heat vent system iF
155 MAX ; l8 /77,_,..,,,,„,
( 'DR jr6
.
__ „., R
HEAT RECOVERY VENTILATOR
I b z ,
a 4 7 rl rl
•i0i bfyf b.._„ ie
ENGINEERING DATA g( � x
THERMALLY CONDUCTIVE,PATENTED DEFROST
ALUMINUM CORE Recirculating damper defrost system.
The counter-flow heat recovery core transfers heat between the two airstreams.It is
easily removed for cleaning or service. CASE
Twenty gauge prepainted galvanized steel for superior corrosion resistance.Insulated to
MOTORS AND BLOWERS prevent exterior condensation.Drain connections 2-1/2 in.(12 mm)OD.Balancing ports
Each airstream has one centrifugal blower driven by a common PSC motor,with multiple are located on door.
fan speed operations.
ELECTRONICS ... ....
FILTERS The DXPLO2 control included with the unit can be wall mounted n a central location of
Washable air filters in exhaust and supply air streams. the home.3 wire 20 gauge(min.)100 ft length(max.). F'L E C O •
MOUNTING _..
Four threaded inserts at corners of the cabinet designed to accept the"s"hooks and WARRANTY
hanging straps supplied with the unit. Units carry a lifetime warranty on the HRV core and a 5 year
replacement parts warranty.
OPTIONAL ACCESSORIES:
TechGWeather Hood le
99-EAG4
Terminator Wireless 20/40/60
99-185 99-EAGS Fitting Min Timer
99-186 i- 99-EAG6k--. 99-TMS99-TM4 99-DET02 `°
99-187 1i 99-EAG8
�, 4 y 99-TM6 r
LIFEBREATH CONTROL OPTIONS TIMER OPTIONS
99-DET01-Lifebreath 20/40/60 Minute Timer
FEATURES 99-DXPLO2 99-BCO2 99-BC03 99-BC04
Initiates high speed Ventilation for 20,40 or 60
5 speed fan operation on each mode ✓ minutes.3 wire connection.
99-DETO2
2 speed fan operation(Low/High) ✓ v- Wireless Lifebreath 20/40/60 Minute Timer
Continuous low speed fan operation ✓ Initiates high speed Ventilation for 20,40 or 60
minutes.Wirelessly connects to main control for
Humidity control through adjustable Dehumidistat ✓ ✓ ✓ ease of installation.40'approximate range.
Excusive to Lifebreath.
Large digital LCD screen ✓
99-RX02-Wireless Lifebreath Repeater
LED status indicator lights ✓ ✓ ✓ Extends range of 99-DET02 Wireless Timers.Plugs
into 120V power outlet.Wirelessly connects to
Continuous Ventilation ✓ V main control and 99-DET02.Install at halfway
✓ ✓ point between timer and main wall control if timer
Continuous Recirculation is out of range.
20 ON/40 OFF V
10 ON/50 OFF V ., ,, i
20 ON/40 Recirculation ✓ ✓ ✓ ~
(blot 'ci1o• o ;,, ,
20/40/60 min.High speed override button ✓ 99 DXPLO2 99-DET02
Compatible with 99-DET02 Wireless Timer ✓ ✓ V ✓ NO
3 wire connection ✓ V V V L IFEBREFI THT
1 Indoor Air Systems
155MAX(01-01-18) www.lifebreath.com
i
i a r
x w
1.
r 155 l AX r
i,
1,3
HEAT RECOVERY VENTILATOR
PERFORMANCE (HVI CERTIFIED) LIFEBRERTH°
J
0.1(25) 0.2(50) 0.3(75) 0.4(100) 0.5(125) 0.6(150) 0.7(175) ELECTRICAL SPECIFICATIONS
IN.W.G.(PA) CFM(L/s) CFM(L/s) CFM(Ifs) CFM(L/s) CFM(Us) CFM(Us) CFM(L/s)
VAC @ 60Hz 115
Net Supply Airflow 184(87) 163(77) 146(69) 132(62) 115(54) 92(43) 60(28) Watts/Low Speed 66
Gross Supply Airflow 188(87) 166(78) 149(70) 134(63) 117(55) 94(44) 61(29) Watts I High Speed 118
Gross Exhaust Airflow 239(113) 228(107) 212(100) 193(91) 172(81) 150(71) 126(60) Amp Rating 1.4
Sensible Effectiveness(ASE) 32°F(0°C) 84% 180 WEIGHT:
@ 59 CFM(28 Us) 71 LBS(32 KG)
Sensible Efficiency(SRE) 160 SHIPPING WEIGHT:
@ 59 CFM(28 Us)
32°F(0°C) 75% 73 LBS(33 KG)
E 140
Sensible Efficiency(SRE) 32°F(0°C) 15%
@64CFM(30Us) • 3 120
Sensible Efficiency(SRE) -13°F(-25°C) 72% l00
NOTE:
@ 64 CFM(30 Us) a Front clearance of 25 in.(635 mm)is
80 recommended for servicing unit.All ducts
r1 S� use 6 in.(152 mm)round collars.Balancing
® c ri us V I- 90 O <1._HK4I 60 dampers are located in all air streams.
,„e„ws..n„a, CERTIFIED IIEeISIEREO
I I I I I I I I•
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Static Pressure(in w.g.)
DIMENSIONS
FRONT VIEW TOP VIEW
Filter IP ' 14 3/4 in.(315 mm)'
Recirculating 1111
Defrost !� Irk —i I I I I
Damper — -
) l`
Removable %' \'4 .°11.,/ w I IIi1� Blower
Heat ����
Recovery Motor stale air to outside
Core Km
. - Fresh air from outside
`` "'..� - Stain air from inside
ill
�, Ilk -/..,-.11,1 ♦ •
y Fresh air to inside
Bin.Roun(d152Coll marsm) l — 33 5/8 in.(854 mm) — 'I •o v
Date: WARRANTY
Contractor: Units carry a lifetime warranty
Tag:
on the HRV core and a 5 year
replacement parts warranty.
Project. Qty: Supplier:
Engineer: Quote#: _ All units conform to CSA and UL standards
I/
Control: Submitted By: LIFEBRERTH°
II Indoor Air Systems
Timer: Timer Qty:
1SSMAX(01-01-18) www.lifebreath.com