Manual S , _ 2lI 1 Manual S Compliance Report Job: St—...1 RIDGE DUPLEX... ' Date: May 30,2018 Entire House By: t FOOTHILL BUILDERS Plan: SMOKE RIDGE DUPLEX... QUEENSBURY,NY 12804 Project Information For: JOE LEUCI, FOOTHILL BUILDERS i JUN 12 2018 i 11,1 ) QUEENSBURY, NY 12804 1 (--% Cooling Equipment Design Conditions Outdoor design DB: 85.0°F Sensible gain: 15669 Btuh Entering coil DB: 75.4°F Outdoor design WB: 71.0°F Latent gain: 4193 Btuh Entering coil WB: 62.7°F Indoor design DB: 75.0°F Total gain: 19862 Btuh Indoor RH: 50% Estimated airflow: 678 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split AC ^O r�Y Manufacturer: YORK Model: HPS017120-075+AH017 F I LE V ff Actual airflow: 573 cfm Sensible capacity: 0 Btuh 0% of load Latent capacity: 0 Btuh 0% of load REVIEWED FOR Total capacity: 0 Btuh 0% of load SHR: 0% e-,v c'nnl= COMPLIANCE Heating Equipment Design Conditions Outdoor design DB: -4.0°F Heat loss: 79320 Btuh Entering coil DB: 64.0°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Gas furnace Manufacturer: York Model: YPLC080B12MP12C Actual airflow: 573 cfm Output capacity: 62000 Btuh 78% of load Temp. rise: 50 °F 308.8-1-21.41 RC-0342-2018 Foothills Builders 35 Smoke Ridge Rd., Lot 21A Meets are all requirements of ACCA Manual S. 1/2 of 2-Family 1465 s.f., Gar. 231 s.f. ® 2018-May-30 09:59:00 wrightsoft Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1 ACC*, ...rthy\Documents\York\SMOKE RIDGE DUPLEX LEFT.rup Calc=MJ7 Front Door faces: N A- , ; �' sidential Plans Examiner Review Form Form ACCk for rlviC System Design (Loads, Equipment, Ducts) 15Mar09 NrConioxivCcitadasofAmata QUEENSBURY NY Header Information Contractor: FOOTHILL BUILDERS REQUIRED ATTACHMENTS ATTACHED Manual J1 Form(and supporting worksheets): Yes 0 No D Mechanical license: or MJ1AE Form*(and supporting worksheets): Yes 0 No D OEM performance data(heating,cooling,blower): Yes ❑ No ❑ Building plan#: SMOKE Manual D Friction Rate Worksheet: Yes ❑ No ❑ RIDGE Duct distribution sketch: Yes 0 No ❑ Home address(Streetrxock,Subdivision): , Entire House HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Winter Design Conditions Building Outdoor temperature: -4 °F Orientation: Front Door faces North Indoor temperature: 68 °F North,East,West,South,Northeast,Northwest,Southeast,Southwest Total heat loss: 79320 Btuh Number of bedrooms: 3 Conditioned floor area: 3808 ft° Summer Design Conditions Number of occupants: 0 Outdoor temperature: 85 °F Indoor temperature: 75 °F Windows Roof Grains difference: 27 gr/Ib al' 0% RH Eave overhang depth: 0 ft Sensible heat gain: 17410 Btuh Internal shade: none Eave Latent heat gain: 4659 Btuh Blinds,drapes,etc. Depth Window Total heat gain: 22069 Btuh Number of skylights: 0 HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Cooling Equipment Data Blower Data Equipment tye: Gas furnace Equipment type: Split AC Heating cfm: 573 umace,Heatpump,Boiler,etc. Air Conditioner,Heat pump,etc. Cooling cfm: 573 . Model: York Model: YORK Static pressure: 0 in H2O YPLC080B12MP12C - HPS017120-075+AH017 Fan's rated extemal static pressure for design airflow Heating output capacity:. 62000 Btuh Total cooling capacity: 0 Btuh Heat pumps-capacity at winter design oudoorconditions Sensible cooling capacity: 0 Btuh Aux.heating output capacity: 0 Btuh Latent cooling capacity: 0 Btuh HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Design airflow: 573 cfm Longest supply duct: 0 ft Duct Materials Used Equipment design ESP: 0 in H2O Longest return duct: 0 ft Trunk duct: Total device pressure losses: 0 in H2O Total effective length(TEL): 0 ft Available static pressure(ASP): 0 in H2O Friction rate: 0 in/100ft Branch duct: Sheet metal Friction Rate=ASP=(TELx 100) I declare the load calculation,equipment,equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: Contractor's signature: Date: Reserved for County,Town