TAB Report 12-30-20 20-250FIRM: MTI - Mechanical Testing, Inc. 4 Chelsea Place, Suite 102 Clifton Park NY 12065 PHONE: 518) 450-7292 FAX: 518) 450-7295 CUSTOMER: Hilltop Construction PROJECT #: 20-250 PROJECT ADDRESS: 160 Aviation Road Queensbury NY 12804 DATE: 2020-12-30 CONTACT: Rich Wyckoff United Cerebral Palsy Association-New Respite Care Facility 4 Chelsea Pl, Suite 102 Clifton Park, NY 12065 Phone: 518-450-7292 Fax: 518-450-7295 Design Review - Commissioning - Fire Life Safety - Test And Balance - ASHRAE 110 -Drone Sales/Inspections Terms and Abbreviations ACH- Air Changes per Hour AHU- Air Handling Unit AK- Free Area of Duct AVG- Average BHP- Brake Horsepower BV- Ball Valve (Shut Off Valve) CB- Circuit Breaker CBV- Calibrated Balance Valve CD-Ceiling Diffuser CFM- Cubic Feet per Minute CHWS- Chilled Water System CRAC- Computer Room Air Conditioner CS- Circuit Setter CUH- Cabinet Unit Heater DAT- Discharge Air Temperature DD- Direct Drive (motor) Des.- Design Disch.- Discharge DNE- Does Not Exist DP- Discharge Pressure of Pump/Pressure Drop EA- Exhaust Air EAV- Exhaust Air Valve EAT- Entering Air Temperature EF- Exhaust Fan EG- Exhaust Grille ERU- Energy Recovery Unit E.S.P.- External Static Pressure EWT- Entering Water Temperature FCU- Fan Coil Unit FD- Fire Damper FLA- Full Load Amperage Flow Coeff. –Correction Factor for Flow to VAV Flow Hood- Instrument that measures airflow FPM- Feet per Minute GPM- Gallons Per Minute HEPA- High Efficiency Particulate Arrestance HP- Horsepower HVAC- Heating Ventilation and Air Conditioning HWS- Hot Water System HX- Heat Exchanger Hz- Hertz In.- Inches In. w.g.- Inches of Water Gauge ISDFT- Insufficient Straight Duct for Traverse Kfactor- Correction factor to the free area needed to calculate CFM. LAT- leaving Air Temperature LWT- Leaving Water Temperature MAU- Make Up Air Handling Unit MAX- Maximum set point/flow MIN- Minimum set point/flow NI-Not Installed NIS-Not in Scope O/A- Outside Air OBD- Opposed Blade Damper OD- Outside Diameter Measurement of Sheave PH- Phase PSI- Pounds per Square Inch RA- Return Air RAT- Return Air Temperature RF- Return Fan RHC- Reheat Coil RPM- Revolutions per Minute RTU- Roof Top Unit SA- Supply Air SAV- Supply Air Valve SAT- Supply Air Temperature S.F.- Service Factor SF- Supply Fan SP- Suction Pressure of Pump/ Static Pressure Sq. ft.- Square Feet TAB- Test, Adjust and Balance TDV- Triple Duty Valve TP- Thermally Protected TSP- Total Static Pressure UH- Unit Heater V- Volts VAV- Variable Air Volume Box VD- Volume Damper VFD- Variable Frequency Drive VVT- Variable Volume Terminal WC- Water Column 3 3 4 4 10 15 20 20 23 26 Table of Contents Instruments Used Instruments Used* AME* F-1* F-2* F-3* Exhaust Fans EF-1 DEF-1* DEF-2* PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 Page 2 of 28 2020-12-30 Air Instruments Used Instruments Used* AIR Manufacturer Evergreen Telemetry Calibration Date 11/19/2020 Model No.S-PVF-1 Tech Name RW Serial No.1500191 WATER Manufacturer Not Applicable Calibration Date Not Applicable Model No.Not Applicable Tech Name Not Applicable Serial No.Not Applicable IMAGES: PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 Instruments Used*Page 3 of 28 2020-12-30 Design Actual %Design Actual % AME* F-1* UNIT DATA Equipment Location Basement Filter Type Pleated Area Served Left Side Building Filter Quantity 1 Unit Manufacturer York Filter Size 25x16x5 in Unit Model No.CF24AXA1A Performed By RW Unit Serial No.W1B9599130 Pass/Fail F-1* / Test Data* TEST DATA Total Unit CFM 805 CFM 785 CFM 98 O/A Damper Position See Note % Outlet CFM 750 CFM 756 CFM 101 R/A Damper Position See Note % Outside Air CFM 102 CFM 103 CFM 101 Discharge Air Temp 120 deg F Return Air CFM 703 CFM 682 CFM 97 Hertz at Design CFM 60 Hz Fan RPM Direct Drive RPM Direct Drive RPM Test Date 12/30/2020 NOTES: Test Data Outside Air CFM The O/A intake is connected to a common return plenum all 3 units use. MTI traversed the O/A intake total and divided this by 3 to show the ESTIMATED O/A to each unit. The total flow at the O/A intake is shown under the Outside Air traverse info (308 cfm) F-1* / Motor Data* PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-1*Page 4 of 28 2020-12-30 Design Actual %Design Actual % MOTOR DATA Motor Manufacturer Encite Power Factor 0.850 Motor Frame Not Listed Plate Volts 115 Volts Motor RPM Direct Drive RPM Actual Volts 120 Volts Motor Horsepower 1/2 HP Plate Amps 6.4 Amps Motor Phase / Hertz 1/60 Actual Amps 4.90 Amps Service Factor 1 Starter Heater EP Efficiency 0.850 Brake Horsepower 0.569 NOTES: Motor Data Efficiency The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP. F-1* / Drive Data* DRIVE DATA Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in Motor Bore Direct Drive in No. of Belts Direct Drive Motor Sheave % Closed Direct Drive %Belt