ComCheck COMcheck Software Version 4.1.1.0
IP\Afil Interior Lighting Compliance -
FILE COPY
Project Information
Energy Code: 2015 IECC
Project Title: Glen Falls Center for Nursing and Rehabilitation
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
152 Sherman Ave Greg Galiczewski
Glen Falls, NY 2801 _ Edge Plus Co Architecture, LLC
(] 4770 White Plains Road, First Floor
Additional Efficiency Package(s) D U �L Bronx, NY 10470
11718-408-5100
JUL 15 info@edgeand.com
2019 REVIEWED FOR
Unspecified TOWN OFQUEENSBURY ENERGY CODE COMPLIANCE
Allowed Interior Lighting Power BUILDING&CODES
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B X C)
1-Common Space Types:Office-Enclosed 1014 1.11 1126
Total Allowed Watts= 1126
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
1-Common Spce Tyg ..Office- Enclosed
LED 1:LED Panel 33W: 1 15 33 501
LED 2:Other: 1 1 48 48
LED 3:Other: 1 1 17 17
LED 4:LED Linear 33W: 1 1 30 30
LED 5:Other: 1 2 15 30
Total Proposed Watts= 626
nterior Lighting PASSES: Design 44%better than code
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist. e
LLP1:6 (;),AL-ic-2EwSF1 An NY 44t) ��0Nki• �,---- ---- --- ?ACM
Name-Title Signature �,skED ARc,. Date / I
0 �yM. Gq�,c�0
4/ o c°
ILI �4
* As,� b.,./,
Nf 1
03 714'6 O42-
Project Title: Glen Falls Center for Nursing and Rehabilitation OF NE Report date: 07/11/19
Data filename: C:\Users\Steve\Dropbox\20181SG18029A Glens Falls\Email\E-Mail I. - : •-I6-28\Glen Falls Page 1 of 5
Renovation.cck
Settlon
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID ---C405.2.1 Lighting controls installed to uniformly OComplies
(EL15]1 reduce the lighting load by at least ❑Does Not
50%. ONot Observable
ONot Applicable
C405.2.1 Occupancy sensors installed in OComplies
(EL18]1 required spaces. ODoes Not
ONot Observable
ONot Applicable
C405.2.1, Independent lighting controls installed OComplies
C405.2.2. per approved lighting plans and all ❑Does Not
3 manual controls readily accessible and
(EL2312 visible to occupants. ❑Not Observable
ONot Applicable
C405.2.2. Automatic controls to shut off all OComplies
1 building lighting installed in all ❑Does Not
(EL22]Z buildings. ['Not Observable
ONot Applicable
C405.2.3 Daylight zones provided with OComplies
[EL16)2 individual controls that control the ❑Does Not
lights independent of general area
lighting. ENot Observable
ONot Applicable
C405.2.3, Primary sidelighted areas are OComplies
C405.2.3. equipped with required lighting ❑Does Not
1, controls. ❑Not Observable
C405.2.3.
2 ONot Applicable
(EL20)1
C405.2.3, Enclosed spaces with daylight area OComplies
C405.2.3. under skylights and rooftop monitors ❑Does Not
1, are equipped with required lighting
C405.2.3. controls. Not Observable
3 ONot Applicable
(EL21]1
C405.2.4 Separate lighting control devices for ❑Complies
IEL4)1 specific uses installed per approved ❑Does Not
lighting plans.
ONot Observable
ONot Applicable
C405.2.4 Additional interior lighting power OComplies
(EL8]1 allowed for special functions per the ❑Does Not
approved lighting plans and is ONot Observable
automatically controlled and
separated from general lighting. ONot Applicable
C405.3 Exit signs do not exceed 5 watts per ❑Complies
(EL611 face. ❑Does Not
❑Not Observable
ONot Applicable
Additional Comments/Assumptions:
IJHigh Impact(Tier 1) L2J Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Glen Falls Center for Nursing and Rehabilitation Report date: 07/11/19
Data filename: C:\Users\Steve\Dropbox\2018\SG18029A Glens Falls\Email\E-Mail OUT\2019-06-28\Glen Falls Page 3 of 5
Renovation.cck
A
Project Title: Glen Falls Center for Nursing and Rehabilitation Report date: 07/11/19
Data filename: C:\Users\Steve\Dropbox\2018\SG18029A Glens Falls\Email\E-Mail OUT\2019-06-28\Glen Falls Page 5 of 5
Renovation.cck