 220VAC @ 50l 60 Hz. 2.5A,max. ............. ....................................... .......................................................................................................;.................................................................................................................................................. 240VAC @ 50!60 Hz. 2.OA,max. Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 1577 North Service Road s Industry, Inc. Florham Park,NJ 07932 East Oakville,Ontario February 2014 Building Technologies Division Tel:(973)593-2600 (sll-FS) L6H OH6/Canada 5upersedes sheet dated 8/11 1 FAX:(908)547-6877 Printed in U.S.A. Tel:[905]465-8000 IR—51 URL:www,usa,Siemens.cam/Fire URL•www.Siemens.CA SIEMENS Catalog Sheet Fire Safety&Security Products FireFinder XLS Card Cage-5 Slots Model CC-5 ARCHITECT AND ENGINEER SPECIFICATIONS •Common card cage for all FireFinder XLS/V option cards •Five (5)slots to mount any option cards—with no restrictions • Mounts on back box or CAB-MP(two-module spaces) • Removable terminal blocks F • Numbered terminal blocks I(l I= • All field-wiring terminations on top (power limited) ° • All internal-wiring terminations on bottom ; (non-power limited) • Molded card guides for card mounting • Card-position locator label on card guide • All cards communicate via common 60-pin power/data bus s ;_ • Screw terminals wire sizes supported: 12 AWG —24AWG • DIN connectors • ®UL 864 91h Edition Listed and OULC Listed; FM,CSFM & NYMEA Approved Product Overview The Model CC-5 card cage provides the physical Field wiring to all devices and circuits mounting location and all wiring connection terminates at the Model CC-5 card cage. points for all fire and voice system options cards All cards designed for use with Model CC-5 for the FireFinder XLS system. route their field wiring terminations to the'top' Specifications of Model CC-5 — these connections are all All cards plugged into the Model CC-5 card cage power limited. Internal wiring connections communicate with other modules of the distribute 24VDC to cards or high-level audio FireFinder XLS panel—via a common, 60-pin data signals (depending on application used) bus. This 60-pin bus runs through the card connected to the bottom of Model CC-5 — cage; making all communication data buses and these connections are all non-power signals available to all cards. Connectors are limited. provided on the left and right side of Model CC-5 All wiring connections to Model CC-5 are made to connect a 60-pin cable for communications to removable terminal blocks. Terminal blocks with the FireFinder XLS operator interface, power are rated for use with wire-sized 12AWG to supplies and amplifiers modules. There are no 24AWG. Each terminal block comes with a active components on Model CC-5. protective cover that also serves as a handle to allow easy terminal-block removal when wires are connected. FireFinder XLS 6320 SIEMENS Industry, Inc. 1 . 27 Building Technologies Division Specifications — (continued) Compatible FireFinder XLS Cards Each connector is numbered to make wiring Any combination of the following (5) option terminations to the correct position on the cards can be installed in the CC-5: terminal block simple and reduce the potential Fire System Cards: for wiring errors. Model CC-5 is shipped with two (2) card Model No. Part No. Description guides (top and bottom) that mount to the DLC 500.033090 Device Loop Card Model CC-5 PCB. The'top'card guide contains a ZIC-4A 500.033050 Zone Indicating Card 4 Circuits blank label for use by the installer to indicate the CRC-6 500-033250 Controllable Relaycard location or card-slot position. The blank label ftt:j 500.033240 Network Interface Card serves as a reminder to the installer to ensure 500.034200 Conventional Detector Card the proper card goes in the correct card slot — Voice system Cards; this is important during commissioning Model No. Part No. Description when cards may be installed after the field- DAC-NET 500.035100 Digital Audio Card-Network wiring terminations have been made —and AIC 500.035300 Audio Input Card when cards are removed for service. ZAC-40 500.035400 40-Walt Zone Amplifier Card All field-wiring terminations are typically TZC-8B 1 500.034110 1 Telephone Zone Card made to the Model CC-5 terminal blocks before the card guides are mounted and the Details for Ordering option cards are installed. Model CC-5 mounts in two (2) of the four(4) available module Model No. Pert No. Description spaces directly on the back box or optional CC-5 1 500-633037 Card Cage 5 Slots Model CAB-MP for installation in the CAB-1, Refer to Installation Instruction:315-033035 CAB-2 or CAB-3 enclosures. Temperature and Humidity Range Products are®UL 864 9th Edition listed for indoor dry locations within a temperature range of 120+1-3°F (49+1-2°C) to 32+1-3°F (0+1-2°C) and at a relative humidity of 93+1-2% at a temperature of 90+1-3°F (324-200. Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario May 2010 Tel:(973)593-2600 (sli) L6T 5E4/Canada 1 . 2 8 FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 Supersede(Rh Zda[ed 7/09 Building Technologies Division URL:www.SBT.Siemens.com/FIS FAX:(905)799-9858 SIEMENS Data Sheet Fire Safety&Security Products FireFinder® XLS Device Loop Card Model DLC ARCHITECT AND ENGINEER SPECIFICATIONS • Quantity 252 addressable points • Provides two(2)intelligent addressable circuits • Compatible with'H'-series,DesigoTm Fire Safety-series and CerberusTM PRO-series of intelligent detectors w•Multi-criteria 1 Carbon Monoxide(CO)Detector with ASAtechnology _ •Multi-criteria Detector pr •Multi-criteria Detector with ASAtechnology •Photoelectric Smoke detector •Quad Interface module •Thermal(Heat)detector • Polarity insensitive via SureWireT°"technology • Quantity 12 diagnostic light-emitting diodes(LEDs) for easy circuit diagnosis • Supports T-Tapping • Onboard,ground-fault detection and short-circuit isolation • Onboard microprocessor for dependable,efficient device communication • Degrade mode • Supports'Class B'or'Class A'wiring • oUL 864 9th Edition Listed&®ULC Listed; DLC DLC FM,CSFM,&NYC Fire Department Approved [Front View] [Side View] Product Overview The Device Loop Card(Model DLC)is the interface used for Model DLC is polarity insensitive via SureWire connection of Desigo and Cerberus PRO intelligent technology,which greatly reduces commissioning time detectors and initiating devices to a single FireFinder normally spent tracing down crossed-field wiring. Model XLS fire-alarm control panel (FACP). Model DLC also can DLC communicates detector information,such as work with Siemens input devices, manual stations and sensitivity of intelligent fire detectors and logic-function control devices. data,to the Person Machine Interface,which is located Each Model DLC plugs into one(1)slot of the Model within the FireFinder XLS system. CC-2 or Model CC-5 card cage. Programming for Model DLC Each device loop card supports two(2),isolated circuits is accomplished via the XLS FACP custom-configuration tool, up to a total of 252 addressable devices—as well as relay Zeus. Model DLC takes one(1)address on the network, and audible bases,remote lamps and duct-detector communicating up to a total 252 detectors and devices. housings in any combination. The microprocessor Model DLC has 12 LEDs for diagnostic purposes,and controls the onboard isolation in case there is a short in provides ground-fault detection and zone-isolation circuitry. any of the circuits,thus allowing the other circuit to Specifications continue operating. For continuous protection,the on- Model DLC initializes,operates and maintains all devices board microprocessor continues to operate even in the residing on its two(2)circuits. Model DLC event of a XLS CPU failure. communicates all relevant device and event information (Alarm,Trouble and Supervisory commands)to FireFinder XLS,and supervises the device loop circuit. Device Loop Card 6312 SIEMENS Industry,Inc. Building Technologies Division 1 . 29 Temperature and Humidity Range Details for Ordering — (continued) The Device Loop Card is 4DUL 864 91h Edition Listed —'H'-Series— for indoor dry locations within a temperature range Model Part of 120+/-3'F(49+1-2°C)to 32+/-3°F(0+/-2°C)and a Description .Number Number relative humidity of 93+/-2%at a temperature of HFP-11 500-033290 FirePrint Detector 90+/-3'F(32+/-2'C). HFPT-11 500-033380 Thermal Detector HMS-D 500-033400 Dual-Action Manual Station HMS-M 500-033450 Manual Station,Metal HMS-S 500-033200 Single-Action Manual Station HMS-SA 500-034150 Single-Action Manual Station Electrical Ratings (Auxiliary Contact),[Canada only] 24V Current-Draw: HMS-2S 500-033460 Two-Stage Manual Station 0 [Canada only] I tkplane] 1 HTRI-D 500-033360 Dual-Input Module 24V Current Draw:, 100mA+1.4mA I HTRI-M 500-034000 Mini-Input Module [screw TerrisinaiI per device I HTRI-R 500-033300 Single-Input w/Relay 24V Current Draw! 145mA+1.8mA HTRI-S 500-033370 Single-Input Module [Standby] per device 6.2V Cures or —200mA Cerberus PRO Series— Modet Part Device Loop Draw: 375mA,max. Description [at 30vDc,mail [power limited] dumber Number FDCI0422 S54322-F4-A1 Quad Interface Module HI921 S54320-F5-A2 Thermal(Heat)Detector OH921 S54320-F6-A2 Addressable Multi-Criteria Detector OP921 S54320-F4-A2 Photoelectric Smoke Detector OOHC941 S54320-F8-A2 Multi-Criteria Fire 1 CO Detector Details for Ordering ASAtechnology —Desigo Series— 0OH941 S54320-F7-A2 Multi-Criteria Fire Detector w/ASAtechnology Mode( Part Number Number Description —Other Modules and Devices— FDCI0422 S54322-F4-A1 Quad Interface Module Model Part FDOT421 S54320-F6-A1 Addressable Multi-Criteria Detector bescClption. Number Number FD0421 S54320-F4-A1 Photoelectric Smoke Detector FDT421 S54320-F5-At Thermal(Heat)Detector ILED-HC 500-048637 Intelli ent Remote Lamp,Ceiling Mount Multi Criteria Fire 1 CO Detector ILED-HW 500-048809 Intelligent Remote Lamp,Wall Mount FDOOTC441 55432048-A1 DLC 500-033090 Device Loop Card w/ASAtechnology FD00T441 55432047-A1 Multi-Criteria Fire Detector I PMI 1500-0330701 Operator Interface/System CPU w/ASAtechnolo PMI-2 S54430-Cl-Al I Person Machine Interface 2 Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard SIEMENS Industry,Inc. Florham Park,NJ 07932 Brampton,Ontario May 2013 Building Technologies Division Tel:(973)593-2600 (Sip L6T 5E4/Canada Supersedes sheet dated 5/10 FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 (Rev.3) URL:www.USA.Siemens.com/Fire FAX:(905)799-9858 1 . 