Municipality or Authority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist 41- wrightsoft® Right-Suite®Universal 2017 17.0.16 RSU25116 Pro ect Summary Job: SMOKE RIDGE DUPLEX... z Date: May 30,2018 Entire House By: FOOTHILL BUILDERS Plan: SMOKE RIDGE DUPLEX... • QUEENSBURY,NY 12804 Pro'ect Information For: JOE LEUCI, FOOTHILL BUILDERS QUEENSBURY, NY 12804 • Notes: Desi• n Information Weather: Glens Falls AP, NY, US Winter Design Conditions Summer Design Conditions Outside db -4 °F Outside db 85 °F Inside db 68 °F Inside db 75 °F Design TD 72 °F . Design TD 10 °F Daily range M Relative humidity 50 % Moisture difference 27 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 74620 Btuh Structure 14938 Btuh Ducts 4700 Btuh Ducts 731 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 79320 Btuh Use manufacturer's data n Rate/swing multiplier 0.90 Infiltration Equipment sensible load 14102 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 4193 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Heating Cooling (none) Area(ft2) 3808 3808 Equipment latent load 4193 Btuh Volume(ft') 34272 34272 Air changes/hour 0.70 0.40 Equipment total load 18296 Btuh Equiv.AVF (cfm) 400 228 Req. total capacity at 0.70 SHR 1.7 ton Heating Equipment Summary Cooling Equipment Summary Make York Make YORK Trade YORK Trade SampCorp Model YPLC080B12MP12C Cond HPS017120-075 AHRI ref 2008747 Coil AH017 AHRI ref Efficiency 80AFUE Efficiency 11.0 EER, 12 SEER Heating input 80000 Btuh Sensible cooling 12600 Btuh Heating output 62000 Btuh Latent cooling 5400 Btuh Temperature rise 98 °F Total cooling 18000 Btuh Actual air flow 573 cfm Actual air flow 573 cfm Air flow factor " 0.007 cfm/Btuh Air flow factor 0.037 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.79 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. y Wrl htsoft® 2018-May-30 09:59:00 9 Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1 ACCA ...rthy\Documents\York\SMOKE RIDGE DUPLEX LEFT.rup Calc=MJ7 Front Door faces: N - Rig ht-J®Worksheet Job: SMOKE RIDGE DUPLEX LE... ' -`' ,, Entire House Date: May 30,2018 By: FOOTHILL BUILDERS Plan: SMOKE RIDGE DUPLEX LE... QUEENSBURY, NY 12804 MANUAL J:7th Ed. 1 Name of room Entire House Room1 Room2 Room3 2 Length of exposed wall • 556.0 ft 138.0 ft 34.0 ft 29.0 ft 3 Room dimensions 1.0 x 944.0 ft 14.0 x 20.0 ft 1.0 x 194.0 ft 4 Ceilings Condit.Option 9.0 ft d 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 5004 **** **** 1242 **** **** 306 **** **** 261 **** **** Exposed b 0 0 Il1111 **** **** 111111 **** **** I I I I I I **** **** I I I I I I **** **** walls and c 0 0 IIIIII **** **** 111111 **** **** IIIIII **** **** I I I I I I **** **** partitions d 0 0 IIIIII **** **** I I I I I I **** **** 111111 **** **** Illiil **** **** e 0 0 IIIIII **** **** IIII11 **** **** II!HI **** **** I I I I I I **** **** f 0 0 IIIIII **** **** IIIIII **** **** !mu **** **** ill III **** **** 6 Windows and a 3A0 39.7 ** 150 5951 **** 0 0 **** 30 1190 **** 30 1190 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** d 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 *""* e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 90 **** 1710 0 **** 0 30 **** 570 30 **** 570 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 30 **** 2040 0 **** 0 0 **** 0 0 **** 0 SE/SW 0 0 **** 0 0 **** 0 0 ***" 0 0 **** 0 South 34.0 30 **** 1020 0 **** 0 0 **** 0 0 **** 0 Horz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 105 3478 657 0 0 0 21 696 131 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 4749 25645 4844 1242 6707 1267 255 1377 260 231 1247 236 exposed b 0 0 111111 0 0 111111 0 0 nnn 0 0 IIIIII 0 0 walls and c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 partitions d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 e 0 0 IIIIII 0 0 111111 0 0 111111 0 0 null 0 0 f 0 0 111111 0 0 111111 0 0 111111 0 0 IIIIII 0 