Loading...
HVACFILE COPY The Caroline HVAC Load Calculations for Caruso Home Builders F whispecing Pirned wage Prepared By: ‘Adams Heating And Cooling ‘Monday,October 29,2018 Rhvac is an ACCA approved Manual J and Manual D computer programCalculationsareperformedperACCAManualJ8thEdition,Version 2,and ACCA Manual D. [Project ReportaProjectTitle:The Caroline Designed By:Adams Heating And Cooling Project Date:Friday,October 26,2018 Client Name:Caruso Home Bulders ‘Client Address:122 Richmond Hill Drive ‘Client Comment: ‘Company Name:‘Adams Heating And Cooling ‘Company Comment:(eeRSoTSeieeeona]Reference City:‘Schenectady,New York Building Orientation:Front door faces South Daily Temperature Range:Medium Latitude:42 Degrees Elevation:378 ft. Altitude Factor:0.986 Outdoor Outdoor Outdoor Indoor Indoor GrainsDryBulbWetBulbRelHumRelHumDoBulbDifference Winter:5 0.31 na na nla ‘Summer:95 72 33%50%%17(nenEeapeeRyCE]Total Building Supply CFM:1,225 CFM Per Square ft.:0.287 Square ft.of Room Area:4273 ‘Square ft.Per Ton:1,648 Volume (ft?):21,718(aSAEE]Total Heating Required Including Ventilation Air:53,035 Btuh 53.035 MBH Total Sensible Gain:27,890 Btuh 90 % Total Latent Gain:3,219 Btuh 10 % Total Cooling Required Including Ventilation Air:34,109 Btuh 2.59 Tons (Based On Sensible +Latent) Rhvac is an ACCA approved Manual J and Manual D computer program Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions, CA\...SUNTTLO.th Monday,October 29,2018,2:47 PM The Caroline ||Page3|[Miscellaneous Report ] Rhvac -Residential &Light Commercial HVAC Loads ©Elite Software Development,inc. ‘System 1 ‘Outdoor Outdoor ‘Outdoor indoor Indoor Grains Input Data.Dry Bulb Wet Bulb Rel.Hum_Rel.Hum Dry Bulb Difference Winter:5 0.31 100%nia 70 na ‘Summer:95 72 33%50%75 17.01 [Duct Sizing Inputs ] ‘Main Trunk Runouts Calculate:Yes Yes Use Schedule:Yes Yes Roughness Factor:0.00300 0.01000 Pressure Drop:0.1000 in.wg./100 ft.0.1000 in.wg./100 ft. Minimum Velocity:650 ft/min 450.ft/min Maximum Velocity:900.ft/min 750.ft/min ‘Minimum Height:0 in,0 in. ‘Maximum Height:8 in,0 in. [OutsideAirData=u Winter ‘Summer Infiltration Specified:0.370 AC/hr 0.190 AC/hr 134 CFM 69 CFM Infiltration Actual:0.331 AC/hr 0.093 AC/hr Above Grade Volume:XK 21718 Cutt.X21718Cut. 7,184 Cu.ft/pr 2,017 Cu.ft/hr X.0.0167 x.00187 Total Building Infiltration:120 CFM 34 CFM Total Building Ventilation:60 CFM 60 CFM —System 1-— Infiltration &Ventilation Sensible Gain Multiplier:21.70 =(1.10 X 0,986 X 20.00 Summer Temp.Difference) Infiltration &Ventilation Latent Gain Multiplier:141.41 =(0.68 X 0.986 X 17.01 Grains Difference) Infiltration &Ventilation Sensible Loss Multiplier:81.38 =(1.10 X 0.986 X 75.00 Winter Temp.Difference) ‘Winter infitration Specified:0.370 AC/hr (134 CFM),Construction:Average ‘Summer Infiltration Specified:0.190 AC/hr (69 CFM),Construction:Average CA\..\UNTTLO.rho Monday,October 29,2018,2:47 PM (Load Preview Report 7.Walk In Closet Master Bath @-Rear Enty 40Powder Room ‘t-Laundy 12 Bedroom 2 13.Untinished Bedroom 4 M-Bedkoom 3 1S.Upstairs Foyer CA\...\SUNTTLO.tho Monday, October 29, 2018, 2:47 PM [Duct Size Preview oem or Jeouce|aime)Maman)Mag |Pram)Se)Sie]Oa]we||Aa |Bet [Sie name :Waccty|"Naocty|‘Padr|‘L%80|Loss|velocty|tangs |89 |G|Ak,|Sut Sistem + Supply Runouts Zone + ‘Basement putin 450,750,at o a2.ivina Roon/Fover putin 450,750,ms at 252 2] 2-Diina Room futin —450,«=750)ssi 23 “exten utin —450«=750s ste 2Pantyeeeeer20.1 “4 eater Bator ee ee ee soo +5 "Waka Cet puttin 450—=S 750s at 108.4 14 Mate Bat putin 450.