TAB Report 12-28-20 20-551FIRM: MTI - Mechanical Testing, Inc. 4 Chelsea Place, Suite 102 Clifton Park NY 12065 PHONE: (518) 450-7292 FAX: (518) 450-7295 CUSTOMER: BPI Piping PROJECT #: 20-551 PROJECT ADDRESS: 742 Bay Road Queensbury NY 12801 DATE: 2020-12-28 CONTACT: Kevin Greenwood / Jon Aguilar Queensbury Highway Department New Vehicle Garage 4 Chelsea Pl, Suite 102 Clifton Park, NY 12065 Phone: 518-450-7292 Fax: 518-450-7295 Design Review - Commissioning - Fire Life Safety - Test And Balance - ASHRAE 110 -Drone Sales/Inspections Terms and Abbreviations     ACH​- Air Changes per Hour   AHU​- Air Handling Unit  AK​- Free Area of Duct   AVG​- Average   BHP​- Brake Horsepower   BV​- Ball Valve (Shut Off Valve)   CB​- Circuit Breaker   CBV​- Calibrated Balance Valve   CD​-Ceiling Diffuser   CFM​- Cubic Feet per Minute   CHWS​- Chilled Water System   CRAC​- Computer Room Air Conditioner   CS​- Circuit Setter   CUH​- Cabinet Unit Heater   DAT​- Discharge Air Temperature   DD​- Direct Drive (motor)  Des.​- Design   Disch​.- Discharge   DNE​- Does Not Exist   DP​- Discharge Pressure of Pump/Pressure Drop   EA​- Exhaust Air   EAV​- Exhaust Air Valve   EAT​- Entering Air Temperature   EF​- Exhaust Fan   EG​- Exhaust Grille   ERU​- Energy Recovery Unit   E.S.P​.- External Static Pressure   EWT​- Entering Water Temperature   FCU​- Fan Coil Unit   FD​- Fire Damper   FLA​- Full Load Amperage   Flow Coeff.​ –Correction Factor for Flow to VAV   Flow Hood​- Instrument that measures airflow   FPM​- Feet per Minute GPM- Gallons Per Minute   HEPA​- High Efficiency Particulate Arrestance   HP​- Horsepower   HVAC​- Heating Ventilation and Air Conditioning   HWS​- Hot Water System   HX​- Heat Exchanger   Hz​- Hertz   In.​- Inches   In. w.g.​- Inches of Water Gauge   ISDFT​- Insufficient Straight Duct for Traverse   Kfactor​- Correction factor to the free area   needed to calculate CFM.   LAT​- leaving Air Temperature   LWT​- Leaving Water Temperature   MAU​- Make Up Air Handling Unit   MAX​- Maximum set point/flow   MIN​- Minimum set point/flow   NI​-Not Installed   NIS​-Not in Scope   O/A​- Outside Air   OBD​- Opposed Blade Damper   OD​- Outside Diameter Measurement of Sheave   PH​- Phase   PSI​- Pounds per Square Inch   RA​- Return Air   RAT​- Return Air Temperature   RF​- Return Fan   RHC​- Reheat Coil   RPM​- Revolutions per Minute   RTU​- Roof Top Unit   SA​- Supply Air   SAV​- Supply Air Valve   SAT​- Supply Air Temperature   S.F.​- Service Factor  SF​- Supply Fan   SP​- Suction Pressure of Pump/ Static Pressure   Sq. ft​.- Square Feet   TAB​- Test, Adjust and Balance   TDV​- Triple Duty Valve   TP​- Thermally Protected   TSP​- Total Static Pressure   UH​- Unit Heater   V​- Volts   VAV​- Variable Air Volume Box   VD​- Volume Damper   VFD​- Variable Frequency Drive   VVT​- Variable Volume Terminal   WC​- Water Column   3 3 5 5 9 13 17 21 21 24 27 Table of Contents *Instruments Used Instruments Used HV* HV-1* HV-2* HV-3* HV-4* Exhaust Fan EF-1 EF-2 EF-3* PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 Page 2 of 29 2020-12-28 *Instruments Used Instruments Used AIR Manufacturer Evergreen Telemetry Calibration