COM[heck Software Version 4.0.2.2
Envelope Compliance Certificate
EFILE COPY
Project Information
Energy Code: 2014 New York Energy Conservation Construction Code
Project Title: Wedgewood Apartments
Location: Warren County, New York 302,9_1-28.1 CC-000364-2016
Climate Zone: &a
Project Type: New Construction Sehermerhorn Wedgewood LLC
Vertical Glazing/Wall Area: 12% 27-47 Wedgewood Drive, Bldg. #3
8-unit apt. 9782 s.f., garage 2288 s.f.
Construction Site: Owner/Agent: Designer/Contractor:
Burke Drive Schermerhom Properties,Inc. Ethan P. Hall
Queensbury, NY 12804 536 Bay Road Rucinski Hall Architecture
Suite 2 134 Dix Ave
Queensbury, NY 12804 Glens Falls, NY 12801
518-798-0674 518-741-0268
rich@schermerhornproperties.com ephall@nycap.rr.com
Building Area Floor Area
1-Multifamily: Residential 9782
Additional Efficiency Package ,JUN 14 201
Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance.calculations. - --
Envelope Assemblies � ' ``•.:1-' _. ,�.`.- ''��._._. r-.
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R Value U-Factor Factona;
Perimeter
Roof 1:Attic Roof with Wood Joists,[Bldg.Use 1 -Multifamily] 4832 38.0 0.0 0.027 0.021
Exterior Wall 1:Wood-Framed, 16"o.c.,[Bldg.Use 1 -Multifamily] 1593 19.0 3.6 0.052 0.051
Window 1:Vinyl/Fiberglass Frame:Operable,Pert.Specs.:Product IO 62 - - 0.320 0.430
product label,SHGC 0.35,[Bldg.Use 1 -Multifamily](b)
Door 1: Insulated Metal,Swinging,[Bldg.Use 1-Multifamily] 20 - - 0.300 0.370
Door 2: Insulated Metal,Swinging,[Bldg.Use 1-Multifamily] 20 - -- 0.300 0.370
Door 3: Insulated Metal,Swinging,[Bldg.Use 1-Multifamily] 20 - -- 0.300 0.370
Door 4:Insulated Metal,Swinging,[Bldg.Use 1-Multifamily] 20 - - 0.300 0.370
Door 5:Insulated Metal,Swinging,[Bldg.Use 1-Multifamily] 20 - - 0,300 0.370
Door 6:Insulated Metal,Swinging,[Bldg.Use 1 -Multifamily] 20 -- --- 0.300 0.370
Door 7:Insulated Metal,Swinging,[Bldg.Use 1-Multifamily] 20 - - 0.300 0.370
Door 8:Insulated Metal,Swinging,[Bldg.Use 1-Multifamily] 20 - - 0.300 0.370
Door 9:Insulated Metal,Swinging,[Bldg.Use 1 -Multifamily] 20 - - 0.300 0.370
Door 10:Insulated Metal,Swinging,[Bldg.Use 1 -Multifamily] 20 - - 0.300 0.370
Door 11:Insulated Metal,Swinging,[Bldg.Use 1 -Multifamily] 20 - - 0.300 0.370
Door 12:Insulated Metal,Swinging,[Bldg.Use 1 -Multifamily] 20 -- - 0.300 0.370
Door 13:Insulated Metal,Swinging,[Bldg.Use 1 -Multifamily] 20 - 0.300 0.370
Door 14:Insulated Metal,Swinging,[Bldg.Use 1 -Multifamily] 20 --- -- 0.300 0.370
Exterior Wall 2:Wood-Framed,*"o.c.,[Bldg.Use 1 -Multifamily] 461 19.0 3.6 0.052 0.051
Door 15:Insulated Metal,Swinging,[Bldg.Use 1-Multifamily] 20 - - 0.300 0.370
Exterior Wall 3:Wood-Framed,16"o.c.,[Bldg.Use 1 -Multifamily] 190 19.0 3.6 0.052 0.051
Exterior Wall 4:Wood-Framed, 16"o.c.,[Bldg.Use 1-Multifamily] 1593 19.0 3.6 0,052 0.051
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhorn\Wedgewood Apartments\Wedgewood Apartments.cck Page 1 of 20
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R-Value U-Factor Factors",
Perimeter
Window 2:Vinyl/Fiberglass Frame:Operable,Pert.Specs.:Product ID 186 - --- 0.320 0.430
product label,SHGC 0.35,[Bldg.Use 1 -Multifamily](b)
Door 16:Glass(>50%glazing):Nonmetal Frame,Non-Entrance Door, 40 - - 0.320 0.770
Perf.Specs.:Product ID product label,SHGC 0.35,[Bldg.Use 1 -
Multifamily](b)
Door 17:Glass(>50%glazing):Nonmetal Frame,Non-Entrance Door, 40 - - 0.320 0.770
Perf.Specs.:Product ID product label,SHGC 0.35,[Bldg.Use 1 -
Multifamily](b)
Door 18:Glass(>50%glazing):Nonmetal Frame,Non-Entrance Door, 40 - - 0.320 0.770
Perf.Specs.:Product ID product label,SHGC 0.35,[Bldg.Use 1 -
Multifamily](b)
