TAB Report 12-30-20 20-250FIRM:
MTI - Mechanical Testing, Inc.
4 Chelsea Place, Suite 102
Clifton Park NY 12065
PHONE:
518) 450-7292
FAX:
518) 450-7295
CUSTOMER:
Hilltop Construction
PROJECT #:
20-250
PROJECT ADDRESS:
160 Aviation Road
Queensbury NY 12804
DATE:
2020-12-30
CONTACT:
Rich Wyckoff
United Cerebral Palsy Association-New
Respite Care Facility
4 Chelsea Pl, Suite 102 Clifton Park, NY 12065
Phone: 518-450-7292 Fax: 518-450-7295
Design Review - Commissioning - Fire Life Safety - Test And Balance - ASHRAE 110 -Drone Sales/Inspections
Terms and Abbreviations
ACH- Air Changes per Hour
AHU- Air Handling Unit
AK- Free Area of Duct
AVG- Average
BHP- Brake Horsepower
BV- Ball Valve (Shut Off Valve)
CB- Circuit Breaker
CBV- Calibrated Balance Valve
CD-Ceiling Diffuser
CFM- Cubic Feet per Minute
CHWS- Chilled Water System
CRAC- Computer Room Air Conditioner
CS- Circuit Setter
CUH- Cabinet Unit Heater
DAT- Discharge Air Temperature
DD- Direct Drive (motor)
Des.- Design
Disch.- Discharge
DNE- Does Not Exist
DP- Discharge Pressure of Pump/Pressure Drop
EA- Exhaust Air
EAV- Exhaust Air Valve
EAT- Entering Air Temperature
EF- Exhaust Fan
EG- Exhaust Grille
ERU- Energy Recovery Unit
E.S.P.- External Static Pressure
EWT- Entering Water Temperature
FCU- Fan Coil Unit
FD- Fire Damper
FLA- Full Load Amperage
Flow Coeff. –Correction Factor for Flow to VAV
Flow Hood- Instrument that measures airflow
FPM- Feet per Minute GPM- Gallons Per Minute
HEPA- High Efficiency Particulate Arrestance
HP- Horsepower
HVAC- Heating Ventilation and Air Conditioning
HWS- Hot Water System
HX- Heat Exchanger
Hz- Hertz
In.- Inches
In. w.g.- Inches of Water Gauge
ISDFT- Insufficient Straight Duct for Traverse
Kfactor- Correction factor to the free area
needed to calculate CFM.
LAT- leaving Air Temperature
LWT- Leaving Water Temperature
MAU- Make Up Air Handling Unit
MAX- Maximum set point/flow
MIN- Minimum set point/flow
NI-Not Installed
NIS-Not in Scope
O/A- Outside Air
OBD- Opposed Blade Damper
OD- Outside Diameter Measurement of Sheave
PH- Phase
PSI- Pounds per Square Inch
RA- Return Air
RAT- Return Air Temperature
RF- Return Fan
RHC- Reheat Coil
RPM- Revolutions per Minute
RTU- Roof Top Unit
SA- Supply Air
SAV- Supply Air Valve
SAT- Supply Air Temperature
S.F.- Service Factor
SF- Supply Fan
SP- Suction Pressure of Pump/ Static Pressure
Sq. ft.- Square Feet
TAB- Test, Adjust and Balance
TDV- Triple Duty Valve
TP- Thermally Protected
TSP- Total Static Pressure
UH- Unit Heater
V- Volts
VAV- Variable Air Volume Box
VD- Volume Damper
VFD- Variable Frequency Drive
VVT- Variable Volume Terminal
WC- Water Column
3
3
4
4
10
15
20
20
23
26
Table of Contents
Instruments Used
Instruments Used*
AME*
F-1*
F-2*
F-3*
Exhaust Fans
EF-1
DEF-1*
DEF-2*
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
Page 2 of 28 2020-12-30
Air
Instruments Used
Instruments Used*
AIR
Manufacturer Evergreen Telemetry Calibration Date 11/19/2020
Model No.S-PVF-1 Tech Name RW
Serial No.1500191
WATER
Manufacturer Not Applicable Calibration Date Not Applicable
Model No.Not Applicable Tech Name Not Applicable
Serial No.Not Applicable
IMAGES:
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
Instruments Used*Page 3 of 28 2020-12-30
