TAB Report 12-28-20 20-551FIRM:
MTI - Mechanical Testing, Inc.
4 Chelsea Place, Suite 102
Clifton Park NY 12065
PHONE:
(518) 450-7292
FAX:
(518) 450-7295
CUSTOMER:
BPI Piping
PROJECT #:
20-551
PROJECT ADDRESS:
742 Bay Road
Queensbury NY 12801
DATE:
2020-12-28
CONTACT:
Kevin Greenwood / Jon Aguilar
Queensbury Highway Department New
Vehicle Garage
4 Chelsea Pl, Suite 102 Clifton Park, NY 12065 Phone: 518-450-7292 Fax: 518-450-7295 Design Review - Commissioning - Fire Life Safety - Test And Balance - ASHRAE 110 -Drone Sales/Inspections
Terms and Abbreviations
ACH- Air Changes per Hour
AHU- Air Handling Unit
AK- Free Area of Duct
AVG- Average
BHP- Brake Horsepower
BV- Ball Valve (Shut Off Valve)
CB- Circuit Breaker
CBV- Calibrated Balance Valve
CD-Ceiling Diffuser
CFM- Cubic Feet per Minute
CHWS- Chilled Water System
CRAC- Computer Room Air Conditioner
CS- Circuit Setter
CUH- Cabinet Unit Heater
DAT- Discharge Air Temperature
DD- Direct Drive (motor)
Des.- Design
Disch.- Discharge
DNE- Does Not Exist
DP- Discharge Pressure of Pump/Pressure Drop
EA- Exhaust Air
EAV- Exhaust Air Valve
EAT- Entering Air Temperature
EF- Exhaust Fan
EG- Exhaust Grille
ERU- Energy Recovery Unit
E.S.P.- External Static Pressure
EWT- Entering Water Temperature
FCU- Fan Coil Unit
FD- Fire Damper
FLA- Full Load Amperage
Flow Coeff. –Correction Factor for Flow to VAV
Flow Hood- Instrument that measures airflow
FPM- Feet per Minute GPM- Gallons Per Minute
HEPA- High Efficiency Particulate Arrestance
HP- Horsepower
HVAC- Heating Ventilation and Air Conditioning
HWS- Hot Water System
HX- Heat Exchanger
Hz- Hertz
In.- Inches
In. w.g.- Inches of Water Gauge
ISDFT- Insufficient Straight Duct for Traverse
Kfactor- Correction factor to the free area
needed to calculate CFM.
LAT- leaving Air Temperature
LWT- Leaving Water Temperature
MAU- Make Up Air Handling Unit
MAX- Maximum set point/flow
MIN- Minimum set point/flow
NI-Not Installed
NIS-Not in Scope
O/A- Outside Air
OBD- Opposed Blade Damper
OD- Outside Diameter Measurement of Sheave
PH- Phase
PSI- Pounds per Square Inch
RA- Return Air
RAT- Return Air Temperature
RF- Return Fan
RHC- Reheat Coil
RPM- Revolutions per Minute
RTU- Roof Top Unit
SA- Supply Air
SAV- Supply Air Valve
SAT- Supply Air Temperature
S.F.- Service Factor
SF- Supply Fan
SP- Suction Pressure of Pump/ Static Pressure
Sq. ft.- Square Feet
TAB- Test, Adjust and Balance
TDV- Triple Duty Valve
TP- Thermally Protected
TSP- Total Static Pressure
UH- Unit Heater
V- Volts
VAV- Variable Air Volume Box
VD- Volume Damper
VFD- Variable Frequency Drive
VVT- Variable Volume Terminal
WC- Water Column
3
3
5
5
9
13
17
21
21
24
27
Table of Contents