Door 19:Glass(>50%glazing):Nonmetal Frame,Non-Entrance Door, 40 - - 0.320 0.770
Perf.Specs.:Product ID product label,SHGC 0.35,[Bldg.Use 1 -
Multifamily](b)
Door 20:Glass(>50%glazing):Nonmetal Frame,Non-Entrance Door, 40 - --- 0.320 0.770
Perf.Specs.:Product ID product label,SHGC 0.35,[Bldg.Use 1 -
Multifamily](b)
Door 21:Glass(>50%glazing):Nonmetal Frame,Non-Entrance Door, 40 - - 0.320 0,770
Perf.Specs.:Product ID product label,SHGC 0.35,[Bldg.Use 1 -
Multifamily](b)
Exterior Wall 5:Wood-Framed, 16"o.c.,[Bldg.Use 1 -Multifamily] 461 19.0 3.6 0.052 0.051
Door 22:Insulated Metal,Swinging,[Bldg.Use 1 -Multifamily] 20 --- - 0.300 0.370
Exterior Wali 6:Wood-Framed, 16"o.c.,[Bldg.Use 1 -Multifamily] 190 19.0 3.6 0.052 0.051
Exterior Wall 7:Wood-Framed, 16"o.c.,[Bldg.Use 1 -Multifamily] 1294 19.0 3.6 0.052 0.051
Window 3:Vinyl/Fiberglass Frame:Operable,Pert.Specs.:Product ID 54 - --- 0.320 0.430
product label,SHGC 0.35,[Bldg.Use 1 -Multifamily](b)
Window 4:Vinyl/Fiberglass Frame:Operable,Perf,Specs.:Product ID 62 - - 0.320 0.430
product label,SHGC 0.35,[Bldg.Use 1 -Multifamily](b)
Exterior Wall 8:Wood-Framed,16"o.c.,[Bldg.Use 1 -Multifamily] 415 19.0 3.6 0.052 0.051
Exterior Wall 9:Wood-Framed,16"o.c.,[Bldg.Use 1 -Muftifamily] 171 19.0 3.6 0,052 0.051
Exterior Wall 10:Wood-Framed,16"o.c.,]Bldg.Use 1-Multifamily] 1294 19.0 3.6 0.052 0.051
Window 5:Vii nyllFlberglass Frame:Operable,Pert.Specs.:Product ID 310 - - 0.320 0.430
product label,SHGC 0.35,[Bldg.Use 1 -Multifamily](b)
Door 23:Glass(>50%glazing):Nonmetal Frame,Non-Entrance Door, 40 - - 0.320 0.770
Perf.Specs.:Product ID product label,SHGC 0.35,[Bldg.Use 1 -
Multifamily](b)
Door 24:Glass(>50%glazing):Nonmetal Frame,Non-Entrance Door, 40 - - 0.320 0.770
Perf,Specs.:Product ID product label,SHGC 0.35,[Bldg.Use 1 -
Multifamily](b)
Exterior Wall 11:Wood-Framed,16"ac.,[Bldg.Use 1-Multifamily] 415 19.0 3.6 0.052 0.051
Exterior Wall 12:Wood-Framed,16"o.c.,[Bldg.Use 1-Multifamily] 171 19.0 3.6 0.052 0.051
Floor 1:Slab-On-Grade:Unheated,Vertical 4 ft.,[Bldg.Use 1- 449 - 10.0 0.495 0.520
Multifamily](c)
(a)Budget U-tactors are used for software baseline calculations ONLY,and are not code requirements.
(b)Fenestration product performance must be certified in accordance with NERC and requires supporting documentation.
(c)Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Envelope PASSES: ■ ode i"i
Envelope Compliance Statement
Compliance Statement. The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed envelope systems have been
designed to meet the 2014 New York Energy Conservation Construction Code requirements in COMcheck Version 4,0.2,2 and to
comply with the mandatory requirements listed in the Inspection Checklist.
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:ISchermerhorn\Wedgewood ApartmentslWedgewood Apartments.cck Page 2 of 20
Ethan P. Hall-Architect ' IJUA/�
{came-Title Signa rti Date
!IA r4 Ysry...
Project Title, Wedgewood Apartments Report date: 11/03/15
Data filename: Y:1Schermerhorn\Wedgewood Apartments\Wedgewood Apartments.cck Page 3 of 20
COMcheck Software Version 4.0.2,2
Interior Lighting Compliance certificate
Project Information
Energy Cade: 2014 New York Energy Conservation Construction Code
Project Title: Wedgewood Apartments
Project Type: New Construction
Construction Site: Owner/Agent Designer/Contractor:
Burke Drive Schermerhorn Properties, Inc. Ethan P. Hall
Queensbury, NY 12804 536 Bay Road Rucinski Hall Architecture
Suite 2 134 Dix Ave
Queensbury, NY 12804 Glens Falls, NY 12801
518-798-0674 518-741-0268
rich@schermerhornproperties.com ephall@nycap.rr.com
Additional Efficiency Package
Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations.