Design Actual %Design Actual %
AME*
F-1*
UNIT DATA
Equipment Location Basement Filter Type Pleated
Area Served Left Side Building Filter Quantity 1
Unit Manufacturer York Filter Size 25x16x5 in
Unit Model No.CF24AXA1A Performed By RW
Unit Serial No.W1B9599130 Pass/Fail
F-1* / Test Data*
TEST DATA
Total Unit CFM 805 CFM 785 CFM 98 O/A Damper Position See Note %
Outlet CFM 750 CFM 756 CFM 101 R/A Damper Position See Note %
Outside Air CFM 102 CFM 103 CFM 101 Discharge Air Temp 120 deg F
Return Air CFM 703 CFM 682 CFM 97 Hertz at Design CFM 60 Hz
Fan RPM Direct Drive
RPM
Direct Drive
RPM
Test Date 12/30/2020
NOTES:
Test Data
Outside Air CFM
The O/A intake is connected to a common return plenum all 3 units use. MTI traversed the O/A intake total and divided this by 3 to show the ESTIMATED O/A to each unit. The total flow at the O/A
intake is shown under the Outside Air traverse info (308 cfm)
F-1* / Motor Data*
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-1*Page 4 of 28 2020-12-30
Design Actual %Design Actual %
MOTOR DATA
Motor Manufacturer Encite Power Factor 0.850
Motor Frame Not Listed Plate Volts 115 Volts
Motor RPM Direct Drive RPM Actual Volts 120 Volts
Motor Horsepower 1/2 HP Plate Amps 6.4 Amps
Motor Phase / Hertz 1/60 Actual Amps 4.90 Amps
Service Factor 1 Starter Heater EP
Efficiency 0.850 Brake Horsepower 0.569
NOTES:
Motor Data
Efficiency
The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
F-1* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in
Motor Bore Direct Drive in No. of Belts Direct Drive
Motor Sheave % Closed Direct Drive %Belt Size Direct Drive
Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in
F-1* / Test Pressures*
TEST PRESSURES
Total Static Pressure
Not Listed in.
H2O
0.45 in. H2O Pre-Filter DP
Not Listed in.
H2O
See Note in.
H2O
External Static Pressure 0.70 in. H2O 0.45 in. H2O 64 Pre-Heat Coil DP
Not Listed in.
H2O
Not Applicable
in. H2O
Discharge Static 0.11 in. H2O Cooling Coil DP
Not Listed in.
H2O
Not Applicable
in. H2O
Suction Static 0.34 in. H2O Static at Furthest VAV Not Applicable in. H2O
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-1*Page 5 of 28 2020-12-30
Design Actual %Design Actual %
Photo's
Mix Box/Pre-Filter SP
Not Listed in.
H2O
See Note in.
H2O Sys. Operational Static Not Applicable in. H2O
TEST PRESSURES
NOTES:
Test Pressures
Mix Box/Pre-Filter SP
No where to safely drill a hole to take a static’s inside the unit. Filters and fan are back to back. Numbers provided are before filter, and after discharge.
F-1* / Photo's
PHOTO'S
Unit Photo F-1
IMAGES:
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-1*Page 6 of 28 2020-12-30
F-1* / Traverse Summary
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-1*Page 7 of 28 2020-12-30
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*F-1 SA Main 14x10 0.970 830 805 809 785 0.080
Outside Air*See Note See Note 10 0.550 See Note 560 308 0.090
Totals 805 1093
NOTES:
Traverse Summary
Outside Air* / System
The O/A intake is connected to a common return plenum all 3 units use. MTI traversed the O/A intake total and divided this by 3 to show the ESTIMATED O/A to each unit.
Outside Air* / Actual CFM
Plunger installed preset to 305 cfm per sheet metal contractor.
