ResCheck 7 ;'-- Generated by REScheck-Weft Software tlr Compliance Certificate Project Cerrone Builders Inc Energy Code: 2018 IECC Location: Glens Falls, New York Construction Type: Single-family 315:1-1.6 Project Type: New Construction RC-0620-2020 Conditioned Floor Area: 1,500 ft2 Cerrone Builders Glazing Area 17% 17 Alessia Dr, lot 2 Climate Zone: 6 (7635 HDD) SFD w/gas fp 1500 s.f., Gar. 400 s.f. Permit Date: Permit Number: Construction Site: Owner/Agent: Designer/Contractor: 17 Alessia Drive Daniel W. Ryan P.E. WM Lot 2 P.O. Box 596 Queensbury, NY 12804 Glens Falls, NY 12801 dryan@dwrpe.com Y�t�r $ °x i' gf ._ tl' aff,V f *dI f, t .1f 4 r°ktl *' r,I ."',6! 4-L'°a$ S 4 i a :f a , k t t COIri?-I .7. r-'. GG4 7l1Sin EU i %Ix. F€ tv r , y ti , w i. ` ,.. � .�.�� .w�Tu � m�r,�.? ,., :�;or ��.,'�z5 ,xe.ka �H �L`3�r�'�rs ._ �.EF �y��„�''€`:.....s � z ..:�'�� � .,"�a�,��. `�. ,.`‘•;,v .-. Compliance: 1.7%Better Than Code Maximum UA: 239 Your UA: 235 The%Better or Worse Than Code Index reflects how close to compliance the house Is based on code trade-off rules. It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home. - Envelope Assemblies • Gross Are a ea Cavity, Cony: Assembly . ` " or" U-Factor UA," ' - o _ . 'Perimeter R:Val. R Value ` Ceiling 1: Raised or Energy Truss 1,500 49.0 0.0 0.020 30 Wall 1:Wood Frame, 16"o.c. 1,440 21.0 0.0 0.057 67 Door 1: Solid 18 0.140 3 Door 3: Solid 20 0.240 5 Door 2: Glass 40 0.290 12 Window 1:Vinyl/Fiberglass Frame:Double Pane with Low-E 185 0.290 54 Basement Wall 1: Solid Concrete or Masonry 1,248 0.0 15.0 0.046 56 Wall height: 7.8' Depth below grade: 6.8' Insulation depth: 7.8' Window 4:Vinyl/Fiberglass Frame:Double Pane 7 0.400 3 Window 3:Vinyl/Fiberglass Frame:Double Pane with Low-E 16 0.290 5 0CT 07 2020 , TOWN OF OUEENSBURY BUILDING&CODES Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 1 of10 Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other calculations submitted with the permit application.The proposed building has been designed to meet the 2018 IECC requirements in REScheck Version : REScheck-Web and to comply with the mandatory requirements list d 1 the REScheck Inspection Checklist. Daniel W. Ryan P.E. / ,4 `t, 10/3/20 Name-Title Signature Date ENGINEERS STAMP: of 1\lew IF THE SIAM . 'It NAT (f5 ,leiti; L NOT IN BLUE INK, THIS Si rr, iSTT ,a '1 i i'Ye AN ILLEGAL COPY OR A IbEl� Put t it r JA 41 I ;;"` 1[NTS NOT GONTANIN x RIGIN.::-' l 11 D Si11IAT E�' 1OULl} NOT BE USED TOO "It, WAG i? I'I ,I t� .9STf UCTlON, A Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 2 of10 REScheck Software Version m REScheck-Web 4Y` Inspection Checklist Energy Code: 2018 IECC Requirements: 0.0% were addressed directly in the REScheck software Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement,the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section " Plans Verified Field Verified # Pre-Inspection/Plan Review Complies? Comments/Assumptions Valuer Value 103.1, Construction drawings and ❑Complies 103.2 documentation demonstrate ❑Does Not [PR1]1 energy code compliance for the ,building envelope.Thermal ❑Not Observable envelope represented on Not Applicable construction documents. 