Date 9/16/20 Model No.S-PVF-1 Tech Name Kevin Greenwood Serial No.1400282 WATER Manufacturer Not Applicable Calibration Date Not Applicable Model No.Not Applicable Tech Name Kevin Greenwood Serial No.Not Applicable ALTERNATE METER Meter Type Not Applicable Serial No.Not Applicable Manufacturer Not Applicable Calibration Date Not Applicable Model No.Not Applicable PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 Instruments Used Page 3 of 29 2020-12-28 Air IMAGES: PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 Instruments Used Page 4 of 29 2020-12-28 Design Actual %Design Actual % HV* HV-1* UNIT DATA Equipment Location Garage Filter Type Wire Mesh Area Served Garage Filter Quantity 4,4 Unit Manufacturer Captiveaire Filter Size 20x30x2 in Unit Model No.A3-D.1000-G18 Performed By KG/CS Unit Serial No.Not Listed Pass/Fail Pass HV-1* / Test Data* TEST DATA Total Unit CFM 5555 CFM 6028 CFM 109 O/A Damper Position 100 % Outlet CFM Not Applicable CFM Not Applicable CFM R/A Damper Position Not Applicable % Outside Air CFM 5555 CFM 6028 CFM 109 Discharge Air temp Not Applicable deg F Return Air CFM Not Applicable CFM Not Applicable CFM Hertz at Design CFM Not Applicable Hz Fan RPM 750 RPM 722 RPM 96 Test Date 12/24/20 HV-1* / Motor Data* MOTOR DATA Motor Manufacturer Westinghouse Volts T1 210 Volts Motor Frame 182T Volts T2 210 Volts Motor RPM 1755 RPM Volts T3 209 Volts Motor Horsepower 3.0 HP Plate Amps 8.6 Amps Motor Phase 3 Amps T1 7.70 Amps Motor Hertz 60 Hz Amps T2 7.60 Amps PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-1*Page 5 of 29 2020-12-28 Design Actual %Design Actual % Service Factor 1.15 Amps T3 7.70 Amps Efficiency 0.895 Starter Heater CB Power Factor 0.875 Brake Horsepower 2.937 Plate Volts 208 Volts MOTOR DATA HV-1* / Drive Data* DRIVE DATA Motor Sheave/OD Size 2VP42 Fan Bore 1 3/16 in Motor Bore 1 1/8 in No. of Belts 2 Motor Sheave % Closed 75 %Belt Size BX60 Fan Sheave/OD Size BK90H Center Distance 21 in HV-1* / Test Pressures* TEST PRESSURES Total Static Pressure .71 in. H2O 0.92 in. H2O 130 Pre-Filter DP Not Listed in. H2O 0.02 in. H2O External Static Pressure .50 in. H2O 0.15 in. H2O 30 Pre-Heat DP Not Listed in. H2O 0.77 in. H2O Discharge Static 0.05 in. H2O Cooling Coil DP Not Applicable in. H2O Not Applicable in. H2O Suction Static 0.87 in. H2O Static at Furthest VAV Not Applicable in. H2O Mix Box/Pre-Filter SP Not Listed in. H2O 0.10 in. H2O Sys. Operational Static Not Applicable in. H2O HV-1* / Photos* PHOTO'S Unit Photo PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-1*Page 6 of 29 2020-12-28 Photo's IMAGES: HV-1* / Static Profile* STATIC PROFILE Static Profile IMAGES: PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-1*Page 7 of 29 2020-12-28 HV-1* / Traverse Summary TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*SA Discharge 22x20 3.060 1815 5555 1970 6028 Not Applicable Totals 5555 6028 PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-1*Page 8 of 29 2020-12-28 Design Actual %Design Actual % HV-2* UNIT DATA Equipment Location Garage Filter Type Wire Mesh Area Served Garage Filter Quantity 4,4 Unit Manufacturer Captiveaire Filter