30 SIEMENS Data Sheet Fire Safety Products FireFinder® XLS / XLSV Zone-Indicating Card Model ZIC-4A ARCHITECT AND ENGINEER SPECIFICATIONS • Operates audible or visual notification appliances • One(1)or(2)two-channel voice operation • Operates audio speakers(25V or 70VRMS) • Three(3)unique signals from each circuit -x • Available bell-follower application 11 • Four(4)Class A or Class B circuits • 24 VDC at 3.0 Amps per circuit _•::+ 3 • Built-in strobe synchronization • City-tie or leased-line output • Coded audibles available i S • Fully programmable r> • On-board microprocessor • • Automatic I manual control • March time I Uniform Code 3 r • Selectable degrade operation • Built-in,ground-fault detection ?•'= t • Silenceable I non-silenceable option ' • Circuits power limited,per NEC 760 • NFPA 13,pre-action and deluge ZIC-4A I ZIC-4A • N FPA 2001, FM-200 Releasing (Front View) (Side View) • Releasing service FM Approved for single and double interlock, . OUL B64 901 Edition Listed&OULC Listed, ■ k pre-action system operation FM(13010)&NYC(16160)Fire Dept.Approved Product Overview The Zone-Indicating Card(Model ZIC-4A)provides four Model ZIC 4A plugs into one(1)slot in the Model CC- (4)fully supervised and programmable output circuits 5 or Model CC-2 Card Cage,and has on-board LEDs for for use on the FireFinder fire alarm control panels system status and troubleshooting. Indication of (FACPs). power,communication,internal operation,and Model ZIC-4A supplies four(4)'Class B'or'Class A'type ground-fault conditions are provided,as well as output circuits—power limited to 3.0Amps maximum indication of circuit activation or Trouble conditions. per circuit. Each circuit can be independently All system-status conditions are also reported to each programmed for use with listed audible or visual XLS system's Person Machine Interface(PMI.) Each notification appliances,listed emergency-audio circuit or output may be controlled automatically with speakers,municipal tie boxes,leased lines,or as system-logic programming,via the ZEUS custom- releasing circuits. configurable programming tool or manually,using the Model Z04A can send audio to additional speaker FireFinder XLS keypad on the PMI. zones,via the Model ERA2004-Al booster amplifier. Automatic control may also be time based. Each circuit or output can be manually Armed'or 'Disarmed'via the PMI's keypad. ,{ XLS Zone-Indicating Card, ZIC-4A 63 1 6 SIEMENS Industry,Inc. Building Technologies Division 1 . 31 Product Overview- (continued) When any circuit or output has been'Disarmed;the Leased Line-Each of the four(4)circuits on Model ZIC-4A Model PMI display will indicate the affected circuit or can be configured for connection to a leased line.The output,and the`Partial System Disable'LED will circuits can be programmed to transmit Alarm, illuminate-until the circuit or output has been returned Supervisory,or Trouble signals. A leased-line module to the'Armed'condition. Model ZIC-4A circuits can also (Model LLM-1)is required for this feature. be manually energized or de-energized when in the Bell Follower-Each of the four(4)circuits on Model 'Disarmed'state,via the PMI. ZIC-4A can be configured as a NAC that can follow the input Model ZIC-4A contains a microprocessor,which allows from another NAC in an external FACP. Circuit 1 on a notification-circuit outputs to function in a degrade Model ZIC-4A card within a FireFinder XLS system mode-even if the main FireFinder XLS processor or enclosure can be configured as the Bell Follower-Primary the local-network communication link has failed. In a and is connected to the external NAC. degrade mode,Model ZIC-4A will respond to an Alarm Any other ZIC-4A circuit in that enclosure can be or Trouble from any intelligent-addressable initiating configured to follow the state of the Primary Bell Follower. device or conventional-zone initiating device This feature can be used to synchronize coded or ANSI connected in the same local enclosure. Temporal patterns for audible sounds with another FACP. Standard NAC zone-Each of the four(4)circuits on Model ZIC-4A can be configured for use as a standard notification appliance circuit(NAC). The NAC output Controls and Indicators can be used as a steady, strobe-synchronized, or RESET switch— Re-initializes Model ZIC-4A card only zone-coded output. Available coding includes ANSI Temporal,March Time 120-pulse-per-minute(PPM), POWER LED ---- Indicates the power is applied to March Time 60 PPM,March Time 30 PPM,Canadian Model ZIC-4A Two-stage 30 PPM, Canadian Two-stage 120 PPM and CARD-FAIL LED-- Illuminates when the card custom coding. microprocessor has failed Outputs may be programmed through logic to transmit CAN-FAIL LED— Illuminates when the CAN up to three (3)different signal types,depending on communication fails and Model event priority.For instance,the same circuit can be ZIC-4A is in degrade mode programmed to transmit the ANSI Temporal pattern for evacuation,March Time 120 PPM for tornado notifica- HNET-FAIL LED— Illuminates when the HNET tion,and a custom code for recall. communication fails and Model Standard speakerzone--Each of the four(4)circuits on ZIC-4A is in degrade mode Model ZIC-4A can be configured for use as a standard GND-FAULT LED--Indicates the detection of a ground- speaker circuit in single or dual-channel systems. fault condition(either negative or Model ZIC-4A can be used with the Model ZAM-180 bulk positive)on the field wiring of amplifier,or Model ZAC-40 amplifier card. Each circuit Model ZIC-4A on Model ZIC-4A is limited to 96 Watts per zone. ZONE-ACTIVE— Illuminates to indicate the zone Releasingzone-Each of the four (4) circuits on LEDs has been activated either Model ZIC-4A can be configured for use as a releasing automatically or manually.There is circuit.This circuit can be used to release Sinorix®227 one(1)LED for each zone. or 1230 agents. For proper supervision of a releasing circuit,the Model REL-EOL module must be used. Model TROUBLE IEDs— Indicates the presence of a Trouble REL-EOL can use power directly from the FireFinder XLS condition(either open circuit or system. No external, regulated power supply is a short circuit)onn the zone. There is one(1)LED for each zone required. Municipal Tie-Each of the four(4)circuits on Model ZIC- 4A can be configured so that it can be connected to and activate a municipal city tie box. The circuit meets the Temperature and Humidity Range requirement of some jurisdictions to allow the box to be Products are OUL 864 911,Edition Listed for indoor dry reset before the FACP. A leased-line module locations within a temperature range of 120+1-37 (Model LLM-1)is required for this feature. (49+1-2°C)to 32+1-3°F(0+l-2°C)and a relative humidity of 93+1-2%at a temperature of 90+1-3*F(32+1-20C). SIEMENS Industry,Inc. Building Technologies Division 1 . 32 Electrical Ratings Details for Ordering 24V Back Platte or External See:Note below Part Pawed Current urawt Model Descrtp#ton Nurribur 24V Current Draw Total Device Current (screw7erminat) Z1C 4A 500 033050 Zone Indicating Card 6 2V Current Draw (Back Plane] 0 REL-EOL 500-696359 End-of-Line Releasing Module 24V Current Draw 89mA (Standby] Note: The 24V current is dependent on the wiring type and usage of each ZICCkt setting for Model ZIC-4A. The following table contains the required current draws for the wiring type and usage of each zone: ZIC 4A Current.R!pq U i reM en t [ztc-gq standby tutrent 89iiA1 Zone usage Output,rwlt Class A'Current RgguITemer►f equ.(rement Not Used 0 0 NAC 17MA 6mA Strobe—Sync. 17mA 6mA Strobe—Unsync. 17n1A 6mA Municipal Tie—USA 34mA 0 Municipal Tie—Canada 17mA 0 Releasing Zone 17mA 0 Leased Line—Alarm 17mA 0 Leased Line—Trouble 17mA 0 Leased lane— 17mA 0 Supervisory Bell Follower— 0 0 Primary Bell Follower— 17mA 6mA Secondary S eakerZone 34mA 6mA NAC—coded 17mA 6n1A SIEMENS Industry,Inc. Building Technologies Division 1 . 33 r... is ii" Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each produces installation instructions. Fire Safety Fire Safety 8 Fernwood Road 1577 North Service Road SIEMENS Industry,Inc. Florham Park,NJ07932 East Oakville,Ontario August 2015 Building Technologies Division Tel:(973)593-2600 15114s1 L6H OH61 Canada Supenedesst adated 11IZO14 FAX:(908)547-6877 Printed In U.SA. Tel:19051465-8000 lRe..6J 1 . 