Loading...
RPLUM-003507-2019 06142019INSPECTION WORKSHEET (RPLUM-003507-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-000368-2016 Case Module:Permit Inspection Date:Fri Jun 14, 2019 Inspection Status:Partial Pass Inspector:John O'Brien Inspection Type:Rough Plumbing Job Address:Parcel Number:75, 77, 81, 83, 87, 89, 93, 95 Wedgewood DR Bldg. 7 Queensbury, NY 12804 302.9-1-28.1 Contact Type Company Name Name Granted Permission Schermerhorn R.E. Holdings VANDERWARKER, DARREN Applicant Schermerhorn R.E. Holdings VANDERWARKER, DARREN Primary Owner SCHERMERHORN WEDGEWOOD LLC Contractor Schermerhorn R.E. Holdings VANDERWARKER, DARREN Architect Rucinski-Hall Architecture Checklist Item Passed Comments Building Inspector Notes NO 10/2/17 Plumbing Under Slab Approved -Pressure Test Ok! 6/14/19 Rough Plumbing Partial Approval - Sanitary Approved - Water Approved - Pressure Tests Ok! Plumbing Under Slab YES 10/2/17 Plumbing Under Slab Approved -Pressure Test Ok! Rough Plumbing / Nail Plates NO 6/14/19 Rough Plumbing Partial Approval - Sanitary Approved - Water Approved - Pressure Tests Ok! Jun 14, 2019 Page (1) INSPECTION WORKSHEET (RPLUM-003507-2019) Checklist Item Passed Comments Cleanout every 100 feet change of direction YES 10/2/17 Plumbing Under Slab Approved -Pressure Test Ok! Pressure Test YES 10/2/17 Plumbing Under Slab Approved -Pressure Test Ok! Air Head YES Air 5 psi or 10 ft. above highest conn. for 15 minutes YES 10/2/17 Plumbing Under Slab Approved -Pressure Test Ok! -6 psi Air 6/14/19 Sanitary Pressure Test Approved - 5 psi or greater Pressure Test YES 6/14/19 Sanitary Pressure Test Approved - 5 psi or greater Air Head YES 10/2/17 Plumbing Under Slab Approved -Pressure Test Ok! -6 psi Air 6/14/19 Water Pressure Test Approved - 99 psi or greater 50 P.S.I for 15 minutes YES 6/14/19 Water Pressure Test Approved - 99 psi or greater Air Test Gas Piping 10 psi for 10 Minutes NO All Return Air Hard Duct Work NO Duct Insulation - if required in unheated spaces NO Duct Testing Outside Conditioned Space NO Duct work sealed properly NO Jun 14, 2019 Page (2) O'Brien, John (Inspector)