F-1* / Supply Outlet Summary
SUPPLY OUTLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
SO-001 114 BR-A 6 0.196 434 85 458 389 76 90
SO-002 114 BR-A 6 0.196 434 85 549 466 91 107
SO-003 110 BR-A 6 0.196 332 65 594 335 66 101
SO-004 109 BR-A 6 0.196 255 50 494 232 45 91
SO-005 108 BR-A 6 0.196 510 100 477 521 102 102
SO-006 107 BR-A 6 0.196 332 65 411 349 68 105
SO-007 103 BR-A 6 0.196 434 85 559 426 83 98
SO-008 103 BR-A 6 0.196 434 85 474 470 92 108
SO-003A 110 BR-A 6 0.196 332 65 371 321 63 97
SO-006A 110 BR-A 6 0.196 332 65 608 355 70 107
Totals 750 756
F-1* / Return Inlet Summary
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-1*Page 8 of 28 2020-12-30
RETURN INLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
RI-001 133 RRA 36x22 5.500 582 3200 434 434 2387 75
Totals 3200 2387
NOTES:
Return Inlet Summary
RI-001 / Room No.
RI-001 applies to F1/F2/F3. This represents the total return flow to the plenum. The difference between the flow at the inlets and the total return at the units can be attributed to leakage around the
units.
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-1*Page 9 of 28 2020-12-30
Design Actual %Design Actual %
F-2*
UNIT DATA
Equipment Location Basement Filter Type Pleated
Area Served Center Building Filter Quantity 1
Unit Manufacturer York Filter Size 25x16x5 in
Unit Model No.CF42CXA1A Performed By RW
Unit Serial No.W1B9654961 Pass/Fail
F-2* / Test Data*
TEST DATA
Total Unit CFM 1415 CFM 1379 CFM 97 O/A Damper Position See Note %
Outlet CFM 1380 CFM 1328 CFM 96 R/A Damper Position See Note %
Outside Air CFM 102 CFM 103 CFM 101 Discharge Air Temp 120 deg F
Return Air CFM 1313 CFM 1278 CFM 97 Hertz at Design CFM 60 Hz
Fan RPM
Direct Drive
RPM
Direct Drive
RPM
Test Date 12/29/2020
NOTES:
Test Data
Outside Air CFM
The O/A intake is connected to a common return plenum all 3 units use. MTI traversed the O/A intake total and divided this by 3 to show the ESTIMATED O/A to each unit. The total flow at the O/A
intake is shown under F-1 in the Outside Air traverse info (308 cfm)
F-2* / Motor Data*
MOTOR DATA
Motor Manufacturer Encite Power Factor 0.850
Motor Frame Not Listed Plate Volts 115 Volts
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-2*Page 10 of 28 2020-12-30
Design Actual %Design Actual %
Motor RPM 1050 RPM Actual Volts 120 Volts
Motor Horsepower 1/2 HP Plate Amps 6.6 Amps
Motor Phase / Hertz 1/60 Actual Amps 6.20 Amps
Service Factor 1 Starter Heater EP
Efficiency 0.850 Brake Horsepower 0.721
MOTOR DATA
NOTES:
Motor Data
Efficiency
The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
F-2* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in
Motor Bore Direct Drive in No. of Belts Direct Drive
Motor Sheave % Closed Direct Drive %Belt Size Direct Drive
Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in
F-2* / Test Pressures*
TEST PRESSURES
Total Static Pressure 0.60 in. H2O 0.33 in. H2O 55 Pre-Filter DP
Not Listed in.
H2O
See Note in.
H2O
External Static Pressure
Not Listed in.
H2O
0.33 in. H2O Pre-Heat Coil DP
Not Listed in.
H2O
See Note in.
H2O
Discharge Static 0.09 in. H2O Cooling Coil DP
Not Listed in.
H2O
Not Applicable
in. H2O
Suction Static 0.24 in. H2O Static at Furthest VAV Not Applicable in. H2O
Mix Box/Pre-Filter SP
Not Listed in.
H2O
See Note in.
H2O
Sys. Operational Static Not Applicable in. H2O
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-2*Page 11 of 28 2020-12-30
Photo's
NOTES:
Test Pressures
Mix Box/Pre-Filter SP
No where to safely drill a hole to take a static’s inside the unit. Filters and fan are back to back. Numbers provided are before filter, and after discharge.