*Instruments Used
Instruments Used
HV*
HV-1*
HV-2*
HV-3*
HV-4*
Exhaust Fan
EF-1
EF-2
EF-3*
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
Page 2 of 29 2020-12-28
*Instruments Used
Instruments Used
AIR
Manufacturer Evergreen Telemetry Calibration Date 9/16/20
Model No.S-PVF-1 Tech Name Kevin Greenwood
Serial No.1400282
WATER
Manufacturer Not Applicable Calibration Date Not Applicable
Model No.Not Applicable Tech Name Kevin Greenwood
Serial No.Not Applicable
ALTERNATE METER
Meter Type Not Applicable Serial No.Not Applicable
Manufacturer Not Applicable Calibration Date Not Applicable
Model No.Not Applicable
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
Instruments Used Page 3 of 29 2020-12-28
Air
IMAGES:
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
Instruments Used Page 4 of 29 2020-12-28
Design Actual %Design Actual %
HV*
HV-1*
UNIT DATA
Equipment Location Garage Filter Type Wire Mesh
Area Served Garage Filter Quantity 4,4
Unit Manufacturer Captiveaire Filter Size 20x30x2 in
Unit Model No.A3-D.1000-G18 Performed By KG/CS
Unit Serial No.Not Listed Pass/Fail Pass
HV-1* / Test Data*
TEST DATA
Total Unit CFM 5555 CFM 6028 CFM 109 O/A Damper Position 100 %
Outlet CFM Not Applicable
CFM
Not Applicable
CFM R/A Damper Position Not Applicable %
Outside Air CFM 5555 CFM 6028 CFM 109 Discharge Air temp Not Applicable deg F
Return Air CFM Not Applicable
CFM
Not Applicable
CFM Hertz at Design CFM Not Applicable Hz
Fan RPM 750 RPM 722 RPM 96 Test Date 12/24/20
HV-1* / Motor Data*
MOTOR DATA
Motor Manufacturer Westinghouse Volts T1 210 Volts
Motor Frame 182T Volts T2 210 Volts
Motor RPM 1755 RPM Volts T3 209 Volts
Motor Horsepower 3.0 HP Plate Amps 8.6 Amps
Motor Phase 3 Amps T1 7.70 Amps
Motor Hertz 60 Hz Amps T2 7.60 Amps
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-1*Page 5 of 29 2020-12-28
Design Actual %Design Actual %
Service Factor 1.15 Amps T3 7.70 Amps
Efficiency 0.895 Starter Heater CB
Power Factor 0.875 Brake Horsepower 2.937
Plate Volts 208 Volts
MOTOR DATA
HV-1* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size 2VP42 Fan Bore 1 3/16 in
Motor Bore 1 1/8 in No. of Belts 2
Motor Sheave % Closed 75 %Belt Size BX60
Fan Sheave/OD Size BK90H Center Distance 21 in
HV-1* / Test Pressures*
TEST PRESSURES
Total Static Pressure .71 in. H2O 0.92 in. H2O 130 Pre-Filter DP Not Listed in.
H2O 0.02 in. H2O
External Static Pressure .50 in. H2O 0.15 in. H2O 30 Pre-Heat DP Not Listed in.
H2O 0.77 in. H2O
Discharge Static 0.05 in. H2O Cooling Coil DP Not Applicable
in. H2O
Not Applicable
in. H2O
Suction Static 0.87 in. H2O Static at Furthest VAV Not Applicable in. H2O
Mix Box/Pre-Filter SP Not Listed in.