Size 20x30x2, 20x25x2 in Unit Model No.A3-D.1000-G18 Performed By KG/CS Unit Serial No.Not Listed Pass/Fail Pass HV-2* / Test Data* TEST DATA Total Unit CFM 5555 CFM 5266 CFM 95 O/A Damper Position 100 % Outlet CFM Not Applicable CFM Not Applicable CFM R/A Damper Position Not Applicable % Outside Air CFM 5555 CFM 5266 CFM 95 Discharge Air temp Not Applicable deg F Return Air CFM Not Applicable CFM Not Applicable CFM Hertz at Design CFM Not Applicable Hz Fan RPM 750 RPM 717 RPM 96 Test Date 12/24/20 HV-2* / Motor Data* MOTOR DATA Motor Manufacturer Westinghouse Volts T1 210 Volts Motor Frame 182T Volts T2 210 Volts Motor RPM 1755 RPM Volts T3 210 Volts Motor Horsepower 3.0 HP Plate Amps 8.6 Amps Motor Phase 3 Amps T1 7.50 Amps Motor Hertz 60 Hz Amps T2 7.80 Amps Service Factor 1.15 Amps T3 7.80 Amps Efficiency 0.895 Starter Heater CB PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-2*Page 9 of 29 2020-12-28 Design Actual %Design Actual % Power Factor 0.875 Brake Horsepower 2.860 Plate Volts 208 Volts MOTOR DATA HV-2* / Drive Data* DRIVE DATA Motor Sheave/OD Size 2VP42 Fan Bore 1 3/16 in Motor Bore 1 1/8 in No. of Belts 2 Motor Sheave % Closed 75 %Belt Size BX60 Fan Sheave/OD Size BK90H Center Distance 21 in HV-2* / Test Pressures* TEST PRESSURES Total Static Pressure .71 in. H2O 1.53 in. H2O 215 Pre-Filter DP Not Listed in. H2O 0.03 in. H2O External Static Pressure .50 in. H2O 0.37 in. H2O 74 Pre-Heat DP Not Listed in. H2O 1.19 in. H2O Discharge Static 0.04 in. H2O Cooling Coil DP Not Applicable in. H2O Not Applicable in. H2O Suction Static 1.49 in. H2O Static at Furthest VAV Not Applicable in. H2O Mix Box/Pre-Filter SP Not Listed in. H2O 0.30 in. H2O Sys. Operational Static Not Applicable in. H2O HV-2* / Photos PHOTO'S Unit Photo PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-2*Page 10 of 29 2020-12-28 Photo's IMAGES: HV-2* / Static Profile* STATIC PROFILE Static Profile IMAGES: PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-2*Page 11 of 29 2020-12-28 HV-2* / Traverse Summary TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*SA Discharge 22x20 3.060 1815 5555 1721 5266 Not Applicable Totals 5555 5266 PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-2*Page 12 of 29 2020-12-28 Design Actual %Design Actual % HV-3* UNIT DATA Equipment Location Garage Filter Type Wire Mesh Area Served Garage Filter Quantity 4,4 Unit Manufacturer Captiveaire Filter Size 20x30x2 in Unit Model No.A3-D.1000-G18 Performed By KG/CS Unit Serial No.Not Listed Pass/Fail Pass HV-3* / Test Data* TEST DATA Total Unit CFM 5555 CFM 5272 CFM 95 O/A Damper Position 100 % Outlet CFM Not Applicable CFM Not Applicable CFM R/A Damper Position Not Applicable % Outside Air CFM 5555 CFM 5272 CFM 95 Discharge Air temp Not Applicable deg F Return Air CFM Not Applicable CFM Not Applicable CFM Hertz at Design CFM Not Applicable Hz Fan RPM 750 RPM 717 RPM 96 Test Date 12/24/20 HV-3* / Motor Data* MOTOR DATA Motor Manufacturer Westinghouse Volts T1 209 Volts Motor Frame 182T Volts T2 210 Volts Motor RPM 1755 RPM Volts T3 210 Volts Motor Horsepower 3.0 HP Plate Amps 8.6 Amps Motor Phase 3 Amps T1 8.00 Amps Motor Hertz 