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts 1 ft2 (B X C)
1-Multifamily 9782 0.60 5869
Total Allowed Watts= 5869
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per tamp!Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
1-Multifamily
Compact Fluorescent 1:Spiral 23W:Electronic: 1 108 32 3456
Total Proposed Watts= 3466
LightingInterior Design better than code
Interior Lighting Compliance Statement
Compliance Statement. The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been
designed to meet the 2014 New York Energy Conservation Construction Code requirements in COMcheck Version 4.0.2.2 and to
comply with the mandatory requirements listed in the Insp ' n Che t,
Ethan P. Hall-Architect gJw
Name-Title ature Date
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:1Schermerhorn\Wedgewood ApartmentslWedgewood Apartments.cck Page 4 of 20
COMcheck Software Version 4.0.2+2
Exterior Lighting Compliance Certificate
Project Information
Energy Code: 2014 New York Energy Conservation Construction Code
Project Title: Wedgewood Apartments
Project Type: New Construction
Exterior Lighting Zone 2(Residential mixed use area)
Construction Site: Owner/Agent: Designer/Contractor:
Burke Drive Schermerhorn Properties, Inc. Ethan P.Hall
Queensbury, NY 12804 536 Bay Road Rucinski Hall Architecture
Suite 2 134 Dix Ave
Queensbury, NY 12804 Glens Falls, NY 12801
518-798-0674 518-741-0268
rich@schermerhornproperties.com ephall@nycap.rr,com
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts 1 Unit Wattage (B X C)
Entry canopy 8 ft2 0.25 Yes 2
Total Tradable Watts(a)= 2
Total Allowed Watts= 2
Total Allowed Supplemental Watts(b)= 600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-trad able and tradable areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID: Description 1 Lamp!Wattage Per Lamp 1 Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Enter canopy(8 ft2):Tradable Wattage
Compact Fluorescent 1:Spiral 23W:Electronic: 1 16 32 512
Total Tradable Proposed Watts= 512
Exterior Lighting PASSES: Desi n 15% better than code
Exterior Lighting Compliance Statement
Compliance Statement. The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed exterior lighting systems have been
designed to meet the 2014 New York Energy Conservation Construction Code recLUirernents in COMcheck Version 4.0.2.2 and to
comply with the mandatory requirements listed in the Insp n Che t
Ethan P. Hall-Architect 4')"Y& j(JlK'
Name-Title St9ilature Date
Project Title: Wedgewood Apartments Report date: 11103/15
Data filename: Y:\Schermerhorn\Wedgewood Apartments\Wedgewood Apartments cck Page 5 of 20
COMcheck Software Version 40002,2
Mechanical Compliance Certificate
Project Information
Energy Code: 2014 New York Energy Conservation Construction Code
Project Title: Wedgewood Apartments
Location: Warren County,New York
Climate Zone: 6a
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor.
Burke Drive Schermerhorn Properties,Inc. Ethan P.Hall
Queensbury,NY 12804 536 Bay Road Rucinski Hall Architecture
Suite 2 134 Dix Ave
Queensbury,NY 12804 Glens Falls,NY 12801
518-798-0674 518-741-0268
rich@schermerhomproperties.com ephall@nycap.rr.com
Additional Efficiency Package
Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations.
Mechanical Systems List
Quantity System Type&Description
1 HVAC System 1(Single Zone):
Heating:1 each-Central Furnace,Gas,Capacity=45 kBW/h
Proposed Efficiency=93.00%Et,Required Efficiency=80.00%Et
Cooling:1 each-Packaged Terminal Unit,Capacity=15 kBtu/h,Air-Cooled Condenser,Air Economizer
Proposed Efficiency=13.00 EER,Required Efficiency=9.30 EER
Fan System: FAN SYSTEM 1—Compliance(Motor nameplate HP method):Passes
Fans:
FAN 1 Supply,Constant Volume,175 CFM,0.5 motor nameplate hp
1 Water Heater 1:
Electric Storage Water Heater,Capacity:0 gallons w/Circulation Pump
No minimum efficiency requirement applies
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document Is consistent with the building plans,
specifications,and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 2014 New York Energy Conservation Construction Code requirements in COMcheck Version 4.0.2.2 and to
comply with the mandatory requirements listed in the Inspeow Checl i t. /J
Ethan P.Hall-Architect , A L1N
Name-Title Si tura Date
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhom\Wedgewood Apartments\Wedgewood Apartments.cck Page 6 of 20
COMcheck Software Version 400.2.2
Inspection Checklist
Energy Code: 2014 New York Energy Conservation Construction Code
Requirements: 100.0%were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen.For each
requirement,the user certifies that a code requirement will be met and haw that is documented, or that an exception
is being claimed.Where compliance is itemized in a separate table,a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
&Re .ID
C103.2 Plans and/or specifications provide all ❑Complies Requirement will be met.
[PR1]1 information with which compliance ❑Does Not
can be determined for the building Location on plans/spec:A-1
envelope and document where DNot Observable
exceptions to the standard are ❑Not Applicable
claimed.