H2O 0.10 in. H2O Sys. Operational Static Not Applicable in. H2O
HV-1* / Photos*
PHOTO'S
Unit Photo
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-1*Page 6 of 29 2020-12-28
Photo's
IMAGES:
HV-1* / Static Profile*
STATIC PROFILE
Static Profile
IMAGES:
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-1*Page 7 of 29 2020-12-28
HV-1* / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*SA Discharge 22x20 3.060 1815 5555 1970 6028 Not Applicable
Totals 5555 6028
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-1*Page 8 of 29 2020-12-28
Design Actual %Design Actual %
HV-2*
UNIT DATA
Equipment Location Garage Filter Type Wire Mesh
Area Served Garage Filter Quantity 4,4
Unit Manufacturer Captiveaire Filter Size 20x30x2, 20x25x2 in
Unit Model No.A3-D.1000-G18 Performed By KG/CS
Unit Serial No.Not Listed Pass/Fail Pass
HV-2* / Test Data*
TEST DATA
Total Unit CFM 5555 CFM 5266 CFM 95 O/A Damper Position 100 %
Outlet CFM Not Applicable
CFM
Not Applicable
CFM R/A Damper Position Not Applicable %
Outside Air CFM 5555 CFM 5266 CFM 95 Discharge Air temp Not Applicable deg F
Return Air CFM Not Applicable
CFM
Not Applicable
CFM Hertz at Design CFM Not Applicable Hz
Fan RPM 750 RPM 717 RPM 96 Test Date 12/24/20
HV-2* / Motor Data*
MOTOR DATA
Motor Manufacturer Westinghouse Volts T1 210 Volts
Motor Frame 182T Volts T2 210 Volts
Motor RPM 1755 RPM Volts T3 210 Volts
Motor Horsepower 3.0 HP Plate Amps 8.6 Amps
Motor Phase 3 Amps T1 7.50 Amps
Motor Hertz 60 Hz Amps T2 7.80 Amps
Service Factor 1.15 Amps T3 7.80 Amps
Efficiency 0.895 Starter Heater CB
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-2*Page 9 of 29 2020-12-28
Design Actual %Design Actual %
Power Factor 0.875 Brake Horsepower 2.860
Plate Volts 208 Volts
MOTOR DATA
HV-2* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size 2VP42 Fan Bore 1 3/16 in
Motor Bore 1 1/8 in No. of Belts 2
Motor Sheave % Closed 75 %Belt Size BX60
Fan Sheave/OD Size BK90H Center Distance 21 in
HV-2* / Test Pressures*
TEST PRESSURES
Total Static Pressure .71 in. H2O 1.53 in. H2O 215 Pre-Filter DP Not Listed in.
H2O 0.03 in. H2O
External Static Pressure .50 in. H2O 0.37 in. H2O 74 Pre-Heat DP Not Listed in.
H2O 1.19 in. H2O
Discharge Static 0.04 in. H2O Cooling Coil DP Not Applicable
in. H2O
Not Applicable
in. H2O
Suction Static 1.49 in. H2O Static at Furthest VAV Not Applicable in. H2O
Mix Box/Pre-Filter SP Not Listed in.
H2O 0.30 in. H2O Sys. Operational Static Not Applicable in. H2O
HV-2* / Photos
PHOTO'S
Unit Photo
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-2*Page 10 of 29 2020-12-28
Photo's
IMAGES:
HV-2* / Static Profile*
STATIC PROFILE
Static Profile
IMAGES:
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-2*Page 11 of 29 2020-12-28
HV-2* / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*SA Discharge 22x20 3.060 1815 5555 1721 5266 Not Applicable
Totals 5555 5266
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-2*Page 12 of 29 2020-12-28
Design Actual %Design Actual %
HV-3*
UNIT DATA
Equipment Location Garage Filter Type Wire Mesh
Area Served Garage Filter Quantity 4,4
Unit Manufacturer Captiveaire Filter Size 20x30x2 in
Unit Model No.A3-D.1000-G18 Performed By KG/CS
Unit Serial No.Not Listed Pass/Fail Pass
HV-3* / Test Data*
TEST DATA
Total Unit CFM 5555 CFM 5272 CFM 95 O/A Damper Position 100 %
Outlet CFM Not Applicable
CFM
Not Applicable
CFM R/A Damper Position Not Applicable %
Outside Air CFM 5555 CFM 5272 CFM 95 Discharge Air temp Not Applicable deg F
Return Air CFM Not Applicable
CFM
Not Applicable
CFM Hertz at Design CFM Not Applicable Hz
Fan RPM 750 RPM 717 RPM 96 Test Date 12/24/20
HV-3* / Motor Data*
MOTOR DATA
Motor Manufacturer Westinghouse Volts T1 209 Volts
Motor Frame 182T Volts T2 210 Volts
Motor RPM 1755 RPM Volts T3 210 Volts
Motor Horsepower 3.0 HP Plate Amps 8.6 Amps
Motor Phase 3 Amps T1 8.00 Amps
Motor Hertz 60 Hz Amps T2 7.80 Amps
Service Factor 1.15 Amps T3 8.00 Amps
Efficiency 0.895 Starter Heater CB
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-3*Page 13 of 29 2020-12-28
Design Actual %Design Actual %
Power Factor 0.875 Brake Horsepower 3.037
Plate Volts 208 Volts
MOTOR DATA
HV-3* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size 2VP42 Fan Bore 1 3/16 in
Motor Bore 1 1/8 in No. of Belts 2
Motor Sheave % Closed 75 %Belt Size BX60
Fan Sheave/OD Size BK90H Center Distance 21 in
HV-3* / Test Pressures*
TEST PRESSURES
Total Static Pressure .71 in. H2O 1.55 in. H2O 218 Pre-Filter DP Not Listed in.
