ResCheck /r
f
aciREScheck Software Version 4.6.4
ComplianceCertificate
jECEOVE
281 li
Project 26x42 (1092) RANCH MAY $ 1
Energy Code: 2015 IECC - - -
Location: Glens Falls, New York � � OF � � (� Y
BU
Construction Type: Single-family ILDING`' ES
Project Type: New Construction
Orientation: Bldg. faces 180 deg. from North
Conditioned Floor Area: 1,092 ft2 309.17-1-2.2 RC-0232-2018
Glazing Area 12% Bell, Chris
Climate Zone: 6 (7635 HDD) 86 Eagan Road
Permit Date:
Permit Number: • Single Family Dwelling 1092 s.f.
Construction Site: Owner/Agent: Designer/Contractor:
86 EAGAN RD CLUTE ENTERPRISES, INC
QUEENSBURY, NY 12804 6 HOLDEN AVE
QUEENSBURY, NY 12804
518-793-7277
CLUTEENTERPRISES@GMAIL.COM
Compliance: Passes using UA trade-off
Compliance: 5.4%Better Than Code Maximum UA: 168 Your UA: 159
The%Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.
Envelope Assemblies -
AssemblyGross Area Cavity Cont.
°r R-Value R-Value U-Factor UA
Perimeter
Ceiling 1: Raised or Energy Truss 1,025 38.0 0.4 0.025 26
Wall 1:Wood Frame, 16"o.c. 200 19.0 0.0 0.060 9
Orientation: Front
Window 1: Vinyl Frame:Double Pane with Low-E 30 0.290 9
Orientation: Front
Door 1:Solid 20 0.160 3
Orientation: Front
Wall 2:Wood Frame, 16"o.c. 328 19.0 0.0 0.060 17
Orientation:Left side
Window 2:Vinyl Frame:Double Pane with Low-E 22 0.290 6
Orientation: Left side
Door 2: Solid 19 0.160 3
Orientation: Left side
Wall 3:Wood Frame, 16"o.c. 200 19.0 0.0 0.060 12
Orientation: Back
Wall 4:Wood Frame, 16" o.c. 328 19.0 0.0 0.060 15
Orientation: Right side
Window 3:Vinyl Frame:Double Pane with Low-E 30 0.290 9
Orientation: Right side
Door 3: Glass 40 0.310 12
Orientation: Right side
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Ciutel\Rescheck\2018-86 EAGAN RD QSBY-26x42 (1092) RANCH.rck Page 1 of10
Gross Area Cavity Cont.
Assembly or R-Value R-Value U-Factor UA
Perimeter
Basement Wall 1:Solid Concrete or Masonry 184 0.0 19.0 0.038 7
Orientation: Front
Wall height: 7.8'
Depth below grade: 7.0'
Insulation depth: 7.8'
Basement Wall 2: Solid Concrete or Masonry 306 0.0 19.0 0.038 12
Orientation: Left side
Wall height: 7.8'
Depth below grade: 7.0'
Insulation depth: 7.8'
Basement Wall 3: Solid Concrete or Masonry 184 0.0 19.0 0.038 7
Orientation: Back
Wall height: 7.8'
Depth below grade: 7.0'
Insulation depth:7.8'
Basement Wall 4: Solid Concrete or Masonry 306 0.0 19.0 0.038 12
Orientation: Right side
Wall height: 7.8'
Depth below grade: 7.0'
Insulation depth:7.8'
Compliance Statement: The proposed building design described here is -insistent with t► .u', z pl.r specifications,and other
calculations submitted with the permit application.The proposed bui ng ha own de '•n;, . ee 'tee 2015 IECC requirements in
REScheck Version 4.6.4 and to comply with the mandatory require, ents ' e. m - •E . k In O `• Checklist.
Name-Title y
S'+.- . e Date
Project Notes:
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Clute1\Rescheck\2018-86 EAGAN RD QSBY- 26x42 (1092) RANCH.rck Page 2 of10
'EREScheck Software Version 4.6.4
(I Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section Plans Verified Field Verified
# Pre-Inspection/Plan Review Value Value Complies? Comments/Assumptions
&Req.ID ,
103.1, Construction drawings and - . ❑Complies
103.2 documentation demonstrate i. _ y❑Does Not
[PR1]1 energy code compliance for the .: ' : _, - i
;❑Not Observable
4 building envelope.Thermal r ❑Not Applicable
envelope represented on
construction documents.