C103.2 Pians,specifications,and/or ❑Complies Requirement will be met.
[PR2]1 calculations provide all information []Does Not
with which compliance can be []Not Observable Location on plans/spec:A-1
determined for the mechanical ❑Not Applicable
systems and equipment and
document where exceptions to the
standard are claimed.Load
calculations per acceptable
engineering standards and
handbooks.
C103.2 Plans,specifications,and/or ElComplies Requirement will be met.
[PR3]1 calculations provide all information '❑Does Not
.with which compliance can be Location on plans/spec:A-1
determined for the service water '❑Not Observable
heating systems and equipment and ❑Not Applicable
document where exceptions to the
standard are claimed.Hot water
system sized per manufacturer's
sizing guide.
C103.2 Plans,specifications,and/or ❑Complies Requirement will be met.
[PR4]1 calculations provide all information []Does Not
with which compliance can be ❑Not Observable Location on plans/spec:A-1
determined for the interior lighting
and electrical systems and equipment :❑Not Applicable
and document where exceptions to
the standard are claimed.Information
provided should include interior
lighting power calculations,wattage of
bulbs and ballasts,transformers and
control devices.
C103.2 Plans,specifications,and/or ❑Complies Requirement will be met.
[PR8]1 calculations provide all Information ❑Does Not
with which compliance can be ❑Not Observable'Location on plans/spec:A-1
determined for the exterior lighting
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed.Information
provided should include exterior
lighting power calculations,wattage of
bulbs and ballasts,transformers and
control devices.
C406 Plans,specifications,and/or ❑Complies Requirement will be met.
[PR9]1 calculations provide all information 0Does Not
with which compliance can be ❑Not Observable Location on plans/spec:A-1
determined for the additional energy
efficiency package options. ❑Not Applicable
11 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\schermerhorn\Wedgewood Apartments\Wedgewood Apartments.cck Page 7 of 20
Section
# Plan Review Complies? Comments/Assumptions
&Req.ID
C402.3.1 Vertical fenestration area <=30 ❑Complies Requirement will be met.
[PR10]1 percent of the gross above-grade wall '❑Does Not
area phot Observable.Location on plans/spec:A-1
❑Not Applicable
C402.3.1 Skylight area <=3 percent of the ❑Complies Requirement will be met.
[PR11]1 gross roof area. ❑Does Not
.❑Not Observable Location on plans/spec:A-1
❑Not Applicable
C402.3.2. Areas with obstructions that block ❑Complies Exception:Skylights designed to exclude direct sunlight
2 direct beam sunlight on>=1/2 of the ❑Does Not entering the occupied space by the use of fixed or automated
[PR15]1 roof over the enclosed area for more []Not Observable baffles.
than 1,500 daytime hours per year
between 8 am and 4 pm. ❑Nat Applicable
Additional Comments/Assumptions:
11 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhom\Wedgewood Apartments\Wedgewood Apartments.cck Page 8 of 20
Sectio-1— Footing/.Foundation Plans Verified Field Verified
# Complies? Comments/Assumptions
&Reg. D inspection Value Value
C402.2.6 Slab edge insulation R-value. R- R- ❑Complies See the Envelope Assemblies
[FO3]2 Unheated ❑ Unheated ❑Does Not table for values.
❑ Heated ❑ Heated ❑Not Observable
❑Not Applicable
C303.2 Slab edge insulation installed per %DComplies Requirement will be met.
[FO4)2 manufacturer's instructions. ❑Does Not
❑Not Obseryable Location on plans/spec:A-
x•
TIN
ot Applicable 1
C402.2.6 Slab edge insulation ft ft ❑Complies See the Envelope Assemblies
[FO5]2 depth/length.Slab insulation ❑Does Not table for values.
extending away from building is
covered by pavement or>=10 ❑Not Observable
inches of soil. ❑Not Applicable
C403.2.7, 'Exterior insulation protected ❑Complies Requirement will be met.
C408.2.8, 'against damage,sunlight, c r ❑Does Not
C404.5 moisture,wind,landscaping and
[FO6]1 equipment maintenance 's ❑Not Observable
activities. s ❑Not Applicable
C403.2.4. Freeze protection and snow/ice ❑Complies Exception:Requirement
5 melting system sensors for future ❑Does Not does not apply.
[FO9]3 connection to controls.
❑Not Observable
` ❑Not Applicable
C402.2.8 Bottom surface of floor structures ''. ,_ ❑Complies Exception: Requirement
[FO12]3 incorporating radiant heating a; i f ,t� { ',❑Does Not does not apply.
insulated to>=R-3.5. a
'ONot Observable
See the Envelope Assemblies
❑Not Applicable table for values.
Additional Comments/Assumptions:
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhorn\Wedgewood Apartments\Wedgewood Apartments.cck Page 9 of 20
Section-T— Pians Verified Field Verified
Framing!Rough-In Inspection Value Value Complies? Comments/Assumptions
&Req.I D
C402.4.1, The building envelope contains a ;❑Complies Requirement will be met.
