Wedgewood Building 5_57 Wedgewood Dr_air leakage resultsTesting Company: Name:LoCascio Energy Solutions Address:20 Ogden Rd. Queensbury , NEW YORK 12804 Phone: 5188573144 Technician: Name:Anthony LoCascio Credentials:HERS Rater#4242961 Email:tony@locascioenergysolutions.com Building Information: Project ID:Wedgewood Building 5 Address:Wedgewood Dr Queensbury, NY 12804 Geo-Tag Data:Latitude: 43.325916 Longitude: -73.684380 Timestamp: 2020-04-22 11:38:55 Customer Information: Name:Schermerhorn Holdings Address:536 Bay Rd Queensbury, NY 12804 Measured Leakage:1,036.0 CFM50 Test ID:57 Wedgewood Dr Purpose of Test:RESNET Multi-Pt Env. Leakage Measured ACH50:6.14 (+/- 2.6%)Effective Leakage Area: 91.4 in² Building Volume:10,127.0 ft³Enclosure Surface Area: 1,066.0 ft² Flow Coefficient (C):169.7 (+/- 11.8%)Exponent (n): 0.462 (+/- 0.034) Correlation Coefficient:0.99920 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 63 °F Altitude: 455.0 ft Outdoor Temp: 34 °F Time Average Period: 10 seconds Test Date and Time:2020-04-22 12:13:00 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -20.6 -60.0 -78.7 -58.1 -39.8 1,145.7 Ring A -48.0 -67.7 -47.1 -31.0 1,013.1 Ring A -35.0 -55.5 -34.8 -24.8 907.7 Ring A -23.0 -42.7 -22.0 -148.4 722.5 Ring B -10.0 -32.7 -12.0 -85.4 549.4 Ring B Test Equipment: Flow Device:Model 3 110V Fan Serial #: 3173 Custom Calibration Date: 2020-02-10 Pressure Gauge:DG1000 Serial #: 3173 Calibration Date: 2019-02-18 Deviations from Standard: n value is outside of normally accepted limits. Comments: Envelope Leakage Test (Page 2) Report generated by TEC Auto Test version 1.6.3 (2), © 2019 by The Energy Conservatory, Inc.