=S 750 mst 450 +s Rear Entry ulin 450,—=SS 750 mst asa “4 10Ponder Room utin 450,750,tat 2008 toa sLaunry futtin —450=S 750 sat 02 1‘28edc0m 2 futin —450,=750 tat sar 15 {2Ustnihed Batroom 4 autin —450«=750,sat 5569 2sBeton3fuin—450—«=750s at soe 15 Snare Fovee euin —450«==750,mst 1758 “4 Other Ducts in Sytem 1 Sco Main Tank euin ___650___sn0 uns 04 54 208__Summary svstom 1 Heatna Flow 834 Cooling Flow:1225 CA\...\UNTTLO.tho:Monday,October 28,2018,2:47 PM The Caroline Page 6 Riivac -Residential &Light Commercial HVAC Loads Elite Software Development,inc. ‘ABR Wholesalers [Rochester]Gg ‘Area Sen tat ‘Sen Total Quan Loss.Gain Gain.Gain| 3A-v-0:Glazing-Double pane low-e (e =0.40),operable 3298 13,110 0 13.610 13,610 window,vinyl frame,u-value 0.53,SHGC 0.56 14P:Door-Metal -Polyurethane Core 378 822 o 340 340 15C19-Ow-8:Wall-Basement,,framing with R-19 sill to 1497.6 4,829 0 0 0 floor in 2 x 6 cavity,core,no board insulation,plus interior finish,wood studs,8'floor depth 412E-Osw:Wall-Frame,R-19 insulation in 2 x 6 stud 23129=11,795 0 3,524 3,524 cavity,no board insulation,siding finish,wood studs 16C-38:RoofiCeiling-Under Attic with Insulation on Attic 2181.2 4,195 0 2.517 2.517 Floor (also use for Knee Walls and Partition Ceilings),Vented Attic,No Radiant Barrier,White or Light Color Shingles,Any Wood Shake,Light Metal, Tar and Gravel or Membrane,R-38 insulation 214-20:Floor-Basement,Concrete slab,any thickness,2 1806.2 3,658 0 0 0 or more feet below grade,no insulation below floor, ___any floor cover,shortest side of floor slab is 20 wide Subtotals for structure:38,409 0 19,991 19,991 People:4 800 920 1,720 Equipment:1349 «4,948 6.297 Lighting:0 0 0 Ductwork:0 0 0 0 Infiltration:Winter CFM:120,Summer CFM:34 9,743 385 94414Ventilation:Winter CFM:60,Summer CFM:60 4.883 685 1,302 1.987 Total Building Load Totals:63,035 3.219 27,880 31,109 [Cheek Figures.] Total Building Supply CFM:1,225 CFM Per Square ft 0.287 ‘Square ft.of Room Area:4,273 Square ft.Per Ton:1,648 Volume (ft)21718 [Building Loads } Total Heating Required including Ventilation Air.53,035 Btuh 53.035 MBH Total Sensible Gain:27,890 Btuh 80 % Total Latent Gain:3,219.Btuh 10 % Total Cooling Required Including Ventilation Air:31,109_Btuh 2.59 Tons (Based On Sensible +Latent) [Notes|1 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Ecition,Version 2,and ACCA Manual D. All computed resuits are estimates as building use and weather may vary. |Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at |your design conditions, CA..-UNTTLO.th9 Monday,October 29,2018,2:47 PM Rhivac -Residential &Lia ‘ABR Wholesalers [Rochester]The Caroline|Rochester.NY 14609-6136.Page 7 Building Pie Chart -|§ "Elite Software Development,inc. Floor 7%Ventilation 9% Roof 8% Infiltration 18% Door 2% Wall 31% Glass 25% Roof 8%Ventilation 6% Infiltration 4% Wall 11% Equipment 20% People 6% Door 1% Glass 44% CA\...\UNTTLO.tho Monday,October 29,2018,2:47 PM Riivac -Residential &Light Commercial HVAC Loads §|ABR Wholesalers [Rochester |Rochester,NY 14609-6136 [System 1_Summary Loads Elite Software Development,Inc. ‘The Caroline|Page6] ‘Component ‘Area ‘Sen Lat ‘Sen Total Description.Quan.Loss.Ge |3A-v-0:Glazing-Double pane low-e (e =0.40),operable 3298 13,110 0 13610 13,610 |window,vinyl frame,u-value 0.63,SHGC 0.56 |11P:Door-Metal -Polyurethane Core.37.8 822 0 340 340 15C19-Ow-8:Wall-Basement,,framing with R-19 sill to 1497.6 4,828 0 0 0 floor in 2 x 6 cavity,core,no board insulation,plus interior finish,wood studs,8"floor depth 12E-Osw:Wall-Frame,R-19 insulation in 2 x 6 stud 23129 11,795 o 3,524 3,824 cavity,no board insulation,siding finish,wood studs | 