2005-825 TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5902 (518) 761-8201
4z Community Development- Building &Codes (518) 761-8256
CERTIFICATE OF OCCUPANCY
Permit Number. P20050825 Date Issued: Friday, December 08, 2006
This is to certify that work requested to be done as shown by Permit Number P20050825
has been completed.
Tax Map Number. 523400-316-010-0001-008-000-0000
Location: 296 BIG BOOM Rd
Owner. SHEERER, BRIAN
Applicant: BRIAN & PATTY SHEERER
This structure maybe occupied as a:
Single Family Dwelling By Order of Town Board
TOWN OF QUEENSBURY
Issuance of this Certificate of Occupancy DOES NOT relieve the
j/V //�—
property owner of the responsibility for compliance with Site Plan,
Variance, or other issues and conditions as a result of approvals by the Director of Building&Code nfo ent
Planning Board or Zoning Board of Appeals.
TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5902 (518) 761-8201
Community Development-Building& Codes (518) 761-8256
BUILDING PERMIT
Permit Number: P20050825 Application Number: A20050825
Tax Map No: 523400-316-010-0001-008-000-0000
Permission is hereby granted to: BRIAN & PATTY SHEERER
For property located at: 296 BIG BOOM Rd
in the Town of Queensbury,to construct or place
at the above location in accordance with application together with plot plans and other information hereto filed
and approved and in compliance with the NYS Uniform Building Codes and the Queensbury Zoning
Ordinance. Type of Construction Value
Owner Address: HERBERT RICHARDSON LE
SHEERER, BRIAN Single Familv Dwelling $70,000.00
296 BIG BOOM Rd Total Value $70,000.00
QUEENSBURY, NY 12804-0000
Contractor or Builder's Name / Address Electrical Inspection Agency
Plans&Specifications
2005-825
1400 SQ FT SINGLE FAMILY DWELLING
U Z
$168.00 PERMIT FEE PAID-THIS PERMIT EXPIRES: Sunday, October 28, 2007
(If a longer period is required,an application for an extension must be made to the code Enforcement Officer
of the Town of Queensbury before the expiration date.)
0 o
Dated at the To of Q nsb � a ber 28, 2005
SIGNED BY � -. for the Town of Queensbury.
Director of Building&Code Enforcement
TOWN OF QUEENSBURY
742 Bay Road,Queensbury,NY 12804-5902 (518)761-8201
Community Development-Building& Codes (518) 761-8256
BUILDING PERMIT
Permit Number: P20050825 Application Number: A20050825
Tax Map No: 523400-316-010-0001-008-000-0000
Permission is hereby granted to: BRIAN K PATTY SHF,F,RER
For property located at: 296 BIG BOOM Rd
in the Town of Queensbury,to construct or place
at the above location in accordance with application together with plot plans and other information hereto filed
and approved and in compliance with the NYS Uniform Building Codes and the Queensbury Zoning
Ordinance. Type of Construction Value
Owner Address: HERBERT RICHARDSON LE
SCOTT RICHARDSON Single Family Dwelling $70,000.00
Total Value $70,000.00
17 BOSS Rd
QUEENSBURY, NY 12804
Contractor or Builder's Name /Address Electrical Inspection Agency
Plans&Specifications
2005-825
1400 SQ FT SINGLE FAMILY DWELLING
$168.00 PERMIT FEE PAID-THIS PERMIT EXPIRES: Saturday, October 28, 2006
(If a longer period is required,an application for an extension must he made to the code Enforcement Officer
of the Town of Queensbury be(Qrg the expiration date.)
Dated at the Town of Queens l�u�y da , 2005
SIGNED BY for the Town of Queensbury.
Director of Building&Code Enforcement
© �� ��'
Check Residential Plan Review: One& Two Family Dwellings
Y/N
2)Full sets of plans
Over 1,500 sq. ft.—Stamped
Design Loads On Plans: 90 Wind Floor Loads 40 psf
70 Ground Snow Load Sleeping Areas and Attics 30 psf
Calculations:
Window Schedule With Glass Size
Door Schedule/Main Entrance 36"Door
Emergency Escape Or Bedrooms and Habitable Space
Above/Below grade,5.7 sq.ft.
Grade,5.0 sq.ft.
24"(h)x 20"(w)min.
44"Max.Height above floor
Residential Check Paperwork Compliance and Inspectors Checklist: OK
mpproofmg/Waterproofing Materials On Plans
Foundation Drainage On Plans,if required
6"Drop in 10'Exterior Grade
Framing Cross Section For Each Roof Line,Vertical Fire Stopping Every 10' Where
e uired
Ice and Snow shield 24"Inside Exterior Wall/24"Inside Knee Walls
Platforms At Exterior Doors
Stairway Headroom 6' 8'All Stairs 36"Width
Stair Run and Rise
Winder Run and Rise
AA
/� iral Not Allowed From 2 Story
' moke Detectors Battery Backup and Proper Location
Bathroom Fixtures Proper Clearance
Hall Width,36"min.
Handrails More Than One Riser On Open Sides
Railing and Guards>30"/Basement Stairs Included/Closed Risers More Than 4"in Ht.