60 Hz Amps T2 7.80 Amps Service Factor 1.15 Amps T3 8.00 Amps Efficiency 0.895 Starter Heater CB PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-3*Page 13 of 29 2020-12-28 Design Actual %Design Actual % Power Factor 0.875 Brake Horsepower 3.037 Plate Volts 208 Volts MOTOR DATA HV-3* / Drive Data* DRIVE DATA Motor Sheave/OD Size 2VP42 Fan Bore 1 3/16 in Motor Bore 1 1/8 in No. of Belts 2 Motor Sheave % Closed 75 %Belt Size BX60 Fan Sheave/OD Size BK90H Center Distance 21 in HV-3* / Test Pressures* TEST PRESSURES Total Static Pressure .71 in. H2O 1.55 in. H2O 218 Pre-Filter DP Not Listed in. H2O 0.02 in. H2O External Static Pressure .50 in. H2O 0.45 in. H2O 90 Pre-Heat DP Not Listed in. H2O 0.71 in. H2O Discharge Static 0.05 in. H2O Cooling Coil DP Not Applicable in. H2O Not Applicable in. H2O Suction Static 1.14 in. H2O Static at Furthest VAV Not Applicable in. H2O Mix Box/Pre-Filter SP Not Listed in. H2O 0.41 in. H2O Sys. Operational Static Not Applicable in. H2O HV-3* / Photos* PHOTO'S Unit Photo PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-3*Page 14 of 29 2020-12-28 Photo's IMAGES: HV-3* / Static Profile* STATIC PROFILE Static Profile IMAGES: PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-3*Page 15 of 29 2020-12-28 HV-3* / Traverse Summary TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*SA Discharge 20x22 3.060 1815 5555 1723 5272 Not Applicable Totals 5555 5272 PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-3*Page 16 of 29 2020-12-28 Design Actual %Design Actual % HV-4* UNIT DATA Equipment Location Garage Filter Type Wire Mesh Area Served Garage Filter Quantity 4,4 Unit Manufacturer Captiveaire Filter Size 20x30x2 in Unit Model No.A3-D.1000-G18 Performed By KG/CS Unit Serial No.Not Listed Pass/Fail Pass HV-4* / Test Data* TEST DATA Total Unit CFM 5555 CFM 5370 CFM 97 O/A Damper Position 100 % Outlet CFM Not Applicable CFM Not Applicable CFM R/A Damper Position Not Applicable % Outside Air CFM 5555 CFM 5370 CFM 97 Discharge Air temp Not Applicable deg F Return Air CFM Not Applicable CFM Not Applicable CFM Hertz at Design CFM Not Applicable Hz Fan RPM 750 RPM 625 RPM 83 Test Date 12/24/20 HV-4* / Motor Data* MOTOR DATA Motor Manufacturer Westinghouse Volts T1 210 Volts Motor Frame 182T Volts T2 210 Volts Motor RPM 1755 RPM Volts T3 209 Volts Motor Horsepower 3.0 HP Plate Amps 8.6 Amps Motor Phase 3 Amps T1 7.00 Amps Motor Hertz 60 Hz Amps T2 6.80 Amps Service Factor 1.15 Amps T3 6.80 Amps Efficiency 0.895 Starter Heater CB PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-4*Page 17 of 29 2020-12-28 Design Actual %Design Actual % Power Factor 0.875 Brake Horsepower 2.670 Plate Volts 208 Volts MOTOR DATA HV-4* / Drive Data* DRIVE DATA Motor Sheave/OD Size 2VP42 Fan Bore 1 3/16 in Motor Bore 1 1/8 in No. of Belts 2 Motor Sheave % Closed 0 %Belt Size BX90H Fan Sheave/OD Size BK90H Center Distance 21 in HV-4* / Test Pressures* TEST PRESSURES Total Static Pressure .71 in. H2O 1.10 in. H2O 155 Pre-Filter DP Not Listed in. H2O 0.09 in. H2O External Static Pressure .50 in. H2O 0.30 in. H2O 60 Pre-Heat DP Not Listed in. H2O 0.74 in. H2O Discharge Static 0.05 