RPLUM-001787-2019 04032019INSPECTION WORKSHEET (RPLUM-001787-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:CC-000362-2016 Case Module:Permit
Inspection Date:Wed Apr 3, 2019 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Rough Plumbing
Job Address:Parcel Number:8, 10, 14, 16, 20, 22, 26, 28 Wedgewood
DR Bldg. 2
Queensbury, NY 12804
302.9-1-28.1
Contact Type Company Name Name
Primary Owner SCHERMERHORN WEDGEWOOD
LLC
Architect Rucinski-Hall Architecture
Applicant Schermerhorn R.E. Holdings VANDERWARKER, DARREN
Contractor Schermerhorn R.E. Holdings VANDERWARKER, DARREN
Granted Permission Schermerhorn R.E. Holdings VANDERWARKER, DARREN
Checklist Item Passed Comments
Building Inspector Notes NO 7/26/17 Plumbing Under Slab Approved
3/14/19 all plumbing above slab ok. Connection from above
slab to under slab needs to be verified and tested.
4/3/19 Plumbing Partial Approval-Bldg #2
- Pressure test approved for sanitary.
- Pressure test approved for water.
- 3" vent stacks extended inside building envelope 1'.
Plumbing Under Slab YES 7/26/17 Plumbing Under Slab Approved
Rough Plumbing / Nail Plates YES 4/3/19 Plumbing Partial Approval-Bldg #2
- Pressure test approved for sanitary.
- Pressure test approved for water.
- 3" vent stacks extended inside building envelope 1'.
Apr 03, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001787-2019)
Checklist Item Passed Comments
Cleanout every 100 feet change of direction YES
Pressure Test YES Still need to test and verify tubs
Air Head YES 7/26/17 Plumbing Under Slab Approved
- Pressure test ok! 6 psi
4/3/19 7 psi air test
5 psi or 10 ft. above highest conn. for 15 minutes YES 7/26/17 Plumbing Under Slab Approved
- Pressure test ok! 6 psi
4/3/19 7 psi air test
Pressure Test YES 4/3/19 7 psi air test
Air Head YES Sprinkler system tested with 50 PSI air
50 P.S.I for 15 minutes YES 100 psi
Air Test Gas Piping 10 psi for 10 Minutes NO
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO
Apr 03, 2019 Page (2)
O'Brien, John (Inspector)