Safety Glazing Notes For Required Areas
Garage Fire Separation
arage Floor Sloped
ttic Access
Roof over 30"—22"x 30"/Crawl Spaces 18"x 24"Access
Carbon Monoxide Detector Lowest Sleeping Level
Soil Test Results, if required
Septic To Well Or Water Line Separation
All Paperwork Signed
Project Name Y� }' o BP#
j�
Address:
Building Permit Submission SFD
Checklist 2-Family
All items below must be checked either yes,no or not applicable prior to submission of any building
permit to the Town of Queensbury Building Department. If any of the below items are lacking,the permit
will not be accepted until such time as the application is deemed complete for submission.
1. Building Permit Application Completed ... ... ... ... ... ... ... ... ... ... ... ... . A yes ❑no ❑n/a
2. Energy Form or C lieckMate Energy Code Compliance Forms Complete .. W yes ❑no ❑n/a
(2 copies)
3. Energy Code Inspector's Report from CheckMate Program.. ... ... ... ... .. yes ❑no ❑n/a
(2 copies)
4. Septic application completely filled out(if applicable)... ... ... ... ... ... ... ... ]yes ❑no ❑n/a
5. Solid Fuel Burning or Gas Appliance Form... ... ... ... ...... ... ... ... ... ... ... . Oyes ❑no ❑n/a
6. Electrical Inspection Form... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 0.. ... .. ❑yes Ono ❑n/a
7. Two (2) complete sets of structural drawings... .. ... ... ... ... ... ... ... ... ... ... . ®yes ❑no ❑n/a
a) floor plan;b) foundation plan;c) cross sections:d)elevations;
e)window and door schedule
8. Two(2) site plans showing location of the structure to be built. ... ... ... ... Eyes Ono ❑n/a
location of well or water lines,location of septic system or sewer line.
9. Setbacks from property lines to new structure... ... ... ... ... ... ... ... ... ... .. ©yes [-]no ❑n/a
10. Setbacks to neighboring wells and septic systems,including onsite well... . ❑yes Ono Qn/a
and septic systems (if applicable)
11. Driveway Permit... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 9yes Ono Qn/a
Date:
Staff Initial:
L:\SueHemingway\BuildingTemut.FORNLS\Generic Checklist.doc January28,2003
WINDOW SCHEDULE
Job Sit /Address: Date:
Owner: r+ten Application No.
Window Window Window Unit or Rough Rough SQ.FT. SQ.FT SQ.FT, Clear Clear Special Hardware
Number or Manufaturor Model/Type Stock Openin Opening Glass/Vis Egress/Cie Opening Opening or Instructions
Letter on Name Numbe g Height ible Vent ar Width In Height
Plan Cali Width Light Opening Inches In Inches
Size
p t,� �( f
d t. ! t "l 6/ 1/ /•/ r ^ Ajr Lam' /V
` Sty C!J /V Tf —
�"
VIISItY �a st, ,"tEt'r. 6 > > n J 3 /cA
,✓ `
36,
..t
Example Entry
A Andersen Narroline 3062 3' 2 6'5 '/2 15.30 8.36 6.01 34 2415135" Tempered
Double 1/3" 11/16 Glazing
Hun
C:\Documents and Settings\Sue\Local Settings\TempVindow Schedule.doc
Application for Permit—Septic Disposal System
Town of Qtteensbuty 742 Day Road Queensbury,NY 12804 (518) 761-8256
1. OWNER INFORMATION:
- Location of installation: Office Use................................................
Tax Map No..s�/, J�/ ' - File Permit No. `
�.y,a.. �� S� Fee Paid
Owner's Name: YZlaaV �erEV
............. ....................................................................................
Address: r +rS r r �l I�l IvZ
2. INSTALLER'S NAME PHONE NO. z _�W6
3. RESIDENCE INFORMATION: (circle year of dwelling, indicate#bedroom(s)and multiply N of
bedrooms with applicable gallons per bedroom to equal total daily fluty)
Year of House: No of Bedrooms Cnirtntitntinn Total Daily Plow
1980 or older x ' 150 gaVbdnn =
1980— 1991 x 130 gaVbdrm =
1991 —present x 1.10 gal/bdrm = 236
Garbage Grinder Installed yes / no
Spa or Whirlpool Installed yes / no -
4. PARCEL INFORMATION: (circle applicable information & indicate measurements)
�Qp9�IS�t21U 1_(9 Q.LQtI!1 V!'14.0r _a_kggk._O! �A.t4ri�ll_. D i stic W:ttQr_Supply
cr1 wh I do/rlh nnu�•I�n
g o( fee[ feet
Steep slope clay if well; water supply
%slope other from any septic-system
depth: absorption is ft.
other
Percolation!T)st: (To be completed by licensed professional engineer or architect)
!late: minute per Inch
5. PROPOSED SYSTEM: For New Construction: All individual sewage disposal systems must be designed by n licensed
professional engineer or architect(unless installed in a Planning Board approved subdivisi 1 AVW2. 11ons to llie size
of the septic tank and leach held for each Garbage Grinder, Spa or Whirllxiol Tub.
Septic Tank: gallon (min. size 1,000 gal.)
Tile Field: each trench 5_fT. Total System Length:QJdfi.
Seepage Pit(s): number of V size of each: fl. by fi.
Size of Stone to be used: It / depth or
Bed System Size: x
Alternative System: length and/or size
6. HOLDING TANK SYSTEM: (if required)
Number of tanks: / Size of each: gallons /TOTAL Capacity: gallons
Note: Alarm System and associated electrical work must be inspected by a Town approved
electrical inspection agency.
7. SIGNATURE &INFORMATION FOR RESPONSIBLE PERSON(please read)
For your protection,please note that pursuant to Section 136-29 of the Code of the Town
of Quoensbury, any permit or approval granted which is based upon or is granted in
reliance upon any material misrepresentation or failure to make a material fact or
circumstance known by or on behalf of an applicant, shall be void.
I have read the regulations with respect o flits application and agree to abide by those and all
requiremeIgnature
ofwn of Que sb Its
Sewage Disposal Ordinance.
' f
0 esponsible person Date
Principal • w l' ��pa Structure Building Permit Application
Application & Plans subiect to review before issuance of a valid permit for construction D00 8XS
Instructions: A permit must be obtained before beginning construction. No inspections will be made until the
applicant has received a valid building permit. All applicants' spaces on this application must be completed and
must appear on the application form.
Applicant/Builder l Y► czr cr �t 51�P Per Owner:
Address:
�L ► C1_ Address: _ ��_ rb"J-Q� e k .,C
Home Phone: ` l c ` -� 0
-,��i..J�S '713-6 �`� Home Phone: " S '/ - � _
Email Address: $5�$ a n Cowl Email Address:
Cell Phone: S,234 -- C,3/., - y.�24,G Cell Phone:
FAX Phone: FAX Phone:
Person responsible for supervision of work with respect to building and codes compliance:
Name: nc -, tee vet
Address: Phone
ll '6� J
Location of proposed construction: Lot No. IV 19 Legal Address: �Z9� ',G �ad _r �tta+�
Tax Map Number: _ 1� , l(3 1 — Subdivision Name:
Estimated Cost of Construction: $ "IC)
Proposed construction is for: _Residential Use _Commercial Use
Name of Business: JU
If proposed construction is an addition, what will use of new addition be?
New Addition Alteration Proposed Construction 10 floor 2^d floor Other Total Proposed
structure (Occupancy Type) Sq. Ft. sq.ft. Sq. Ft. Square feet Height
Ft, 8 in.
Single-family Dwelling a N 6 O
Two-Family Dwelling
Townhouse
Multifamily Dwelling
Number of Units:
Office
Mercantile
Manufacturing
Other:
Attached Garage 1, 2, 3
Type of Heating System: Electric, Oi Gas Wood, Forced Hot Air, Baseboard, Other: ► rb &_
f a fireplace and/or woodstove are being installed, please refer to a separate application.
4pplications are subject to Zoning Administrator, Code Compliance, and Structural Plan review.
the Building and Codes Office will allow commencement of your proposed project only after
ssuance of your permit.
i
)eclaration: Please sign below after you have carefully read the statement:
.o the best of my knowledge, the statements contained in the application, together with the plans and
pecifications submitted, are a true and complete statement of all proposed work to be done on the described
Dremises and that all provisions of the Building Codes, the Zoning Ordinance, and all other laws pertaining to the
)roposed work shall be complied with, whether specified or noted, and that such work is authorized by the owner.
:urther, it is understood that I/we shall submit prior to a Certificate of Occupancy or Certificate of Compliance
)eing issued, as requested by the Zoning Administrator or Director of Building and Codes, an As-Built Survey by a
censed surveyor, drawn to scale, showing actual location of all newI
ruction.
�)ate:1 ,I h — 5 Applicant/Builder Signature:-_R_ _
he application of dated is hereby approved and
permission granted for th /on7st),uction, reconstruction or alt ati of a bull ng/and or accessory structure as set
orth above.
Date: Authorized Signature:
:\Sue Hemingway\Buiiding.Permit.FORMS\Principal Structure Permit Application.doc V:12/14/04
Final VSiveeyInspection
Dept. of Community Development
Town of Queensbury
742 Bay Road
Queensbury,NY 12804
Date received:
NAME:
LOCATION: 7c1t4
PERMIT#
Final Survey Plot Plan
Avvroved Denied
The attached final
survey has been
received by the
Dept.of ,V
Community
Development.
Upon review the
sHgej has been.
Craig Brown,Aning Administrator
Notes:
L:\SueHemingway\Building.Codes.Inspection.FORMS\Fina1 Survey
Zoning Administrator.doe
OLD IRON
PIPE FOUND1
CONC.MON. —--—----- A
FOUND �I /OD.// OLD IRON
PIPE FOUND
I .
r
N
n
o
LL '
2 ,
w
Lands N/F Darryl Lien "' N
N 1191/72 LL Q
(Fly lands of Miles and David Waters) R w
W LU
Z
Lu
= V
z �
C� ZW
pia ` I a C
— ------- �� L7- oo'= E o F o
FOUND f APPROP.MAP 100.1 FT.+ BASE OF IRON IRON ROD
O1 PIPE FOUND ��i SET
S A 'IV �. ) CRUSHED STONE DRIVE rATER 0
'a Y Area: 1.209 Acres ± �oRcNk J LL �
Q
�- METER• Z 3 N`Q
v } ` , `O Known as"296 Big Boom Road" STEPS+ w M,o " O
c30 0 0
4) N p Q N WOOD DECK_ U.z o STEP W N r
? aEi Tax Map No.: 316„10-1-8 0 o LL CONC.PORCH o \ ov o
U 1-y Z WITH ROOF 'L Cr
iL
LL ti U y�0 a Q1 aQ o
z LM I ---- — _—_ Q w o
C �
a � CONIC PAD i` �CONC.PAD NOTE: o � � m DEED REFERENCES:
= WILP GAS TANK \, WI AC UNIT F
C 0 I Building offsets to property 4 Evergreen Abstracting Company, Inc.
0 o a I lines are measured from To
m U) cc `IRON ROD
r- �- SET foundation corners. a
CONC.MON. 0-�O '� Brian Sheerer
�, O i ri IRON ROD 113
\
FOUND a (�^ O/ _ 2�� OQ 39 7. 3G SET D: 8/5/2005
Q •J C R: 8/8/2005 1460/242
h i
W (Quit Claim Deed)
Go
w Scott Richardson
APPROP.MAP: 100.1 FT. To
Brian and Patty J. Sheerer
o `— _ a — _ _ J _ Lands N/F Max and Madeline Schenk_ _ _ _ ! __, �''1n"
FOUND ON — '� 256/80 and 939/1 NM 37/2 D: 8/24/2005
R: 9/6/2005 1465/145
(Quit Claim Deed)
�I•.r � t
N w
M
M O Uj
\\ ,
r
CONC.MO
FOUND
MAP
of a survey of lands of
BrianandPatty J. Sheerer
situated in
Town of Queensbury Warren County , N.Y.
Scale: 1" = 50' November 28, 2006
Survey and Map by
CHARLES T. NACY
Licensed Land Surveyor
32 John Street
Queensbury,NY 12804
Only copies made from the original of this Unauthorized alteration or addition to a survey
survey map which are marked with an map bearing a licensed land surveyor's seal is
t original of the land surveyor's embossed a violation of Section 7209,subdivision 2,of the
It seal and bearing the surveyor's original New York State Education Law.
signature in red ink shall be considered
valid and true copies.
10-/z �- X J112�10,K
Queensbury Building & Code Enforcement - Reside l Inspection
Office No.(518)761-8256 Arrive: Z art: a P
Date Inspection request received:
P q Inspector's Initi s:
NAME: PE T#: O
LOCATION: _ D
TYPE OF STRUCTURE:
Comm nts
Yes No N/A
Building Number/Address visible from road
Chimney Height/"B"Vent/Direct Vent Location
Fresh Air Intake
3 inch Plumbing Vent through roof minimum 6 inches
Roof Complete/Exterior Finish Com lete
Platform at all exterior doors
Guards at stairs,decks,patios more than 30 inches above grade
Guard at stairwell at 34 inches or more
Guard at deck,porches 36 inches or more
Handrail Termination at Newell Post or Wall
Interior/Exterior Railings 34 inches to 38 inches
Interior Handrails @ stairs 2 or more risers
Grade away from foundation 6 inches witb 10 feet
6 inch clearance to sill plate
Gas Valve shut-off exposed/regulator 18 inches above grade
Interior privacy/trim/doors/main entrance 36 inches
Bathroom/Kitchen watertight
Safety glazing/W" dow in stairwells safety glazing
Interior Smoke tectors:
Every level: Ev ry Be oon.
Outside every bedroom ea: ' I
Inter Connected: Battery backup: J
Carbon Monoxide Detector
Attic access 30 inches x 22 inches x 30 inches(hei ht)in accessible area
Crawl Spaces 18 inch x 24 inch access, 1 s . ft.-150 s .ft.vents
Bathroom Fans,if no window
Plumbing fixtures
Foundation insulation
Floor truss,draft stopping finished basement 1,000 s .ft.
Emergency egress below grade
Gas Furnace shut-off within 30 feet or within line of site
Oil Furnace shut-off at entrance to furnace area
Furnace/Hot Water Heater operating
Low water shut-off boiler
Relief Valve(s)installed/Heat Trap/Water Temp 110
Enclosed Stairs Sheetrock Underside minimum%"Gypsum
Basement stairs closed rise>4 inches
Garage Floor Pitched
Garage fireproofing/Y4 hour fire door/door closer
Duct work Sealed properly
Gas Logs in Sealed or Glass Enclosure
Final Electrical
Final Survey Plot Plan
As Built Septic System/Sewer Dept.Inspection Sticker �1 )
Site Plan /Variance required
Flood Plain Certification,if required
Okay to issue C/C or C/O[Temporary/Permanent
L:\Building&Codes Forms\Building&Codes\Inspection Forms\Residential Final Inspection Form revised 100405.doc
COMMONWEALTH ELECTRICAL INSPECTION SERVICE,INC.
Main Office 176 Doe Run Road-Manheim,PA 17545
MUNICIPAL CERTIFICATE - ELECTRICAL APPROVAL
Permit No........................................Cert. N2 9 0 5 7 5 Cut-in Card No......I......I.......................
Owner............... ................................................................/....r.�.............. .....
Location...... - ........... L�9...... .....1 :................................. ...................................
J
Installation Consisting of.................................. ?��� �L' ..............................
g / ...............................j.................... ,t
"N. � �..........4........7......�.. .................................................................
....................................................................................................................................................................................
r--
InstalledBy....sj.`.......�Y..........-.....................................................Lic.No...................................................
The conditions following governed the issuance of this certificate,and any certificate previously issued is
cancelled:-
This certificate only covers the electrical equipment and installation conditions as of date. Upon the
introduction of additional equipment or alterations,application shall be promptly made for inspection.
Inspectors of this Company shall have the privilege of mak "nspections at any time, and if its
vles are violated,the/Company shall have the right t re ke t s ific
)ate... /.,z 6.........I....... INSPECTOR...............................................................................................
Member N.F.P.A.,I.A.E.1.
-Z AJEZNE�611 Y 7
Foundation Inspection Report
Office No.(518)761-8256 Date Inspection r est ved:
Queensbury Building&Code Enforcement Arrive: part: aa ✓
742 Bay Rd.,Queensbury,NY 12804 Inspector's Initial
NAME: {� C ' P T
LOCATION: SPECT ON:
TYPE OF STRUCTURE:
Comments
Y N N/A
Footings
--�--,) N
Piers
Monolithic Slab
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this purpose on site.
Foundation/Wallpour
Reinforcement in Place
Footing Dowels or Keyway in place
Foundation Dampproofmg
Foundation Waterproofing
Footing Drain Daylight or Sump
Footing Drain Stone:
12 inch width
6 inches above footing
6 mil poly for wet areas under slab
Backfill Approval
Plumbing Under Slab
PVC/Cast/Copper
Foundation Insulation Interior/Exterior
R-
Rough Grade 6 inch drop within 10 ft.
L:\Building&Codes Forms\Building&Codes\Inspection Foams\Foundation Inspection Report.doc
Last printed 12/20/2005 9:24:00 AM
Rough Plumbing / Insulation Inspection Report
Office No. (518) 761-8256 Date Inspection request received: 6 O
Queensbury Building & Code Enforcement Arrive: am/pm Depart a Jpm
742 Bay Road, Queensbury, NY 12804 Inspector's Initials:
NAME: 41 PERMIT #: -
LOCATION: INSPECT ON:
TYPE OF STRUCTURE:
Y N N/A
Rough Plu / Nail Plates
in Vent / Vents in Place
1 1/2 inch minimum Drain Size
Washing Machine Drain 2 inch minimum
Cleanout every 100 feet / change of direction
Pressure Test
Dra' \ '
ead J �t \,
. r ft. above highest connection for 15 minutes
Pr est
Water Supply Piping
Air/ Head
5Q-E.S,I for 15 minutes
nsultio / Residential Check/ Commercial Check
-Fralie'r Vent Attic Vent
Duct/ Hot Water Piping Insulation
If required unheated spaces
Combustion Air Supply for Furnace
Duct work sealed properly / No duct tape
COMMENTS:
LAPam Whiting\Building&Codes\Inspection Forms\Rough Plumbing Insulation Report.revised Nov 17 2003.doc Revised February 15,2005
Rough Plumbing / Insulation Inspection Report
Office No. (518) 761-8256 Date Inspection request received:
Queensbury Building& Code Enforcement Arrive: am/pm Depart: `�'am/pm
742 Bay Road, Queensbury,NY 12804 Inspector's Initials: A�� j 1
NAME: PERMIT #: 0 O /
LOCATION: INSPECT ON: 4,1 9 -f)(2
TYPE OF STRUCTURE:
Y N N/A
PVC: R-1,R-2,R-3,R4 Drain/Vents
Cast Iron, Copper Drain/Vent/Comm.
Plumbing Vent/Vents in Place
Rough Plumbing/Nail Plates
1 % inch min..Drain Size
Washi 'Machine Drain 2 inch min.
He or Air Supply Test
rain and Vents
5 PSI or 10 feet above highestL 6-L-�KLZCI
connection for 15 minutes
Cleanout every 100 feet/change of direction
Water Supply Piping
Cooper Commercial
Cooper,CPVC,Pex One and Two-Family
Insulation/Residential Check/Commercial Check
Pro er Vent,Attic Vent
Duct/Hot Water Piping Insulation
If required unheated spaces
Combustion Air Supply for Furnace
Duct work sealed properl /No duct tape
COMMENTS:
LASueHemingway\Building.Codes.Inspection.FORMS\Rough Plumbing Insulation Report.doc November 17,2003
Framing / Firestopping Inspection Report
Office No. (518)761-8256 Date Inspection request received:
Queensbury Building&Code Enforcement Arrive: am/pm Depart: am/pm
742 Bay Road,Queensbury,NY 12804 Inspector's Initials:
1
NAME: PERMIT#:
LOCATION: " cr, INSPECT ON:
TYPE OF STRUCTURE:
Y N N/A COMMENTS
Warning
Attic Access 22"x 30"minimum
Jack Studs/Headers
Bracing/Bridging
Joist hangers
Jack Posts/Main Beams
Exterior sheeting nailed properly
12"O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate
1 %s w) 16 gauge(8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
Ice and water shield 24 inches from wall
Fire separation 1,2, 3 hour
Fire wall 2, 3,4 hour
Firestopping
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side Yz inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/Bedrooms
24 in. (H)
20 in. (W)
5.7 sf above/below grade
5.0 sf grade L
Framing/ Firestopping Inspection Report
Office No.(518) 761-8256 Date Inspection request received:
Queensbury Building&Code Enforcement Arrive: am/pm Depart:7�arnYp
742 Bay Road,Queensbury,NY 12804 Inspector's Initials:
NAME: J e PERMIT#.
LOCATION: f c 1✓D - INSPECT ON: L
TYPE OF STRUCTURE: ,
Y N/A COMMENTS
ming
Attic Access 22"x 30"minimum
Jack Studs/Headers
Bracing/Bridging
Joist hangers
Jack Posts/Main Beams cCJG �
Exterior sheeting nailed properly
12"O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate _
1 /a w) 16 gauge(8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
Ice and water shield 24 inches from wall
Fire separation 1, 2, 3 hour
Fire wall 2, 3,4 hour
Firestopping
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side %2 inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/Bedrooms
24 in. (H)
20 in. (W)
5.7 sf above/below grade
5.0 sf grade
- 4
Septic Inspection Report
Office No.(518)761-8256 Date Insp ction� quest received:
Queensbury Building&Code Enforcement Arrive: / ( am/p epart: _am/pm
742 Bay Rd., Queensbury,NY 12804 Inspe or's Initials:
NAME: �-��'_ � PERMIT NO.:
LOCATION: INSPECT ON: — Z
RECHECK:
Comments and/or diagram
Soil Type: Sa d/ Clay
Type of Wa r: ^nicipj/Well Water 1�
Waterline sepAtion d' ance
Well separation atstrhce ft.
Other wells: ft.
Absorption Field: Total length ft.
Length of each trench ft.
Depth of trenches ft.
Size of Stone
Seepage Pits: Number
Size: x
Stone Size:
Piping Si2p,, Type
Building to tank
Tank to Distributio Box K �3i
Distribution Bo ield/Pit k Zb
Opening SealeA V N/Partial
End Caps
Location/Separations
Foundation to tank ft.
Foundation to absorption ft.
Separation of Pits ft.
Conforms as per Plot Plan Y N
Engineer]Report and As-Built Y N
Location of System on Property:
Front Rear Left Side Right Side
Middle Front Middle Rear
System Use Status•
Approved
Partial Approved and needs to be re-inspected,please call the Building&Codes Office
Disapproved
Last revised 1/6/05
Framing / Firestopping Inspection Report
Office No. 518 761-8256 Date his ection re t r cei e
( ) /
Queensbury Building&Code Enforcement Arrive: ', art. s a m
742 Bay Road,Queensbury,NY 12804 Inspector's In'
NAME: rr C<-✓ PERMIT#:
LOCATION: cuf'�. INSPECT ON:
TYPE OF STRUCTURE: /
Y N N/A Framing COMMENTS
Attic Access 22"x 30"minimum
Jack Studs/Headers
Bracing/Bridging
Joist hangers
Jack Posts/Main Beams
Exterior sheeting nailed properly
12"O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in.or more
Headroom 6 ft. 8 in.
Notches/Holes/Bearing Walls
Metal Strapping for Notches Top Plate
1 '/z w 16 gauge(8) 16D nails each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
ce and water shie nches from wall
Fire separation 1, 2, 3 hour
Fire wall 2, 3,4 hour
Firestopping
Penetration sealed
16 inch insulation in cavity min.
Garage Fire Separation
House side '/2 inch or 5/8 inch Type X
Garage side 5/8 inch Type X
Ceiling/wall
Windows Habitable Space/Bedrooms
24 in.(H)
20 in. (W)
5.7 sf above/below grade
5.0 sf grade
Foundation Inspection Report
�T(
Office No. (518)761-82.56 Date Inspection request received: On]
7 O a
Queensbury Building&Cade Enforcement Arrive: ain/pi %s epart- pm
742 Bay Rd., Queensbury,NY 12804 Inspector's Initials:
NAME: ���' �``— ? PERMIT#:
LOCATION: LP v:a _ INSPECT ON:
TYPE OF STRUCTURE:
Comments
Footings
Piers
Monolithic Slab
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this purpose on site. _
Foundation/Wallpour
Reinfor entin Place
Foundation Dampproo ii
Foundation/Waterproofing
Type of Dampproofing;Waterproofing
Footing Drain Daylight or Sump _
Footing Drain Stone:
1 inch width
'6 inches above footing
6 mil poly for wet areas under slab
Backf"ill Approval
Plumbing Under Slab
PVC/Cast/Copper
Foundation Insulation Interior/Exterior
R-
Rough Grade 6 inch drop within 10 ft.
LASuellemingway\Ruilding.Codes.InspectionTORM ST oundati on Inspection Report.doe January 28,2003
y:
d`
f
Foundation Inspection Report
i
f
P
Office No. (518) 761-82.56 Date Inspection request received:
Queensbury Building&Code Enforcement Arrive: anvpm �� Depart: am/ in
742 Bay Rd., Queensbury,NY 12804 Inspector's Initials:
NAME: _ PERMIT#:
LOCATION: _ Z U,�• _ INSPECT ON:
TYPE OF STRUCTURE: <, 2 ��//����
14
C Pments
Y tN N/A_�
ootings
Piers i
Monolithic Slab
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this purpose on site.—Y
Foundation/Walipour
Reinforcement in Place
Foundation Dampproofing
Foundation/Waterproofing
Type of Dampproofing/Waterproofing
Footing Drain Daylight or Sump T—
Footing Drain Stone:
12 inch width
6 inches above footing
6 mil poly for wet_areas under slab
Backfrll Approval
Plumbing Under Slab
PVC/Cast/Copper
Foundation Insulation Interior/Exterior
R-
Rough Grade 6 inch drop within 10 ft. 1_
L\SueHemingway\Building.0 Odes-Inspection.FORM SToundation Inspeciion Report.doc January 28,2003
Sheerer
296 Big Boom Road
Tax Map#316.10-1-S
S
i
52'
� W',
0 0
Ttr
o+oo
�tK
ff
3
I s
R
N
� X
,
Permit Number
REScheck Compliance Certificate Checked By/Date
New York State Energy Conservation Construction Code
REScheck Software Version 3.6 Release 2
Data filename: C:\Documents and Settings\Tanya\My Documents\ARCIRTECTURAL\SHEERER\RANCH.rck
PROJECT TITLE: Patty& Richard Sheerer Residence
COUNTY: Warren
STATE: New York
HDD: 7635
CONSTRUCTION TYPE: Detached 1 or 2 Family
HEATING TYPE: Non-Electric
WINDOW /WALL RATIO: 0.11
DATE: 10/14/05
DATE OF PLANS: October 10, 2005
PROJECT DESCRIPTION:
New 2X6 wood constructed ranch with porch on Full f5undation
DESIGNER/CONTRACTOR:
Tanya L.B.Bruno
Architectural Planning Consultant
119 Gurney Lane
Queensbury,NY 12804
(518)222,4973 fax 793.3380
COMPLIANCE: Passes
Maximum UA= 297
Your Home UA=255
14.1%Better Than Code(UA)
Gross Glazing
Area or Cavity Cont. or Door
Perim R-Value R-V -Fact r IJA
Ceiling 1: Raised or Energy Truss 1300 38.0 0.0 33
Wall 1: Wood Frame, 16"o.c. 1500 19.0 0.0 79
Window 1: Vinyl Frame:Double Pane with Low-E 38 0.320 12
Window 2: Vinyl Frame:Double Pane with Low-E 16 0.320 5
Window 3: Vinyl Frarne:Double Pane with Low E 16 0.320 5
Window 4: Vinyl Frame:Double Pane with Low-E 16 0.320 5
Window 5: Vinyl Frame:Double Pane with Low-E 16 0.320 5
Window 6: Vinyl Frame:Double Pane with Low-E 9 0.320 3
Door 1: Solid 20 0.340 7
Door 2: Glass 41 0.350 14
Door 3: Glass 19 0.350 7
Basement Wall 1: Solid Concrete or Masonry 1250 11.0 0.0 80
Wall height: 7.9'
Depth below grade: 6.8'
Insulation depth: 7.9'
COMPLIANCE STATEMENT: The proposed building represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application. The proposed systems have been
designed to meet the New York State Energy Conservation Construction Code requirements. When a Registered Design
Processional has stamped and signed this page, they are attesting that to the best ofhis/her knowledge, belief and
professional judgment, such plans or specifications are in compliance with this Code.
Builder/Designer ��Z/����� Date tOs-
V �
REScheck Inspection Checklist
New York State Energy Conservation Construction Code
REScheck So$ware Version 3.6 Release 2
DATE: 10/14/05
PROJECT TITLE: Patty& Richard Sheerer Residence
Bldg. j
Dept. j
Use i
j
j Ceilings:
[ ] j 1. Ceiling 1: Raised or Energy Truss, R-38.0 cavity insulation
j Comments:
Insulation must achieve full height over the plate lines of exterior walls.
j
j Above-Grade Walls:
[ ] j 1. Wall 1: Wood Frame, 16" o.c., R-19.0 cavity insulation
j Comments:
j
j Basement Walls:
[ ] ( 1. Basement Wall 1: Solid Concrete or Masonry, 7.9'ht/6.8'bg/7.9' insul,
j R-11.0 cavity insulation
j Comments:
j
j Windows:
[ ] j 1. Window 1: Vinyl Frame:Double Pane with Low-E, U-factor: 0.320
j For windows without labeled U-factors, describe features:
j #Panes Frame Type Thermal Break? [ )Yes [ ]No
j Comments:
[ ] i 2. Window 2: Vinyl Frame:Double Pane with Low-E, U-factor. 0.320
j For windows without labeled U-factors, describe features:
j #Panes Frame Type Thermal Break? [ ]Yes [ ]No
j Comments:
[ ] 3. Window 3: Vinyl Frame:Double Pane with Low-E, U-factor: 0.320
j For windows without labeled U-fcctors, describe features:
j #Panes Frame Type Thermal Break? [ ]Yes [ ]No
j Comments:
[ ] j 4. Window 4: Vinyl Frame:Double Pane with Low-E, U-factor: 0.320
j For windows without labeled U-fcctors, describe features:
i #Panes Frame Type Thermal Break? [ ]Yes [ ]No
j Comments:
[ ] j 5. Window 5: Vinyl Frame:Double Pane with Low-E, U-factor: 0.320
j For windows without labeled U-factors, describe features:
#Panes Frame Type Thermal Break? [ ]Yes [ ]No
j Comments:
[ ] ( 6. Window 6: Vinyl Frame:Double Pane with Low-E, U-factor: 0.320
j For windows without labeled U-factors, describe features:
j #Panes Frame Type Thermal Break? [ ]Yes [ ]No
j Comments:
• w `
j
j Doors:
[ ] j 1. Door 1: Solid, U-factor: 0.340
j Comments:
[ ] j 2. Door 2: Glass, U-fictor: 0.350
Comments:
[ ] { 3. Door 3: Glass, U-factor. 0.350
{ Comments:
j
j Air Leakage:
[ ] j Joints, penetrations, and all other such openings in the building envelope that are sources of air
j leakage must be sealed.
Recessed lights must be 1)Type IC rated, or 2)installed inside an appropriate air-tight assembly
j with a 0.5" clearance from combustible materials. Ifnon-IC rated, the fixture must be installed with a
1 3" clearance from insulation.
j
j Vapor Retarder:
[ ] j Required on the warm-in-winter side of all non-vented framed ceilings, walls, and floors.
j
{ Materials Identification:
[ ] j Materials and equipment must be installed in accordance with the manuficturer's installation instructions.
[ ] j Materials and equipment must be identified so that compliance can be determined.
[ J j Manufacturer manuals for all installed heating and cooling equipment and service water heating
j equipment must be provided.
[ ] j Insulation R-values and glazing U-factors must be clearly marked on the building plans or specifications.
j
j Duct Insulation:
[ ] ( Supply ducts in unconditioned attics or outside the building must be insulated to R-11.
[ J j Return ducts in unconditioned attics or outside the building must be insulated to R-6.
[ ] j Supply ducts in unconditioned spaces must be insulated to R-11.
[ ] j Return ducts in unconditioned spaces(except basements)must be insulated to R-
[ J j Return ducts in unconditioned spaces(except basements)must be insulated to R-2..
j Insulation is not required on return ducts in basements.
j
j Duct Construction:
[ J j All joints, seams, and connections must be securely fastened with welds, gaskets, mastics(adhesives),
j mastic-plus-embedded-fabric, or tapes. Tapes and mastics must be rated UL 181A or UL 181B.
( Exception:Continuously welded and locking-type longitudinal joints and seams on ducts
j operating at less than 2 in. w.g. (500 Pa).
[ J j The HVAC system must provide a means fir balancing air and water systems.
j
j Temperature Controls:
[ ] i Each dwelling unit has at lesat one thermostat capable of automatically adjusting the space
j temperature set point of the largest zone.
j
j Electric Systems:
[ ] j Separate electric meters are required for each dwelling unit.
j
i Fireplaces:
j J j Fireplaces must be installed with tight fitting non-combustible fireplace doors.
[ ] j Fireplaces must be provided with a source of combustion air, as required by the Fireplace construction
j provisions ofthe Building Code of New York State, the Residential Code of New York State or
< � e
the New York City Building Code, as applicable.
I
Service Water Heating:
[ ] I Water heaters with vertical pipe risers must have a heat trap on both the inlet and outlet unless the
water heater has an integral heat trap or is part of a circulating system.
[ ] I Insulate circulating hot water pipes to the levels in Table 1.
I
Circulating Hot Water Systems:
[ ] I Insulate circulating hot water pipes to the levels in Table 1.
i
I Swimming Pools:
[ ] I All heated swimming pools must have an on/offheater switch and require a cover unless over 20%
ofthe heating energy is from non-depletable sources. Pool pumps require a time clock.
I
Heating and Cooling Piping Insulation:
[ ] ( HVAC piping conveying fluids above 105 OF or chilled fluids below 55 T must be insulated to the
levels in Table 2.
Table 1: Minimum Insulation Thickness for Circulating Hot Water Pipes.
Insulation Thickness in Inches by Pipe Sizes
Heated Water Non7Circulating Runouts Circulating Mains and Runouts
Temperature(F) LID to 1„ JW to 1.25" 1.5"to 2.0" Over 2„
170-180 0.5 1.0 1.5 2.0
140-169 0.5 0.5 1.0 1.5
100-139 0.5 0.5 0.5 1.0
Table 2: Minimum Insulation Thickness for HVAC Pipes.
Fluid Temp. Insulation Thickness in Inches by pine Sizes
Pijng System Types Ranee(F) 2"Runouts 1" and Less 1.25"to 2" 2 " t "
Heating Systems
Low Pressure/Temperature 201-250 1.0 1.5 1.5 2.0
Low Temperature 120-200 0.5 1.0 1.0 1.5
Steam Condensate(far£ed water) Any 1.0 1.0 1.5 2.0
Cooling Systems
Chilled Water, Refrigerant, 40-55 0.5 0.5 0.75 1.0
and Brine Below 40 1.0 1.0 1.5 1.5
NOTES TO FIELD(Building Department Use Only)