C402.4.2 continuous air barrier that is ❑Does Not
[FR16]1 sealed in an approved manner ;QNot Observable Location on plans/spec.A-
and either constructed or tested 1
In an approved manner.Air ❑Not Applicable
barrier penetrations are sealed in
an approved manner.
C402.4.3, Factory-built fenestration and ❑Complies Requirement will be met.
C402.4.4 doors are labeled as meeting air ED
Does Not
[FR18]3 leakage requirements.
:. IQNot Observable
:❑Not Applicable
C402.4.7 Vestibules are installed on all ❑Complies Exception:Requirement
[FR17]3 building entrances.Doors have ❑Does Not ;does not apply,
self-closing devices.
[]Not Observable
r , ❑Not Applicable
C402.3.3, Vertical fenestration U-Factor. U- U- ❑Complies See the Envelope Assemblies
C402.3.4 ❑Does Not table for values.
[FR8]' QNot Observable
❑Not Applicable
C402.3.3 Vertical fenestration SHGC value. SHGC: SHGC: ❑Complies See the Envelope Assemblies
[FR10]1 ❑Does Not table for values.
[]Not Observable
❑Not Applicable
0303.1.3 Fenestration products rated in ❑Complies Requirement will be met.
[FR1211 accordance with NFRC. ❑goes Not
QNot Observable location on plans/spec:A-
❑Not Applicable
0303.1.3 Fenestration products are - ❑Complies Requirement will be met.
[FR13]11 certified as to performance labels.-.., ❑Does Not
or certificates provided. ,[]Not Observable Location on plans/spec:A-
F 1
[]Not Applicable
C402.2.7 U-factor of opaque doors U- U ❑Complies See the Envelope Assemblies
[FR14]2 associated with the building ❑ Swinging ❑ Swinging ❑Does Not table for values.
thermal envelope meets Nonswinging ❑ Nonswinging []Not Observable
requirements. ❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhom\Wedgewood Apartments\Wedgewood Apartments.cck Page 10 of 20
Section
# Plumbing Rough-In Inspection Complies? Comments/Assumptions
& Re .ID
0404.3 Temperature controls installed on ❑Complies Requirement will be met.
(131-5]3 service water heating systems(110 OF ❑Does Not
for dwelling units and lavatories in ❑Not Observable Location on plans/spec:A-1
public restrooms and 90 OF for other
occupancies. ❑Not Applicable
0404.4 Automatic time switches installed to ❑Complies Requirement will be met.
(131_3]1 automatically switch off the ❑Does Not
recirculating hot-water system or heat []Not Observable Location on plans/spec:A-1
trace.
❑Nat Applicable
Additional Comments/Assumptions:
1 lHigh Impact{Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhom\Wedgewood Apartments\Wedgewood Apartments.cck Page 11 of 20
Section Mechanical Rough-In Plans Verified Field Verified
# Inspection Value Value Complies? Comments/Assumptions
&Req.ID
C403.2.3 HVAC equipment efficiency Efficiency: Efficiency: ❑Complies See the Mechanical Systems list
[ME5512 verified. ❑Does Not for values.
❑Not Observable
❑Not Applicable
0402,4.5. Stair and elevator shaft vents ❑Complies Exception: Requirement
1 have motorized dampers that ❑Does Not does not apply.
[ME3]3 automatically close.
❑Not Observable
❑Nat Applicable
C402.4.5. Outdoor air and exhaust systems ❑Complies .Exception:Gravity dampers
2 have motorized dampers that ❑Does Not acceptable in systems with
[ME5813 automatically shut when not in ❑Not Observable outside or exhaust air flow
use and meet maximum leakage rates less than 300 cfm.
rates.Check gravity dampers :❑Not Applicable
where allowed. ,
C403.2.5. Demand control ventilation ❑Complies Exception:Requirement
1 provided for spaces>500 ft2 and + ❑Does Not does not a I
[ME5911 >25 people/1000 ft2 occupant PP y
density and served by systems r Notobservable
with air side economizer,auto ❑Not Applicable
modulating outside air damper ;
control,or design airflow>3,000 '.
cfm.
C403.2.7 HVAC ducts and plenums R- R- ❑Complies Exception: Requirement
[ME60]2 insulated.Where ducts or ❑Does Not does not apply.
plenums are installed in or under
a slab,verification may need to []Not Observable
occur during Foundation ❑Not Applicable
Inspection.
C403.2.8 'Thermally ineffective panel ❑Complies Exception: Requirement
[ME41]3 surfaces of sensible heating []Does Not does not apply.
panels have insulation>=R 3 5. ?
❑Not Observable
❑Not Applicable
C403.2.7 Ducts and plenums sealed based ` ' ❑Complies Exception:Requirement
[ME10]2 on static pressure and location P ❑Does Not does not apply.
[]Not Observable
❑Not Applicable
C403.2.7, Ductwork operating>3 in.water .. ❑Complies Exception: Requirement
1.3 column requires air leakage { s t ❑Does Not does not apply.
[ME11]3 testing. <
a:_; ; r ❑Not Observable
i . ❑Not Applicable
C408.2.2. 'Air outlets and zone terminal 1` ❑Complies Exception:Requirement
1 devices have means for air ; ❑Does Not does not apply.