F-2* / Photo's
PHOTO'S
Unit Photo F-2
IMAGES:
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-2*Page 12 of 28 2020-12-30
F-2* / Traverse Summary
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-2*Page 13 of 28 2020-12-30
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*F-2 SA Main 20x20 2.780 509 1415 496 1379 0.100
Totals 1415 1379
F-2* / Supply Outlet Summary
SUPPLY OUTLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
SO-001 115 BR-A 7 0.270 556 150 347 507 137 91
SO-002 115 BR-A 7 0.270 556 150 399 501 135 90
SO-003 116 BR-A 6 0.196 510 100 490 495 97 97
SO-004 117 BR-A 7 0.270 519 140 356 475 128 92
SO-005 134 BR-A 6 0.196 510 100 373 501 98 98
SO-006 133 BR-A 6 0.196 510 100 441 515 101 101
SO-007 132 BR-A 6 0.196 510 100 239 500 98 98
SO-008 102 BR-A 6 0.196 434 85 298 441 86 102
SO-009 102 BR-A 6 0.196 434 85 273 428 84 99
SO-010 101 BR-A 6 0.196 510 100 260 510 100 100
SO-011 130 BR-A 6 0.196 357 70 332 363 71 102
SO-007A 132 BR-2 6 0.196 510 100 257 492 96 96
SO-005A 134 BR-A 6 0.196 510 100 374 496 97 97
Totals 1380 1328
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-2*Page 14 of 28 2020-12-30
Design Actual %Design Actual %
F-3*
UNIT DATA
Equipment Location Basement Filter Type Pleated
Area Served Bight Side Building Filter Quantity 1
Unit Manufacturer York Filter Size 25x16x5 in
Unit Model No.CF30BXA1A Performed By RW
Unit Serial No.W2F0914816 Pass/Fail
F-3* / Test Data*
TEST DATA
Total Unit CFM 1015 CFM 1033 CFM 102 O/A Damper Position See Note %
Outlet CFM 980 CFM 983 CFM 100 R/A Damper Position See Note %
Outside Air CFM 103 CFM 103 CFM 100 Discharge Air Temp 120 deg F
Return Air CFM 912 CFM 930 CFM 102 Hertz at Design CFM 60 Hz
Fan RPM
Not Listed
RPM
Direct Drive
RPM
Test Date 12/29/2020
NOTES:
Test Data
Outside Air CFM
The O/A intake is connected to a common return plenum all 3 units use. MTI traversed the O/A intake total and divided this by 3 to show the ESTIMATED O/A to each unit. The total flow at the O/A
intake is shown under F-1 in the Outside Air traverse info (308 cfm)
F-3* / Motor Data*
MOTOR DATA
Motor Manufacturer EGenteq Ensite Power Factor 0.850
Motor Frame Not Listed Plate Volts 115 Volts
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-3*Page 15 of 28 2020-12-30
Design Actual %Design Actual %
Motor RPM Direct Drive RPM Actual Volts 120 Volts
Motor Horsepower 1/2 HP Plate Amps 6.4 Amps
Motor Phase / Hertz 1/60 Actual Amps 5.70 Amps
Service Factor 1 Starter Heater EP
Efficiency 0.850 Brake Horsepower 0.662
MOTOR DATA
NOTES:
Motor Data
Efficiency
The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
F-3* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in
Motor Bore Direct Drive in No. of Belts Direct Drive
Motor Sheave % Closed Direct Drive %Belt Size Direct Drive
Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in
F-3* / Test Pressures*
TEST PRESSURES
Total Static Pressure 0.60 in. H2O 0.5 in. H2O 83 Pre-Filter DP
Not Listed in.
H2O
See Note in.
H2O
External Static Pressure
Not Listed in.
H2O
0.5 in. H2O Pre-Heat Coil DP
Not Listed in.
H2O
See Note in.
H2O
Discharge Static 0.35 in. H2O Cooling Coil DP
Not Listed in.
H2O
See Note in.
H2O
Suction Static 0. in. H2O Static at Furthest VAV Not Applicable in. H2O
Mix Box/Pre-Filter SP
Not Listed in.
H2O
See Note in.
H2O
Sys. Operational Static Not Applicable in. H2O
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-3*Page 16 of 28 2020-12-30
Photo's
NOTES:
Test Pressures
Mix Box/Pre-Filter SP
No where to safely drill a hole to take a static’s inside the unit. Filters and fan are back to back. Numbers provided are before filter, and after discharge.
