RPLUM-003507-2019 06142019INSPECTION WORKSHEET (RPLUM-003507-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000368-2016 Case Module:Permit
Inspection Date:Fri Jun 14, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:75, 77, 81, 83, 87, 89, 93, 95 Wedgewood
DR Bldg. 7
Queensbury, NY 12804
302.9-1-28.1
Contact Type Company Name Name
Granted Permission Schermerhorn R.E. Holdings VANDERWARKER, DARREN
Applicant Schermerhorn R.E. Holdings VANDERWARKER, DARREN
Primary Owner SCHERMERHORN WEDGEWOOD
LLC
Contractor Schermerhorn R.E. Holdings VANDERWARKER, DARREN
Architect Rucinski-Hall Architecture
Checklist Item Passed Comments
Building Inspector Notes NO 10/2/17 Plumbing Under Slab Approved
-Pressure Test Ok!
6/14/19 Rough Plumbing Partial Approval
- Sanitary Approved
- Water Approved
- Pressure Tests Ok!
Plumbing Under Slab YES 10/2/17 Plumbing Under Slab Approved
-Pressure Test Ok!
Rough Plumbing / Nail Plates NO 6/14/19 Rough Plumbing Partial Approval
- Sanitary Approved
- Water Approved
- Pressure Tests Ok!
Jun 14, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-003507-2019)
Checklist Item Passed Comments
Cleanout every 100 feet change of direction YES 10/2/17 Plumbing Under Slab Approved
-Pressure Test Ok!
Pressure Test YES 10/2/17 Plumbing Under Slab Approved
-Pressure Test Ok!
Air Head YES Air
5 psi or 10 ft. above highest conn. for 15 minutes YES 10/2/17 Plumbing Under Slab Approved
-Pressure Test Ok!
-6 psi Air
6/14/19 Sanitary Pressure Test Approved
- 5 psi or greater
Pressure Test YES 6/14/19 Sanitary Pressure Test Approved
- 5 psi or greater
Air Head YES 10/2/17 Plumbing Under Slab Approved
-Pressure Test Ok!
-6 psi Air
6/14/19 Water Pressure Test Approved
- 99 psi or greater
50 P.S.I for 15 minutes YES 6/14/19 Water Pressure Test Approved
- 99 psi or greater
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO
Jun 14, 2019 Page (2)
O'Brien, John (Inspector)