18C-38:Roof/Ceiling-Under Attic with Insulation on Attic 2151.2 4,195 0 2.517 2.517 Floor (also use for Knee Walls and Partition Ceilings),Vented Attic,No Radiant Barrier,White or Light Color Shingles,Any Wood Shake,Light Metal Tar and Gravel or Membrane,R-38 insulation 21A-20:Floor-Basement,Concrete stab,any thickness,2 1806.2 3,658 0 0 0 or more feet below grade,no insulation below floor, any floor cover,shortest side of floor slab is 20'wide ‘Subtotals for structure 38,409 o 19,991 19,991 | People:4 800 920 4,720 Equipment:1,349 4,948 6.297 Lighting:0 0 0 Ductwork:0 0 0 0 Infiltration:Winter CFM:120,Summer CFM:34 9,743 385 729 4414 Ventilation:Winter CFM:60,Summer CFM:60 4.883 685 4,302 1.987 System 1 Load Totals:53,035 3219 27,890 31,109 [Cheek Figures ] ‘Supply CFM:1,225 CFM Per Square ft 0.287 Square ft.of Room Area 4.273 Square ft.Per Ton:1,648 Volume (ft)36,167 [System Loads zl Total Heating Required Including Ventilation Air 53,035 Btuh 53.035 MBH Total Sensible Gain 27,890 Btuh 80 % Total Latent Gain 3,219.Btuh 10 % Total Cooling Required Including Ventilation Air 31,109_Btuh 2.59 Tons (Based On Sensible +Latent) (Notes:J your design conditions, Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at CA\...\UNTTLO.th Monday,October 29,2018,2:47 PM ‘ABR Wholesalers {Rochester]The Caroline Rochester,NY 14809-6135 [Equipment Data -System 1[Rhvac -Residential &Light Commercial HVAC Loads &Elite Software Development,Inc. Cooling System Type:Standard Air Conditioner Outdoor Model:13AJN42 Indoor Model:H,RE43(6,9)60 Outdoor Manufacturer:RHEEM Indoor Manufacturer:ADP. ‘AHRI Reference No.200923845 Capacity 40000 Efficiency:14.5 SEER Heating System Type:Natural Gas Fumace Model:R92PA0851521MSA Tradename:RHEEM,RUUD Manufacturer:RHEEM SALES COMPANY,INC. Description’Natural Gas or Propane Fumace Capactty 78000 Efficiency:92 AFUE This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data:SODB:95F,SOWB:72F,WODB:-5F,SIDB:75F,SIRH:50%,WIDB:70F,Sen.gain: 27,890 Btuh,Lat.gain:3,219 Btuh,Sen.loss:63,035 Btuh,Entering clg.coil DB:76F,Entering cig.coil WB:63F,Entering htg.coil DB:62.9F,Cig.coil TD:20F,Hig.coil TD:70F,Req,clg.airflow:1225 CFM,Req.hig.airflow:634 CFM CA..\-UNTTLO.rho Monday,October 29,2018,2:47 PM [Manual S Performance Data -System 1 Outdoor Dry Bulb’95 Sensible Gain 27,890 ‘Outdoor Wet Bulb’72 Latent Gain:3.219 Indoor Dry Bulb:75 Total Gain:31,109 Indoor RH:50 Load SHR:0.90 Elevation:378 ‘Supply Airflow:1,225 Latitude:42 Entering Dry Bulb:76 Altitude Factor:0.99 Entering Wet Bulb:63 ‘Standard Air Conditioner Model:13AJN42+H,RE43(6,9)60,Nominal Capacity:40,000 Interpolation Results: Percent LoadofLoadSensibleCapacity:0 27,890 0% Latent Capacity:0 3,219 0% Total Capacity:0 31,109 0% system's equipment was selected in accordance with ACCA Manual S. CA...\SUNTTLO.th Monday,October 29,2018,2:47 PM [System 1,Zone 1 Summary Loads (Average Load Procedure for Rooms)| 3A-v-0:Glazing-Double pane low-e (e =0.40),operable 329.8 13,110 13610 13,610 window,vinyl frame,u-value 0.53,SHGC 0.56 114P:Door-Metal -Polyurethane Core 378 822 0 340 340 15C19-Ow-8:Wall-Basement,,framing with R-19 sill to 1497.6 4,829 0 0 0 floor in 2 x 6 cavity,core,no board insulation,plus interior finish,wood studs,8"floor depth 12E-Osw:Wall-Frame,R-19 insulation in 2 x 6 stud 23129©11,795 0 3,524 3,524 cavity,no board insulation,siding finish,wood studs 16C-38:Roof/Ceiling-Under Attic with Insulation on Attic,21812 4,195 o 2.517 2517 Floor (also use for Knee Walls and Partition Ceilings),Vented Attic,No Radiant Barrier,White or Light Color Shingles,Any Wood Shake,Light