Signed Inspection Report (03-03-2020) (9).pdfINSPECTION WORKSHEET (FRM-001180-2020)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0480-2018 Case Module:Permit
Inspection Date:Tue Mar 3, 2020 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Framing
Job Address:Parcel Number:11 Beacon Hollow DR
Queensbury, NY, 12804
297.13-1-39
Contact Type Company Name Name
Engineer Rucinski-Hall Architecture
Applicant HAYES CONSTRUCTION GROUP,
LLC
Primary Owner HAYES CONSTRUCTION GROUP,
LLC
Contractor HAYES CONSTRUCTION GROUP,
LLC
Granted Permission HAYES CONSTRUCTION GROUP,
LLC
Checklist Item Status
Building Inspector Notes Failed
3/3/20 Framing Partial Approval
- All 2"x10" floor joists doubled up for plumbing penetrations need to be nailed or screwed in a row of 3 at 6" oc on
both sides of joists.
CALL FOR RECHECK BEFORE SHEETROCK!
Framing Failed
3/3/20 Framing Partial Approval
- All 2"x10" floor joists doubled up for plumbing penetrations need to be nailed or screwed in a row of 3 at 6" oc on
both sides of joists.
CALL FOR RECHECK BEFORE SHEETROCK!
Air Seal all Plates and Sills Passed
Mar 03, 2020 Page (1)
INSPECTION WORKSHEET (FRM-001180-2020)
Checklist Item Status
Sealed at shoe plate
Air Seal All Registers at Floor Passed
No mechanicals cut in at time of inspection
Air Sealing all Joints Before Insulation Passed
Provide air sealing at gaps, penetrations, etc...
Exterior sheeting nailed properly Passed
Zip system
Headroom 6 ft. 8 in.Passed
No stairs in at time of inspection
Verified 2/24/20
Ice and water shield 24 inches from wall Passed
1 /23/20
Soffits-Insulation Baffel Passed
Provide air baffles at roof trusses prior to insulation
Verified 2/24/20
Windows Habitable Space Bedrooms Passed
No windows installed at time of inspection
Windows verified 2/24/20 with U factors of 31, just under threshold of 32
As per R312.2.1 of the IRC, window sills located less than 24" above finished floor and greater than 72" above the
finished grade are to be provided with window opening control devices (child safety)
Mar 03, 2020 Page (2)