H2O 0.02 in. H2O
External Static Pressure .50 in. H2O 0.45 in. H2O 90 Pre-Heat DP Not Listed in.
H2O 0.71 in. H2O
Discharge Static 0.05 in. H2O Cooling Coil DP Not Applicable
in. H2O
Not Applicable
in. H2O
Suction Static 1.14 in. H2O Static at Furthest VAV Not Applicable in. H2O
Mix Box/Pre-Filter SP Not Listed in.
H2O 0.41 in. H2O Sys. Operational Static Not Applicable in. H2O
HV-3* / Photos*
PHOTO'S
Unit Photo
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-3*Page 14 of 29 2020-12-28
Photo's
IMAGES:
HV-3* / Static Profile*
STATIC PROFILE
Static Profile
IMAGES:
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-3*Page 15 of 29 2020-12-28
HV-3* / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*SA Discharge 20x22 3.060 1815 5555 1723 5272 Not Applicable
Totals 5555 5272
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-3*Page 16 of 29 2020-12-28
Design Actual %Design Actual %
HV-4*
UNIT DATA
Equipment Location Garage Filter Type Wire Mesh
Area Served Garage Filter Quantity 4,4
Unit Manufacturer Captiveaire Filter Size 20x30x2 in
Unit Model No.A3-D.1000-G18 Performed By KG/CS
Unit Serial No.Not Listed Pass/Fail Pass
HV-4* / Test Data*
TEST DATA
Total Unit CFM 5555 CFM 5370 CFM 97 O/A Damper Position 100 %
Outlet CFM Not Applicable
CFM
Not Applicable
CFM R/A Damper Position Not Applicable %
Outside Air CFM 5555 CFM 5370 CFM 97 Discharge Air temp Not Applicable deg F
Return Air CFM Not Applicable
CFM
Not Applicable
CFM Hertz at Design CFM Not Applicable Hz
Fan RPM 750 RPM 625 RPM 83 Test Date 12/24/20
HV-4* / Motor Data*
MOTOR DATA
Motor Manufacturer Westinghouse Volts T1 210 Volts
Motor Frame 182T Volts T2 210 Volts
Motor RPM 1755 RPM Volts T3 209 Volts
Motor Horsepower 3.0 HP Plate Amps 8.6 Amps
Motor Phase 3 Amps T1 7.00 Amps
Motor Hertz 60 Hz Amps T2 6.80 Amps
Service Factor 1.15 Amps T3 6.80 Amps
Efficiency 0.895 Starter Heater CB
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-4*Page 17 of 29 2020-12-28
Design Actual %Design Actual %
Power Factor 0.875 Brake Horsepower 2.670
Plate Volts 208 Volts
MOTOR DATA
HV-4* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size 2VP42 Fan Bore 1 3/16 in
Motor Bore 1 1/8 in No. of Belts 2
Motor Sheave % Closed 0 %Belt Size BX90H
Fan Sheave/OD Size BK90H Center Distance 21 in
HV-4* / Test Pressures*
TEST PRESSURES
Total Static Pressure .71 in. H2O 1.10 in. H2O 155 Pre-Filter DP Not Listed in.
