ComCheck . COMcheck Software Version 4.0.7.2 Review
rtft
II Envelope Compliance Certificate
E GjpPst
Project Information FILE
Energy Code: 2015 IECC
Project Title: O'Reilly Auto Parts Store
Location: Glens Falls, New York
Climate Zone: 6a REVIEWED FOR
Project Type: New Construction
Vertical Glazing/Wall Area: 7`)/° ENERGY CODE COMPLIANCE
Construction Site: Owner/Agent: Designer/Contractor:
682 Glen Street O'Reilly Automotive Phase Zero Design
Queensbury, NY 12804 233 South Patterson 35 Pond Park Rd
Springfield, MO 65801 Bay 16
Hingham, MA 02043
781-452-7121
LSirois@gmail.com
Building Area Floor Area
1-Retail : Nonresidential 7453
Additional Efficiency Package
High efficiency HVAC.Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist
report.
Envelope Assemblies
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R-Value U-Factor Factor(e)
Perimeter
Roof 1:Metal Building,Standing Seam,Double Insulation Layer with 7453 11.0 25.0 0.029 0.031
Thermal Blocks(d),[Bldg.Use 1 -Retail]
Floor 1:Slab-On-Grade:Unheated,Vertical 4 ft.,[Bldg.Use 1 - 345 --- 10.0 0.480 0.540
Retail](c)
NORTH
Exterior Wall 4:Concrete Block:8",Partially Grouted,Cells Empty, 1298 0.0 9.0 0.083 0.080
Normal Density,Furring:Metal,[Bldg.Use 1 -Retail]
Door 3:Insulated Metal,Swinging,[Bldg.Use 1 -Retail] 21 --- --- 0.310 0.370
Door 4:Insulated Metal,Non-Swinging,[Bldg.Use 1 -Retail] 48 --- --- 0.340 0.340
EAST
Exterior Wall 3:Concrete Block:8",Partially Grouted,Cells Empty, 1322 0.0 9.0 0.083 0.080
Normal Density,Furring:Metal,[Bldg.Use 1 -Retail]
SOUTH
Exterior Wall 2:Concrete Block:8",Partially Grouted,Cells Empty, 1474 0.0 9.0 0.083 0.080
Normal Density,Furring:Metal,[Bldg.Use 1 -Retail]
Window 2:Metal Frame with Thermal Break:Fixed,Perf.Specs.: 370 --- --- 0.320 0.360
Product ID Kawneer,SHGC 0.40,PF 0.50,[Bldg.Use 1 -Retail](b)
Door 6:Glass(>50%glazing):Metal Frame,Entrance Door,Perf. 21 --- --- 0.320 0.770
Specs.:Product ID kawneer,SHGC 0.40,[Bldg.Use 1 -Retail](b)
WEST
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: H:\Retail\OReilly Auto parts\1 -PERMITTED 2117238 Queensbury NY\Queensbury NY Page 1 of 9
ComCheck.cck
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R-Value U-Factor Factor.,
Perimeter
Exterior Wall 1:Concrete Block:8",Partially Grouted,Cells Empty, 1322 0.0 9.0 0.083 0.080
Normal Density,Furring: Metal,(Bldg.Use 1 -Retail)
Door 5:Insulated Metal,Swinging,(Bldg.Use 1 -Retail] 21 --- --- 0.310 0.370
(a)Budget U-factors are used for software baseline calculations ONLY,and are not code requirements.
(b)Fenestration product performance must be certified In accordance with NFRC and requires supporting documentation.
(c)Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
(d)Thermal spacer block with minimum R-3.5 must be installed above the purlin/batt,and the roof deck secured to the purlins.
nvelope PASSES: Design 3% better than code
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit a lication. The proposed envelope systems have been
designed to meet the 2015 IECC requirements in COMcheck Versio 1 4.0.7,2 Review and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
��hM% 'Hm544 -tJP- fi tNu
-et-(' • 1.8
Name-title Ignature Date
� ARCy(<7kED
KI/Lie /)`4g � "' �l! �0
Q t ICP, s'�a•a 1' -1
l), 029423 40 *
FoF NE`N
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: H:\Retail\OReilly Auto parts\1 - PERMITTED 2117238 Queensbury NY\Queensbury NY Page 2 of 9
ComCheck.cck
COMcheck Software Version 4.0.7.2 Review
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 Plans and/or specifications provide all DComplies
[PR1]1 information with which compliance ODoes Not
can be determined for the building
envelope and document where ❑Not Observable
exceptions to the standard are ❑Not Applicable
claimed.