34 URL•wY4%v.usa.5temens.comlFire URL:www.Siemens.CA SIEMENS Catalog Sheet Fire Safety&Security Products FireFinder XLS Network Interface Card Model NIC-C ARCHITECT AND ENGINEER SPECIFICATIONS • HNET communications 4 • XNET communications mc-C • CAN network communications ,k • Supports Class B-Style 4 or Class A - Style 7 wiring for XNET or HNET • Supervises the HNET or XNET and CAN networks • Diagnostic LEDs • Isolates short circuit faults • Ground-fault detection • Network repeater • Downloadable firmware • ®UL 9th Edition Listed &®ULC Listed; FM, CSFM and NYMEA Approved Model NIC-C Model NIC-C (Front View) (Side View) Product Overview The Network Interface Card(Model NIC-C)provides HNET or When Model NIC-C is used for XNET communications, XNET network communications between enclosures. In Model NIC-C provides communication between systems. addition to the HNET or XNET communication,Model NIC-C The maximum XNET Model NIC-C cards on a single system provides CAN network communication within an enclosure (single node)is one(1)-for a total of(59)XNET Model or external to the enclosure. The HNET or XNET can be NIC-C cards on a peer-to-peer, networked system. The XNET wired Class B-Style 4 or Class A-Style 7,but the CAN Model NIC-C card must reside in the same enclosure as the network can only be wired Class B-Style 4. Person Machine Interface(Model PMI). Specifications Model NIC-C supervises the XNET network to ensure p proper operation. Model NIC-C also isolates a short-circuit A single Model NIC-C can provide either HNET or XNET fault to each individual segment of the XNET network. communications. The CAN interface is available Model NIC-C provides an electrical repeater for each regardless of the HNET or XNET usage. XNET pair. MXL systems may also reside on the same When Model NIC-C is used for HNET communications, XNET with FireFinder XLS systems. Model NIC-C provides communication between enclosures The FireFinder XLS will also report all events over the within a single system. The maximum HNET Model NIC-C XNET to the Network Command Center for display. cards on a single system (single node)is 50. Model NIC-C Events are displayed on Model NCC-G: Trouble, supervises the HNET network to insure proper operation. Acknowledge,Alarm-Silence and System-Reset Model NIC-C also isolates a short-circuit fault to each commands are also initiated at Model NCC. Model NCC individual segment of the HNET network. Model NIC-C can also be used to perform maintenance commands on provides an electrical repeater for each HNET pair. an individual Fire Finder XLS on the XNET. FireFinder XLS 6338 SIEMENS Industry, Inc. Building Technologies Division 1 . 35 Specifications — (continued) Details for Ordering The NIC-C Card takes one card slot and mounts in a \ Model Pan Description CC-2 or CC-5 Card cage inside a CAB-1, CAB-2,or \y Number Number CAB-3 Enclosure. NIC-C 500.033240 1 Network tntertace Card The NIC-C provides the CAN network which supports the LCM-8/SCM-8/FCM-6/OCM-161 SIM-16 CAN Temperature and Humidity Range modules. Up to(99)CAN module addresses are available per enclosure. Products are®UL 864 9th Edition listed for indoor dry locations within a temperature range of 120+/-3°F The NIC-C Card has diagnostic LEDs that indicate (49+1-20C)to 32+/-30F(0+/-20C)and at a relative Card Fail, CAN Fail, HNET Fail,XNET Fail, Ground humidity of 93+1-2%at a temperature of 90+/-3°F Fault, Loop-A Fail and Loop-B Fail,as well as LEDs to (32+/-20C). indicate Power, Style and Active Networks. Electrical Ratings Input Power Output Power 24V Beek Plane Current 120rnA Eaen FNlETIXNET 8V peak to peak max. Screw TwnwnW 24V Curerd 0 And CAN Network Par 7&Mmax.(dump maq tanarniaaion) 6.2V Back Plane Curent 0 24V Standby Current 120rn4 Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario May2010 Building Technologies Division Tel:(973)593-2600 (Slq L6T 5E4/Canada Supersedes sheet dated 7/09 13 6 FAX:(908)547-6877 Panted in U.S.A. Tel:(905)799-9937 (Rev.2) . URL:www.SBT.Siemens.com/FIS FAX:(905)799-9858 SIEMENS Catalog Sheet Fire Safety& Security Products FireFinder XLS Switch-Control Module / LED-Control Module / Fan-Control Module Models SCM-8, LCM-8 and FCM-6 ARCHITECT AND ENGINEER SPECIFICATIONS SCM-8 LCM-8 FCM-6 • Eight(8) programmable switches •Six (6) sets of the push-button, (Model SCM-8) programmable fan-control switches • Protected space provided for labeling (Model FCM-6) • Discreet switches • Manual 'On'/'Off'/'Automatic' positions • Multi-color LEDs for clear indication of • Positive feedback(supervised) system status . LED indication of fan status • Modular ('On'/'Off'/'Trouble') • Programmable LED annunciation •Protected label provided • Remote mounting in REMBOX2 or • Modular REMBOX4 enclosures •Activation-stagger timer • ®UL 864 91h Edition Listed &®ULC Listed; FM,CSFM &NYMEA Approved Products Overview SCM-8 Model SCM-8 is a Siemens FireFinder XLS option One of the LEDs assigned to each switch is a dual- module that provides manual control of the color LED used to indicate what type of signal is Emergency Voice Evacuation System or Manual active. This LED may also be lighted steady or Fire-System Control. Each Model SCM-8 module flashing to further indicate system status. provides eight(8) momentary push-button For example,zones active to the evacuation audio switches and 16 LEDs to indicate their status. Each channel will have the LED lighted RED and steady; switch is assigned two (2) LEDs and a label to zones active to the Alert audio channel will have indicate the switch's programmed usage. The label the LED lighted RED and flashing;zones selected slides behind a clear, protective membrane, for paging will have the LED lighted GREEN and flashing until the microphone key is pressed. FireFinder XLS 6317 SIEMENS Industry, Inc. Building Technologies Division 1 . 37 Products Overview— (continued) SCM-8 When the zone-transfer confirmation message is When in the automatic position, the red and green received by the XLS command console,the LED will LEDs indicate Fan / Damper status ('On'/'Off') based change to steady GREEN, indicating that it is clear to on the system logic that can be programmed to page. Telephone zones with an incoming call in automatically control the fan outputs. When progress will have an LED flashing GREEN until manually switched to the'Off position, the red LED selected at the command console—at which time the will flash, indicating the output circuit used to turn LED will change to steady GREEN, etc. This process off the Fan 1 Damper has activated. The red LED will allows the operator easy, clear access to the overall light a steady stream of red to indicate positive system condition at all times. The second LED is feedback of the Fan I Damper actually turning off amber, and is used to indicate a fault condition. (via a monitored input). When manually switched Each Model SCM-8 module and each switch is fully to the'On'position,the green LED will flash, programmable, and may be used to control speaker indicating the output circuit used to turn on the circuits and a wide range of general system functions Fan I Damper has activated. The green LED will such as: All Call,All Evoc, Warden's Page,Speaker, light to a steady green to indicate positive feedback etc. Any number of circuits may be grouped and of the Fan / Damper actually turning on (via a controlled by a single switch. Switch usage and zone monitored input.) groupings are assigned using the ZEUS system switch LED programming software. Position Indicators Description Each Model SCM-8 module is mounted on a hinged AUTO OFF-Red Solid Based on System logic Driving Outputs g ON-Green Solid panel as a part of the FireFinder XLS command Green Flashing Command Sent out to Turn On Outputs console enclosure. ON Green Solid Output's On-Positive Feedback Received that Output is On LCM-8 Red Flashing Command Sent Out to Turn Off Outputs Model LCM-8 is a FireFinder XLS-option module that OFF Red Solid that Out Off-Positive Feedback Received that Output Is Off provides LED annunciation of system activity. Each Model LCM-8 module contains eight(8)groups of During system reset—when switches have been two (2) LEDs—each of which can be assigned to manually set to the'ON'or the'OFF'position—their desired outputs using the ZEUS programming associated outputs do not change state. The software. Eight(8) LEDs are capable of being lighted switches stay either'On'or'Off — based on the either RED or GREEN (flashing or steady.) The position of the switch. remaining LEDs are AMBER(flashing or steady.) Outputs will only change state when manually A space is provided for labeling of LED functions.The controlled via the'On'/'Off'switch or based on label slides behind a clear, protective membrane. system logic when switch is in the'Auto'position. Model LCM-8 dimensions are identical to Model SCM- Each Model FCM-6 module is mounted on a hinged 8, and Model LCM-8 is mounted on the same hinged panel as a part of the FireFinder XLS command panel as a part of the FireFinder XLS command console enclosure. Any combination of Model SCM- console enclosure. Any combination of Models SCM- 8, Model LCM-8 or Model FCM-6 modules may be 8 and LCM-8 modules may be used. mounted on the inner-door mounting plate(Model FCM-6 ID-MP). A six-conductor cable is supplied for interconnection of the modules. A 30-inch cable Model FCM-6 is a FireFinder XLS command- console option module that provides manual (Model CCL) is available for connection between rows. control of building HVAC system fans and dampers. Each Model FCM-6 module provides six Models SCM-8, LCM-8, and FCM-6 may be remotely (6) sets of three(3) push-button switches for mounted up to 1,000 feet from the main enclosure. manual system control. Each switch has three(3) REMBOX2 and REMBOX4 lobby enclosures are associated LEDs to indicate Fan 1 Damper status: required for remote mounting of Models SCM-8, 'OFF'(Red LED),'ON'(Green LED),'TROUBLE' LCM-8 and FCM-6. The CAN sounder board (Model (Yellow LED). CSB) is optionally available for audible feedback for remote mounting applications. SIEMENS Industry, Inc. 1 . 