103.1, ``Construction drawings and ;❑Complies 103.2, 'Construction demonstrate l❑Does Not 403.7 `energy code compliance for ;r .,❑ [PR3]1 f lighting and mechanical systems. i Not Observable Systems serving multiple ;!❑Not Applicable dwelling units must demonstrate x !compliance with the IECC ;Commercial Provisions. 302.1, ,+ #Heating and cooling equipment is Heating: Heating: ❑Complies 403.7 ;sized per ACCA Manual S based Btu/hr Btu/hr ❑Does Not [PR2]? on loads calculated per ACCA Cooling: Cooling: ❑Not Observable Manual J or other methods Btu/hr Btu/hr approved by the code official. ❑Not Applicable v. 3 Additional Comments/Assumptions: 11High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 3 of10 Se2 g c ion " Plans Verified Field Venfieti # Foundation Inspection ' Complies? Comments/Assumptions &RegID, P Value Vague 402.1.1 `Conditioned basement wall R- R- Complies See the Envelope Assemblies [F04]1 (insulation R-value.Where interior R- R- ODoes Not table for values. !insulation is used, verification may need to occur during ONot Observable Insulation Inspection. Not ONot Applicable required in warm-humid locations in Climate Zone 3. 303.2 Conditioned basement wall ❑Complies [F05]1 insulation installed per ❑Does Not t l manufacturer's instructions, ONot Observable i❑Not Applicable 402.2.9 Conditioned basement wall ft ft ❑Complies See the Envelope Assemblies [F06]1 insulation depth of burial or ODoes Not table for values. C distance from top of wall. ONot Observable ONot Applicable 30312.1 IA protective covering is installed ! ,, °, I❑Complies [FO11]2 Ito protect exposed exterior ❑Does Not i insulation and extends a ' minimum of 6 in. below grade. i❑Not Observable j❑Not Applicable 403,9Snow-and ice-melting system ` ; ' OComplies [F012]2 'controls installed. ; , ,,ODoes Not ii 1 ,10Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2., Medium Impact(Tier 2) ,3 Low Impact(Tier 3) Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 4 of10 Plans Verified weld,Verified Framing t Rough In Inspection GomPh- ' Comrr%en s( ..' , '�t,, ,S Req.ID- +lyalu®� Value , 402.1.1, Door U-factor. U- U- ❑Complies See the Envelope Assemblies 402.3.4 ODoes Not table for values. [FR1]1 ONot Observable { ONot Applicable 402.1.1, Glazing U-factor(area-weighted U- U- ❑Complies See the Envelope Assemblies 402.3.1, average). ODoes Not table for values. 402.3.3, 402.5 ONot Observable [FR2]1 ONot Applicable 303.1.3 U-factors of fenestration products ° `; r,'', DComplies [FR4]1 are determined in accordance ' f� , ODoes Not a with the NFRC test procedure or taken from the default table. Not Observable j❑Not Applicable 402.4.1.1 Air barrier and thermal barrier ,•�,4 .ti. , .11Complies [FR23]1 installed per manufacturer's , ., ." ODoes Not instructions, -^ :Not Observable E f ONot Applicable 402.4.3 Fenestration that is not site built F' „''l❑Complies [FR20]1 is listed and labeled as meeting ODoes Not AAMA/WDMA/CSA 101/1.5.2/A440 a or has infiltration rates per NFRC :Not Observable 400 that do not exceed code ❑Not Applicable limits. b:.R 402.4 5 y" IC-rated recessed lighting fixtures " l❑Complies [FR16]2 ., sealed at housing/interior finish ,,❑Does Not and labeled to indicate s2.0 cfm I " ' ❑Not Observable leakage at 75 Pa. ONot Applicable 403.3.1 Supply and return ducts in attics , ❑Complies [FR12]1 insulated >= R-8 where duct is `S❑Does Not C >= 3 inches in diameter and >= ' R-6 where <3 inches. Supply and ,1,,Y< > ❑Not Observable !return ducts in other portions of ]❑Not Applicable (the building insulated >= R-6 for i i , 'diameter>= 3 inches and R-4.2 i ', (for<3 inches in diameter. 1 i ,`� 403.3.2 Ducts, air handlers and filter ,',i❑Complies [FR13]1 boxes are sealed with i °;I❑Does Not joints/seams compliant with .❑Not Observable International Mechanical Code or International Residential Code, as 4 s ❑Not Applicable applicable, g a ' 403.3 5';, 'Building cavities are not used as ; , ❑Complies [FR15]3 ducts or plenums. j = ODoes Not 1 ' 3 ' '1❑Not Observable ' '-, I". DNot Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3, Low Impact(Tier 3) Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 5 of10 Secteon.. ._ '"° plans Ve¢i�ed �F�eli! Vermfeeii .f : � , Framing;/Rough !n Inspection Complies? Com hent /Assum n ptios Value Value 403.3 7 ;!Ducts declared to be within the f OComplies [FR28]3 , !conditioned space are either 1) as ❑Does Not ;completely within the continuous air barrier and within the building , ,; r ❑Not Observable • ,,I thermal envelope, 2)buried ❑Not Applicable !within ceiling insulation in Iaccordance with Section R403.3.6 and the air handler is located completely within they continuous air barrier and within I } the building thermal envelope :',hand the duct leakage is <= 1.5 " 'S cfm/100 square feet of $ !conditioned floor area served by the duct system, or 3)the ceiling ' insulation R-value installed ,against and above the insulated 1duct>=to the proposed ceiling 'insulation R-value, less the R- value of the insulation on the • • HVAC piping conveying fluids R- R- ❑Complies [FR1-7=]? '.. above 105°F or chilled fluids ❑Does Not T•. below 55°F are insulated to aR- °?. 3 :Not Observable ❑Not Applicable 403.4.1 Protection of insulation on HVAC y" 4❑Complies [FR24]1 piping. °' 9 y.'0Does Not ' :>;❑Not Observable ❑Not Applicable 4015 3 ` 1 Hot water pipes are insulated to R- R- ❑Complies (FR18]2 "-' zR 3. ❑Does Not -, ONot Observable ❑Not Applicable 403 6' , Automatic or gravity dampers are ; ❑Complies .[FRT9]2 installed on all outdoor air t }' °' ODoes Not intakes and exhausts, Observable �„ ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) •2` Medium Impact(Tier 2) w3;' Low Impact(Tier 3) Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 6 of10 • Section t plans Ve"rified Field Verified `, • Insulation Inspection Value Value Complies? Comments/Assumptions 3031 All installed insulation is labeled ❑Complies [IN13]2 or the installed R-values 10Does Not provided. ( ❑Not Observable I❑Not Applicable 4021.1, Wall insulation R-value. If this is a R- R- ❑Complies See the Envelope Assemblies 402.2.5, I mass wall with at least 1/2 of the 0 Wood ❑ Wood Does Not table for values. 402.2.6 wall insulation on the wall ❑ Mass ❑ Mass ONot Observable [IN3]1 exterior,the exterior insulation requirement applies(FR10). ❑ Steel 0 Steel ENot Applicable 303.2 Wall insulation is installed per ❑Complies [IN4]1 manufacturer's instructions. §❑Does Not :Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact (Tier 2) -3: Low Impact(Tier 3) Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 7 of10 Section: Plans Verified Field l/erified p # Final Inspection Provisions. Complies? Comments/Assumptions i6alue Value q. 402.1.1, Ceiling insulation R-value. R- R- DComplies See the Envelope Assemblies 402.2.1, 0 Wood ❑ Wood ❑Does Not table for values. 402.2.2, 0 Steel 0 Steel ❑Not Observable 402.2.6 [Fll]1 ❑Not Applicable 303.1.1.1, Ceiling insulation installed per ( !DComplies 303.2 I manufacturer's instructions, s , .1DDoes Not [FI2]1 I Blown insulation marked every i 1300 ft2. • Not Observable ❑Not Applicable 4022 3 ;Vented attics with air permeable j❑Complies [FI22]2 1insulation include baffle adjacent s ❑Does Not Ito soffit and eave vents that t ;extends over insulation. Not Observable ❑Not Applicable 402.2.4 !Attic access hatch and door R- R- DComplies [FI3]1 insulation zR-value of the ❑Does Not adjacent assembly. Not Observable :Not Applicable 402.4.1.2 Blower door test @ 50 Pa. <=5 ACH 50 = ACH 50 = ❑Complies [FI17]1 ach in Climate Zones 1-2, and DDoes Not <=3 ach in Climate Zones 3-8. :Not Observable ❑Not Applicable 403.3.3 (Ducts are pressure tested to cfm/100 cfm/100 DComplies [FI27]1 idetermine air leakage with ft2 ft2 ODoes Not either: Rough-in test:Total leakage measured with a Not Observable pressure differential of 0.1 inch ONot Applicable Ew.g. across the system including 1the manufacturer's air handler enclosure if installed at time of (test. Postconstruction test:Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer's air !handler enclosure. I E S 403.3.4 1Duct tightness test result of<=4 cfm/100 cfm/100 DComplies [FI4]1 (cfm/100 ft2 across the system or ft2 ft2 ❑Does Not !<=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in ❑Not Observable tests,verification may need to Not Applicable occur during Framing Inspection. 403.3.2.1 Air handler leakage designated DComplies [F124]1 by manufacturer at<=2%of , " ❑Does Not design air flow. . ❑Not Observable j ( -IDNot Applicable 403.1.3. !Programmable thermostats Complies [FI9]2 installed for control of primary i Does Not cheating and cooling systems and initially set by manufacturer toy: ❑Not Observable °::!code specifications. ❑Not Applicable 403`.1 2 1Heat pump thermostat installed `'❑Complies [FI10]2 on heat pumps. 10Does Not ❑Not Observable r, :Not Applicable 403.5 1 , 1Circulating service hot water r ❑Complies [FI11]2 {systems have automatic or ' ❑Does Not taccessible manual controls. s 1 ❑Not Observable ❑Not Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3'` Low Impact(Tier 3) Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 8 of10 Sectiorti Plans Ventrest ,,Fileld'Verifire i # Final Inspection'Provisions Complies?- Comments/Assumptions Value` Value 403.6.1 #All mechanical ventilation system , w ❑Complies [FI25]2 ;fans not part of tested and listed E ❑Does Not IHVAC equipment meet efficacy 'and air flow limits per Table Not Observable R403.6°1° u'' 1❑Not Applicable 403.2 , 1 Hot water boilers supplying heat ❑Complies [F126]2 through one-or two-pipe heating ` ' ❑Does Not systems have outdoor setback control to lower boiler water ['Not Observable !temperature based on outdoor % ❑Not Applicable ;temperature. r 403.51.1 ;Heated water circulation systems . 1❑Complies [FI28]2 ' ;have a circulation pump.The o . ❑Does Not !system return pipe is a dedicated , ; return pipe or a cold water supply ,❑Not Observable ,•;pipe. Gravity and thermos- y., ' ❑Not Applicable . ;!syphon circulation systems are = 'not present. Controls for (circulating hot water system ;pumps start the pump with signal 1 ,for hot water demand within the ' !occupancy. Controls I `s 'automatically turn off the pump !when water is in circulation loop ;,;` # - !is at set-point temperature and . „,, no demand for hot water exists. 403.5 1.2 !Electric heat trace systems } i iElComplies [FI2932 ;comply with IEEE 515,1 or UL ° Does Not 515.Controls automatically ) ❑Not Observable -':I adjust the energy input to the ;heat tracing to maintain the ❑Not Applicable !desired water temperature in the {piping. € 1 4035°2 ;Demand recirculation water ❑Complies [FI30]2 ;systems have controls that ' , .;•$❑Does Not 'manage operation of the pump ,?and limit the temperature of the ,.,(❑Not Observable (water entering the cold water '#❑Not Applicablepiping to <= 104°F, i 403.5 4 - !Drain water heat recovery units _ 11:1Complies [FI31]2 •,'.!tested in accordance with CSA . z, ❑Does Not 1B55,1. Potable water-side 1, , pressure loss of drain water heat )❑Not Observable recovery units < 3 psi for ! l❑Not Applicable !individual units connected to one i ,, tor two showers. Potable water- l r !side pressure loss of drain water " ! '!heat recovery units < 2 psi for ' ' . �,..`I• !individual units connected to '` ! ;three or more showers. ❑Com 404.1 190%or more of permanent plies [FI6]1 !fixtures have high efficacy lamps • ;❑Does Not ❑Not Observable ;r❑Not Applicable 404.1".3. 1Fuel gas lighting systems have l - i-jDComplies [F123]3-,„ I no continuous pilot light. k ❑Does Not ❑Not Observable ff ❑Not Applicable 401.3 1Compliance certificate posted, t Complies [F17]2' E '. ❑Does Not ❑Not Observable ! ! ❑Not Applicable 1 High Impact(Tier 1) 2, Medium Impact(Tier 2) ,3'. Low Impact(Tier 3) Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 9 of10 sects®n � Plans Verified Field Verifies Final . �. Inspection Provisions. Complies? Comments/Assumptions Value. Value ' ` , ..' .• .. .;. °,;° " 303.3 ;Manufacturer manuals for r❑Complies [FI18)3 {mechanical and water heating 1 ❑Does Not systems have been provided. >❑Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) ..2 Medium Impact(Tier 2) 3, Low Impact(Tier 3) Project Title: Cerrone Builders Inc Report date: 10/03/20 Data filename: Page 10 of10 Efficiency d Insulation'Rating :� 3�' r x = ..ay ' R Value Above-Grade Wall 21.00 Below-Grade Wall 15.00 Floor o.00 Ceiling / Roof 49.00 Ductwork (unconditioned spaces): wGlass&boor Rating : r, ' U Factory i% SHGC Window 0.29 Door 0.29 Heating&Coolmg.Equipment`, t2..Effjciency Heating System: Cooling System: Water Heater: Name: Date: Comments t.., r,.—..,,......... :fh, 155 MAX • • (\, .. • , HEAT RECOVERY VENTII_ATOR ,s,::,,,,,,vqi,4%.5,i,,,,. ''..• ' : Ci 7;1' :4 . 1,',..•-?';iii'W'rc,;',!,':::::,..'..Y',:.'',;:..,,.-: 1 ! ,."' ' !!'-:; M IA ' PERFORMANCE(Hvi CERTIFIED) ,,,,,,,,,,,,,:ora'm:5.40.,:roRiifriiiiA ' 5 ca . !„.0,, -„.1, ,..:.',,,,.-' , , , ; , w c , prr,,,,,,,,,K!,,,,,,','....,..:-., ,,/,,,,:?.,..,,,',. ,,;'/,:,,.4,,,,,e'.??,,:.:,,:,.',.-1..;:i ..., a •-• . , , „, .... : , ,r. ,, .,., , ,:. „ . .. , . r , ,. .. r .P'-'--..'''''.",--,-"*''ff''-'2'''''..."',,,'i,: ,,•',';'",,..'n"''-''..2L.Y.1 -cl -e CL, IA ....... ' 0.1(25) 0.2(50) 0.3(7S) OA(100) 0.5(125) 0.6(350) 0.7(3.7S) . . ELECTRICAL SPECIFICATIONS CD IN.W.G.(PA) GI'M(l's) CFM(L s) CFm(L.s) CrIvi(1,$) Cm(L‘s) CM(vs) cnryi 0_,s) cri 9, ri I VAC 0 6.011i. ...,.,,!:116:- •',... 0 IQ Net StiOpliAlrflety• . 'rnii4;(01)''',[' 163:0: ;':14k(6q)::':..:0i104,,::'':,116(54):,..'.'192:(43):P;',li60(28) 1 %.Wittil.1;i6'Sjiiii&&;"5,P.4:„;4';'''66';','.4,,., 0 ,,:o.,,.,„, ....:,(..,.c. ,-,-,,)p ;:;:*.;':''1:,;;;!. ' ,,,.''',..1.1 cp 6iiiii's'''ii`P:i'il;':iii'c4:1',ii':',Vi Ti''''itflii8lj'',:;,''',''''jiii:Cief'c.'1491,(Ii) '''''. .,:i134.:(03)'i-),, -,,111.;(55) .;V.... 94444p •,':.‘61129r,',i Watts I High Speed 7:lz.118 ''4 ' ° :'' Amp A i i ',9i6Pi*iritn.'.i ilt: Gross Exhaust:Ali-flow ,;':, p,.,(ili).-.:,':,?*(197t ,,.21 ,(10(i) ',,Int(V).'..1.:,::,17i01),,,i !,;0,p.:(11)6:7,.;0261qq) -, :,,.. , Iv , . r6,.w;; ..s.-,!,,,„„:„•,,,,,i 0 0 c7) , . Sensible EffectiVeriess CASE) c'':,,32SF(0r;6).,-2:,r•Ciai.(%••-• '°° . WEIGHT: .iab 0 is) KG) " 0 0 0 32,,,,F toocry,;.•:.,:,,,,150/0,,,;• SHIPPING WEIGHT: u) Is) 73 LEIS(33 KG) 1-t' 0 .,'co''.,,,',, ty @ 64 CFM(30 Us);• :','"''',"`,1,L',.'.!". :.'',.•,,.:.',",,;!!' '''' . ,Sensible'EfffellfficOREk4 13°F-(26°C) '':':'1.1270',.._ : loo ' . NOTE:, ',;,,..',•:, , ‘,!r' C''' .a' . Front clearance of 25 in.(635 mm)is recothinended for servicing unit,All ducts; . BO •. ifs' gi use 6 in.(152 mm)round collars.Balancing. i.4-,..e'7 e, leitIli. IOU, Ai La7A r.. 60 darnperi arq located in all air streamS, ':'!.:ftz''-,./‘'. cmi"us 14VI 9001 '' -"21,2-4 : c,.,....,....... nowymiest Millgt11111' „ , , „ 0.1 0.2 0.3 0.4 0.5 . , . static Preture(in w.g.) 1- , • CO° ' ' ffd ' 1,-- : 00 n a DIMENSIONS :z FRONT VIEW TOP VIEW N C - 41 i 9° •••• • • t 4-7.—•—•- .4 I 14 3/4 in.(315 min) I M = Al* ReolreulitIng 8p1 63 . MIME , MENEM 1 I 1 1 Defrost 1111111111111 , ' 11.1111MIM CM C=) • Darivw UWWOMMMMIIIIMMWOMMIrMMrEMMI A.— ' itil,_03/ Iiiill.1111111.11..\\i i 01,-- : Erb Removable 1 Blower 11 7J Heat 1 / Motor T t*,Stale alr to outpld 1 Recovery Mg/ ,, _ co BO Fresh air from outs Core 1111M111 .$-'` • Fresh elr to Inside . V ., . 8in.(152 mni) I, 33 5/8 In.(854 moil io -c.., v ii Round Collars i . . Date: , WARRANTY Contractor: Units carry a lifetime warranty Tag', • On the miqv core and a S year replacement parts warranty. Project' city' Supplier: . Quote#: AU units conform to CsA and UL standards Engineer' a g . .. Control; Submitted By: LIFEBREfITH' . . Ng Indoor Air Systems', Timer. Timer city: 1S5MAX(01-01-10) www.lifebreath.com, fee �`r . y ., , , , a". r^..t.N. lit.,M r 4i 155 MAX .. : ,, . . . HEAT RECOVERY VENTILATOR • • -' • 1, t , � f 4Fa''`r ar! ,� ,, r L/FE®RER.ri ` ENGINEERING DATA i , : , m,� },, THERMALLY CONDUCTIVE,PATENTED DEFROST "' l ALUMINUM CORE Recirculating damper defrost system. The counter-flow heat recovery•core transfers heat between the two airstreams.It is easily removed for cleaning or service. CASE Twenty gauge prepainted galvanized steel for superior corrosion resistance.Insulated to MOTORS AND BLOWERS prevent exterior condensation.Drain connections 2-1/2 in.(12 mm)OD.Balancing ports. Each airstream has one centrifugal blower driven by a common PSC motor,with multiple are located on door. fan speed operations. ELECTRONICS FILTERS The DXPLO2 control included with the unit can be wall mounted in a central location of Washable air filters in exhaust and supply air streams, the home.3 wire 20 gauge(min.)100 ft length(max.). MOUNTING ,>u Four threaded inserts at corners of the cabinet designed to accept the"s"hooks and WARRANTY hanging straps supplied with the unit. •units carry e lifetime warrondy do the HRV core and a$year n - reptaceman6,perts Warranty. OPTIONAL ACCESSORIES: . i, ; , t, t TechGrltte ii + s , l i , r .s i , , Weather Hood €A i' 99-EAG4 Terminator„ �i ,Wireless 20/40/80 ; 99185 '� 't ' Min Timer 99-ERGS 99,Tii Y 99186 E r 99 TM4, �� i99 DET02 " ? 99 EAG6 ,'• � '� 99187 'i�r m� ,I '99 EAGU �V / �'' 99 TM5 r r, , , 4 .� 99 TM6 S !� S r jf i 1A :7t i •1 I t.. LIFEBREATH CONTROL OPTIONS TIMER OPTIONS FEATURES 99-QXPL•02 $9-BCO2 q' 99=8CQ3 99-BC04 99-DETO3 Lifebreath 20/40/60 Minute Timer Initiates high speed Ventilation for 20,40 or 60 „ ' minutes.3 wire connection. ;; ,, 5 speed fan:operation'on each modes 1 t, ✓ 99-DETO2 2 speed fan operation(Low/High) `✓ ✓ Wireless Lifebreath 20/40/60 Minute Timer 4 3 '' 'I, ✓ Initiates high speed Ventilation for 20,40 or 60 u, i. t CentiiWOnS low speed fan'operatlge`,1 '' ,`': �� �� ,i• „ for • minutes.Wirelessly connects to main contra( Humidity control through adjustable Dehumidistat ✓' ✓ ✓ ease of installation.40'approximate range, . Excusive to Lifebreath, i ` , Large digital LCD screen `:t,,, } , ✓r 99 RX02-Wireless Lifebreath Repeater LED statue indicator lights , •✓ ✓ ✓:, Extends range of 99-DET02 Wireless Timers,Plugs �, s _t into 120V power outlet.Wirelessly connects to " 'Continuous Ventilation main control and 99-OET02.Install at halfway, point between timer and main wall control if timer Continuous Recirculation ✓ ✓ „ is out of range. a � 20 ON140 OFF- „r'. .: " '�' :wry,; .,a,. 10 ON/50 OFF •a '' 20 0N/40 Recirculation << ✓, 's . ✓ •• ✓ i_ J: 20/40/60 min,High speed override button ✓` 99 OXPL02 99-DET02` • "i Compatible with',99 DET02 Wireless Timer ✓ ✓ ✓ ✓' 3 wire connection '! V ✓" IFE Eli indoor Air Systems LSSMAX(01-01-18) www.lifebreath.com