ComCheck 8/22/2018 15:36 5187983859
G PETER JENSEN PAGE 01
FILE COPY
COMcheck Software Version 4.0.8.2
cilEnvelope Compliance Certificate
Project Information
Energy: 2015 IECCPr REVIEWED FOR
Location:
ct tion: e: ERROL SILV BERG ENERGY CODE COMPLIANCE
Location Lake George,New York
Climate lane: 8a
Project Type: Addition
Construction Site: OwneriAged: DesignerlContrador:
230 Lockhart Mountain Road Errol Silverberg G.Peter Jensen
Queensbury,NY 12804 230 Lockhart Mountain Road 17 West Road
Queensbury.NY 12804 South Glens Falls,NY 12803
(518)798-3859
Building Area Floor Area
-
1-Parkilg Garage_Nonresidential 2304
Envelope Assemblies
Assembly Gross AMR Cavity Cont. Proposed Budget U.
or R Value *Value U.factor Factor
Perimeter
Roof 1:Attic Root with Wood Joists,[Bldg.Use 1-Parting Geroge] 2304 38.0 0.0 0.027 0.021 --
Fbor 1:sleb-On-Grede:Unhested,Venice'4 ft.,I81dg.Um 1•Parking 221 — 10.0 0.480 0.540
Garage)(b)
NOM
Exlorior Wet 1:Wood-Framed,18'oz.,(81dg.Use 1-Parking Garage) 1152 21.0 2.6 0.052 0,061
Door 1:insulated Metal,Swinging.(Bldg.Use 1•Parking Garage) 20 — — 0.200 0.370
EASI
Exterior Wel 2:Wood-Framed.18'o.c.,[Bldg.Use 1-Parking Garage) 288 21.0 2.5 0.062 0.051
Door 2:Insulated Metal,Non-Swegin0,(Bldg.Use 1-Parting Garage] 180 — — 0.050 0.050
24:11tIti
Extaior Wall 3:Wood-Framed,16"o.c.,(Bldg.Use 1-Parking Gauge] 924 21.0 2.5 0.052 0.051
Door 3:insulated Metal.Swinging,(Bldg.Use 1-Parking Garage) 20 — — 0.200 0.370
WEST
Exterior Web 4:Wood-Framed.16'o.c.,(Bldg.Use 1-Parkig Garage) 288 21.0 2.5 0.052 0.051
Door 4:insulated Metal.Non-Swinging.(Bldg.Use 1-Perking Garage) 180 -- — 0.050 0.050
(a)Budget U-factors are used for software baseline colorations ONLY,and are not code requirements.
(b)Slab-On-Grade proposed and budget Uaootore shown in table are F-factors.
Project Notes
Project Title: ERROt.SILVERBERG Report date: 08 22/18
Data filename: C:1Users1PeteADocuments1COMcheclASilverberg.cck Page 1 of 9
uri/LL/Li7 ti 1]:.3b 518/983859
G PETER JENSEN PAGE 02
nvelope PASSES: Design 1%bettor than code
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented In this document Is consistent with the building plans,
specifications,and other calculations submitted with this permit application.The proposed envelope systems have been
designed to meet the 2015 IECC requirements In COMcbeck Version 4.0.8.2 and to comply with any applicable mandatory
requirements listed In the Inspection Checklist.
G.PETER JE T. lizi ::: g
� ���
Name-Title r► : ` =7 9 1 •re ire t) e
SOUTH GLENS FALLS
Addition to existing garage NEW YORK 12803
Plan 18-0204 (518)798-3859 161;E 0 A AC
` 4.f
��rr n.%
1. 0
`h, °tetra ce
top woo
Project Title: ERROL SILVERBERG Report date: 08/22/18
Data filename: C:Wsers Meter\DocumentslCOMchecktSilverberg.cck Page 2 of 9
COMcheck Software Version 4.0.8.2
Afii rit
Interior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: ERROL SILVERBERG
Project Type: Addition
Construction Site: Owner/Agent: Designer/Contractor:
230 Lockhart Mountain Road Errol Silverberg G.Peter Jensen
Queensbury, NY 12804 230 Lockhart Mountain Road 17 West Road
Queensbury, NY 12804 South Glens Falls,NY 12803
(518)798-3859
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Mowed Watts
(ft2) Watts/ft2 (B X C)
1-Parking Garage 2304 0.21 484
Total Allowed Watts= 484
Proposed Interior Lighting Power
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
1-Parking Garage
LED 1:LED PAR 13W: 1 8 13 104
LED 2:LED Other Fixture Unit 6.5W: 1 2 6 13
Total Proposed Watts= 117
Interior Lighting PASSES: Design 76% better than code
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications,and other calculations submitted with this permit application.The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.8.2 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist. ,
G. PETER JENSEN i4. j /-. --,..._. /4/�
Name-Title 17 WEST ROAD 'Signature Date
SOUTH GLENS FALLop Ns
NEW YORK 12803 ,s�AE D A RC
(518)798-3859 �p`��-ciR•+aFNs yil
••• ir,7 °
d' 02802� 4
P
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 3 of 13
fiCOMcheck Software Version 4.0.8.2
l Exterior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: ERROL SILVERBERG
Project Type: Addition
Exterior Lighting Zone 2(Residentially zoned area)
Construction Site: Owner/Agent: Designer/Contractor.