38 Building Technologies Division Electrical Ratings Details for Ordering 24V Back Plane Current 0 Model No. Part No. Description Screw Terminal 24V Current 14mA max SCM-8 500.033040 Switch Module(8 Switches) +t mA per active LED LCM-8 500.033100 LED Annunciator Module(8 LED Sets) 6.2V Back Plane Current 0 FCM-6 500.033140 Fan Control Module Switches(On-Off-Auto) 24V Standby Current 14mAmax ID-MP 500.633027 Inner Door MountingPlate +tmA per active LED (Accepts up to 4 Modules) Temperature and Humidity Range CSB 500-033130 CAN Sounder Board Products are®UL 864 9th Edition listed for indoor CCL 599-634214 CAN-CABLE-Lon 30 in.6-Conductor dry locations within a temperature range of BCM 500-033320 Blank Plate 120+1-3°F(49+1-2°C)to 32+1-37 (0+1-2°C)and at a relative humidity of 93+1-2%at a temperature of 90+1-3°F (32+1-2°C). Wiring Diagram Mounting Diagram ° ID-MP } � o MOUNTING PLATE o SCM-8 a MODULES = �{ i oo FCM-6 0 = MODULE r� ` I !i CSB (! SOUNDER 0 \� BOARD'\ e } Installing FCM-6, LCM-8 Mounting the CSB and SCM-8 Modules SIEMENS Industry, Inc. Building Technologies Division 1 . 39 Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario May 2010 "I /I 0 Building Technologies Division Tel:(973)593-2600 (sn) L6T 5E4/Canada supenedeyheet dated 7109 1 `t FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 (Rev.2) URL:www.SBT.Siemens.com/FIS FAX:(905)799-9858 SIEMENS Installation Instructions Model CAB-BATT/R Battery Box INTRODUCTION The Model CAB-BATT/R Battery Box from Siemens Building Technologies, Inc. is used to house BTX-2 (75AH)and BTX-3(100AH) batteries for the FireFinder-XLS System and up to 100AH battery sets for the FS-250 and FS-250C Systems.The CAB-BATT is black and the CAB-BATT-R is red.The CAB-BATT-R will be referred to in the remainder of this document as the CAB-BATT. The CAB-BATT consists of a door and a backbox, as shown in Figure 1.The door is permanently hinged left. The backbox can be placed on the floor directly underneath the CAB enclosure to which it supplies battery backup or it can be mounted on a flat surface with four user- supplied bolts that are a maximum of 1/8 inch in diameter. KNOCKOUTS FOR WIRING CAB-BATT Figure 1 CAB-BATT Enclosure YWW�F� CABB-BATT Enclosure is for indoor use only in dry environments. INSTALLATION Prior to installation consider the following: • Weight and size of the enclosure. • Local codes. Install the backbox: 1. Select a clean, dry, shock and vibration free surface in a protected environment. Siemens Building Technologies P/N 315-033917-6 Fire Safety 1 . 41 2. Position the backbox directly beneath the CAB enclosure to which it will be wired, lining up the knockouts in the CAB-BATT with the knockouts in the CAB enclosure. 3. Position the backbox so that it is clear of obstructions and the front door opens freely. 4. Mark the locations of the two upper mounting bolts of the backbox on the wall. (Refer to Figure 2.) 21.25 in 06 in ■eea�era"ar� 9.0 in 12.00 in e0.437 in (2 HOLES) 26.125 in Figure 2 Mounting Holes For CAB-BATT 5. Drill the two holes located in the previous step and screw in the top bolts, leaving a small gap between the wall and each top bolt. 6. Place the backbox over the two top bolts and allow it to slide down over the bolts. 7. Mark, drill, and install the two bottom bolts in the backbox. 8. Tighten all four bolts securely against the back wall of the backbox. 9. Place the batteries in the bottom of the CAB-BATT. WIRING The main AC power line must be turned OFF priorto installation. WARNING Install Wiring Wire in accordance with local codes and NEC 760. 1. Remove the knockouts in the top of the battery box and bottom of CAB enclosure for entry of battery wiring. 2. Connect the Battery Wire Assembly to the batteries in the CAB-BATT. If a longer wire is required, use a minimum of 12 AWG. For FireFinder-XLS, use P/N 465-633943, supplied with the PSC-12 (Refer to Figure 3 and the PSC-12 Installation Instructions, P/N 315-033060.) For FS-250 or FS- 250C use the Battery Cable Assembly supplied with the FS-250/ FS-250C hardware kit(Refer to Figure 4). SPECIFICATIONS CAB-BAIT: 26-1/8"W x 8 3/s"D x 12"H Siemens Building Technologies 2 P/N 315-033917-6 Fire Safety 1 . 42 CC-5 CC-5 IE3 0 0 0 0 0 0 O O O O O O O O O O TYPICAL CAB-2 ; ENCLOSURE CC-5 Ors o 4@V10 TB)« PSC-12 0 _ 0 0 t D O O O O , 10 OP PTB a � 12 in.long wire Battery Wire provided with Assembly—► PSC=12�\P/N 465-633943 Black ............ Red CAB-BATT - Wire + - wire+ Battery Battery Figure 3 Typical Battery Connections From FireFinder-XLS To CAB-BATT Siemens Building Technologies 3 P/N 315-033917-6 Fire Safety 1 . 43 0 0 0 FS-MB/ ° o FS-MB2 FS-DLC(FS-250) OR Im FDLC(FS-250C) TX-3 I 0 0 TO DISPLAY 0 LL 0 BOARD BRDG TX-2 0 0 rw W TX-1 FS-DACT OR FS MT LL 0 0 AC O 0 0 POWER BATTERY WIRE ASSEMBLY PROVIDED WITH HARDWARE KIT 12"LONG WIRE PROVIDED WITH HARDWARE KIT Black .............. Red CAB-BATT — Wire + — wire+ Battery Battery Figure 4 Typical Battery Connections From FS-250/FS-250C To CAB-BATT Siemens Building Technologies,Inc. Siemens Building Technologies,Ltd. 8 Fernwood Road 2 Kenview Boulevard Florham Park,New Jersey 07932 Brampton,Ontario L6T 5E4 Canada P/N 315-033917-6 1 . 44 SIEMENS Data Sheet Fire Safety Products HTRI-Series Interface Modules Models HTRI-D, HTRI-R and HTRI-S (and USCG-HPLATE for Marine installs) ARCHITECT AND ENGINEER SPECIFICATIONS • Interfacing and supervising normally open(N.0) or normally closed(N.C)contacts • Integral single-pole,double-throw(SPDT)relay on Model HTRI-R(up to 4 amps) • Dual input on Model HTRI-D,using a single address • Polarity insensitive with SureWirew technology • Dynamic supervision • Two-wire operation • Multi-color light-emitting diode(LED)indicates system status: GREEN I AMBER I RED ^^tee • Mounts in a flinch(10.2 cm.)square,2--'/4"(5.7 cm.) deep single-gang or double-gang back box • Easy front access to programming port and wiring terminals • Comes with 5"x 5"(12.7-x-12.7 cm.)plastic faceplate - Separate metal cover plate required for use in Marine installations • Electronic address programming • Electronic address programming is easy and dependable is easy and dependable • Device Programmer/Tester programs and verifies address • ®UL Listed&OULC Listed; of the device and tests for proper functionality FM,CSFM and NYCFD Approved Product Overview The Siemens—Fire Safety HTRI-series Intelligent Model HTRI-S can only monitor and report the status interface modules are designed to provide the means of the contact,while Model HTRI-R incorporates an of interfacing direct shorting devices to the fire-alarm addressable'Form C'relay. control panel (FACP)loop circuit. The Model HTRI-R relay and contact device input are The HTRI-series modules provide the most advanced controlled at the same address. For the FACP,the method of address programming and supervision on relay and input contact can be controlled as a the market--combined with sophisticated control separate function. The relay is typically used where panel communication. Each HTRI-series interface control or shunting of external equipment is required. module incorporates a microcomputer chip,and each The Model HTRI-D is a dual-input module that is interface module achieves the state of an'intelligent designed to supervise and monitor two(2)sets of dry device'through its microcomputer-chip technology, contacts. Model HTRI-D only requires one(1) combined with its sophisticated, bi-directional communication capabilities with the FACP. address,but responds independently to each input. Model HTRI-D is ideal for monitoring a water-flow Specifications switch and its respective valve tamper switch. The Siemens Mode HTRI-series intelligent interface Model HTRI-D flashes twice—once for each address, modules are available in three(3)types: Model HTRI- and Model HTRI-R LED indicates a change of state in D,as well as Models HTRI-S and HTRI-R,which are both the relay. The device`s microcomputer chip has the designed to monitor a(N.0)or(N.C)dry contact. capacity of storing,in memory,identification The interface module reports the status of the(N.0)or information;as well as important operating-status data. (N.C)contact to the control panel. HTRI Series Interface Modules 6304 SIEMENS Industry,Inc. Building Technologies Division 1 . 45 Specifications (continued) Electrical Ratings Each Model HTRI device has a multi-color LED that Relay Ratings,Model HTRX-R— (cont:d) flashes GREEN when operating in Normal;AMBER if 3.5A,120 VAC(0.6P.F.) unit is in Trouble condition, and RED to indicate a 3.OA,30 VDC(0.6P.F.) change of state. 1<nti;ucttve 2oA,120 VAC(0.4P.F.) Field-Device Programmer 2.oA,12o VAC(o.35P.F.) Siemens--Fire Safety innovative technology allows HTRI-series intelligent interface modules to be OMNI z.OA,30 VDC(0.35P.F.) programmed via the Device Programming I Test Unit: a compact, portable and menu-driven Mounting Diagram accessory that makes programming and testing an Models HTRI-S, HTRI-D and HTRI-R mount directly interface device faster, easier and more dependable into a 4-inch (10.2 cm.)square,21/4"(5.7 cm.)