H2O 0.09 in. H2O
External Static Pressure .50 in. H2O 0.30 in. H2O 60 Pre-Heat DP Not Listed in.
H2O 0.74 in. H2O
Discharge Static 0.05 in. H2O Cooling Coil DP Not Applicable
in. H2O
Not Applicable
in. H2O
Suction Static 0.96 in. H2O Static at Furthest VAV Not Applicable in. H2O
Mix Box/Pre-Filter SP Not Listed in.
H2O 0.25 in. H2O Sys. Operational Static Not Applicable in. H2O
HV-4* / Photos*
PHOTO'S
Unit Photo
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-4*Page 18 of 29 2020-12-28
Photo's
IMAGES:
HV-4* / Static Profile*
STATIC PROFILE
Static Profile
IMAGES:
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-4*Page 19 of 29 2020-12-28
HV-4* / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*SA Discharge 22x20 3.060 1815 5555 1755 5370 Not Applicable
Totals 5555 5370
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
HV-4*Page 20 of 29 2020-12-28
Design Actual %Design Actual %
Exhaust Fan
EF-1
UNIT DATA
Equipment Location West Wall Unit Serial No.261S179384-702
Area Served Garage Performed By KG/CS
Unit Manufacturer Cook Pass/Fail Pass
Unit Model No.30XMWH Date of Test 12/24/20
TEST DATA
Total Unit CFM (MAX)10000 CFM 10787 CFM 108 Fan RPM 1116 RPM 1120 RPM 100
Outlet CFM Not Applicable
CFM
Not Applicable
CFM Operational Static Press.Not Applicable in. H2O
Total Unit CFM (MIN)Not Applicable
CFM
Not Applicable
CFM Hertz at Design CFM Not Applicable HZ
MOTOR DATA
Motor Manufacturer Century Power Factor 0.850
Motor Frame Y145T Plate Volts 115 Volts
Motor RPM 1745 RPM Actual Volts 118 Volts
Motor Horsepower 2.0 HP Plate Amps 20.4 Amps
Motor Phase 1 Actual Amps 19.80 Amps
Motor Hertz 60 Hz Starter Heater Adj. at 22
Service Factor 1.15 Brake Horsepower 2.263
Efficiency 0.850
DRIVE DATA
Motor Sheave/OD Size MVL40B Fan Bore 1 in
Motor Bore 3/4 in No. of Belts 1
Motor Sheave % Closed 50 %Belt Size AX26
Fan Sheave/OD Size AK54 Center Distance 26 in
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
EF-1 Page 21 of 29 2020-12-28
Design Actual %Design Actual %
TEST PRESSURES
Total Static Pressure .50 in. H2O 0.44 in. H2O 88 Discharge Static 0.17 in. H2O
Suction Static 0.27 in. H2O Filter DP (If Applicable)Not Applicable
in. H2O
Not Applicable
in. H2O
NOTES:
Motor Data
Efficiency
The Efficiency and Power Factor are not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
EF-1 / Photos*
Unit Photos Unit Photos
IMAGES:
EF-1 / Traverse Summary
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
EF-1 Page 22 of 29 2020-12-28
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*EA Discharge 38x38 8.020 1247 10000 1345 10787 Not Applicable
Totals 10000 10787
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
EF-1 Page 23 of 29 2020-12-28
Design Actual %Design Actual %
EF-2
UNIT DATA
Equipment Location West Wall Unit Serial No.261S179384-701
Area Served Garage Performed By KG/CS
Unit Manufacturer Cook Pass/Fail Pass
Unit Model No.30XMWH Date of Test 12/24/20
TEST DATA
Total Unit CFM (MAX)10000 CFM 10747 CFM 107 Fan RPM 1116 RPM 1118 RPM 100
Outlet CFM Not Applicable
CFM
Not Applicable
CFM Operational Static Press.Not Applicable in. H2O
Total Unit CFM (MIN)Not Applicable
CFM
Not Applicable
CFM Hertz at Design CFM Not Applicable HZ