230 Lockhart Mountain Road Errol Silverberg G. Peter Jensen
Queensbury, NY 12804 230 Lockhart Mountain Road 17 West Road
Queensbury, NY 12804 South Glens Falls,NY 12803
(518)798-3859
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts/Unit Wattage (B X C)
Entry canopy 2 ft2 0.25 Yes 0
Total Tradable Watts(a)= 0
Total Mowed Watts= 0
Total Allowed Supplemental Watts(b)= 600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Entry canopy(2 ft2):Tradable Wattage
LED 1:LED A Lamp 9W: 1 2 9 18
Total Tradable Proposed Watts= 18
Exterior Lighting PASSES: Design 97% better than code
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications,and other calculations submitted with this permit application.The proposed exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.8.2 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
G. PETER JENSEN � >%`,lf�' y /.01r'
Name-Title 17 WEST ROAD ;-Signature . Date
SOUTH GLENS FALLS
NEW YORK 12803 10,ED AAC
(518)798-3859 ��tb oela j4 ti%
lo
IrC�F'.'`14 r* w
1. 6,0 .•
dkk °eegt° c 0'
Project Title: ERROL SILVERBERG E OF pjel Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverb- •. "/ Page 4 of 13
COMcheck Software Version 4.0.8.2
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions"column is provided by the user in the COMcheck Requirements screen. For each
requirement,the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed.Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
&Req.lD
C103.2 Plans and/or specifications provide all ❑Complies
[PR1]1 information with which compliance ❑Does Not
can be determined for the building
envelope and document where ['Not Observable
exceptions to the standard are ❑Not Applicable
claimed.
C103.2 Plans, specifications,and/or ❑Complies
[PR4]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the interior lighting ['Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed.Information
provided should include interior
lighting power calculations,wattage of
bulbs and ballasts,transformers and
control devices.
C103.2 Plans,specifications,and/or ❑Complies
[PR8]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the exterior lighting ❑Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed.Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
C402.4.1 The vertical fenestration area<=30 ❑Complies
[PR1O]1 percent of the gross above-grade wall ❑Does Not
area.
['Not Observable
❑Not Applicable
C402.4.1 The skylight area<= 3 percent of the ❑Complies
[PR11j1 gross roof area. ❑Does Not
❑Not Observable
❑Not Applicable
C406 Plans,specifications,and/or ❑Complies
[PR9]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the additional energy ['Not Observable
efficiency package options. Observable,_,
Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 5 of 13
•
•
Section
Footing/Foundation Inspection Complies? Comments/Assumptions
&Req.ID
C303.2 Slab edge insulation installed per ❑Complies
[FO4]2 manufacturer's instructions. ❑Does Not
['Not Observable
❑Not Applicable
C303.2.1 Exterior insulation protected against ❑Complies
[FO6]' damage,sunlight, moisture,wind, ❑Does Not
landscaping and equipment
maintenance activities. ['Not Observable
❑Not Applicable
C402.2.5 Slab edge insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[FO3]2 ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.6 Radiant heating systems panels ❑Complies See the Envelope Assemblies table for values.
[FO12]3 insulated to>=R-3.5 on face opposite ❑Does Not
space being heated.
[Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 6 of 13
•
Section
Framing/Rough-In Inspection Complies? Comments/Assumptions
&Req.ID
C303.1.3 Fenestration products rated in ❑Complies
[FR12]2 accordance with NFRC. ❑Does Not
❑Not Observable
❑Not Applicable
C303.1.3 Fenestration products are certified as ❑Complies
[FR13]1 to performance labels or certificates ❑Does Not
provided. ['Not Observable
❑Not Applicable
C402.4.3 Vertical fenestration SHGC value. ❑Complies See the Envelope Assemblies table for values.
[FR10]1 Does Not
❑Not Observable
❑Not Applicable
C402.4.3, Vertical fenestration U-Factor. ❑Complies See the Envelope Assemblies table for values.
C402.4.3. ❑Does Not
4
(FR8]1 ❑Not Observable
❑Not Applicable
C402.4.4 U-factor of opaque doors associated ❑Complies See the Envelope Assemblies table for values.
[FR14]2 with the building thermal envelope ❑Does Not
meets requirements.
❑Not Observable
❑Not Applicable
C402.5.1 The building envelope contains a ❑Complies
[FR16]1 continuous air barrier that is sealed in ❑Does Not
an approved manner and either
constructed or tested in an approved [Not Observable
manner.Air barrier penetrations are ❑Not Applicable
sealed in an approved manner.
C402.5.2, Factory-built fenestration and doors ❑Complies
C402.5.4 are labeled as meeting air leakage ❑Does Not
[FR18]3 requirements.
['Not Observable
❑Not Applicable
C402.5.7 Vestibules are installed on all building ❑Complies
[FR17]3 entrances. Doors have self-closing ❑Does Not
devices.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1'High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 7 of 13
•
Section
# Mechanical Rough-In Inspection Complies? Comments/Assumptions
&Req.ID
C402.5.5, Stair and elevator shaft vents have ❑Complies
C403.2.4. motorized dampers that automatically DDoes Not
3 close.
[MEW ['Not Observable
❑Not Applicable
C402.5.5, Outdoor air and exhaust systems have ❑Complies
C403.2.4. motorized dampers that automatically ❑Does Not
3 shut when not in use and meet ❑Not Observable
[ME58]3 maximum leakage rates.Check
gravity dampers where allowed. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 8 of 13
Section
Rough-In Electrical Inspection Complies? Comments/Assumptions
&Req,ID
C405.2.1 Lighting controls installed to uniformly ❑Complies
[EL1511 reduce the lighting load by at least DDoes Not
50%. ['Not Observable
DNot Applicable
C405.2.1 Occupancy sensors installed in ❑Complies
[EL18]1 required spaces. ❑Does Not
['Not Observable
DNot Applicable
C405.2.1, Independent lighting controls installed ❑Complies
C405.2.2. per approved lighting plans and all ❑Does Not
3 manual controls readily accessible and
[EL23]2 visible to occupants. DNot Observable
DNot Applicable
C405.2.2. Automatic controls to shut off all DComplies
1 building lighting installed in all ❑Does Not
(EL22]2 buildings.
DNot Observable
DNot Applicable
C405.2.3 Daylight zones provided with ❑Complies
[EL16]2 individual controls that control the DDoes Not
lights independent of general area [Not Observable
lighting.
DNot Applicable
C405.2.3, Primary sidelighted areas are ❑Complies
C405.2.3. equipped with required lighting ElDoes Not
1, controls. :Not Observable
C405.2.3.
2 ❑Not Applicable
[EL20]1
C405.2.3, Enclosed spaces with daylight area ❑Complies
C405.2.3. under skylights and rooftop monitors DDoes Not
1, are equipped with required lighting
C405.2.3. controls. DNot Observable
3 DNot Applicable
[EL21]1
C405.2.4 Separate lighting control devices for ❑Complies
[EL411 specific uses installed per approved ❑Does Not
lighting plans.