-deep than previous methods. box back box,or to a user-supplied double-gang back The programmer I tester eliminates the need for box. A 5"(12.7 cm.)square,off-white faceplate is mechanical addressing mechanisms,such as: included with each HTRI-series module. program jumpers,DIP switches or rotary dials, since Note: For Marine installations,a metal cover faceplate(Model Mode) DPU electronically sets the HTRI-series USCG-HPLATE)Is available separately. The faceplate must y be used to protect Siemens HTRI-series interface modules interface address into the non-volatile memory of from receiving radio-frequency interference(RFI). the interface microcomputer-chip. MOUNTING SLOTS Vibration,corrosion and other conditions that FOR 4-INCH deteriorate mechanical addressing mechanisms are SWITCHBOX no longer a cause for concern. The HTRI-series is fitted with screw terminals for connection to an addressable circuit,and is fully O o Q compatible on the same Siemens FACPs with 2; - Siemens Model'H'-series intelligent detectors; 1 IiTR1-S/-D/R Model'HMS'-serles addressable manual stations,or 2 MODULE any other addressable intelligent modules 3 °U o Q (e.g.—Model HZM or Model HCP). 4 ® MOUNTING s HOLES FOR e SW iTCHPLATE Temperature and Humidity Range ' Model HTRI-series intelligent interface modules are ©UL Listed. Environmental operating conditions for HTRI-D,HTRI-R and HTRI-S modules are 32°F(0*Q to 0 `� O 120°F(49°C)with a relative humidity of no greater _A than 93%,non-condensing. MOUNTING SLOTS FOR DOUBLEGANG SWITCHBOX Electrical Ratings Details for Ordering Current Part 1.3mA Model Descnpt[on (Active orStatldby) Number. Relay Ratings,Model HTRI-R HTRI-R 500-033300 Single Input Module Wth Relay 4 Amps,125 VAC HTRI-D 500-033360 Dual Input Module Resistive HTRI-S 500-033370 Single Input Module 4 Amps,30 VDC USCG- S54319-F22-Ai *Metal Cover Plate for HPLATE HTRI Series Interface Modules "denotes for required use with Marineonty instoBallons/ap pllcattons Notice. This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 1577 North service Road SIEMENS Industry,Inc. Florham Park,NJ 07932 East Oakville,Ontario February 2016 BuildingTechnologies Division Tel:(973)593-2600 (WS) L6H OH6 f Canada Supersedes sheet deice 612015 Tec o g taev.41 FAX:(908)547-6877 Printed In U.S.A. Tel:[905[465-8000 1 . 46 URL: www.usA.siemens.commRE URL: %wow.Siemens.CA SIEMENS Data Sheet Fire Safety&Security Products Intelligent Detection Devices TRI Series — Intelligent Initiating Interface Modules [For use with FireFinder® XLS and MXL Panels] Models TRI-D, TRI-R and TRI-S ARCHITECT AND ENGINEER SPECIFICATIONS • Used as an intelligent initiating interface module for the FireFinder XLS and MXL fire-alarm control panels(FACPs) { • Interfaces and supervises normally open(N.0)contacts , • Integral single-pole,double-throw(SPDT)relay(up to 4 amps),Model TRI-R • Dual input for Model TRI-D • Multi-color light-emitting diode(LED)indicates detector status (green,amber,red) • Simple front-end access to programming port and wiring terminals • Mounts in a 4"-square,2-1/8"-deep standard or double-gang box • Dynamic supervisionw • 5-x-5-inch faceplate included ,aM� • Two-wire operation • Compatible with Model DPU or FPI-32 field programmer/tester t • Electronic-address programming is simple and dependable • ®UL Listed,®ULC Listed; CSFM and NYC Fire Department Approved Product Overview The Model TRI-series of intelligent interface The sole purpose of Model TRI-S is to monitor and modules from Siemens—Fire Safety is designed to report the status of the contact,while Model TRI-R provide the means of interfacing direct shorting incorporates an add ressa ble'Form C relay. The devices to Model MLC for the FireFinder XLS FACP, relay and contact device input for Model TRI-R are or to Model ALD for the MXL system, respectively. controlled at the same address. The relay and input The Model TRI-series of intelligent interface contact can be controlled as a separate function. modules provides the most advanced method of The relay is typically used where control or shunting address programming and supervision—combined of external equipment is required. with sophisticated FACP communication. Each Model TRI-D is a dual-input module that is designed to Model TRI-series interface module incorporates a supervise and monitor two(2)sets of dry contacts. microcomputer chip. In turn,the microcomputer- Model TRI-D requires two(2)address settings. Model chip technology and its sophisticated bi-directional TRI-D is ideal for monitoring a waterflow switch and its communication capabilities with the FACP,achieve respective valve tamper switch. the state of an'Intelligent Device: Model TRI-series has a multi-color LED that flashes Specifications green when operating normally;amber, if unit is in The Model TRI-series of intelligent interface trouble condition,and red to indicate a change of modules is available in three(3) models. Models status command. Model TRI-D flashes two(2)times— TRI-S and TRI-R are designed to monitor a normally once for each address,and the red LED of Model TRI-R open(N.O.)dry contact. The interface module indicates a change of state in the relay. reports the contact's status to the FACP. TRI Series—Intelligent Initiating Interface Modules 61 79 SIEMENS Industry, Inc. Building Technologies Division 1 . 47 Specifications — (continued) Electrical Ratings The microcomputer chip for the Model TRI-series of Current Draw: 1.5mA devices has the capacity of storing—in memory— [Active or standby] identification information as well as important Model TRI-R Relay Ratings: operating status information. 4A,125VAC Siemens—Fire Safety innovative technology allows Resistive: 4A,30VDC all Model TRI-series intelligent interface modules to 3.5A,120VAC[0.6 P.F] be programmed and tested,via Model DPU or the 3.OA,30VDC[0.6 P.F] FPI 32 Programmer/Tester. Each of these Inductive: 2.OA, 120VAC[0.4 P.F]2.OA, 120VAC[0.35 P.F] programmer/testers is a compact, portable and 2.OA, 120VAC[0.35 P.F] menu-driven accessory that makes programming and testing an interface device faster,easier and more dependable than previous methods. Mounting Diagram Model DPU or the FPI-32 eliminates the need for mechanical addressing mechanisms(such as: MOJNJT NU SI_015 SOH 4-INCH program jumpers, DIP switches,or rotary dials), SNNIU..14HOX since either programmer I tester device ' electronically sets the address of the Model TRI- series into the interface's microcomputer-chip, non- i volatile memory. Vibration,corrosion and otherLED conditions that deteriorate mechanical addressing 102 mechanisms are no longer a cause for concern. VOUWINO O The Model TRI-series of intelligent interface sa �> F of s For; modules is fitted with screw terminals for ,, 1rvVlCHl1l Ali connection to an addressable circuit,and is fully pia; compatible on the same circuit with all intelligent - - Model FP; Model IL and Model ID-60-series \ a' 6,' detectors.Model MSI Series addressable manual stations,or any other addressable intelligent ---- ivN,?IiNTft;S 07S modules,such as Model CZM or Model ICP. �QII oca.ai:t �aN All Model TRI-series intelligent interface modules svv rcr{00x are SUL and®ULC Listed. Details for Ordering Model Part Shipping Wei.9ht Number Number Description �.. Oz. Kg. TRI-D 500-896226 Dual-Input Intelligent 7 0 2 Interface Module Single-Input[w/relay] TRI-R 500-896224 Intelligent Interface 7 0.2 Module Single-Input TRI-S 500-896225 Intelligent Interface 7 0.2 Module Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario Building Technologies Division Tel:(973)593-2600 (Su-Fs) L6T 5E4/Canada Supersedes 2e0a�5/ob FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 nee.i� URL:www,usa,Siemens.com/Fire FAX:(905)799-9858 1 . 48 SIEMENS Data Sheet Fire Safety&Security Products Intelligent Initiating Devices Intelligent Device Interface Module Model HTRI-M (STRI-M for Canada) ARCHITECT AND ENGINEER SPECIFICATIONS • Interfaces and supervises normally open(N.O.)contacts: [i.e.—fire detection] • Interfaces and supervises normally closed(N.C.)contacts: [i.e.—security detection] • Compact size allows mounting in single-gang box behind equipment • Polarity insensitive with SureWir6rm technology • Innovative technology supports comprehensive system and interface communication ^•� «t • Dynamic supervision r. • Two-wire operation YM!7.U7a;U> • Device Programmer/ Test Unit programs and verifies address and test functionality sW'NWres • ®UL Listed,®ULC Listed; FM,CSFM and NYC Fire Department Approved Product Overview Specifications The Intelligent Interface Module(Model HTRI-M) Each Model HTRI-M interface module is is designed to provide the means of interfacing programmed,via Model DPU,which is a compact, direct shorting devices to the Device Program! portable and menu-driven accessory that makes Test Unit(Model DPU)for various Siemens—Fire programming and testing a given interface more Safety fire-alarm control panels(FACPs). accurately and efficiently than ever before. Model HTRI-M provides the most advanced Model DPU eliminates the need for mechanical- method of address programming and supervision addressing mechanisms—such as program —including sophisticated FRCP-communication— jumpers, DIP switches or rotary dials—since in the fire and life safety market. Each Model Model DPU sets the interface address of Model HTRI-M interface module incorporates HTRI-M into its microcomputer-chip, non-volatile microcomputer-chip technology,and advanced memory electronically. bi-directional communication capabilities with the Vibration,corrosion and other conditions that respective FACP. deteriorate mechanical-addressing mechanisms Model HTRI-M is designed to monitor a N.O. or are no longer a cause for concern. Model HTRI-M N.C.dry contact,and reports the contact status to is connected to Model DPU with the programming the FACP. The microcomputer chip for Model cable provided with the tester.This programming HTRI-M has the capacity of storing—in memory— cable(P/N 110-e94927) utilizes two(2)alligator identification information, as well as integral clip connectors,to attach to the HTRI-M. operating-status data. Intelligent Device Interface Module 6308 SIEMENS Industry,Inc. Building Technologies Division 1 . 