RPLUM-001736-2019 04012019INSPECTION WORKSHEET (RPLUM-001736-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0530-2018 Case Module:Permit
Inspection Date:Mon Apr 1, 2019 Inspection Status:Partial Pass
Inspector:Mark Smith Inspection Type:Rough Plumbing
Job Address:Parcel Number:15 GENISTA LN
Lake George, NY 12845
289.10-1-36
Contact Type Company Name Name
Contractor Barber, Daniel
Architect Williams, Danny
Primary Owner Judkins, David
Granted Permission Barber, Daniel
Primary Owner Judkins, Dawn
Applicant Williams, Danny
Checklist Item Passed Comments
Building Inspector Notes NO 4/1/19 plumbing for gas lines approved. Plumbing for radiant
heat under slab approved.
Rough Plumbing / Nail Plates NO
Plumbing Vent Vents in Place NO
3" Vent Through Roof NO
1 ½ inch minimum Drain Size NO
Washing Machine Drain 2 inch minimum NO
Apr 01, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001736-2019)
Checklist Item Passed Comments
Washing Machine Trap: 18"-24" discharge NO
Cleanout every 100 feet change of direction NO
Pressure Test NO Verify pressure for radiant heat
Drain Vent NO
Air Head NO
5 psi or 10 ft. above highest conn. for 15 minutes NO
Pressure Test NO
Water Supply Piping YES Plumbing for radiant heat under slab approved. Holding 50
psi for 15 minutes
Air Head NO
50 P.S.I for 15 minutes NO
Air Test Gas Piping 10 psi for 10 Minutes YES Gas piping verified, holding 10 psi for15 minutes
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO
Apr 01, 2019 Page (2)
Smith, Mark (Inspector)