in. H2O Cooling Coil DP Not Applicable in. H2O Not Applicable in. H2O Suction Static 0.96 in. H2O Static at Furthest VAV Not Applicable in. H2O Mix Box/Pre-Filter SP Not Listed in. H2O 0.25 in. H2O Sys. Operational Static Not Applicable in. H2O HV-4* / Photos* PHOTO'S Unit Photo PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-4*Page 18 of 29 2020-12-28 Photo's IMAGES: HV-4* / Static Profile* STATIC PROFILE Static Profile IMAGES: PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-4*Page 19 of 29 2020-12-28 HV-4* / Traverse Summary TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*SA Discharge 22x20 3.060 1815 5555 1755 5370 Not Applicable Totals 5555 5370 PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 HV-4*Page 20 of 29 2020-12-28 Design Actual %Design Actual % Exhaust Fan EF-1 UNIT DATA Equipment Location West Wall Unit Serial No.261S179384-702 Area Served Garage Performed By KG/CS Unit Manufacturer Cook Pass/Fail Pass Unit Model No.30XMWH Date of Test 12/24/20 TEST DATA Total Unit CFM (MAX)10000 CFM 10787 CFM 108 Fan RPM 1116 RPM 1120 RPM 100 Outlet CFM Not Applicable CFM Not Applicable CFM Operational Static Press.Not Applicable in. H2O Total Unit CFM (MIN)Not Applicable CFM Not Applicable CFM Hertz at Design CFM Not Applicable HZ MOTOR DATA Motor Manufacturer Century Power Factor 0.850 Motor Frame Y145T Plate Volts 115 Volts Motor RPM 1745 RPM Actual Volts 118 Volts Motor Horsepower 2.0 HP Plate Amps 20.4 Amps Motor Phase 1 Actual Amps 19.80 Amps Motor Hertz 60 Hz Starter Heater Adj. at 22 Service Factor 1.15 Brake Horsepower 2.263 Efficiency 0.850 DRIVE DATA Motor Sheave/OD Size MVL40B Fan Bore 1 in Motor Bore 3/4 in No. of Belts 1 Motor Sheave % Closed 50 %Belt Size AX26 Fan Sheave/OD Size AK54 Center Distance 26 in PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 EF-1 Page 21 of 29 2020-12-28 Design Actual %Design Actual % TEST PRESSURES Total Static Pressure .50 in. H2O 0.44 in. H2O 88 Discharge Static 0.17 in. H2O Suction Static 0.27 in. H2O Filter DP (If Applicable)Not Applicable in. H2O Not Applicable in. H2O NOTES: Motor Data Efficiency The Efficiency and Power Factor are not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP. EF-1 / Photos* Unit Photos Unit Photos IMAGES: EF-1 / Traverse Summary PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 EF-1 Page 22 of 29 2020-12-28 TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*EA Discharge 38x38 8.020 1247 10000 1345 10787 Not Applicable Totals 10000 10787 PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 EF-1 Page 23 of 29 2020-12-28 Design Actual %Design Actual % EF-2 UNIT DATA Equipment Location West Wall Unit Serial No.261S179384-701 Area Served Garage Performed By KG/CS Unit Manufacturer Cook Pass/Fail Pass Unit Model No.30XMWH Date of Test 12/24/20 TEST DATA Total Unit CFM (MAX)10000 CFM 10747 CFM 107 Fan RPM 1116 RPM 1118 RPM 100 Outlet CFM Not Applicable CFM Not Applicable CFM Operational Static Press.Not Applicable in. H2O Total Unit CFM (MIN)Not Applicable CFM Not Applicable CFM Hertz at Design CFM Not Applicable HZ MOTOR DATA Motor Manufacturer Century Power Factor 0.850 Motor Frame