C402.4.1 The vertical fenestration area <= 30 ❑Complies
[PR1O]1 percent of the gross above-grade wall DDoes Not
area.
DNot Observable
❑Not Applicable
C402.4.1 The skylight area <= 3 percent of the ❑Complies
[PR11]1 gross roof area. ❑Does Not
:Not Observable
ONot Applicable
C406 Plans, specifications, and/or DComplies
[PR9]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the additional energy ['Not Observable
efficiency package options. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: H:\Retail\OReilly Auto parts\1 -PERMITTED 2117238 Queensbury NY\Queensbury NY Page 3 of 9
ComCheck.cck
Section
# 1 Footing/Foundation Inspection Complies? Comments/Assumptions
& Req.ID I
C303.2 Slab edge insulation installed per ❑Complies
[FO4]2 manufacturer's instructions. ❑Does Not
❑Not Observable
❑Not Applicable
C303.2.1 Exterior insulation protected against ❑Complies
[FO6]1 damage, sunlight, moisture, wind, ❑Does Not
landscaping and equipment
maintenance activities. ['Not Observable
❑Not Applicable
C402.2.5 Slab edge insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[FO3]2 ElDoes Not
❑Not Observable
❑Not Applicable
C402.2.6 Radiant heating systems panels OComplies See the Envelope Assemblies table for values.
[FO12]3 insulated to>=R-3.5 on face opposite ❑Does Not
space being heated.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: H:\Retail\OReilly Auto parts\1 -PERMITTED 2117238 Queensbury NY\Queensbury NY Page 4 of 9
ComCheck.cck
Section
# • Framing/Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C303.1.3 Fenestration products rated in ❑Complies
[FR12]z accordance with NFRC. ❑Does Not
['Not Observable
ONot Applicable
C303.1.3 Fenestration products are certified as ❑Complies
[FR13]1 to performance labels or certificates ❑Does Not
provided.
ONot Observable
ONot Applicable
C402.4.3 Vertical fenestration SHGC value. ❑Complies See the Envelope Assemblies table for values.
[FR10]1 ❑Does Not
['Not Observable
ONot Applicable
C402.4.3, Vertical fenestration U-Factor. ❑Complies See the Envelope Assemblies table for values.
C402.4.3. ❑Does Not
4
[FR8)1 ['Not Observable
ONot Applicable
C402.4.4 U-factor of opaque doors associated ❑Complies See the Envelope Assemblies table for values.
[FR14]2 with the building thermal envelope ['Does Not
meets requirements.
❑Not Observable
❑Not Applicable
C402.5.1. The building envelope contains a ❑Complies
2.2 continuous air barrier that is sealed in ❑Does Not
[FR20]1 an approved manner and average
assembly air leakage <= 0.04 cfm/ft2. ['Not Observable
Air barrier penetrations are sealed in ONot Applicable
an approved manner.
C402.5.2, Factory-built fenestration and doors ❑Complies
C402.5.4 are labeled as meeting air leakage ❑Does Not
[FR1813 requirements.
:Not Observable
❑Not Applicable
C402.5.7 Vestibules are installed on all building ❑Complies
[FR17]3 entrances. Doors have self-closing ❑Does Not
devices.
ONot Observable
ONot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: H:\Retail\OReilly Auto parts\1 -PERMITTED 2117238 Queensbury NY\Queensbury NY Page 5 of 9
ComCheck.cck
Section
# ' Mechanical Rough-In Inspection Compiles? Comments/Assumptions
& Req.ID
C402.5.5, Stair and elevator shaft vents have Complies
C403.2.4. motorized dampers that automatically ❑Does Not
3[MEW close. ❑Not Observable
❑Not Applicable
C402.5.5, Outdoor air and exhaust systems have DComplies
C403.2.4. motorized dampers that automatically ❑Does Not
3 shut when not in use and meet
[ME58]3 maximum leakage rates.Check :Not Observable
gravity dampers where allowed. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: H:\Retail\OReilly Auto parts\1-PERMITTED 2117238 Queensbury NY\Queensbury NY Page 6 of 9
ComCheck.cck
•
•
Section
# ' Insulation Inspection Complies? Comments/Assumptions
& Req.ID
C303.1 Roof insulation installed per DComplies
[IN3]1 manufacturer's instructions. Blown or ❑Does Not
poured loose-fill insulation is installed
only where the roof slope is<=3 in ❑Not Observable
12. ❑Not Applicable
C303.1 Building envelope insulation is labeled DComplies
[IN10]2 with R-value or insulation certificate ❑Does Not
providing R-value and other relevant
data. [Not Observable
❑Not Applicable
C303.2 Above-grade wall insulation installed DComplies
[IN7]1 per manufacturer's instructions. ❑Does Not
❑Not Observable
❑Not Applicable
C303.2.1 Exterior insulation is protected from DComplies
[IN14]2 damage with a protective material. ❑Does Not
Verification for exposed foundation
insulation may need to occur during ❑Not Observable
Foundation Inspection. ❑Not Applicable
C402.1.3 Non-swinging opaque doors have R- DComplies
[IN19]3 4.75 insulation. ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.1 Insulation intended to meet the roof DComplies
[IN17]3 insulation requirements cannot be ❑Does Not
installed on top of a suspended
ceiling. Mark this requirement :Not Observable
compliant if insulation is installed ❑Not Applicable
accordingly.