103.1, Construction drawings and ❑Complies
103.2, documentation demonstrate ❑Does Not
403.7 energy code compliance for
[PR3]1 lighting and mechanical systems. 4 ❑Not Observable
Systems serving multiple r ;❑Not Applicable
dwelling units must demonstrate
compliance with the IECC I
Commercial Provisions. F -
302.1, Heating and cooling equipment is Heating: Heating: ElComplies
403.7 sized per ACCA Manual S based Btu/hr Btu/hr ❑Does Not
[PR2]z on loads calculated per ACCA Cooling: Cooling: ❑Not Observable
Manual J or other methods Btu/hr Btu/hr ❑Not Applicable
approved by the code official.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Clutel\Rescheck\2018-86 EAGAN RD QSBY- 26x42 (1092) RANCH.rck Page 3 of10
Section Plans Verified Field Verified
Foundation Inspection Value Value Complies? Comments/Assumptions
&Req.ID
402.1.1 Conditioned basement wall R- R- ❑Complies See the Envelope Assemblies
[FO4]1 insulation R-value.Where interior R- R-
❑Does Not table for values.
;insulation is used,verification ['Not Observable
may need to occur during
Insulation Inspection. Not ❑Not Applicable
;required in warm-humid locations
lin Climate Zone 3.
7
303.2 Conditioned basement wall . .'.= ::: F ❑Complies
[FO5]1 insulation installed per ,:_ ` %:, r,_, E,: . = :i❑Does Not
manufacturer's instructions.
} ['Not Observable
- ❑Not Applicable
402.2.9 ;Conditioned basement wall ft ft . ❑Complies See the Envelope Assemblies
[FO611 insulation depth of burial or ❑Does Not table for values.
distance from top of wall. ❑Not Observable
❑Not Applicable
303.2.1 A protective covering is installed ; ❑Complies
[FO11]2 to protect exposed exterior : *`. - • ❑Does Not
insulation and extends a
minimum of 6 in. below grade. ( ❑Not Observable
❑Not Applicable
403.9 ;Snow-and ice-melting system .," " <-=- ;❑Complies
[FO12]2 controls installed. ❑Does Not
( , ;;'❑Not Observable
;❑Not Applicable
Additional Comments/Assumptions:
•
•
•
•
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Clutel\Rescheck\2018-86 EAGAN RD QSBY-26x42 (1092) RANCH.rck Page 4 of10
Section Plans Verified Field Verified
# Framing/Rough-In Inspection Value
Value Complies? Comments/Assumptions
&Req.ID
402.1.1, Door U-factor. U- U- ❑Complies ;See the Envelope Assemblies
402.3.4 ❑Does Not table for values.
[FR1F- ;
f .❑Not Observable •
❑Not Applicable
402.1.1, Glazing U-factor(area-weighted U- a U- il=IComplies See the Envelope Assemblies
402.3.1, average). ❑Does Not table for values.
402.3.3,
402.3.6, [Not Observable
402.5 ❑Not Applicable
[FR2]i
303.1.3 U-factors of fenestration products : - - :❑Complies
[FR4]1 are determined in accordance s`'_';.,. Oboes Not
with the NFRC test procedure or
taken from the default table. ;;.A❑Not Observable
}..... ;❑Not Applicable
402.4.1.1 ,Air barrier and thermal barrier t -":- ;❑Complies
[FR23]'- :installed per manufacturer's +❑Does Not
i instructions. 1
{ r❑Not Observable
❑Not Applicable
402.4.3 ;Fenestration that is not site built `$$ -❑Complies
[FR20]' :is listed and labeled as meeting 4 $ ; 1❑Does Not
AAMA/WDMA/CSA 101/I.S.2/A440 x-
9) or has infiltration rates per NFRC ;;';_ ,'-,: - ;::_ �. ..:..; :: , _._ ,',; ❑Not Observable
400 that do not exceed code )❑Not Applicable
limits. [ '
402.4.5 IC-rated recessed lighting fixtures =` - _ ❑Complies
[FR16]z sealed at housing/interior finish - - ❑Does Not
and labeled to indicate<_2.0 cfm
leakage at 75 Pa. ;. 3❑Not Observable
'(❑Not Applicable
403.2.1 Supply and return ducts in attics ; -, - %I❑Complies
[FR12p- insulated8 >=R-8 where duct is ,,, `;❑Does Not
41 >= 3 inches in diameter and >= _,
R-6 where< 3 inches.Supply and k ; ;❑Not Observable
return ducts in other portions of r- ,❑Not Applicable
the building insulated >= R-6 for
diameter>= 3 inches and R-4.2
for< 3 inches in diameter. ' ' f ' '"
403.3.3.5 Building cavities are not used as E ❑Complies
[FR15]3 ducts or plenums. I ❑Does Not