F-3* / Photo's
PHOTO'S
Unit Photo F-3
IMAGES:
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-3*Page 17 of 28 2020-12-30
F-3* / Traverse Summary
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-3*Page 18 of 28 2020-12-30
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*F-1 SA Main 18x10 1.250 812 1015 826 1033 0.350
Totals 1015 1033
F-3* / Supply Outlet Summary
SUPPLY OUTLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
SO-001 118 BR-A 7 0.270 444 120 412 450 122 101
SO-002 118 BR-A 7 0.270 444 120 453 445 120 100
SO-003 122 BR-A 6 0.196 383 75 313 380 74 99
SO-004 123 BR-A 6 0.196 510 100 522 511 100 100
SO-005 124 BR-A 6 0.196 255 50 410 254 50 100
SO-006 125 BR-A 6 0.196 383 75 510 383 75 100
SO-007 129 BR-A 7 0.270 444 120 506 440 119 99
SO-008 129 BR-A 7 0.270 444 120 515 450 122 101
SO-003A BR2 6 0.196 510 100 592 509 100 100
SO-006A BR2 6 0.196 510 100 496 513 101 101
Totals 980 983
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
F-3*Page 19 of 28 2020-12-30
Design Actual %Design Actual %
Exhaust Fans
EF-1
UNIT DATA
Equipment Location Roof Unit Serial No.See Notes
Area Served General Exhaust Performed By RW
Unit Manufacturer See Notes Pass/Fail Pass (See Notes)
Unit Model No.See Notes Date of Test 12/30/2020
TEST DATA
Total Unit CFM (MAX)555 CFM 536 CFM 97 Fan RPM
Not Listed
RPM
See Notes
RPM
Outlet CFM 520 CFM 536 CFM 103 Operational Static Press.Not Applicable in. H2O
Total Unit CFM (MIN)Not Applicable
CFM
Not Applicable
CFM Hertz at Design CFM 60 HZ
MOTOR DATA
Motor Manufacturer See Notes Power Factor See Notes
Motor Frame See Notes Plate Volts 115 Volts
Motor RPM 1550 RPM Actual Volts See Notes Volts
Motor Horsepower 1/8 HP Plate Amps See Notes Amps
Motor Phase 1 Actual Amps See Notes Amps
Motor Hertz 60 Hz Starter Heater CB
Service Factor See Notes Brake Horsepower
Efficiency See Notes
DRIVE DATA
Motor Sheave/OD Size See Notes Fan Bore See Notes in
Motor Bore See Notes in No. of Belts See Notes
Motor Sheave % Closed See Notes %Belt Size See Notes
Fan Sheave/OD Size See Notes Center Distance See Notes in
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
EF-1 Page 20 of 28 2020-12-30
Design Actual %Design Actual %
TEST PRESSURES
Total Static Pressure 0.6 in. H2O
See Notes in.
H2O
Discharge Static See Notes in. H2O
Suction Static See Notes in. H2O Filter DP (If Applicable)See Notes in.
H2O
See Notes in.
H2O
NOTES:
Unit Data
Pass/Fail
The fan is installed on a pitched roof with surrounding ice, unable to safely access the info at the roof level. MTI set the fan for design flow at the inlets.
EF-1 / Photos
Unit Photos EF-1
IMAGES:
EF-1 / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*See Note See Note See Note See Note See Note See Note See Note
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
EF-1 Page 21 of 28 2020-12-30
Totals 0 0
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
NOTES:
Traverse Summary
Main Traverse* / System
No access to duct, above hard ceiling.