49 Specifications—(continued) Electrical Rating Model HTRI-M has five (5) leads [one(1)of the Current Draw: five(5) leads is for grounding],which are wired (Active or Standby) 1.5mA to the system with user-supplied wire nuts. Model HTRI-M is fully compatible on the same Model DLC circuit with all intelligent Siemens Details for Ordering Model'H'-series detectors; Model'HMS'-series addressable, manual stations;or any other Model Part Model'H'-series addressable intelligent modules Number Number Description (i.e.—Model HZM or Model HCP). HTRI-M 500-034000 single-Input Intelligent Interface Module In Canada,order: Model Fart Descript Number Pfalrriber ion, ,,, STRI-M 500-034000c single-Input Intelligent Interface Module Note: For shipping-weight considerations,each Model HTRI-series is approximately 3.5 oz.(0.1 kg). Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario June 2013 Building Technologies Division Tel:(973)593-2600 Sii_FS L6T 5E4/Canada Supersedes sheet dated 12/11 FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 (Rev.3) URL:www.usa.Siemens.com/Fire FAX:(905)799-9858 1 . 50 EaST TM Conventional Initiating L11e Safety a Communlcatlons Rate-of- ri se/Fixed Temperature Heat Detectors 280B-PL Series (0 Overview Standard Features 28OB-PL Series heat detectors offer fixed temperature or combs- • UL listed for 50 ft.(15.2m)spacing nation rate-of-rise and fixed temperature detection. • Single pole — normally open contact RATE-OF-RISE:A temperature Increase at the sensor of 15T • Low profile with mounting plate (9°C)or more per minute activates the rate-of-rise feature,This • Pure white finish closes the contacts in the sensor to transmit the alarm condition Mounting fiexibillty with screw terminals to the fire alarm control panel.When the rate-of-rise element alone has been activated,the sensor is self-restoring. • Easy twist-on installation FIXED TEMPERATURE:If the temperature of the center disk • On-site testing of rate-of-rise feature rises to the sensor's rated temperature,the fixed temperature • Positive operating indication —for fixed temperature element element activates.This closes contacts in the sensor and trans- mits an alarm condition to the fire alarm control panel.The fixed temperature element Is non-restorable and,when activated,the Application detector must be replaced.The need for replacement is indicated Heat detectors are most suitable for environments where rapid fire when the center disk has fallen free from the detector. development can be expected.When selecting the location on the ceiling for the heat sensor,do not locate it in direct path of hot or cold air flow.Refer to the detector specifications for the recom- mended maximum spacing,Earlier detector response may be obtained by reducing the spacing between detectors. Installation Edwards 280B series heat sensors come standard with a white plastic reversible mounting plate.The plate is designed for surface or flush mounting and installs directly to a standard North Ameri- can Th or 4 inch octagon box.Once the mounting plate is fixed,a simple twist will lock the sensor in place.It can be removed using a screwdriver to release the tamper-resistant locking finger.This helps prevent unauthorized removal. Page 1 of 2 85001-0261 Issue 4 1 . 51 Mounting The plastic mounting plate is molded to accommodate To NJSTARR O - TO NS AR CT exposed wiring. DETECTOR AND MOUNTING PLATE,PUSH UP AND TURN (INeI�Su,C'u'�) CLOCKWISE. _ 4 -1 ct - _.._ 1-leg, 'QE-bWARDS TO LOCIG DETECTOR ITH t LIFT LOCMNG FlNGEfl WfTN C NMM,,MW g A UTC Fire 4 ewurlty Company SCREW DRIV TIP AND TURN DETECTOR COUNTER- CLOCKWISE Detection&alarm since 1872 o.lu• +mm) U.S. 2LOC1gHG rwacfls T 888-378-2329 SURPACE FLUSH SURFACE MOUNTING MOUNTING p MOUNTING F 888-503-3998 sloE — Canada Chubb-Edwards >+� (/27mm) SURFACE I1Mmn) - -T_ _ T 519 378 2430 MOUNT 2 IN-OUTS F 519 376 7258 N WIRE ETFiMlCE .� Southeast Asia " T:+65 6391 9300 F:+65 6391 9306 BREAK AWAY 2 SECTIONS IRONY VI" (52—) FROMT VIEW ON CIRCUMFERENCE Meaty M—'Pme PM India 2Ao#1PL iadar rlwntaN) PNntie RFaerN°la Meaning PYIe C,I.N.YHGAPL T:+91 80 4344 2000 F:+91 80 4344 2050 Specifications Australia T+81 3 9239 1200 Catalog Number 281E-PL 282B-PL 283B-PL 284B-PL F+61 3 9239 1299 UL Temperature Rating 135°F(57°C) 194°F(90°C) 135°F(57°C) 194°F(90°C) Europa UL Max Ambient Temp,at T+32 2 725 1120 100°F(38°C) 150°F(66°C) 100°F(38°C) 150°F(66°C) Ceiling + 2 2 72188 13 Fixed Temperature and Rate-of- Latin America Detector Type Rise Rate-of-rise; Fixed Temperature Only T 305 593 4301 151 F(9°C) self restoring F 305 593 4300 UL Recommended Cover- 2,500 ft.'(232 m� age" utaflroandseourkyoom UL Recommended Spacing _ 50 ft,(15.2 m) ®2010 UTC Fin&Security. FM Recommended Spacing 30 ft,(9.14 m) All Hphts nerved, --� - .— _. _ _ _. UL Maximum Distance from 25 It,(7,6m)from any wall or prolactlon extending down from the Wall ceiling more than 12 Inches(305 mm) Contacts-Rating Single Pole Normally Open 3,0 amps at 6 to 125 Vac; 1.0 amp at 6 to 28 Vdc,0,3 amps at 125 Vdc;0.1 amps at 250 Vdc WARNING-use For Proparty Protection only:Hen wet- Operating Environment Indoor-Dry sore do not protect We sgalnet Aro and amoke,In moat fins, _ hez rdotm Lewis of smoke,hat and tondo ewes can build up Agency Listings ____ UL,FM CSFM before a hen detector would Ingots,on Wart,klependent Maximum detector cove rage has been detemlkted by 111.to provide deteCtion time equal to BprknWer tieviCeB studies Indeste that hat detectors should"be used wan spaced at 10 R(3.05m) intervals on a smooth ceiling 15 feet 9 Inches(4,8m)high,Higher ceilings may adversely property protection alone Is Involved.In can when We safety affect detection time.Earlier detection may be obtained by reducing the spacing between sensors,(See NFPA 72, Is a factor,the use of smoke detectors Is moo nxmrnded, Chapter 5) Under no circumstances should heat detectors be relied upon as the sole measure to ensure Are*Wetly.However,If they am B�ina ON direct"in the w spy" Ordering Information done tebb,these sensors can contribute,wAllrn an overall Are safety proyam,to redo oN Me risk of odd"propeny ' Wt. Cat.No. Description Ship lb ip 281 B-PL _Heat Detector,135°F(57°C),Rate-of-'Ris_e and Fixed Temperature ------------- 282E PL Heat Detector, 194°F(90'C),Rate-of-Rise and Fixed Temperature _ 1.0 (0.5) 283E PL Heat Detector 135°F(57°C), Fixed Temperature 2846-PL Heat Detector, 194'F(90°C), Fixed Temperature Detector Accessories 280A-PL Plastic Mounting Plate -White,Reversible(included) 0 Page 2 of 2 85001-0261 N Issue 4 1 . 52 _= Intelligent Detection Devices Photoelectric Smoke Detector Mode! OP921 ARCHITECT AND ENGINEER SPECIFICATIONS • Compatible with Siemens Model'H'-series devices on the same loop (with Cerberus PRO fire-alarm control panels[FACPs]or Fir•erind6o XLS FACPs) - • Compatible with Model 87201 DPU (device programmer/loop tester) • Utilizes advanced microprocessor-based signal processing - • Extended temperature and humidity operating range • Each detector is self-testing: - • Self monitored for sensitivity within S UL Listed limits _ s • Complete diagnostics performed every 10 seconds , i sty 9i. - • Polarity insensitive utilizing Sure Wire"technology • Compatible with Model DS-11—series mounting bases • Tri-color detector-status LED with 360°viewing • Field-selectable application sensitivity profiles • Remote sensitivity-measurement capability • Automatic environment compensation • Utilizes advanced signal processing . ®UL268A Listed [for direct air-duct use], • Superior EMI!RFI immunity ®ULC Listed; FM (03230,3210)and CSFM • RoHS compliant ("7272-0067:0258)Approved Product Overview The Photoelectric Smoke Detector(Model OP921)uses Model 87201 DPU eliminates the need for cumbersome, state-of-the-art microcontroller circuitry and surface- unreliable mechanical programming methods,such as dials mount technology for maximum reliability. Model or switches,and reduces installation and service costs by OP921 incorporates an optical sensor using a light- electronically programming and testing the detector prior to scattering detection principle. The device utilizes installation. advanced software algorithms to analyze the signals, For proper operation of the field-device programmer l test and provides highly stable and accurate smoke unit,the technician selects the accessory's program mode, detection. and enters the desired address. In turn,Model 87201 DPU Further,Model OP921 uses state-of-the-art automatically sets and verifies theaddress,as well as tests microprocessor circuitry with error check;detector self- the detector. When in the'tese mode,Model 87201 DPU will diagnostics,and supervision programs. perform a series of diagnostic tests withoutaltering the - Field-Device Programmer/Test Unit address or other stored data,allowing technicians to determine if the detector is operating properly. Model OP921 is compatible with the Siemens field- Model 8720 i DPU operates on AC power or rechargeable device programmer l test unit(Model 87201 DPU), batteries,providing flexibility and convenience in which is a compact,portable,menu-driven accessory programming and testing equipment from practically any for electronically programming and testing detectors location. easily and reliably. Cerberus® PRO 9902 Fire Safety Products Photoelectric Smoke Detector Answers for infrastructure SIUMENS 1 . 