x❑Not Observable
: - ❑Not Applicable
403.4 HVAC piping conveying fluids R- R- ;❑Complies
[FR17]2 :above 105°F or chilled fluids .❑Does Not
;below 55°F are insulated to>_R-
3 ❑Not Observable
❑Not Applicable
403.4.1 Protection of insulation on HVAC I0Complies
[FR24]' piping. I .: inDoes Not
h" ;❑Not Observable
f
`=:,',' >.t 10Not Applicable
403.5.3 Hot water pipes are insulated to R- R- ❑Complies
[FR18]2 a>R-3. ❑Does Not
4. i [Not Observable
❑Not Applicable fi
403.6 Automatic or gravity dampers are „❑Complies
[FR19]2 "installed on all outdoor air i ❑Does Not
intakes and exhausts. ; ; ❑Not Observable
?❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Clutel\Rescheck\2018 - 86 EAGAN RD QSBY-26x42 (1092) RANCH.rck Page 5 of10
Additional Comments/Assumptions:
•
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Clutel\Rescheck\2018-86 EAGAN RD QSBY-26x42 (1092) RANCH.rck Page 6 of10
Section Plans Verified Field Verified
Insulation Inspection ValueValue Complies? Comments/Assumptions
&Req.ID
303.1 ;All installed insulation is labeled ❑Complies
-[IN13]2 or the installed R-values f l - • 3❑Does Not
;provided.
❑Not Observable
. ❑Not Applicable
402.1.1, Wall insulation R-value.If this is a R- R- '❑Complies See the Envelope Assemblies
402.2.5, mass wall with at least 1/2 of the Wood ❑ Wood ❑Does Not table for values.
402.2.6 wall insulation on the wall
[IN3]1 exterior,the exterior insulation El Mass ❑ Mass ['Not Observable
:requirement applies(FR10). El Steel ❑ Steel ❑Not Applicable
303.2 ;Wall insulation is installed per ❑Complies ;
[IN4]1 °manufacturer's instructions. I.` i❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Clutel\Rescheck\2018-86 EAGAN RD QSBY-26x42 (1092) RANCH.rck Page 7 of10
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
&Req.ID -
402.1.1, Ceiling insulation R-value. R- R- ❑Complies :See the Envelope Assemblies
402.2.1, ❑ Wood ;❑ Wood ❑Does Not !table for values.
402.2.2, Steel
402.2.E ❑ ❑ Steel ❑Not Observable
[Fll]1 ❑Not Applicable
•
x F
+ e x
303.1.1.1, Ceiling insulation installed per .' ❑Complies
303.2 manufacturer's instructions. ❑Does Not
[F12]1 Blown insulation marked every
300 ft2. ❑Not Observable
t❑Not Applicable
402.2.3 ;Vented attics with air permeable '"' =' ;.';DComplies
[FI2212 insulation include baffle adjacent l = "❑Does Not
to soffit and eave vents that
'extends over insulation. ; -'-.`❑Not Observable
#❑Not Applicable
402.2.4 °Attic access hatch and door R- R- ❑Complies
[FI3]1 I insulation R-value of the ❑Does Not
;adjacent assembly.
❑Not Observable
ENot Applicable
402.4.1.2 'Blower door test @ 50 Pa. <=5 ACH 50 = ACH 50 = ❑Complies
[FI17]1 Each in Climate Zones 1-2,and ❑Does Not
<=3 ach in Climate Zones 3-8. ❑Not Observable
❑Not Applicable
403.2.3 Duct tightness test result of<=4 cfm/100 cfm/100 ❑Complies
[Fl4]1 cfm/100 ft2 across the system or ft2
ft2 ❑Does Not
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough-in ❑Not Observable
tests,verification may need to ❑Not Applicable
;occur during Framing Inspection.
403.3.2 Ducts are pressure tested to cfm/100 cfm/100 ❑Complies
[F127]1 determine air leakage with ft2 ft2 ❑Does Not
either: Rough-in test:Total
leakage measured with a ❑Not Observable
pressure differential of 0.1 inch ❑Not Applicable
w.g. across the system including
the manufacturer's air handler
enclosure if installed at time of
test. Postconstruction test:Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the entire system
including the manufacturer's air
handler enclosure.
403.3.2.1 Air handler leakage designated i - : ?- - r IEComplies
[FI24]1 by manufacturer at<=2%of { ❑Does Not
design air flow.
r _ ,_ t •�. )❑Not Observable
- ❑Not Applicable
403.1.1 ;Programmable thermostats IEComplies
[FI912 i installed for control of primary s '3❑- Does Not
heating and cooling systems and _
!initially set by manufacturer to ❑Not Observable
code specifications.