0 10 Ceilings a 16G0 2.4 1.1 1920 4562 2154 0 0 0 0 0 0 0 0 0 b 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 c 0 0 111111p 0 111111 0 0 111111p 0 WWII 0 0 e 0 0 nnn 0 0 nisi 0 0 nnn 0 0 111111 0 0 e 0 0 nnn 0 0 Inns 0 0 111111 0 0 111111 0 0 f 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 11 Floors a 1910 1.7 0 1888 3262 0 944 1631 0 280 484 0 194 335 0 (Note:room b 1910 1.7 0 32 55 0 0 0 0 0 0 0 0 0 0 perimeter c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 is displ. d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 for slab e 0 0 will 0 0 111111 0 0 111111 0 0 111111 0 0 floors) f 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 12 Infiltration a 124 9.9 255 31667 2513 0 0 0 51 6333 503 30 3726 296 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 74620 **** **** 8338 **** **** 10080 **** **** 6498 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 4700 **** 6% 525 **** 6% 635 **** 6% 409 **** 15 Total loss=13+14 **** 79320 **** **** 8863 **** **** 10715 ***" **** 6908 **** 16 Int.gains: People @ 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. @ 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 14938 **** **** 1267 **** **** 1464 **** **** 1101 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 "*"" **** 0 **** **** 0 18 Duct gain 5% **** 731 5% **** 62 5% **** 72 5% **** 54 19 Total RSH gain=(17+18)*PLF 1.00 **** 15669 1.00 **** 1329 1.00 **** 1536 1.00 **** 1155 20 Air required(cfm) 573 573 64 49 77 56 50 42 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. 2018-May-30 09:59:00 wrightsoft® Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1 ACt-A ...rthy\Documents\York\SMOKE RIDGE DUPLEX LEFT.rup Cale=MJ7 Front Door faces: N - Right-J®Worksheet Job: SMOKE RIDGE DUPLEX LE... ' ' Entire House Date: May 30,2018 By: FOOTHILL BUILDERS Pfan: SMOKE RIDGE DUPLEX LE... QUEENSBURY,NY 12804 MANUAL J:7th Ed. 1 Name of room Room4 Room5 Room6 Room7 2 Length of exposed wall 5.0 ft 0 ft 54.0 ft 16.0 ft 3 Room dimensions 1.0 x 51.0 ft 5.0 x 7.0 ft 1.0 x 328.0 ft 14.0 x 4.0 ft 4 Ceilings Condit.Option 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 45 **** **** 0 **** **** 486 **** **** 144 **** **** Exposed b 0 0 " IIIIII **** **** 111111 **** **** Milli **** **** IIIIII **** **** walls and c 0 0 IIIIII **** **** mill **** **** IIIIII **** **** IIIIII **** **** partitions d 0 0 111111 **** **** IIIIII **** **** IIIIII **** **** 111111 **** **** e 0 0 111111 **** **** III111 **** **** 111111 **** **** 111111 **** **** f 0 0 mill **** **** 111111 **** **** 111111 **** **** 111111 **** **** 6 Windows and a 3A0 39.7 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** d 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 *`** 7 Windows and North 19.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 SE/SW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 South 34.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Horz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 0 0 0 0 0 0 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 45 243 46 0 0 0 486 2624 496 144 778 147 exposed b 0 0 nnn 0 0 nun 0 0 111111 0 0 111111 0 0 walls and c 0 0 Min 0 0 111111 0 0 111111 0 0 111111 0 0 partitions d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 e 0 0 HMI 0 0 111111 0 0 111111 0 0 111111 0 0 f 0 0 Iron 0 0 nun 0 0 null 0 0 111111 0 0 10 Ceilings a 16G0 2.4 1.1 0 0 0 0 0 0 0 0 0 0 0 0 b 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 C 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 e 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 ' f 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 11 Floors a 1910 1.7 0 51 88 0 35 60 0 328 567 0 56 97 0 (Note:room b 1910 1.7 0 0 0 0 0 0 0 0 0 0 0 0 0 perimeter c 0 0 111111 0 0 will 0 0 111111 0 0 111111 0 0 is displ. d 0 0 IIIIII 0 0 111111 0 0 111111 0 0 1 111 0 0 for slab e 