C402.2.3 Above-grade wall insulation R-value. DComplies See the Envelope Assemblies table for values.
[IN6]1 ❑Does Not
['Not Observable
❑Not Applicable
C402.2.5 Floor insulation R-value. DComplies See the Envelope Assemblies table for values.
[IN8]2 ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.6 Radiant panels and associated DComplies
[IN18]3 components, designed for heat ❑Does Not
transfer from the panel surfaces to the
occupants or indoor space are [Not Observable
insulated with a minimum of R-3.5. ❑Not Applicable
C402.2.2 Roof R-value. For some ceiling DComplies See the Envelope Assemblies table for values.
[IN2]1 systems, verification may need to ❑Does Not
occur during Framing Inspection.
❑Not Observable
❑Not Applicable
C402.5.1. All sources of air leakage in the DComplies
1 building thermal envelope are sealed, ❑Does Not
[IN1]1 caulked, gasketed,weather stripped
or wrapped with moisture vapor- ❑Not Observable
permeable wrapping material to ❑Not Applicable
minimize air leakage.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: H:\Retail\OReilly Auto parts\1-PERMITTED 2117238 Queensbury NY\Queensbury NY Page 7 of 9
ComCheck.cck
Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
C402.5.3 Where open combustion air ducts ❑Complies
[F151]3 provide combustion air to open ❑Does Not
combustion fuel burning appliances,
the appliances and combustion air ❑Not Observable
opening are located outside the ❑Not Applicable
building thermal envelope or enclosed
in a room, isolated from inside the
thermal envelope.Such rooms are
sealed and insulated.
C402.5.6 Weatherseals installed on all loading ❑Complies
[FI37]1 dock cargo doors. ❑Does Not
ONot Observable
❑Not Applicable
C402.5.8 Recessed luminaires in thermal ❑Complies
[FI26]3 envelope to limit infiltration and be IC ❑Does Not
rated and labeled.Seal between
interior finish and luminaire housing. ['Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: H:\Retail\OReilly Auto parts\1 -PERMITTED 2117238 Queensbury NY\Queensbury NY Page 8 of 9
ComCheck.cck
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: H:\Retail\OReilly Auto parts\1 -PERMITTED 2117238 Queensbury NY\Queensbury NY Page 9 of 9
ComCheck.cck
111ACOMcheck Software Version 4.0.8.1
ii Interior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: O'Reilly Auto Parts Store
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
682 Glen Street O'Reilly Automotive Phase Zero Design
Queensbury,NY 12804 233 South Patterson 35 Pond Park Rd
Springfield, MO 65801 Bay 16
Hingham,M
Additional Efficiency Package(s) 78-452--7121
02043
LSirois@gmall,com
Reduced interior lighting power.Requirements are Implicitly enforced within interior lighting allowance calculations.
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts I ft2 (B X C)
1-Retail 7453 1,13 8452
Total Allowed Watts- 8452
Proposed Interior Lighting Power
A B C D E
Fixture ID: Description/Lamp I Wattage Per Lamp/Ballast Lamps/ I of Fixture (C X 0)
Fixture Fixtures Watt.
1-Retell
LED 1:A:Other: 1 52 67 3484
LED 2:B:Other: 1 12 34 408
LED 3:C:Other: 1 33 67 2211
LED 4:D:Other: 1 9 34 306
Total Proposed Watts- 6409
Interior Lighting PASSES: Design 24% better than code
Interior Lighting Compliance Statement 4istt+44a?
Compliance Statement: The proposed interior lighting design repkelertetyi;ki+]s}doc ent is consistent with the building plans,
specifications,and other calculations submitted with this permij4v8pjr�li't,`atton.The`prp p 41 interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck vi fend;(Qi3,?ra[adif8ito, ly'Avith any applicable mandatory
requirements listed in the Inspection Checklist.