Metal, ‘Tar and Gravel or Membrane,R-38 insulation 214-20:Floor-Basement,Concrete slab,any thickness,2 1806.2 3,658 0 0 0 or more feet below grade,no insulation below floor, any floor cover.shortest side of floor slab is 20'wide —‘Subtotals for structure:38,409 0 19,991 19,991 People:4 800 920 1,720 Equipment:4,349 4,948 6,297 Lighting:0 0 0 Ductwork:0 0 0 Inftration:Winter CEM:120,Summer CFM:34 9.743 385 729 System 1,Zone 1 Load Totals:48,152 2.534 26,588 ‘Supply CFM:1,225 CFM Per Square ft:0.287 ‘Square ft.of Room Area’4.273,‘Square ft.Per Ton:1,761 Volume (ft):36,167 Total Heating Required 48,152.Btuh 48.152 MBH Total Sensible Gain 26,588 Btuh 91% Total Latent Gain:2,534 Btuh 9% Total Cooling Required 29,122_Btuh 2.43.Tons (Based On Sensible +Latent) Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at ‘your design conditions. \..\SUNTTLO.tho Monday,October 29,2018,2:47 PM [Detailed Room Loads -Room 1 -Basement (Average Load Procedure) Calculation Mode:Htg.&clg ‘Occurrences:1 Room Lenath:425 ft System Number:1 Room Width:425 ft Zone Number:1 Area 1,806.3 sqft ‘Supply Air:0 CFM Ceiling Height:80 ft ‘Supply Air Changes:0.0 ACihr Volume:14,450 cust.Req.Vent.Clg:0 CFM Number of Registers:0 Actual Winter Vent 11 CFM Runout Air:0 CFM Percent of Supply.0%Runout Duct Size:0 in.Actual Summer Vent.0 CFM Runout Air Velocity 0 ftmin.Percent of Supply:0%Runout Air Velocity 0 ft/min.Actual Winter infil:0 CEM Actual Loss:0.000 in.wg./100 ft.Actual Summer Inf 0 CEM N -Wall-15C19-Ow-8 58 X 8 464 (0.043 32 1,496 0.0 0 0 E -Wall-15C19-Ow-8 35.2 X 8 2816 0.043,32 908 0.0 0 0 'S -Wall-15C19-Ow-8 58 X 8 464 0.043,32 1,496 0.0 0 0 W -Wall-15C19-0w-8 36 X 8 288=0.043 32 929 0.0 0 0 Floor-21A-20 42.5 X 42.5 1806.2 0.027 20 3,658 0.0 0 0 ‘Subtotals for Structure:8.487 0 0 Infil:Win.:0.0,Sum.:0.0 0 0 0 0 0 0 Ductwork:0 0 Room Totals:8.487 0 0 CA..\-UNTTLO.rhS,Monday,October 29,2018,2:47 PM (Detailed Room Loads -Room 2 -Living Room/Foyer (Average Load Procedure)_| eaeaemCalculationMode’Hig,&cla.‘Occurrences:1 Room Length:209 ft ‘System Number:1 Room Width’209 ft Zone Number:1 436.8 sat ‘Supply Air:206 CFM O41 ft ‘Supply Air Changes:3.4 ACihr 3,986 cut.Reg.Vent.Clg 0 CEM Number of Registers:2 Actual Winter Vent:9 CFM Runout Air 403 CFM Percent of Supply.:4%Runout Duct Size:6inActualSummerVent.10 CFM Runout Air Velocity:525 ft/min Percent of Supply:5% Runout Air Velocity:525.fulmin Actual Winter Inf 20 CFM Actual Loss:0.174 in.wg./100 ft.Actual Summer Infi.:6 CFM ‘S -Wall-12E-Osw 29 X 9.1 2099 0.068 61 4,074 15 0 320 W -Wall-12E-Osw 2 X 9.1 182 0.068 54 93 15 0 28 E -Wall-12E-Osw 18.5 X 9.1 138.9 0.068 54 708 15 0 212 S -Door11P 3X67 20 0.290 218 435 90 0 180 S -Gis-3A-v-0 shgc-0.56 0%(2)18 0.530 398 716 349 0 628 E -Gis-3A-v-0 shgc-0.56 0%S (2)30°0.530 398 1,190 632 0 1,892 S -Gis-3A-v-0 shgc-0.56 0%S (2)167 0.530 398 662 349 0 582 UP-Ceil-16C-38 20.9 X 20.9 436.8 20 852 12 0 511 Subtotals for Structure:5,727 0 4,353 Infil:Win.:20.2,Sum.5.7 452 3635 16420272 65 123 Ductwork:_o 0 Room Totals:7,369 654.476 CA..\SUNTTLO.th9 Monday,October 29,2018,2:47 PM [Detailed Room Loads Room 3 Dining Room (Average Load Procedure)]iareeraEereeeeeCalculationMode:Hig.