Y145T Plate Volts 115 Volts Motor RPM 1725 RPM Actual Volts 118 Volts Motor Horsepower 2.0 HP Plate Amps 20.4 Amps Motor Phase 1 Actual Amps 19.60 Amps Motor Hertz 60 Hz Starter Heater Adj at 22 Service Factor 1.15 Brake Horsepower 2.240 Efficiency 0.850 DRIVE DATA Motor Sheave/OD Size MVL40B Fan Bore 1 in Motor Bore 3/4 in No. of Belts 1 Motor Sheave % Closed 50 %Belt Size AX26 Fan Sheave/OD Size AK54 Center Distance 26 in PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 EF-2 Page 24 of 29 2020-12-28 Design Actual %Design Actual % TEST PRESSURES Total Static Pressure .50 in. H2O 0.43 in. H2O 86 Discharge Static 0.17 in. H2O Suction Static 0.26 in. H2O Filter DP (If Applicable)Not Applicable in. H2O Not Applicable in. H2O NOTES: Motor Data Efficiency The Efficiency and Power Factor are not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP. EF-2 / Photos Unit Photos Unit Photos IMAGES: EF-2 / Traverse Summary PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 EF-2 Page 25 of 29 2020-12-28 TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse EA Discharge 38x38 8.020 1247 10000 1340 10747 Not Applicable Totals 10000 10747 PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 EF-2 Page 26 of 29 2020-12-28 Design Actual %Design Actual % EF-3* UNIT DATA Equipment Location Bathroom Unit Serial No.00325M Area Served Bathroom Performed By KG/CS Unit Manufacturer Whisper Green Pass/Fail Pass Unit Model No.FV-0511VK2 Date of Test 12/24/20 TEST DATA Total Unit CFM (MAX)50 CFM 54 CFM 108 Fan RPM Direct Drive RPM Direct Drive RPM Outlet CFM Not Applicable CFM Not Applicable CFM Operational Static Press.Not Applicable in. H2O Total Unit CFM (MIN)Not Applicable CFM Not Applicable CFM Hertz at Design CFM Not Applicable HZ MOTOR DATA Motor Manufacturer Panasonic Power Factor 0.850 Motor Frame Not Listed Plate Volts 120 Volts Motor RPM Not Listed RPM Actual Volts 121 Volts Motor Horsepower Not Listed HP Plate Amps 0.27 Amps Motor Phase 1 Actual Amps 0.13 Amps Motor Hertz 60 Hz Starter Heater CB Service Factor Not Listed Brake Horsepower 0.015 Efficiency 0.850 DRIVE DATA Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in Motor Bore Direct Drive in No. of Belts Direct Drive Motor Sheave % Closed Direct Drive %Belt Size Direct Drive Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 EF-3*Page 27 of 29 2020-12-28 Design Actual %Design Actual % TEST PRESSURES Total Static Pressure Not Listed in. H2O 0.15 in. H2O Discharge Static 0.10 in. H2O Suction Static 0.05 in. H2O Filter DP (If Applicable)Not Applicable in. H2O Not Applicable in. H2O NOTES: Motor Data Efficiency The Efficiency and Power Factor are not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP. EF-3* / Photos* Unit Photos Unit Photos IMAGES: PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 EF-3*Page 28 of 29 2020-12-28 EF-3* / Traverse Summary TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*EA Disc 4 0.087 575 50 620 54 0.160 Totals 50 54 PROJECT NUMBER: 20-551 CONTACT: Kevin Greenwood / Jon Aguilar LOCATION: Queensbury Highway Department New Vehicle Garage 742 Bay Road Queensbury NY 12801 EF-3*Page 29 of 29 2020-12-28