53 Product Overview -- (continued) Sensitivity settings Model 8720 i DPU operates on AC power or rechargeable Application Parameter Sets batteries, providing flexibility and convenience in Model OP921 provides four(4)pre-programmed programming and testing equipment from practically any sensitivity parameter sets that can be selected by the location. FACP to match the expected application or Model OP921 is a plug-in, two-wire and addressable environmental conditions: p g photoelectric smoke detector. Model OP921 is •Sensitive.standard @Underwriters'Laboratories Listed[®UL268A Listed for •Robust direct in-air duct usage]. •Air-duct Each detector consists of a dust-resistant photoelectric Sensitive: This application parameter set is practically chamber and microprocessor-based electronics with a suitable for areas where few misleading sources of false low-profile plastic housing. Every Model OP921 fire alarm are present,and is appropriate where priority is detector is shipped with a protective dust cover: given to detecting open fires as soon as possible(e.g.- typically a clean application with controlled environmental conditions.) 1 Standard: This application parameter set is practically apt for normal office,hotel-lobby-type applications, and is the default setting. Robust: This application parameter set offers improved resistance to false alarms in areas where - misleading sources,such as cigarette smoke or exhaust M1f F fumes,may cause a nuisance alarm. = Air-Duct: This application parameter set is used when 1. Dustcover the detector is used a @UL268A(DI)compliant direct in- 2. Srnoliedetector air duct application without a duct housing. Model OP921 does not require a field sensitivity test. Operation Model OP921 is @UL Listed as a self-testing device and Model OP921 is a wide-spectrum,photoelectric smoke complies with NFPA 72 as a self monitoring detector detector incorporating an infrared light-emitting diode and control panel arrangement. This parameter set is (IRLED),and infrared light-sensing photodiode. Under also used when Model OP921 is used in air-duct normal conditions,light transmitted by the LED is housings(Models FDBZ492 and FDBZ492-NR). directed away from the photodiode and scattered The visible LED flashes green every 10 seconds to through the smoke chamber in a controlled pattern. indicate communication with the FACP,and to notify The smoke chamber is designed to manage light Model OP921 has passed its self-test. Should Model dissipation and extraneous reflections from dust particles OP921 sense a fault or failure within its system,the LED or other non-smoke,airborne contaminants in such a will flash amber,and the detector will transmit the data way as to maintain stable,consistent detector operation. to the FACP. When smoke enters the detector chamber,light emitted A quick visual inspection is sufficient to indicate the from the IRLED is scattered by the smoke particles,and is condition of Model OP921 at any time. if more detailed received by the photodiode: information is required,a printed report can be provided from the compatible FACP,indicating the status and settings assigned to each individual detector. When Model OP921 moves to Alarm mode,the detector will flash red and continue flashing until the system is reset at the FACP. At that same time,any user-defined, system-alarm functions programmed into the system are activated. Model OP921 contains a tri-color LED indicator,capable of flashing any one(1)of three(3)distinct colors: ' green,yellow,or red. During each flash interval,the 1. Labyrinth microprocessor-based detector monitors the following: 2. Optical transmitter 3, optical receiver SIEMENS Industry,Inc. Cerberus@ PRO Building Technologies Division 1 . 54 Operation -- (continued) •Smoke sensitivity is within the range Model OP921 can be applied within the maximum 30- indicated on the nameplate label feet center spacing(900 sq.ft. areas),as referenced in •Smoke in its sensing chamber NFPA 72. This application guideline is based on ideal •Internal sensors and electronics are functional conditions—specifically,smooth ceiling surfaces, Based on the monitoring results,the LED indicator minimal air movement,and no physical obstructions flashes the following colors based on the following between potential fire sources and the actual detector. conditions: Do not mount detectors in close proximity to Flash ventilation or heating and air-conditioning outlets. Flash Condition Interva! Exposed joints or beamed ceilings may also affect safe Color spacing limitations for detectors. (in seconds) P 9 Normal supervisory operation. Should questions arise regarding detector placement, Green* Smoke sensitivity is within rated 10 observe NFPA 72 guidelines. Good fire-protection i.....__ limits. system engineering and common sense dictate how Yellow- Detector is in trouble and needs 4 and when fire detectors are installed and used. replacement. Contact your local Siemens—Fire Safety distributor or Alarm condition. 1 sales office whenever you need assistance applying No Flash: Detector is not powered. —— Model OP921 in unusual applications. Be sure to LED can be turned OFF. follow NFPA guidelines and OUL listed IOULC listed *Please followthe corresponding description of the panel used. installation instructions—included with every Siemens— Fire Safety detector—and local codes as for all fire- Aquick,visual inspection is sufficient to indicate thecondition of protection equipment. the detector at any time. If more detailed information is required, a printed report can be provided from the respective Cerberus PRO Technical Data FACP that indicates the status and settings assigned to each individual detector. Operating Temperature +32°F(0°C)to 120°F(49°C) Installation Range: All Model OP921 detectors use a surface-mounting base, Relative Humidity: 0—95%;non-condensing Model DB-11 or Model DB-11£,which mounts on a 4-inch octagonal,square or single-gang electrical box. The base Air Pressure: No effect utilizes screw-clamp contacts for electrical connections and self-wiping contacts for increased reliability. Air Velocity: 0—4,000 ft.i min(0-20m I sec) The Model DB-11 base can be used with the optional Model LK 11 Input Voltage Range: 16VDC—30VDC detector locking kit,which contains 50 detector locks and an installation tool to prevent unauthorized removal of the detector Alarm Current(max.): 280NA head. Model DB-11 has decorative plugs to cover the outer- mounting screw holes. Standby Current(max.): 280pA, max. (average) Model OP921 may be installed on thesame initiating circuit Maximum Spacing: 30-foot centers(900sq.ft.), with the Siemens Model I-rseries detectors[when used with per NFPA 72 the Cerberus PRO FACPsj-- • Model HFP-11 Detector Weight: 0.317 lbs.(0.144 kg.) •Model'HMS'-series manual stations •Model'HTRI'-series interfaces Mechanical Protection Guard: •Model HCP output-control devices ®UL Listed l OULC Listed • Model'HZW series of addressable, [with STI Guard Model STI-9604] conventional zone modules Application Data Installation of Model OP921 detectors requires a two-wire circuit. In many retrofit cases,existing wiring may be used. 7-tapping'is permitted only for Style 4(Class B)wiring. Model OP921 is polarity insensitive,which can greatly reduce installation and debugging time. SIEMENS Industry,Inc. Cerberuso PRO Building Technologies Division 1 . 55 Mounting Diagram Details for Ordering Dimensions Pelt 4-13" I10.5 cm-)-- _p Model Descrlptlon .: �:N.uh�ber �. El CD T OP921 S54320-F4-A2 Photoelectric Smoke Detector r y,.. DR-11 500-094151 Detector Mounting Base ti.s cA.i DR-11 E 500-094151 E Detector Base{small) t.sa� DB2-HR S54320-F12-Ai Relay Base RL-HC 500.033230 Remote Alarm Indicator: V octagon-box mount,red RL HW 500-033310 Remote Alarm Indicator: single-gang box mount,red FDBZ492 S54319-822-A1 Addressable Air-Duct Housing Detector Compatibility Table FDBZ492-HR S54319-823-Al Addressable Air-Duct l� y Detector with Relay Bata LK 11 500-695350 Base Locking Kit Model Sheet Rescnptlott STI-9604_1 STI Mechanical Protection Guard N.uiinber. See: www.STI-USA.com for further details on ordering 6300 FireFinderm XLS(system overview) Model STI-9604. FC901 9813 50-point panel FC922 9815 252-point system(networkable) In Canada, order: FC924 9815 504-point system(networkable) t 252-point intelligent voice Part Fv922 9821 Model Dscnptfon communication system ; -.Idumbet FV922 9821 504-point intelligent voice DO-11C 500-095687 Detector Mounting Base communication system for@ULC(Listed) SIEMENSCerbe rus® PRO NOTICE--The information contained in this data-sheet document is intended only as a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical,limitation and liability information. Siemens Industry,Inc.--Building Technologies Div. Copies of these instruction sheets and the General Product Warning and Limitations document, 8 Fernwood Road • Florham Park,N1 07932 which also contains important information,are provided with the product and,are available Tel:(973)593-2600 • Fax:(908) 547-6877 from the Manufacturer. information contained in these documents should be consulted before specifying or using the Web:www.USA.Siemens.comlCerberus-PRO product. For further information or assistance concerning particular problems contact the Manufacturer. Building Technologies Division March 2015—supersedes sheet dated 1112011 (Rev.5) SII—Fire Safety (Printed in US.A 1 1 . 56 4 I Wl g yt��g� e � P r Features • Absorbent Glass Mat (AGM) technology for superior performance • Valve regulated, spill proof construction allows safe operation in any position • Power/volume ratio yielding unrivaled energy density • Rugged impact resistant ABS case and cover(UL94-1-113) • Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified • U.L. recognized under file number MH 2O845 9tl Terminals (mm) Performance , ecifications Nominal Voltage........................................................................12 volts(6 cells) Nominal Capacity pos• t Tin plated brass �-A H 20-hr. (1.4A to 10.50 volts 28.0 AH post with'Nut&Bolt, ) ............................................................ fasteners v O 61112 10-hr. (2.62A to 10.50 volts).......................................................... 26.2 AH 5-hr. (5A to 10.20 volts) ............................................................... 25.0 AH 1-hr. (18.6A to 9.00 volts) ............................................................ 18.6 AH 15-min.(58.8A to 9.00 volts)..............................................................14.7 AH Physical Dimensions: Approximate Weight ........................................................ 20.70 lbs.(9.39 kg) Energy Density(20-hr.rate) ................................. 1.51 W-h/in3(91.99 W-h/1) fpeclflc Energy(20-hr.rate) ............................. 16.23 W-h/lb(35.79 W-h/kg) W Internal Resistance(approx.) ...................................................... 10 milliohms Max Discharge Current(7 Min.) ............................................... 84.0 amperes Max Short-Duration Discharge Current(10 Sec.)................ 280.0 amperes Shelf Life(%of nominal capacity at 68°F(20°C)) ° 1 Month......................................................................................................97% T3 Months.....................................................................................................91% HTH 6 Months....................................................................................................83% e Operating Temperature Range L Charge..............................................................4•F(-20•C)to 122•F(500C) Discharge........................................................40°F(-40°C)to 140°F(60°C) L 6.50(165) W.4.92(125) H:6.97(177) HT:6.97(177) Case......................................................................................................ABS Plastic Tolerances are+/-0.04 in.(+/-1mm)and+/-0.08 in.(+/-2mm)for Power-Sonic Chargers............................................PSC-124000A, 124000A-C height dimensions.All data subject to change without notice. lb ensure satc r efficient operation always refer to the latest edition of our Technical Manual,as published on r All data subject to change without nolict www.power-sonic.com / 12 Volt 28.0 AH 100 14.0 ag�y�ne Ambient Temperature 20°C 68°F necessary unless p 100%of Rs require 13.0 a 80 . C before C 5°C use is necessary m 12.0 (41°F) to help recover pf C Ifull capacity. 11.1 nnay fail to restore full io 1.40 40°C 30°C 20°C capacity.Do not c 10.0 2.8 R 40 (104°F) (86°F) (68°F) miser sreach € 5.6 tea 0 12m 9.0 14 U 0 2 4 6 8 10 12 14 16 18 20 Final Voltage 28 Standing Period(Months) 8.0 56 1.2 2.4 6 12 24 36481 2 4 6 8 10 20 4 0 Discharge Tin1e vs. (Jisch�l e Current �._ min ►I'*--h .1 20 Discharge Time 15 10 Life Characteristics in Stand-By Use L Ambient Temperature 20'C(68'F) £ 5 Final 0 100 Voltage m 2 10.5V �� 80 10.2V R 60 a 1 Floa777 t Charging Voltage c 40 2.25-2.30 V/Cell 30 m 20 m 0 F 9.OV 0 1 2 3 4 10 40oC(104°F) 20°C (68°F) Years 0°C (32°F) 5 8.1 V Life Characteristics in Cyclic Use 1.40 2.8 5.6 14 28 56 120 Discharge Current(A) 100Eli =Mt e 80 Cycle Applications:Limit initial current to 8.4A.Charge until battery voltage SL (under charge)reaches 14.4 to 14.7 volts at 68°F(20°C).Hold at 14.4 to 14.7 60 Discharge Dlscharge Discharge volts until current drops to under 280mA.Battery is fully charged under these Depth 100% Depth sov Depth 30% conditions,and charger should be disconnected or switched to"float"voltage. c 40 m 1.Discharge Current 0.2C(Final Voltage 1.7VICell) "Float"or"Stand-By"Service:Hold battery across constant voltage source of m 20 2.Charge Current:0.1C 13.5 to 13.8 volts continuously.When held at this voltage,the battery will seek its 3.Ambient Temperature:20°C to 25°C(68°F to 77°F) own current level and maintain itself in a fully charged condition. 0 0 200 400 600 800 1000 1200 Note:Due to the self-discharge characteristics of this type of battery,it is Number of Cycles imperative that they be charged within 6 months of storage,otherwise permanent loss of capacity might occur as a result of suifation. Further Information Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH. Please refer to our website www.power-sonic.com for a complete range of useful Please refer to the Charger Selection Guide in our specification sheets for"C-Series downloads,such as product catalogs,material safety data sheets(MSDS),ISO Switch Mode Chargers"and"Transformer Type A and F Series".Please contact our certification,etc.. Technical department for advice if you have difficulty In locating suitable models. Contactr rwww.power-sonic.com DOMESTIC SALES CUSTOMER SERVICE TECHNICAL SUPPORT INTERNATIONAL SALES Tel:+1-619-661-2020 Tel:+1-619-661-2030 Tel:+1-619-661-2020 Tel:+1-650-364-5001 Fax:+1-619-661-3650 Fax:+1-619-661-3648 Fax:+1-619-661-3648 Fax:+1-650-366.3662 national-sales@power-smic.00m customer-servioe@power-sonic.com support@power-sonic.com intematonal-sales@power-sonic.com CORPORATE OFFICE• 7550 Panasonic Way• San Diego,CA 921.54• USA•Tel:+1-619-661-2020• Fax:+1.619-661-3650 0211 1M ®2011.Power-Sonic Corporator.All rights reserved.All trademarks are the property of their respecfive owners. 1 . 58 Battery Calc Sheet Edtable Text Version Fixed Ref.No. ,__'._Calculated Submhted By: Project Name: Project Location: Panel Location: Node No: Date: Power Calculations Befirort,Calculations 24V 6.2V Screw Terminal 24V Module Device Description City Backplane Bane Current(mA) Standby 24 VDC Current Current Current (.A) (E) Standby Alarm AIC Audio Input Cab .,. -,.... ALCC Audio Levol Conversion Card t:. ... CDCIA Conventional Detector alb WeCDC4MOM CRCS controlR Reb .Form C D23DDGP I Fill Interface D2326CPS DAc Digital Audio Card DDC DFM INeIDWar CaN NETFiber " Modub ,Y.�' DLC Daviae Loop Card t HFP-11 Photo4hermal detector HFPT-11 Thentrial detectorl. CS41 - DUN oplicallithesingrCO dabGa OOH041 Dust oplicalilinermad detector a OH021 dabdor OPM Photo datactor - 134 I921 Therniall detector FDOOTC"l Dual oplicalithernialICO debetm FDOOT441 Dusttletector ' FD0T421 Photo-Mamml detectore -F00421Photo detector FDT421 Themrl detector FDC1OAFDCIO B. mredub - HMS-25 -µatonal station- HMS-s Manuel station...., --_ HMS-M Manuel station HMS-GA Manual orb ion HMS-6 Manuel station HTRtS Single input module ffi WI-D DZI module HTRI-R S module 1 HTRt#1 to -rrlintewtlale 44 M2M Conwntlonal zone modub MCP Addiversable S22" i-SD44C Irdswasnit LED #LEDkW Intelligent LED _ .. Other FGM - Fan Control Modub FCM Swaches FMT hta'Mae T FN2= Moduas FN200T Fbar Opfic Module HUB-4 FW—n nlcabon Module-1 polts LCM LED Control Module LEDPIOM LED$ lPB Loco]P Board LVMI LMe Voice Module . SIsaM LC CZM-1 Ramop Conven0o�Zonal Module FP•11. „:Pholoserlaamor . 'r FPT-11 i.-Photo eM thamvl: -Into ant coldrd tCP70 ID-SOI I nt thenlwl detector .> ID60V ID-WH ID440Wi '•. .- IDWSH I. ID-WD 1680PT iD80T ILI-11-1M bnttation date&—0300ItAnn. NJ-1A/-1AH ILI-1B61BH ILP YALPT-1 Photoelectric detector MSI-1-2 =;Intaftentnanuai station TRW Irfacs nwdUM TRMD ImMbce dua4tn module x5 TRI-OOR Addresslible interface module MLC Ext Al Lme Cord Bet NIC Network krbrface Cad 1 NIC Xnat Network Interface Card Xnet NIM 7W Network Interbce Module-Wide Area NRC -Network Ring Card C. OCIA Contrd Mcduk CoOedor PMI Control Panel �� .sue •. '.:.. TSP40A Thamal Sbi Printer •�, PMI-2 Control Panel 1 TSP-40A Thermal Strip Printer ,"#�. RNI Remote Network Interface RPM See Note 2 Renrote Printer Module am Switch Control Module �.Switch - ANve PushbuttonSvftch Sim StipannsedirpAlldule „ SBA device SIM Input Sim Relay ROW SSD TZC Teb ne Zone Card '°">T'- Al VPM See Note 2 Weda peripheral Module HLI See Note 2 High Level Interface card XOMC XLS Digital Message Card �. ZAC40 Zone Alrl MlerCard-40W Zone AMDMw Card-40W ZAM120. Zone Cerd-120W - Tatal - 12088dnu Zara APIMW Card-12OW Total ZICs Zane Indicating Cards 9a eo fu MC abet PSC-12 POWW.SuEgy Card M Waft PSC Rela c_Relay on the PSC f See Note l: AUX Standb Current rrA on AC: ram. w See Note 1 AUX Alarm Current mA an A.C. See Note 1 UX Standb Current on m4 - See Note 1 AUX Alarm Current on mA PSX--12 Power Supply Extender 286 Watt - - SeaNatat XStarMD Conant m4 on AC. - -_ B"Note t UX Alarm Current rmAll on A.C. See Note 1 UX Standby Current on Battery rri �"-^' wal Sea Note 1 X Alarm Current on MX Power Supply Limlta Parameter M.value Actual value -Result 24V kne Currant 2A 0.404 8.2V Current 2A 0.200 Tote BeM Sta Currwt 5 0.525 Total 24V Alem Current 12A•Number of PS 0.614 Battery Calculation Max Standby phis] w,mwy:ss mwsrw+.ev .«omp. ,vr+entsl�re.ru r.xesot.aawr..wxers 24 Max AlartlltMnj 5 Battery meeve ]. 20 RegWrod Bdtwy C 17a8 RegpM letlln reserve N.19 Note 1:For each HCP,HZM,CZM-1,ICP25 6 ICP70 add the following current to each PSC-12fPSX-12 AUX power entry if these devices are receiving power from this PSC-12/PSX-12. HCP HZM CZM-1 ICP25 ICP70 AUX Monday Curtest WAI 30 MA 76 mA 12.5 mA OM 10 mA ar UX Am Currant,A m 30 A m 100 A 50 rtW 10 m4 10 m4 UX CURMnt on 30 mA 1 76 mA 112.5 mA 10 mA 1 10 mA AUX Alum Current on B mA - 30 MA 100 mA 1 50 mA 1 10 mA 1 10 rrA Note 2:Only include this module M M is being powered by a PSC-12 or PSX-12 in this enclosure,otherwise leave the quantity as 0. A2 NEALN— a e w -RE NIAN 51STEM NOLESvoamn��mnNrw. 1 E --s S --s 2s 33 s M A aM, W= SYYWL WLE ,ffD F",= PVA FLOOR -- — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — s u s s s m s m s s m s s s Y s WE LEGEND Cs --s s M s s cs Y cs s s FMI cs 5 s k 9 cs s M cs — — — --- SOUND SMEMS INC. GLEN AT fflLAND YEA WS RRE NMM sYsi RISER