EF-1 / Exhaust Inlet Summary
EXHAUST INLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
EI-001 117 ER-A 8x8 1.100 45 50 154 45 50 99
EI-002 109 ER-A 8x8 1.100 45 50 143 45 50 99
EI-003 108 ER-A 8x8 1.100 91 100 87 87 96 96
EI-004 135 ER-A 8x8 1.100 91 100 146 95 105 105
EI-005 123 ER-A 8x8 1.100 91 100 28 99 109 109
EI-006 124 ER-A 8x8 1.100 45 50 110 48 53 106
EI-007 130 ER-A 8x8 1.100 64 70 70 66 73 104
Totals 520 536
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
EF-1 Page 22 of 28 2020-12-30
Design Actual %Design Actual %
DEF-1*
UNIT DATA
Equipment Location Basement Unit Serial No.Not Listed
Area Served Dryer Performed By RW
Unit Manufacturer S&P Pass/Fail Pass
Unit Model No.PV-100xps Date of Test 12/30/2020
TEST DATA
Total Unit CFM (MAX)110 CFM 112 CFM 102 Fan RPM 2500 RPM 2500 RPM 100
Outlet CFM 110 CFM 112 CFM 102 Operational Static Press.Not Applicable in. H2O
Total Unit CFM (MIN)
Not Applicable
CFM
Not Applicable
CFM
Hertz at Design CFM 60 HZ
MOTOR DATA
Motor Manufacturer S&P Power Factor 0.850
Motor Frame Inline Plate Volts 115 Volts
Motor RPM 2880 RPM Actual Volts 120 Volts
Motor Horsepower 1/8 HP Plate Amps 0.8 Amps
Motor Phase 1 Actual Amps 0.70 Amps
Motor Hertz 60 Hz Starter Heater TP
Service Factor 1 Brake Horsepower 0.081
Efficiency 0.850
DRIVE DATA
Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in
Motor Bore Direct Drive in No. of Belts Direct Drive
Motor Sheave % Closed Direct Drive %Belt Size Direct Drive
Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
DEF-1*Page 23 of 28 2020-12-30
Design Actual %Design Actual %
TEST PRESSURES
Total Static Pressure 0.5 in. H2O 0.76 in. H2O 152 Discharge Static 0.56 in. H2O
Suction Static 0.2 in. H2O Filter DP (If Applicable)
Not Applicable
in. H2O
Not Applicable
in. H2O
NOTES:
Motor Data
Efficiency
The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
DEF-1* / Photos
Unit Photos DEF-1
IMAGES:
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
DEF-1*Page 24 of 28 2020-12-30
DEF-1* / Exhaust Inlet Summary
EXHAUST INLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
EI-001 Base EA 4"O 0.087 1264 110 1290 1290 112 102
Totals 110 112
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
DEF-1*Page 25 of 28 2020-12-30
Design Actual %Design Actual %
DEF-2*
UNIT DATA
Equipment Location Basement Unit Serial No.Not Listed
Area Served Dryer Performed By RW
Unit Manufacturer S&P USA Ventilators Pass/Fail Pass
Unit Model No.PV-100xps Date of Test 12/30/2020
TEST DATA
Total Unit CFM (MAX)110 CFM 113 CFM 103 Fan RPM Not Listed
RPM
2500 RPM
Outlet CFM 110 CFM 113 CFM 103 Operational Static Press.Not Applicable in. H2O
Total Unit CFM (MIN)
Not Applicable
CFM
Not Applicable
CFM
Hertz at Design CFM 60 HZ
MOTOR DATA
Motor Manufacturer S&P Power Factor 0.850
Motor Frame Inline Plate Volts 115 Volts
Motor RPM 2500 RPM Actual Volts 120 Volts
Motor Horsepower See Note HP Plate Amps 0.8 Amps
Motor Phase 1 Actual Amps 0.70 Amps
Motor Hertz 60 Hz Starter Heater TP
Service Factor 1 Brake Horsepower 0.081
Efficiency 0.850
DRIVE DATA
Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in
Motor Bore Direct Drive in No. of Belts Direct Drive
Motor Sheave % Closed Direct Drive %Belt Size Direct Drive
Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
DEF-2*Page 26 of 28 2020-12-30
Design Actual %Design Actual %
TEST PRESSURES
Total Static Pressure 0.5 in. H2O 078 in. H2O 15600 Discharge Static 0.58 in. H2O
Suction Static 0.2 in. H2O Filter DP (If Applicable)
Not Applicable
in. H2O
Not Applicable
in. H2O
NOTES:
Motor Data
Efficiency
The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
DEF-2* / Photos*
Unit Photos DEF-2
IMAGES:
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
DEF-2*Page 27 of 28 2020-12-30
DEF-2* / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Main Traverse*DEF-2 Main 4 0.087 1264 110 1298 113 0.200
Totals 110 113
DEF-2* / Exhaust Inlet Summary
EXHAUST INLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
EI-001 Base EA 4'O 0.087 1264 110 See Note 1298 113 103
Totals 110 113
PROJECT NUMBER:
20-250
CONTACT:
Rich Wyckoff
LOCATION:
United Cerebral Palsy Association-New Respite Care
Facility
160 Aviation Road
Queensbury NY 12804
DEF-2*Page 28 of 28 2020-12-30