['Not Observable
❑Not Applicable
C405.2.4 Additional interior lighting power ❑Complies
[EL8]1 allowed for special functions per the DDoes Not
approved lighting plans and is DNot Observable
automatically controlled and
separated from general lighting. DNot Applicable
C405.2.5 Automatic lighting controls for exterior❑Complies
[EL25]"°n lighting installed.Controls will be ['Does Not
daylight controlled,set based on
business operation time-of-day,or ❑Not Observable
reduce connected lighting>30% ❑Not Applicable
C405.3 Exit signs do not exceed 5 watts per ❑Complies
[EL6]1 face. DDoes Not
DNot Observable
['Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 9 of 13
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 10 of 13
Section
Insulation Inspection Complies? Comments/Assumptions
&Req.ID
C303.1 Roof insulation installed per ❑Complies
[IN3]1 manufacturer's instructions.Blown or ❑Does Not
poured loose-fill insulation is installed
only where the roof slope is<=3 in ❑Not Observable
12. ❑Not Applicable
C303.1 Building envelope insulation is labeled ❑Complies
[IN10]2 with R-value or insulation certificate ❑Does Not
providing R-value and other relevant
data. :Not Observable
❑Not Applicable
C303.2 Above-grade wall insulation installed ❑Complies
[IN7]1 per manufacturer's instructions. Does Not
❑Not Observable
❑Not Applicable
C303.2.1 Exterior insulation is protected from ❑Complies
[IN14]2 damage with a protective material. ❑Does Not
Verification for exposed foundation
insulation may need to occur during ❑Not Observable
Foundation Inspection. ❑Not Applicable
C402.1.3 Non-swinging opaque doors have R- ❑Complies
[IN19]3 4.75 insulation. ❑Does Not
[Not Observable
[Not Applicable
C402.2.1 Insulation intended to meet the roof ❑Complies
[IN17]3 insulation requirements cannot be ❑Does Not
installed on top of a suspended
ceiling.Mark this requirement ❑Not Observable
compliant if insulation is installed ❑Not Applicable
accordingly.
C402.2.3 Above-grade wall insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[IN6]1 ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.5 Floor insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[IN8]2 ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.6 Radiant panels and associated ❑Complies
[IN18]3 components,designed for heat ❑Does Not
transfer from the panel surfaces to the❑Not Observable
occupants or indoor space are
insulated with a minimum of R-3.5. ❑Not Applicable
C402.2.2 Roof R-value.For some ceiling ❑Complies See the Envelope Assemblies table for values.
[IN2]1 systems,verification may need to ❑Does Not
occur during Framing Inspection.
❑Not Observable
❑Not Applicable
C402.5.1. All sources of air leakage in the ❑Complies
1 building thermal envelope are sealed, ❑Does Not
[IN1]1 caulked,gasketed,weather stripped ❑Not Observable
or wrapped with moisture vapor-
permeable wrapping material to ❑Not Applicable
minimize air leakage.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 11 of 13
Section
Final Inspection Complies? Comments/Assumptions
&Req.ID
C303.3. Furnished O&M instructions for DComplies
C408.2.5. systems and equipment to the ❑Does Not
2 building owner or designated
[FI17]3 representative. ❑Not Observable
❑Not Applicable
C402.5.3 Where open combustion air ducts DComplies
[F151]3 provide combustion air to open ❑Does Not
combustion fuel burning appliances,
the appliances and combustion air ❑Not Observable
opening are located outside the ❑Not Applicable
building thermal envelope or enclosed
in a room,isolated from inside the
thermal envelope.Such rooms are
sealed and insulated.
C402.5.6 Weatherseals installed on all loading DComplies
[F137]1 dock cargo doors. ❑Does Not
❑Not Observable
❑Not Applicable
C402.5.8 Recessed luminaires in thermal DComplies
(FI26]3 envelope to limit infiltration and be IC ❑Does Not
rated and labeled.Seal between
interior finish and luminaire housing. ❑Not Observable
❑Not Applicable
C405.4.1 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values.
(F118]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans,demonstrating proposed watts ❑Not Observable
are less than or equal to allowed ❑Not Applicable
watts.
C405.5.1 Exterior lighting power is consistent DComplies See the Exterior Lighting fixture schedule for values.
(F119]1 with what is shown on the approved ElDoes Not
lighting plans,demonstrating
proposed watts are less than or equal ❑Not Observable
to allowed watts. Observable,_,
Applicable
C408.2.5. Furnished as-built drawings for DComplies
1 electric power systems within 90 days ❑Does Not
[F116]3 of system acceptance.
❑Not Observable
❑Not Applicable
C408.3 Lighting systems have been tested to DComplies
[F133]1 ensure proper calibration,adjustment, DDoes Not
programming,and operation.
['Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 12 of 13
Project Title: ERROL SILVERBERG Report date: 08/14/18
Data filename: C:\Users\Peter\Documents\COMcheck\Silverberg.cck Page 13 of 13