Norman E.Goth, P.E. April 11,2018
Name-Title Si natue, ', ,,;: Date
1. �.• 066752 •a`'J`�v
e a
•
•401#I,ZG)`ES5\a, 0
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: E:\CLIENTS-O'Reilly Active Stores\Queensbury,NY OR17-148 (New)(Leah)\Com Check\Queensb Page 1 of 3
NY ComCheck.cck
114COMcheck Software Version 4.0.8.1
ii Exterior Lighting Compliance Certificate
1
Project Information
Energy Code: 2015 IECC
Project Title: O'Reilly Auto Parts Store
Project Type: New Construction
Exterior Lighting Zone 2 (Neighborhood business district)
Construction Site: Owner/Agent: Designer/Contractor:
682 Glen Street O'Reilly Automotive Phase Zero Design
Queensbury, NY 12804 233 South Patterson 35 Pond Park Rd
Springfield, MO 65801 Bay 16
Hingham, MA 02043
781-452-7121
LSirois@gmall.cOm
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts I Unit Wattage (B X C)
Driveway 11585 ft2 0,06 Yes 695
Walkway<10 feet wide 1641 ft of 0.7 Yes 1149
Total Tradable Watts(a)- 1844
Total Allowed Watts- 1844
Total Allowed Supplemental Watts(b) = 600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID: Description I Lamp I Wattage Per Lamp I Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Driveway(11585 ft2):Tradable_ ttage
LED 5:P1:Other: 1 2 154 308
Walkway< l0 feet wide(1641 It of walkway length). Tradable Wattage
LED 6:WP1:Other: 1 5 59 295
LED 6:WP2:Other: 1 2 29 58
Total Tradable Proposed Watts• 661
Exterior I ighting PASSES: Design 73%better than code
Exterior Lighting Compliance Statement t,��‘ Ur.NEIv/'•,,
Compliance Statement: The proposed exterior lighting desigekeiaNs4nted in thts►.f." gent is consistent with the building plans,
specifications, and other calculations submitted with this pedrut;appMitli ritfI lt(rCE+itbr.:•s'd exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheclCder/on 4;9:f.),fhd to c4(npt,with any applicable mandatory
requirements listed in the Inspection Checklist. — ' f';.• e
-
Norman E. Goth, P.E. ! -.. 'iv` April 11. 2018
Name -Title Signal �-•
e. 096752 .!„.. Date
.4if�,O ,*°...,.y*�*"_` %�`
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename. E:\CLIENTS-O'Reilly Active Stores\Queensbury, NY OR17-148 (New)(Leah)\Com Check\Queensb Page 2 of 3
NY ComCheck.cck
•
COMcheck Software Version 4.0.8.1
ii Mechanical Compliance Certificate
11111
Project Information
Energy Code: 2015 IECC
Project Title: O'Reilly Auto Parts Store
Location: Glens Falls, New York
Climate Zone: 6a
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
682 Glen Street O'Reilly Automotive Phase Zero Design
Queensbury,NY 12804 233 South Patterson 35 Pond Park Rd
Springfield, MO 65801 Bay 16
Hingham, MA 02041
Additional Efficiency Package(s) 781.452-7121
LSirois@gmall.com
Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations.
Mechanical Systems List
Quantity System Type&Description
3 HVAC System 1 (Single Zone):
Heating:3 each-Unit Heater,Gas,Capacity=180 kBlu/h
Proposed Efficiency-82.00%Ec,Required Efficiency=80.00%Ec
Cooling:3 each-Single Package DX Unit,Capacity-93 kBlu/h,Air-Cooled Condenser,Air Economizer
Proposed Efficiency- 12.00 EER, Required Efficiency: 11.00 EER + 12.6 IEER
Fan System: Unspecified
1 Water Heater 1:
Electric Storage Water Healer,Capacity: 19 gallons
No minimum efficiency requirement applies
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design representq{>•+hdiis7ddd, f?nt is consistent with the building plans,
specifications,and other calculations submitted with this permit Iia ton;,titt/pjp}Seyed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Ve*e_h�4.p.6.1 and td c0 fly with any applicable mandatory
requirements listed in the Inspection Checklist. X .'llORat4E.C�l}I ',•. .
Norman E. Goth, P.E. o April 11.2018
Name-Title Si r+. •- fi- X Date
i'3,'. •096752 L•�i� Z.�
Project Title: O'Reilly Auto Parts Store Report date: 04/11/18
Data filename: E:\CLIENTS-O'Reilly Active Stores\Queensbury, NY OR17-148 (New)(Leah)\Com Check\Queensb Page 3 of 3
NY ComCheck.cck