MOTOR DATA
Motor Manufacturer Century Power Factor 0.850
Motor Frame Y145T Plate Volts 115 Volts
Motor RPM 1725 RPM Actual Volts 118 Volts
Motor Horsepower 2.0 HP Plate Amps 20.4 Amps
Motor Phase 1 Actual Amps 19.60 Amps
Motor Hertz 60 Hz Starter Heater Adj at 22
Service Factor 1.15 Brake Horsepower 2.240
Efficiency 0.850
DRIVE DATA
Motor Sheave/OD Size MVL40B Fan Bore 1 in
Motor Bore 3/4 in No. of Belts 1
Motor Sheave % Closed 50 %Belt Size AX26
Fan Sheave/OD Size AK54 Center Distance 26 in
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
EF-2 Page 24 of 29 2020-12-28
Design Actual %Design Actual %
TEST PRESSURES
Total Static Pressure .50 in. H2O 0.43 in. H2O 86 Discharge Static 0.17 in. H2O
Suction Static 0.26 in. H2O Filter DP (If Applicable)Not Applicable
in. H2O
Not Applicable
in. H2O
NOTES:
Motor Data
Efficiency
The Efficiency and Power Factor are not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
EF-2 / Photos
Unit Photos Unit Photos
IMAGES:
EF-2 / Traverse Summary
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
EF-2 Page 25 of 29 2020-12-28
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse EA Discharge 38x38 8.020 1247 10000 1340 10747 Not Applicable
Totals 10000 10747
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
EF-2 Page 26 of 29 2020-12-28
Design Actual %Design Actual %
EF-3*
UNIT DATA
Equipment Location Bathroom Unit Serial No.00325M
Area Served Bathroom Performed By KG/CS
Unit Manufacturer Whisper Green Pass/Fail Pass
Unit Model No.FV-0511VK2 Date of Test 12/24/20
TEST DATA
Total Unit CFM (MAX)50 CFM 54 CFM 108 Fan RPM Direct Drive
RPM
Direct Drive
RPM
Outlet CFM Not Applicable
CFM
Not Applicable
CFM Operational Static Press.Not Applicable in. H2O
Total Unit CFM (MIN)Not Applicable
CFM
Not Applicable
CFM Hertz at Design CFM Not Applicable HZ
MOTOR DATA
Motor Manufacturer Panasonic Power Factor 0.850
Motor Frame Not Listed Plate Volts 120 Volts
Motor RPM Not Listed RPM Actual Volts 121 Volts
Motor Horsepower Not Listed HP Plate Amps 0.27 Amps
Motor Phase 1 Actual Amps 0.13 Amps
Motor Hertz 60 Hz Starter Heater CB
Service Factor Not Listed Brake Horsepower 0.015
Efficiency 0.850
DRIVE DATA
Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in
Motor Bore Direct Drive in No. of Belts Direct Drive
Motor Sheave % Closed Direct Drive %Belt Size Direct Drive
Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
EF-3*Page 27 of 29 2020-12-28
Design Actual %Design Actual %
TEST PRESSURES
Total Static Pressure Not Listed in.
H2O 0.15 in. H2O Discharge Static 0.10 in. H2O
Suction Static 0.05 in. H2O Filter DP (If Applicable)Not Applicable
in. H2O
Not Applicable
in. H2O
NOTES:
Motor Data
Efficiency
The Efficiency and Power Factor are not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
EF-3* / Photos*
Unit Photos Unit Photos
IMAGES:
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
EF-3*Page 28 of 29 2020-12-28
EF-3* / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*EA Disc 4 0.087 575 50 620 54 0.160
Totals 50 54
PROJECT NUMBER:
20-551
CONTACT:
Kevin Greenwood / Jon Aguilar
LOCATION:
Queensbury Highway Department New Vehicle Garage
742 Bay Road
Queensbury NY 12801
EF-3*Page 29 of 29 2020-12-28