I ,:: :: :>__ :'❑Not Applicable
403.1.2 ;Heat pump thermostat installed ,. ;❑Complies
[FI1012 ion heat pumps. l ❑Does Not
'I❑Not Observable
:. :. i❑Not Applicable
403.5.1 Circulating service hot water a❑Complies
[FI11]2 systems have automatic or I ❑Does Not
(accessible manual controls. j
❑Not Observable
1 ,_ ❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Clutel\Rescheck\2018- 86 EAGAN RD QSBY- 26x42 (1092) RANCH.rck Page 8 of10
h �
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
403.6.1 ;All mechanical ventilation system° F s ❑Complies
[FI2512 'fans not part of tested and listed `=❑Does Not
HVAC equipment meet efficacy j _'; _.
and airflow limits. i ❑Not Observable
;❑Not Applicable
z_.
403.2 Hot water boilers supplying heat i ` ❑Complies
[F126]2 through one-or two-pipe heating `, v.n }=.=w:,:--,.:-:3`- r ;> ;;; -•::<-=:, _3❑Does Not
systems have outdoor setback S
control to lower boiler water ; -. Not Observable
temperature based on outdoor ;❑Not Applicable
temperature.
403.5.1.1 Heated water circulation systems = `�°;❑Complies
[F128]2 have a circulation pump.The ❑Does Not
system return pipe is a dedicated k ;❑Not Observable
return pipe or a cold water supply l ❑Not Applicable
pipe. Gravity and thermos- pp
;syphon circulation systems are
;not present.Controls for
circulating hot water system F i
pumps start the pump with signal[
for hot water demand within the }
occupancy.Controls
automatically turn off the pump i
;when water is in circulation loop i
is at set-point temperature and _
no demand for hot water exists. ;
403.5.1.2 ;Electric heat trace systems ❑Complies
[FI29]2 ;comply with IEEE 515.1 or UL ❑Does Not
515. Controls automatically
adjust the energy input to the a❑Not Observable
heat tracing to maintain the i ;❑Not Applicable
desired water temperature in the I_..
piping.
403.5.2 Water distribution systems that • ❑Complies
[FI3012 have recirculation pumps that ( • ❑Does Not
pump water from a heated water ; ' -
supply pipe back to the heated ( Not Observable
water source through a cold ;`_ s❑Not Applicable
water supply pipe have a
demand recirculation water
system. Pumps have controls i
;that manage operation of the
pump and limit the temperature
of the water entering the cold
;water piping to 104°F. i
403.5.4 ;Drain water heat recovery units , ; ❑Complies
[FI31]2 ',tested in accordance with CSA ❑Does Not
;B55.1. Potable water-side I
pressure •loss of drain water heat ❑Not Observable
recovery units < 3 psi for • '❑Not Applicable
individual units connected to one
;or two showers. Potable water- { ;- _ _ t
(side pressure loss of drain water
;heat recovery units <2 psi for {
;individual units connected to ( 3
three or more showers. `r
404.1 75%of lamps in permanent `-._';❑Complies
[FI6]1 fixtures or 75%of permanent i !❑Does Not
fixtures have high efficacy lamps.f:-',,:`R ❑Not Observable
Does not apply to low-voltage
lighting. ; • ❑Not Applicable
404.1.1 ;Fuel gas lighting systems have ❑Complies
[FI23]3 no continuous pilot light. ;❑Does Not
1 , i❑Not Observable
" ...:._..._ .--_ ... ❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Clutel\Rescheck\2018 - 86 EAGAN RD QSBY-26x42 (1092) RANCH.rck Page 9 of10
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.iD I
401.3 ;Compliance certificate posted. ;❑Complies
[FI7]2 ❑Does Not
;❑Not Observable
;❑Not Applicable
303.3 ;Manufacturer manuals for ❑Complies
[FI18]3 ;mechanical and water heating ..._. ;❑Does Not
systems have been provided. ; ❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 26x42 (1092) RANCH Report date: 04/23/18
Data filename: Z:\Clutel\Rescheck\2018-86 EAGAN RD QSBY-26x42 (1092) RANCH.rck Page 10 of10
. J R
i CI 20 IE
Efficiency15CC Energy Certificate
Insulation Rating R-Value
Above-Grade Wall 19.00
Below-Grade Wall 19.00
Floor 13.00
Ceiling / Roof 38.38
Ductwork (unconditioned spaces): _
Glass&Door Rating U-Factor SHGC
Window 0.29
Door 0.31
Heating&Cooling Equipment Efficiency
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments