2004-052 (2) C" a
G2 --U 5
Permit Number
Lighting and Power Compliance Certificate Checked By/Date
New York State Energy Conservation Construction Code
COMcheck-EZ Software Version 2.4 Release 2c
Data filename:C:\Program Files\Check\COMcheck-EZIQUINN MEDICAL BAYROADLIGHTING.K Ycck.cck
Section 1: Project Information
Project Name: BAY ROAD FIRST FLOOR FLOOR
DRY&K FIT-UP
Designer/Contractor: BAST HATFIELD
1399 VISCHERS FERRY ROAD
CLIFON PARK,NEW YORK 12065-6390
Document Author. BRUNO BATKO
Section 2: General Information
Building Use Description by: Whole Building Type
Building Type Floor Area
Medical and Clinical Care 2531
Project Description(check one):
New Construction _Addition _Alteration _Unconditioned Shell(File Affidavit)
Section 3: Requirements Checklist
Bldg.
Dept.
Use
[ ] Interior Lighting
1. Total actual watts must be less than or equal to total allowed watts
Allowed Watts Actual Watts Complies(Y/N)
4050 4032 YES
Exterior Lighting
[ ] 2. Type(s)of exterior lighting sources:
_Fluorescent Metal Halide _High-Pr.Sodium
Exceptions:
Specialized signal,directional,and marker lighting;lighting highlighting exterior features of
historic buildings;advertising signage;safety or security lighting;low-voltage landscape lighting.
Controls,Switching,and Wiring
[ ] 3. Master switch at entry to hotel/motel guest room.
[ ] 4. Individual dwelling units separately metered.
[ ] 5. Minimum of two switches,dimmer,or occupancy sensor in each space.
Exceptions:
Only one luminaire in space;
Security lighting,24 hour lighting;
The area is a corridor,storage,restroom,retail sales area or lobby.
[ ] 6. Automatic lighting shutoff control in spaces greater than 250 sq.ft in buildings larger than 5,000 sq.ft.
[ ] 7. Photocell/astronomical time switch on exterior lights.
Exceptions: Areas requiring lighting during daylight hours
[ ] 8. Tandem wired one-lamp and three-lamp ballasted luminaires.
Exceptions:
Electronic high-frequency ballasted luminaires not on same switch
[ ] 9. Transformers meet minimum efficiencies listed in Table 805.6.1 or 805.6.2.
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application. The proposed lighting system has been designed to meet
the New York State Energy Conservation Construction Code requirements in COMcheck-EZ Version 2.4 Release 2c
and to comply with the mandatory requirements in the Requirements Checklist.
When a Registered Design Professional has stamped and signed this page,they are attesting that to the best of his/her
knowledge,belief,and professional udgment,such plans or specifications are in compliance with this Code.
Gc a o /
Principal Lighting Designer-Name . ignature D
..
� Y
Lighting Application Worksheet
New York State Energy Conservation Construction Code
COMcheck-EZ Software Version 2.4 Release 2c
Section 1: Allowed Lighting Power Calculation
A B C D
Total
Floor Allowed Allowed
Area Watts Watts
Building Type (ft2) (watts/ft2) (B x C)
Medical and Clinical Care 2531 1.6 4050
Total Allowed Watts= 4050
Section 2: Actual Lighting Power Calculation
A B C D E F
Fixture Fixture Description/ Lamps/ #of Fixture
ID Lamp Description/Wattage Per Lamp/Ballast Fixture Fixtures Watt. (D x E)
1 48"T8 32W/Electronic 3 22 96 2112
2 48"T8 32W/Electronic 2 27 64 1728
3 24"T8U 32W/Electronic 2 3 64 192
Total Actual Watts= 4032
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero,the building complies.
Total Allowed Watts= 4050
Total Actual Watts= 4032
Project Compliance= 18
Lighting PASSES: Design 0.4%better than code
BAST
HATFIELD
GENERAL CONTRACTORS � .
CONSTRUCTION MANAGERS
5,17 'lll �-j tttlTT���
January 30, 2004
David Hatin
Director of Building and Code Enforcement
Town of Queensbury
742 Bay Road
Queensbury, NY 12804
RE: Permit No. P20030444
Bay Road, Queensbury
BHI Project No. 0325
TRANSMITTED:
Three (3) Original and stamped drawings for the Dr. Yovanoff/Dr. KarpTenant
Fit-Up
Two (2) Signed Energy Compliance Certifications
Sincerely,
BAST HATFIELD, INC.
,0
Stephen W. Adler
Project Manager
SWA/hs
Enc.
c: File
1399 Vischers Ferry Road • Halfmoon,New York 12065-6325 ■Telephone(518)373-2000■ FAX 373-2303
"4,
TOWN OF QUEENSBURY
742 Bay Road, Queensbury, NY. 12804-5902
Memorandum
To: Dave Hatin
From: Steve Smith
Date: February 9, 2004
Re: Plan Reviews-ARC / Dr. Yovanoff& Karp-Quinn Medical Bldg.
We completed a review of the submitted plans and have the following items that need to be addressed:
ARC space
- Area of 'escue?—referenced on drawings,need further explanation,not sure what is meant.
- Heat detectors shown in kitchen,janitor closet should be changed to smoke detectors.
- Need additional info on the elevator to determine if a sprinkler head is necessary at top of shaft.(does
car meet ASME A 17.1 standards?) ki
- HVAC shutdown is required.
Dr's Yovanoff&Karp
- Strobes required for bathrooms.
TOWN OF QUEENSBURY COMMUNITY DEVELOPMENT DEPARTMENT