[ME53]3 balancing. ,
❑Not Observable
❑Not Applicable
C403.4.2 :VAV fan motors>=5.0 hp to be VSO VSD ❑Complies Exception:Requirement
[ME66]2 driven by variable speed drive, ❑ Vane axial ❑ Vane axial ❑Does Not does not apply.
have a vane-axial fan with fan fan
variable pitch blades,or have Other ❑ Other ❑Not Observable
controls to limit fan motor ❑Not Applicable
demand.
0403.4.2 VAV fan motors>=5.0 hp to be VSD VSD ❑Complies .Exception:Requirement
[ME66]2 driven by variable speed drive, ❑ Vane axial ❑ Vane axial ❑Does Not does not apply.
have a vane-axial fan with fan fan
variable pitch blades,or have ❑ Other E] Other
❑Not Observable
controls to limit fan motor ❑Nat Applicable
demand.
1 High Impact(Tier 1) 2 1 Medium impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: YASchermerhom\Wedgewood Apartments\Wedgewood Apartments.cck Page 12 of 20
Section Mechanical Rough-In Plans Verified Field Verified
# Inspection Value Value Complies? Comments/Assumptions
& Req.ID
C403.2.6 Exhaust air energy recovery on ❑Complies
[ME57]1 systems meeting Table 0403,2.6 ❑Does Not
❑Not Observable
❑Not Applicable
0403.2,11 Unenclosed spaces that are ❑Complies 'Exception: Requirement
[ME71]2 heated use only radiant heat. ❑Does Not does not apply.
❑Not Observable
❑Not Applicable
0403.4.7 Hot gas bypass limited to: ¢=240 ❑Complies Requirement will be met.
[ME35]1 kBtu{h-50%>240 kBtulh-25% ❑Does Not
❑Not Observable Location on plans/spec: A-
❑Not Applicable 1
0403.3.4 Sleeping rooms in Group R-1 ❑Complies Exception: null.
[ME76]3 occupancies are provided with ❑Does Not
dedicated system to
automatically control HVAC ❑Not Observable
systems and energy consumption ❑Not Applicable
during unoccupied periods.
Controls are designed to raise
cooling and lower heating
temperature set points by at
least 4°F when room is
unoccupied.
C403.3.4 Sleeping rooms in Group R-1 ❑Complies Exception: null.
[ME76]3 occupancies are provided with ❑Does Not
dedicated system to
automatically control HVAC ❑Not Observable
systems and energy consumption ❑Not Applicable
during unoccupied periods,
Controls are designed to raise
cooling and lower heating
temperature set points by at
least 4°F when room is
unoccupied.
Additional Comments/Assumptions:
T JHigh Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11103/15
Data filename: Y:1Schermerhorn\Wedgewood ApartmentslWedgewood Apartments.cck Page 13 of 20
Section
# Rough-In Electrical inspection Complies? Comments/Assumptions
&Re .ID
C405.2.2. Automatic controls to shut off all OComplies Exception:Emergency egress lighting.
1 building lighting installed in all []Does Not
[EL22]2 buildings. []Not Observable
❑Not Applicable
C405.2.1. Independent lighting controls installed OComplies .Requirement will be met.
1 per approved lighting plans and all ;❑Does Not
[EL2312 manual controls readily accessible and []Not Observable Location on plans/spec:A-1
visible to occupants.
❑Not Applicable
C405.2.1. Ughting controls installed to uniformly ❑Complies Exception:Sleeping units.
2 reduce the lighting load by at least ❑Does Not
[EL15]1 50°l0.
ONot Observable
ONot Applicable
C405.2.2. ,Daylight zones provided with OComplies :Exception:Requirement does not apply.
3 individual controls that control the :[]Does Not
[EL16]2 lights independent of general area
lighting. []Not Observable
ONot Applicable
C405.2.3 ;Sleeping units have at least one ❑Complies Requirement will be met.
[EL17]3 master switch at the main entry door ❑Does Not
:that controls wired luminaires and :[]Not Observable
switched receptacles.
ONot Applicable
C405.2.2. Occupancy sensors installed in OComplies Exception:Requirement does not apply.
2 required spaces. :ODoes Not
[EL18]1 ❑Not Observable
ONot Applicable
C405.2.2. Primary sidelighted areas are OComplies Exception:Requirement does not apply.
3 equipped with required lighting ODoes Not
[EL20]1 controls. []Not Observable
ONot Applicable
C405.2.2. Enclosed spaces with daylight area OComplies Exception;Requirement does not apply.
3 under skylights and rooftop monitors ❑Does Not
[EL2111 are equipped with required lighting '[]Not Observable
controls.
❑Not Applicable .
C405.2.4 Automatic lighting controls for exterior'OComplies Requirement will be met.
[EL25]2 lighting installed. ❑Does Not
[]Not Observable Location on plans/spec:A-1
ONot Applicable
C405.2.3 Separate lighting control devices for OComplies Requirement will be met.
[EL4]1 specific uses installed per approved :ODoes Not
lighting plans. []Not Observable:Location on plans/spec;A-1
❑Not Applicable
C405.4 Exit signs do not exceed 5 watts per OComplies Exception:Requirement does not apply.
[EL6]1 face. Oboes Not
ONot Observable
❑Not Applicable
C405.2.3 Additional interior lighting power OComplies Requirement will be met.
[EL8]1 allowed for special functions per the ODoes Not
approved lighting plans and Is []Not Observable Location on plans/spec:A-1
automatically controlled and
separated from general lighting. ❑Not Applicable
Additional Comments/Assumptions:
111 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact{Tier 3]
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhom\Wedgewood Apartments\Wedgewood Apartments.cck Page 14 of 20
I I High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:1Schermerhom\Wedgewood Apartments\Wedgewood Apartments.cck Page 15 of 20
Section Plans Verified Field Verified
# Insulation Inspection Value Value Complies? Comments/Assumptions
&Re .ID
C402.4.1. All sources of air leakage in the ;OComplies Requirement will be met.
1 building thermal envelope are j ❑Does Not
[IN1]1 sealed,caulked,gasketed, r Location on plans/spec:A-
weather stripped or wrapped with =' ONot Observable '1
moisture vapor-permeable ❑Not Applicable
.wrapping material to minimize air
leakage.
C402.4.9 Vapor retarders on the interior EComplies Requirement will be met.
[IN18]1 side of framed walls,floors and ]Does Not
ceilings where the framed cavity ❑Not Observable Location on plans/spec:A-
is not ventilated to allow 1
moisture to escape.Does not ❑Not Applicable
Include below-grade assemblies
C402.4.2. :Roof R-value.For some ceiling R- R- OComplles See the Envelope Assemblies
1 systems,verification may need to [:] Above deck ❑ Above deck ❑Does Not table for values.
[IN2]1 occur during Framing Inspection. ❑ Metal ❑ Metal ❑Not Observable
❑ Attic ❑ Attic ❑Not Applicable
C303.2 Roof insulation installed per _UComplies Requirement will be met.
[IN3]1 manufacturer's instructions. x ❑Does Not
Blown or poured loose-fill kh, ❑Not Observable location on plans/spat:A-
insulation is installed only where „ ; Not Applicable
the roof slope is<=3 in 12. PP
C303.2 Above-grade wall insulation ` r `:OComplies Requirement will be met.
[IN7]1 installed per manufacturer's '❑Does Not
instructions. Location on plans/spec:A-
ONot Observable 1
ONot Applicable
C402.2.5 Floor insulation R-value. R- R- ❑Complies See the Envelope Assemblies
(IN8]2 ❑ Mass ❑ Mass ❑Does Not table for values.
❑ Steel :❑ Steel ❑Not Observable
❑ Wood ❑ Wood '❑Not Applicable
C303.1 Building envelope insulation is ❑Complies Requirement will be met.
[IN10]2 labeled with R-value or insulation ❑Does Not
,certificate providing R-value and
other relevant data. T ❑Not Observable
❑Not Applicable
C303.2.1 Exterior insulation is protected ❑Complies Exception: Requirement
[IN14]2 'from damage with a protective ;❑Does Not does not apply.
material.Verification for exposed
❑Not Observable
foundation insulation may need
to occur during Foundation tr ,` Y ❑Not Applicable
Inspection.
C402.2.1 Insulation intended to meet the ❑Complies Exception:Requirement
(IN17J3 roof insulation requirements `} ❑Does Not does not apply.
cannot be installed on tap of a
suspended ceiling.Mark this = ❑Not Observable
requirement compliant if . ❑Not Applicable
insulation Is installed accordingly.
Additional Comments/Assumptions:
111 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhorn\Wedgewood Apartments\Wedgewood Apartments.cck Page 16 of 20
Section
# Final Inspection Complies? Comments/Assumptions
& Re .ID
C402.4.6 Weatherseals installed on all loading ([]Complies ;Exception:Requirement does not apply.
(FI37]1 dock cargo doors. 'Oboes Not
ONot Observable.
ONot Applicable
C403.2.4. Heating and cooling to each zone is OComplies Requirement will be met.
2 controlled by a thermostat control. []Does Not
[FI47]3 Minimum one humidity control device []Not Observable
on plans/spec:A-1
per installed []Not Applicable
humidification/dehumidification pP
system.
C403.2.4. Thermostatic controls have a 5'F OComplies Requirement will be met.
2 deadband. ODoes Not
[FI38]3 ❑Not Observable Location on plans/spec:A-1
ONot Applicable
C403.2.4. ;Temperature controls have setpoint []Complies Requirement will be met.
2 overlap restrictions. []Does Not
[F120]3 ❑Not Observable Location on plans/spec:A-1
ONot Applicable
C403.2.4. Each zone equipped with setback []Complies Requirement will be met.
3 controls using automatic time clock or ]Does Not
[F139]3 programmable control system. []Not Observable;Location on plans/spec:A-1
;[]Not Applicable
C403.2.4. Automatic Controls:Setback to 55°F !OComplies Requirement will be met.
