blower door test �.00N . NEBPA BLOWER DOOR FORM Home Energy Experts lTortlr East Building. Perlorrar mice Adr-isors 51 S.ZU0..9941 Contractor: Clute Enterprise Inc Date: 5/30/2018 Contractor Address: 6 Holden Ave City: Glens Falls State: NY Zip: 12804 Phone# 518-793-7277 Email: Location tested: 86 Eagan Rd City: Queensbury State: NY Zip: 12804 Customer Name: Phone# Email: Ventilation requirements: Volume= (Height x Living)+(Height x Basement) X 3/60 =ACH per Hour Volume: 18356 x 3= 55069/60 = 917.80CFM @ 50 Maximum CFM 50 to achieve less than 3 ACH= 917.8 Blower Door Diagnostics: Ring Open Inside Temp: 75 Baseline Pressure -49.3 Pa. �A Outside Temp: 80 Fan Pressure -24 Pa. �B C Actual Flow @ CFM50 = 904 cfm@50 CFM@50 x 60/Volume = 2.95 ach New York State Requires builders run a blower door test on new residential buildings to ensure a maximum air leakage of three air changes per hour(ach50). *ACH test results are considerably lower than building standards. Mechanical Ventilation is highly recommended. *As a reference, Energy Star homes must come in at.35 ACH naturally to qualify. Blower Door testing performed by: North East Building Performance Advisors 31 7 Rocky Ridge rrrrrr„1t�1rJV171,4 Warrensburg, NY 12885 . 518-350-2941 BPI, GoIdStar- C CO N T R A C T O R