&og Occurrences:1 Room Length:13.3 ft ‘System Number:1 Room Width 16.0 ft.Zone Number:1 Area:2134 sqft.Supply Air:217 CEM Ceiling Height:ot Supply Air Changes:67 ACihr Volume:1,948 cut,Req.Vent.Clg 0 CEM Number of Registers:2 Actual Winter Vent.8 CFM Runout Air:108 CFM Percent of Supply.4% Runout Duet Size:6 in Actual Summer Vent 11 CFM Runout Air Velocity:552 ft/min Percent of Supply:5% RunoutAir Velocity:552 ft/min.Actual Winter infil 14 CFM Actual Loss:0.192_in.wg./100ft._Actual Summer infil 4 CEM 'S -Wall-12E-Osw 4 X 9.1 365 0.068 54 186 15 0 56 E -Wall-12E-Osw 13.2 9.1 769 0.068 5A 392 15 0 117 N-Wall-12E-Osw 16 X 9.1 86 (0.068 54 438 15 0 131 E -Gls-3A-v-0 shgc-0.56 0%S (3)441 0.530 398 1,752 63.2 0 2.784 N-Gis-3A-v-0 shgc-0.56 100%S 60 0.530 398 2,386 21.3 0 4279 UP-Ceil16C-38 13.3 X 16 2134 0.026.2.0 416 12 °250 Subtotals for Structure:5,570 0 4617 Infil:Win.:13.6,Sum.3.8 303 3635=1103.24 43 83 Ductwork:-0 0 Room Totals:6673 4,700 CA\...\UNTTLO.tho Monday,October 29,2018,2:47 PM [Detailed Room Loads Room 4 Kitchen (Average Load Procedure)]aeeeen) Calculation Mode:Htg,&lg.Room Length:17.0 Room Width:13.3 Area:226.8 Ceiling Height:9.4 Volume:2,089 Number of Registers:2 Runout Air:106 Runout Duct Size:6 Runout Air Velocity:538 Runout Air Velocity:538 Actual Loss: ft ft sqftftcut crM in. fUmin. fUmin. 0.183 _in.wg./100 ft. ‘Ocourrences:1 System Number:1 Zone Number:1 ‘Supply Air:211 CFM ‘Supply Air Changes:6.1 AC/hr Req.Vent.Clg:0 CFM ‘Actual Winter Vent.1 CFM Percent of Supply.0% ‘Actual Summer Vent.10 CFM Percent of Supply:5% ‘Actual Winter Inf 3 CFM Actual Summer Inf 1_CFM‘N-Wall-12E-Osw 7.2 X 9.1 2 65.7,0.068 _335 15 o 100 Subtotals for Structure:335 0 100 Inf:Win.:2.9,Sum.:0.8 66 3.638 239°(0.274 9 18 Ductwork:0 0 Equipment:1,349 4.470 Room Totals:574 1,358 4,588 Coffee maker -brewer 1331 ‘Cooking range no hood -four 13311 burners on high heat Toaster 3532 Dishwasher 4096 Microwave 4949 Refrigerator or freezer -16 1000 cubic feet Total 717, 7167 392 1433 1732 100 25 333 179 25 28 832 448 100 10 353 39 100 25 1024 358 78 25 928 325 100 100 1000 0 4470 1349 CA\...-UNTTLO.tho Monday,October 29,2018,2:47 PM [Detailed Room Loads -Room 5 -Pantry (Average Load Procedure) Calculation Mode:Hig.&cig Room Length:90 ft Room Width’60 ft Area:54.0 sqit Ceiling Height:ot ft Volume:493.cuft. Number of Registers:1 Runout Air 18 CFM Runout Duct Size:4 in Runout Air Velocity:208.ft/min. Runout Air Velocity:208.ft/min. Actual Loss:0.050 ‘Occurrences: ‘System Number: Zone Number: ‘Supply Air: ‘Supply Air Changes: Reg.Vent.Clg: Actual Winter Vent: Percent of Supply.: Actual Summer Vent Percent of Supply: Actual Winter infil .wg./100 ft.Actual Summer Infil.: 48 CEM ACInr CFM CFM crM 0 2 0 1 CFM 5 6 2 CFM E -Wall-12E-Osw 6 X 9.1 548 0.068 54 279 15 83 N -Wall-12E-Osw 9 X 9.1 746 0.068 54 381 15 114 NG shgc-750530 39.8 298 21.3 160. ‘Subtotals for Structure:958 357 infil:Win.:6.4,Sum.1.7 137 3.638 498 0.270 37 Ductwork:HS a o 0 Room Totals:1,456 20 394 C:..\-UNTTLO.tho Monday,October 29,2018,2:47 PM [Detailed Room Loads -Room 6 -Master Bedroom (Average Load Procedure) Calculation Mode’ Room Length: Room Width: Area: Ceiling Height: Volume: Number of Registers: Runout Air: Runout Duct Size: Runout Air Velocity: Runout Air Velocity: Actual Loss: Hig.&clg. 135 ft 155 ft 209.3 sqft 94 ft 4,909 cut. 1 69 CFM 5 in 510 ft/min 510 ft/min 0.212 in.wg./100 ft ‘Occurrences: System Number: Zone Number: ‘Supply Air: ‘Supply Air Changes: Req.Vent.Cig: Actual Winter Vent Percent of Supply. Actual Summer Vent. Percent of Supply: Actual Winter infil Actual Summer Infi NooeevoNBaas 9 9 2 N -Wall-12E-Osw 13.5 X 9.1 938 0.068,54 478 15 0 143, N -Gls-3A-v-o shge-0.56 100%S (2)294 0.530 39.8 4,168 24.3 0 626 UP-Ceil-160-38 13.5 X 15.5 209.2 0.026 2.0 408 412 0 245 ‘Subtotals for Structure:2,054 0 1,014 Infil:Win.:6.5,Sum.:1.5 123 3.637 448 (0.276 18 34 Ductwork:0 0 People:200 latiper,230 sen/per:2 400 460 Room Totals:2,602 418 1,608 CA..\-UNTTLO.thd Monday,October 29,2018,2:47 PM [Detailed Room Loads -Room 7 -Walk in Closet (Average Load Procedure)J (RaaesSSSaeanee)ulation Mode:Occurrences:1 Room Length:‘System Number:1 Room Width:70 ft Zone Number:1 Area:73.5 sq Supply Air:47 CEM Ceiling Height:Ot ft ‘Supply Air Changes:1.5 ACihr Volume:671 cut Reg,Vent.Clg:0 CEM Number of Registers:1 ‘Actual Winter Vent.2 CFM Runout Air:17 CFM Percent of Supply.1%Runout Duet Size 4 iin,‘Actual Summer Vent.:4 CFM Runout Air Velocity 196 ft/min,Percent of Supply:5% Runout Air Velocity 196 f/m Actual Winter infil:7 CFM Actual Loss:0.045 in.wg./100 ft._Actual Summer Inf 2 CFM N -Wall-12E-Osw 10.5 X 9.4 958 0.068 54 489)15 0 148 ‘W-Wall-12E-Osw 7X 9.1 639©0.068 54 326 15 0 7UP-Ceil-16C-38 10.5 X7 735 0.026 20 443 12 Oo.86SubtotalsforStructure:958 0 328 Inf.Wi sum.:2.0 160 3.632 580 (0.269 23 43 Ductwor o o Room Totals:1,538 23 372 CA...A-UNTTLO.tho Monday,October 29,2018,2:47 PM [Detailed Room Loads -Room 8 -Master Bath (Average Load Procedure)] Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: Number of Registers: Runout Air: Runout Duct Size: Runout Air Velocity Runout Air Velocity Actual Loss: W-Wall-12E-Osw 13 X 9.1 W-Gls-3A-v-0 shgo-0.56 0%S UP-Ceil-16C-38 10.5 X 13 Subtotals for Structure: Infil.:Win.:8.3,Sum.:1.5 Ductwor Room Totals: Hig.&clg 105 ft 13.0 ft136.5 sqft 94 ft 1,246 cust 1 63 5 459 459 0.173 in.wg./100 ft. CFM 1026 0.068 16 0.53050.026 119 Occurrences: System Number: Zone Number: Supply Air: Supply Air Changes Reg,Vent.Cig: ‘Actual Winter Vent. Percent of Supply ‘Actual Summer Vent. Percent of Supply: ‘Actual Winter infil: Actual Summer infil 51 523 39.8 636 2.0 266 1,425 3.633 431 oO 1,856 1 1 1 63 CFM 3.0 ACIhr 0 CFM 2 CFM4% 3 CFM5% 5 CFM 1 CFM 15 0 156 63.2 0 4,011 12 oO 160 0 1,327 0.270 "7 32 o 7 1,369 CA...\SUNTTLO.rho Monday,October 29,2018,2:47 PM [Detailed Room Loads -Room 9 -Rear Entry (Average Load Procedure) Calculation Mode:Hig.&cg ‘Occurrences:1 Room Length:123 ft ‘System Number:1 Room Width:20.0 ft Zone Number:1 Area:246.8 sq.ft ‘Supply Air 29 Ceiling Height:4 ft ‘Supply Air Changes:08 Volume:2,252 cut Reg.Vent.Clg:0 Number of Registers:1 Actual Winter Vent:2 Runout Air:29 CFM Percent of Supply.”8 Runout Duct Size:4 in ‘Actual Summer Vent.1 Runout Air Velocity:335 ft/min Percent of Supply:5 Runout Air Velocity 335 ft/min ‘Actual Winter inf 5 Actual Loss:0.127 in.wg./100 ft.Actual Summer infil 1‘W-Wall-12E-Osw 13 X 9.1 1008 0.068 54 514 15 W-Door-11P 27X67 178 0.290 218 387 90 UP-Ceil-16C-38 12.3 X 20 246.8 0.026 2.0 481 12 Subtotals for Structure:1,382 sum:1.5 119 3.633 431 0.270 o 1,813 CFM ACIhr CFM CA...-UNTTLO.th9 Monday,October 29,2018,2:47 PM [Detailed Room Loads Room 10 Powder Room (Average Load Procedure) ERRRORE | Calculation Mode:Hig.&clg,Occurrences:1 Room Length:63 ft System Number:1 Room Wiatth 55 ft Zone Number:1 ‘Area:34.9 sq Supply Air:23 CFM Ceiling Height:a1 ft Supply Air Changes 4.3 ACIhr Volume:318 cuft Req,Vent.Clg 0 CEM Number of Registers:1 ‘Actual Winter Vent:1 CFM Runout Air 23 CFM Percent of Supply.:4% Runout Duet Size 4 in ‘Actual Summer Vent.1 CFM Runout Air Velocity:260.feimin.Percent of Supply:5% Runout Air Velocity:260 ft/min.Actual Winter infil 2 CEM Actual Loss:0.077 in.wg./100 ft.Actual Summer infil:1 CFM W-Wall-12E-Osw 5.5 X 9.1 437 0.068 54 223 15 0 67 W-Gls-3A-v-0 shgo-0.56 0%S_65 0.530 39.8 258 63.2 0 ait ‘Subtotals for Structure:481 0 478 Inf:Win.:2.2,Sum.0.6 50 3.626 182 0.279 7 14 Ductwork O 0RoomTotals:663 7 492 CA\...\SUNTTLO.th:Monday,October 29,2018,2:47 PM [Detailed Room Loads Room 11 Laundry (Average Load Procedure)aCalculationMode:Hig.&cig.Occurrences:1 Room Length:60 ft.System Number:1 Room Width 70 ft Zone Number:1 Area:42.0 sqft Supply Air:53 CFM Ceiling Height:94 ft Supply Air Changes:8.2.ACMhr Volume:383 cust Reg,Vent.Cig:0 CFM Number of Registers:1 ‘Actual Winter Vent.2 CFM Runout Ai:53 CFM Percent of Supply.3% Runout Duct Size:4 in ‘Actual Summer Vent.3 CFM Runout Air Velocity:602.ft/min.Percent of Supp!5% Runout Air Velocity:602.ft/min.‘Actual Winter infil:5 CFM Actual Loss:0.403 in.wg./100 ft._Actual Summer infil.1_CFM W -Wall-12E-Osw 7 X 9.1 574 0.068 54 293 15 0 87 S -Wall-12E-Osw 6 X 9.1 548 0.068 54 278 15 0 83 W-Gls-3A.v-0 shgc-0.56 0%S.65 0.530 398 258 632 0 ait UP-Cell-16C-38 6X7 420.026 20 82 120 49 ‘Subtotals for Structure:912 0 630 Inf:Win.:5.3,Sum.1.5 119 3.633 431 0.270 7 32 Ductwork:0 0 Equipment ee 0 478 Room Totals:4,343 171,140 Vented clothes dryer -10 1707 0 ‘50 50 427 0 percent to space Clothes washing machine -205 °50 50 51 0 10 percent to space Total 478 0 CA..\SUNTTLO.rho,Monday,October 29,2018,2:47 PM [Detailed Room Loads -Room 12 -Bedroom 2 (Average Load Procedure) Calculation Mode’Hig,&ola.‘Occurrences:1 Room Length:13.0 ft,‘System Number:1 Room Width:16.0 ft.Zone Number:1 Area 208.0 sqft ‘Supply Air:69 CFM Ceiling Height:at ft ‘Supply Ait Changes:2.5 ACIhr Volume:1,690 cust Reg.Vent.Cig:0 CFM Number of Registers:1 Actual Winter Vent 6 CFM Runout Air:69 CFM Percent of Supply.8% Runout Duct Size:5 in.Actual Summer Vent 3 CFM Runout Air Velocity:508 ft/min Percent of Supply:5%Runout Air Velocity:508 ft/min Actual Winter Inf:15 CFM Actual Loss:0.210 in.wg./100 ft._Actual Summer Infil.:4 CFM E -Wall-12E-Osw 11X 8.4 894 0.068 5A 456 15 0 136 N-Wall-12E-Osw 13 X 8.1 71.5 0.068 5A 365 15 0 109 W -Wall-12E-Osw 16 X 8.1 130 (0.068 54 663 15 0 198 N--Gis-3A-v-0 shgc-0.56 100%S (2)34.1 0.530 398 1,356 21.3 0 728 UP-Ceil-16C-38 13 X16 208 0.026 2.0 406 12.0 243, ‘Subtotals for Structure:3.246 0 14414 Infil:Win.:14.5,Sum.:4.1 325 3634 11810271 a7 88 Ductwork:_0 0 Room Totals:4427 471,802 CA...SUNTTLO.tho Monday,October 29,2018,2:47 PM Detailed Room Loads -Room 13 -Unfinished Bedroom 4 (Average Load Procedure) Calculation Mode:Hig.&olg Oncurrences:1 Room Length:14.5 ft ‘System Number:1 Room Width’16.3 ft.Zone Number:1 Area’236.9.sq.‘Supply Air:152 CFM Ceiling Height:81 ft ‘Supply Air Changes:47 ACIhe Volume:1,925 cuff Reg,Vent.Clg 0 CFM Number of Registers:2 ‘Actual Winter Vent:6 CFM Runout Air CFM Percent of Supply.4%Runout Duet Size:in ‘Actual Summer Vent.7 CFM Runout Air Velocity:ft/min,Percent of Supply:5% Runout Air Velocity:fumin ‘Actual Winter inf 17 CFM Actual Loss:in.wg./100 ft.Actual Summer Inf 5 CFM N -Wall-12E-Osw 16.2 X 8.1 132 0.068 54 673 15 201 S -Wall-12E-Osw 16.2 X 8.1 132 (0.068 54 673 15 201 W -Wall-12E-Osw 14.5 X 8.1 837 0.068 54 4aar 15 127 W-Gls-3A-v-0 shgo-0.56 0%S (2)341 0.530 308 1,356 63.2 2,156 UP-Ceil-16C-38 14.5 X 16.3 2369 0.026 20 462 412 277 Subtotals for Structure:3,591 2,982 Inf:Win.:17.1,Sum.4.8 382 3635 1,388 (0.272 104 Ductwork:0 0 People:200 latiper,230 sen/per:1 200 230 Room Totals:4,979 255 3,296, CA...SUNTTLO.th Monday,October 29,2018,2:47 PM Calculation Mode:Hig.&clg Occurrences: Room Length:17.0 ft ‘System Number: Room Width:12.0 ft Zone Number:1 Area 204.0 sq.Supply Air:83 CFM Ceiling Height:at ft.Supply Air Changes:3.0 ACIhr Volume:1,658 cust,Req.Vent.Cig:0 CFM Number of Registers:1 Actual Winter Vent.:4 CFM Runout Air:83 CFM Percent of Supply.”5%Runout Duct Size:5 in ‘Actual Summer Vent.4 CFM RunoutAir Velocity 606 ft/min.Percent of Supply:5%Runout Air Velocity:606.ft/min,Actual Winter inf 11.CEM Actual Loss:.298_in.wg./100 ft.Actual Summer infil 3.CFM S -Wall-12E-Osw 17 X 8.1 11141 0.068 5A 567 15 0 169) E -Wall-12E-Osw 12 X 8.1 975 0.068,84 497 15 0 149, S -Gls-3A-v-0 shge-0.56 0%S (2)27 0.530 39.8 4,074 34.9 0 942 UP-Ceil-16C-38 17 X12 204 0.026 20 398 12 o 239 Subtotals for Structure:2,536 0 1,499Inf:Win.:10.5,Sum.3.0 236 3.637 857 0.272 34 64 Ductwork:0 0 People:200 latiper.230 sen/per:_200 230 Room Totals:3,393 234 1,793 CA...“UNTTLO.tho Monday,October 29,2018,2:47 PM [Detailed Room Loads -Room 15 -Upstairs Foyer (Average Load Procedure)] Calculation Mode’ Room Length: Room Width: Area’ Ceiling Height: Volume: Number of Registers: Runout Air: Runout Duct Size: Runout Air Velocity: Runout Air Velocity: Actual Loss: 'S -Wall-12E-Osw 7.2 X 8.1 W -Wall-12E-Osw 4 X 8.1 UP-Ceil-16C-38 12 X12 Subtotals for Structure: Inf:Win:4.1,Sum.1.4 Ductwork: Room Totals: Hig,&clg. 120 ft, 120 ft, 144.0 sat.81 ft 1,170 cust. 1 15 CFM 4 in 176 ft/min. 176 ft/min 58.9 32.5144 ot 0.068 0.068 0.026 ‘Ocourrences: System Number: Zone Number ‘Supply Air ‘Supply Air Changes: Reg.Vent.Clg: Actual Winter Vent. Percent of Supply. ‘Actual Summer Vent. Percent of Supply: Actual Winter infil 0.036 in.wg./100 ft._Actual Summer infil 54 51 3.632 1 1 1 15 08 0 1 9 1 5 4 1 18 15 4.2 0.274 CFM ACIhr CFM CFM % CFM % CEM CFM 0 90 0 50 0 168 0 308 3 25 0 13 333, Monday,October 29,2018,2:47 PM Zone 4 Basement 1806 8487112,0-0 0 0 0 0 02LivingRoomiFoyer—'437—7,369 7 26©525 4,476 65 2082063DiningRoom213°6.673 88 26©552 4.700 430 21774Kitchen227574826©5384588 1,358 211 tt5Pantry541,456 19 14 208394 20 18 186MasterBedroom2032,502 33 15 610 1,508 418 69 697WalkInCloset74115382014196137223778MasterBath1371,856 24 15 459 1,359 7 63 63 9 Rear Entry 247 1,813 24 14 335635 7 29 29 410 Powder Room 35663 9 14 260-492 7 23 23 11.Laundry 42 1,343 8 14 602,4,140 7 53 53 12 Bedroom 2 208 4.427 58 15 50811502 47 69 69 13 Unfinished 237 4.979 66 25 557 3.296255 152 152 Bedroom 4 14 Bedroom 3 204 3,393 45 16 6061793284 83 83 15 Upstairs Foyer 144 1.07914 14176 333 13 15 15Ventilation4.883,-1,302___685 System 1 total 4273 53,035 634 27,890 3,219 1,225 1,228 ‘System 1 Main Trunk Size 30x8 in. Velocity:735 ft/min Loss per 100 ft 189 in.wg(RSSarRe]Net Required:2.59 90%/10%27,890 3,219 34,109 Actual:3.33 75%|25%10,000 40,000HeatingSystem ‘Cooling SystemType:Natural Gas Furnace Standard Air Conditioner Model:R92PA0851521MSA 13AJNA2 Indoor Model:H,RE43(6,9)60BrandRHEEM,RUUD, Description’Natural Gas or Propane Furnace Efficiency:92 AFUE 14.5 SEER ‘Sound:0 0 Capacity:78,000 Btuh 40,000 Btuh Sensible Capacity nla 30,000 Btuh Latent Capacity:nla 10,000 Btuh AHRI Reference No.nla 200923845 ‘This system's equipment was selected in accordance with ACCA Manual Manual S equipment sizing data:SODB:95F,SOWB:72F,WODB:-5F,SIDB:75F,SIRH:50%,WIDB:70F,Sen.gain:27,890 Btuh,Lat.gain:3,219 Btuh,Sen.loss:53,035 Btuh,Entering clg.coil DB:76F.,Entering cig.coil WB:63F,Entering htg,coil DB:62.9F,Clg,coil TD:20F,Hig.coil TD:70F,Req,clg.airflow:1225 CFM,Req.hig.airflow:634 CFM CA...\SUNTTLO.rho Monday,October 29,2018,2:47 PM [Building Rotation Duct Sizes Room or Duct Name [Svstom 1 Supply Runouts Zone 1 “Basement 2.Lvina RoomFover 8.Dining Room 4-Katchen SPanty {Master Bedroom 7-Walk In Closet Master Bath Rear Enty 10-Ponder Room ‘Laundry 12-Beeroom 2 1-Uninished Baskoom 14.Bedkoom 3 $8:Upstairs Foyer Other Duets in Systom 1 Supply Main Trunk [Bia High De Nowheast |Sensibie Gain:21,669 Latent Gain 3.219 Max Duct Sze |Svstem 4 Heating Flow)634 Coolina Flow:1225 CA..\SUNTTLO.tho Monday,October 29,2018,2:47 PM