3 ;(heat)and 85°F(cool); 7-day clock,2- 'ODoes Not
[F140]3 hour occupant override,10-hour []Not Observable'Location on plans/spec:A-1
backup
[]Not Applicable
C408.2.5. :Furnished HVAC as-built drawings []Complies Requirement will be met.
1 submitted within 90 days of system ❑Does Not
(F17]3 acceptance.
[]Not Observable
:]Not Applicable
C303.3,C4Furnished O&M manuals for HVAC OComplies Requirement will be met.
08.2.5.2 systems within 90 days of system .❑Does Not
[FIB]3 acceptance.
❑Not Observable.
ONot Applicable
C408.2.5. An air and/or hydronic system :[]Complies Requirement will be met.
3 'balancing report is provided for HVAC ,[]Does Not
(FI43]1 systems. []Not Observable'Location on plans/spec:A-1
ONot Applicable
C408.2.3. HVAC control systems have been OComplies Requirement will be met.
2 tested to ensure proper operation, :❑Does Not
[F110]1 calibration and adjustment of controls. []Not Observable Location on plans/spec:A-1
ONot Applicable
C404.3 Public lavatory faucet water OComplies Requirement will be met.
[Fl11]3 temperature t=110°F. ]Does Not
ONot Observable Location on plans/spec:A-1
]Not Applicable
C404.5 All piping in circulating system OComplies Exception: Requirement does not apply.
[F125]2 insulated ]Does Not
❑Not Observable
[]Not Applicable
11 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhorn\Wedgewood Apartments\Wedgewood Apartments cck Page 17 of 20
,
Section
#
Final Inspection Complles7 Comments/Assumptions
,Reg.10
C402.4.8 ;Recessed luminaires in thermal :❑Complies Exception:Requirement does not apply.
[FI26]3 envelope to limit infiltration and be IC ❑Does Not
rated and labeled.Seal between
interior finish and luminaire housing. ONot Observable
[]Not Applicable
C403.2.2 'HVAC systems and equipment OComplies Requirement will be met.
[FI27]3 capacity does not exceed calculated :[]Does Not
loads. Location on plans/spec:A-1
[]Not Observable'
ONot Applicable
C408.2.5. Furnished as-built drawings for ❑Complies Requirement will be met.
1 electric power systems within 30 days []Does Not
[FI16]3 of system acceptance.
❑Nat Observable
ONot Applicable
C303.3,C4Fumished O&M instructions for ❑Complies Requirement will be met.
08.2.5.2 systems and equipment to the ;[]Does Not
[FI17]3 building owner or designated []Not Observable
representative.
:ONot Applicable
C405.5.2 Interior installed lamp and fixture OComplies See the Interior Lighting fixture schedule for values.
[F118]1 lighting power is consistent with what :❑Does Not
Is shown on the approved lighting []Not Observable
plans,demonstrating proposed watts
are less than or equal to allowed .[]Not Applicable
watts.
C405.6.2 Exterior lighting power is Consistent `Complies See the Exterior Lighting fixture schedule for values.
[FI19]1 with what is shown on the approved ;[]Does Not
lighting plans,demonstrating []Not Observable
,',proposed watts are less than or equal
to allowed watts. ❑Not Applicable
C408.2.1 .Commissioning plan developed by []Complies Requirement will be met.
[F128]1 registered design professional or :❑Does Not
approved agency. Location on plans/spec:A-1
:❑Not Observable
❑Not Applicable
C408.2.4 'Preliminary commissioning report [ Complies Requirement will be met.
[F129]1 completed and certified by registered ❑Does Not
design professional or approved []Not Observable Location on plans/spec:A-1
agency. ONot Applicable
C408.2.5. Final commissioning report due to -OComplies Requirement will be met.
4 building owner within 90 days of UDoes Not
[F130]1 receipt of certificate of occupancy. ;[]Nat Observable Location on plans/spec:A-1
;[]Not Applicable
C408.2.3. HVAC equipment has been tested to .❑Complies Requirement will be met.
1 ensure proper operation. ❑Does Not
[FI31]1 Location on plans/spec:A-1
❑Not Observable
❑Not Applicable
C408.3 Lighting systems have been tested to 'OComplies Requirement will be met.
[F13311 ensure proper calibration, adjustment, ❑Does Not
programming,and operation. ONot Observable:Location on plans/spec:A-1
,❑Not Applicable
C408.3 Lighting systems have been tested to 'OComplies Requirement will be met.
[F148]1 ensure proper calibration,adjustment, []Does Not
programming,and operation. []Not Observable Location on plans/spec:A-1
ONot Applicable
1 IHigh Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact{Tier 3)
Project Title: Wedgewood Apartments Report date: 11/03/15
Data filename: Y:\Schermerhorn\Wedgewood Apartments\Wedgewood Apartments.cck Page 18 of 20
Section
# Final inspection Complies? Comments/Assumptions
&Re .ID
C406 Efficient HVAC performance,efficient ❑Complies Requirement will be met.
[FI34)1 lighting system, or on-site supply of ❑Does Not
renewable energy consistent with ONot Observable Location on plans/spec:A-1
what is shown the approved plans.
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)