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 floors) f 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 12 Infiltration a 124 9.9 0 0 0 0 0 0 0 0 0 0 0 0 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 331 **** **** 60 **** **** 3191 **** **** 874 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 21 **** 6% 4 **** 6% 201 **** 6% 55 **** 15 Total loss=13+14 **** 352 **** **** 64 **** **** 3392 **** **** 929 **** 16 Int.gains: People @ 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. @ 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 46 **** **** 0 **** **** 496 **** **** 147 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 2 5% **** 0 5% **** 24 5% **** 7 19 Total RSH gain=(17+18)*PLF 1.00 **** 48 1.00 **** 0 1.00 **** 520 1.00 **** 154 20 Air required(cfm) 3 2 0 0 25 19 7 6 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. wr- htsoft® 2018-May-30 09:59:00 9 Right-Suite®Universal 2017 17.0.16 RSU25116 Page 2 ACc ...rthy\Documents\York\SMOKE RIDGE DUPLEX LEFT.rup Calc=MJ7 Front Door faces: N 4 Rig ht-J®Worksheet Job: SMOKE RIDGE DUPLEX LE... :6-- °j' - Entire House Date: May 30,2018 FOOTHILL BUILDERS - Plan: SMOKE RIDGE DUPLEX LE... QUEENSBURY,NY 12804 ' MANUAL J:7th Ed. 1 Name of room Room8 Room9 Room10 Room11 2 Length of exposed wall 140.0 ft 84.0 ft 26.0 ft 0 ft 3 Room dimensions 1.0 x 960.0 ft 1.0 x 576.0 ft 1.0 x 141.0 ft 9.0 x 5.0 ft 4 Ceilings Condit.Option 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 1260 **** **** 756 **** **** 234 **** **** 0 **** **** Exposed b 0 0 IIIIII **** **** IIIIII **** **** IIIIII **** **** IIIIII **** **** walls and c 0 0 IIIIII **** **** IIIIII **** **** IIIIII **** **** I I I ill **** **** partitions d 0 0 IIIIII **** **** IIIIII **** **** IIIIII **** **** !III 11 **** **** e 0 0 IIIIII **** **** IIIIII **** **** IIIIII **** **** IIIIII **** **** f 0 0 IIIIII **** **** IIIIII **** **** IIIIII **** **** IIIIII **** **** 6 Windows and a 3A0 39.7 ** 0 0 **** 30 1190 **** 30 1190 **** 0 0 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** d 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 *" 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 0 **** 0 30 **** 570 0 **** 0 0 **** 0 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 0 **** 0 0 *`*" 0 0 **** 0 0 **** 0 SE/SW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 South 34.0 0 **** 0 0 **"" 0 30 **** 1020 0 **** 0 Holz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 0 0 0 84 2782 526 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 1260 6804 1285 642 3467 655 204 1102 208 0 0 0 exposed b 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 walls and c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 partitions d 0 0 111111 0 0 111111 0 0 111111 0 0 1 1 1111 0 0 e 0 0 111111 0 0 IIIIII 0 0 111111 0 0 111111 0 0 f 0 0 111111 0 0 111111 0 0 I I I111 0 0 111111 0 0 10 Ceilings a 16G0 2.4 1.1 960 2281 1077 576 1369 646 141 335 158 45 107 50 b 0 0 111111 0 0 111111 0 0 IIIIII 0 0 111111 0 0 C 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 d 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 e 0 0 Mill 0 0 IIIIII 0 0 111111 0 0 111111 0 0 f 0 0 Innl 0 0 HMI 0 0 111111 0 0 111111 0 0 11 Floors a 1910 1.7 0 0 0 0 0 0 0 0 0 0 0 0 0 (Note:room b 1910 1.7 0 16 28 0 4 7 0 12 21 0 0 0 0 perimeter c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 is displ. d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 for slab e 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 floors) f 0 0 111111 0 0 IIIIII 0 0 111111 0 0 111111 0 0 12 Infiltration a 124 9.9 0 0 0 114 14157 1124 30 3726 296 0 0 0 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 9113 **** **** 22972 **** **** 6373 **** **** 107 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 574 **** 6% 1447 **** 6% 401 **** 6% 7 **** 15 Total loss=13+14 **** 9687 **** **** 24418 **** **** 6774 **** **** 114 **** 16 Int.gains: People @ 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. @ 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 2362 **** **** 3520 **** *"** 1682 **"* **** 50 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 116 5% **** 172 5% **** 82 5% *"** 2 19 Total RSH gain=(17+18)*PLF 1.00 **** 2478 1.00 **** 3692 1.00 **** 1764 1.00 **** 53 20 Air required(cfm) 70 91 176 135 49 65 1 2 • Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. wr- htsoft® 2018-May-30 09:59:00 9 Right-Suite®Universal 2017 17.0.16 RSU25116 Page 3 AZ-C=P. ...rthy\Documents\York\SMOKE RIDGE DUPLEX LEFT.rup Calc=MJ7 Front Door faces: N u- • Right-J®Worksheet Job: SMOKE RIDGE DUPLEX LE... a ' s Entire House Date: May 30,2018 FOOTHILL BUILDERS Plan: SMOKE RIDGE DUPLEX LE... QUEENSBURY,NY 12804 MANUAL J:7th Ed. 1 Name of room Room12 Room13 2 Length of exposed wall 14.0 ft 16.0 ft 3 Room dimensions 1.0 x 150.0 ft 12.0 x 4.0 ft 4 Ceilings Condit.Option 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Area EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg Htg Clg Htg Clg 5 Gross a 12E3 5.4 1.0 126 **** **** 144 **** **** **** **** **** **** Exposed b 0 0 IIIIII **** **** II1111 **** **** **** **** **** **** walls and c 0 0 111111 **** **** IIIIII **** **** **** **** **** **** partitions d 0 0 mill **** **** IIIIII **** **** **** **** **** **** e 0 0 win **** **** III??? **** **** **** **** **** **** f 0 0 IIIIII **** **** III ill **** **** **** **** **** **** 6 Windows and a 3A0 39.7 ** 30 1190 **** 0 0 **** **** **** glass doors b 0 ** 0 0 **** 0 0 **** **** **** Heating c 0 ** 0 0 **** 0 0 **** **** **** d 0 ** 0 0 **** 0 0 **** **** **** e 0 ** 0 0 **** 0 0 **** **** **** f 0 ** 0 0 **** 0 0 **** **** **** 7 Windows and North 19.0 0 **** 0 0 **** 0 **** **** glass doors NE/NW 0 0 **** 0 0 **** 0 **** **** Cooling E/W 68.0 30 **** 2040 0 **** 0 **** **** SE/SW 0 0 **** 0 0 *** 0 **** **** South 34.0 0 **** 0 0 **** 0 **** **** Horz 0 0 **** 0 0 **** 0 **** **** 8 Other doors a 10D0 33.1 6.3 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 96 518 98 144 778 147 exposed b 0 0 III??? 0 0 111111 0 0 walls and c 0 0 IIIIII 0 0 111111 0 0 partitions d 0 0 IIIIII 0 0 111111 0 0 e 0 0 null 0 0 nun 0 0 f 0 0 IIIIII 0 0 111111 0 0 10 Ceilings a 16G0 2.4 1.1 150 356 168 48 114 54 b 0 0 IIIIII 0 0 111111 0 0 c 0 0 Illnl 0 0 111111 0 0 e 0 0 111111 0 0 111111 0 0 e 0 0 IIIIII 0 0 IIIIII 0 0 f 0 0 IIIIII 0 0 111111 0 0 11 Floors a 1910 1.7 0 0 0 0 0 0 0 (Note:room b 1910 1.7 0 0 0 0 0 0 0 perimeter c 0 0 IIIIII 0 0 111111 0 0 is displ. d 0 0 IIIIII 0 0 111111 0 0 for slab e 0 0 HMI 0 0 111111 0 0 floors) f 0 0 111111 0 0 111111 0 0 12 Infiltration a 124 9.9 30 3726 296 0 0 0 Ventilation 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 5791 **** **** 892 **** **** **** **** **** Less external heating **** 0 **** **** 0 **** **** **** **** **** Less transfer **** 0 **** **** 0 **** **** **** **** **** Heating redistribution **** 0 **** **** 0 **** **** **** **** **** 14 Duct loss 6% 365 **** 6% 56 **** **** **** 15 Total loss=13+14 **** 6155 **** **** 948 **** **** **** **** **** 16 Int.gains: People @ 300 0 **** 0 0 **** 0 **** **** Appl. @ 1200 0 **** 0 0 **** 0 **** **** 17 Subtot RSH gain=7+8..+12+16 **** **** 2602 **** **** 201 **** **** **** **** Less external cooling **** **** 0 **** **** 0 **** **** **** **** Less transfer **** **** 0 **** **** 0 **** **** **** **** Cooling redistribution **** **** 0 **** **** 0 **** **** **** **** 18 Duct gain 5% **** 127 5% **** 10 **** **** 19 Total RSH gain=(17+18)*PLF 1.00 **** 2729 1.00 **** 211 **** **** 20 Air required(cfm) 44 100 7 8 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. wr- ® 2018-May-30 09:59:00 9 Right-Suite®Universal 2017 17.0.16 RSU25116 Page 4 ACCA htsoft...rthy\Documents\York\SMOKE RIDGE DUPLEX LEFT.rup Calc=MJ7 Front Door faces: N •