Size Direct Drive Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in F-1* / Test Pressures* TEST PRESSURES Total Static Pressure Not Listed in. H2O 0.45 in. H2O Pre-Filter DP Not Listed in. H2O See Note in. H2O External Static Pressure 0.70 in. H2O 0.45 in. H2O 64 Pre-Heat Coil DP Not Listed in. H2O Not Applicable in. H2O Discharge Static 0.11 in. H2O Cooling Coil DP Not Listed in. H2O Not Applicable in. H2O Suction Static 0.34 in. H2O Static at Furthest VAV Not Applicable in. H2O PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-1*Page 5 of 28 2020-12-30 Design Actual %Design Actual % Photo's Mix Box/Pre-Filter SP Not Listed in. H2O See Note in. H2O Sys. Operational Static Not Applicable in. H2O TEST PRESSURES NOTES: Test Pressures Mix Box/Pre-Filter SP No where to safely drill a hole to take a static’s inside the unit. Filters and fan are back to back. Numbers provided are before filter, and after discharge. F-1* / Photo's PHOTO'S Unit Photo F-1 IMAGES: PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-1*Page 6 of 28 2020-12-30 F-1* / Traverse Summary PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-1*Page 7 of 28 2020-12-30 TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*F-1 SA Main 14x10 0.970 830 805 809 785 0.080 Outside Air*See Note See Note 10 0.550 See Note 560 308 0.090 Totals 805 1093 NOTES: Traverse Summary Outside Air* / System The O/A intake is connected to a common return plenum all 3 units use. MTI traversed the O/A intake total and divided this by 3 to show the ESTIMATED O/A to each unit. Outside Air* / Actual CFM Plunger installed preset to 305 cfm per sheet metal contractor. F-1* / Supply Outlet Summary SUPPLY OUTLET SUMMARY Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design SO-001 114 BR-A 6 0.196 434 85 458 389 76 90 SO-002 114 BR-A 6 0.196 434 85 549 466 91 107 SO-003 110 BR-A 6 0.196 332 65 594 335 66 101 SO-004 109 BR-A 6 0.196 255 50 494 232 45 91 SO-005 108 BR-A 6 0.196 510 100 477 521 102 102 SO-006 107 BR-A 6 0.196 332 65 411 349 68 105 SO-007 103 BR-A 6 0.196 434 85 559 426 83 98 SO-008 103 BR-A 6 0.196 434 85 474 470 92 108 SO-003A 110 BR-A 6 0.196 332 65 371 321 63 97 SO-006A 110 BR-A 6 0.196 332 65 608 355 70 107 Totals 750 756 F-1* / Return Inlet Summary PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-1*Page 8 of 28 2020-12-30 RETURN INLET SUMMARY Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design RI-001 133 RRA 36x22 5.500 582 3200 434 434 2387 75 Totals 3200 2387 NOTES: Return Inlet Summary RI-001 / Room No. RI-001 applies to F1/F2/F3. This represents the total return flow to the plenum. The difference between the flow at the inlets and the total return at the units can be attributed to leakage around the units. PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-1*Page 9 of 28 2020-12-30 Design Actual %Design Actual % F-2* UNIT DATA Equipment Location Basement Filter Type Pleated Area Served Center Building Filter Quantity 1 Unit Manufacturer York Filter Size 25x16x5 in Unit Model No.CF42CXA1A Performed By RW Unit Serial No.W1B9654961 Pass/Fail F-2* / Test Data* TEST DATA Total Unit CFM 1415 CFM 1379 CFM 97 O/A Damper Position See Note % Outlet CFM 1380 CFM 1328 CFM 96 R/A Damper Position See Note % Outside Air CFM 102 CFM 103 CFM 101 Discharge Air Temp 120 deg F Return Air CFM 1313 CFM 1278 CFM 97 Hertz at Design CFM 60 Hz Fan RPM Direct Drive RPM Direct Drive RPM Test Date 12/29/2020 NOTES: Test Data Outside Air CFM The O/A intake is connected to a common return plenum all 3 units use. MTI traversed the O/A intake total and divided this by 3 to show the ESTIMATED O/A to each unit. The total flow at the O/A intake is shown under F-1 in the Outside Air traverse info (308 cfm) F-2* / Motor Data* MOTOR DATA Motor Manufacturer Encite Power Factor 0.850 Motor Frame Not Listed Plate Volts 115 Volts PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-2*Page 10 of 28 2020-12-30 Design Actual %Design Actual % Motor RPM 1050 RPM Actual Volts 120 Volts Motor Horsepower 1/2 HP Plate Amps 6.6 Amps Motor Phase / Hertz 1/60 Actual Amps 6.20 Amps Service Factor 1 Starter Heater EP Efficiency 0.850 Brake Horsepower 0.721 MOTOR DATA NOTES: Motor Data Efficiency The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP. F-2* / Drive Data* DRIVE DATA Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in Motor Bore Direct Drive in No. of Belts Direct Drive Motor Sheave % Closed Direct Drive %Belt Size Direct Drive Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in F-2* / Test Pressures* TEST PRESSURES Total Static Pressure 0.60 in. H2O 0.33 in. H2O 55 Pre-Filter DP Not Listed in. H2O See Note in. H2O External Static Pressure Not Listed in. H2O 0.33 in. H2O Pre-Heat Coil DP Not Listed in. H2O See Note in. H2O Discharge Static 0.09 in. H2O Cooling Coil DP Not Listed in. H2O Not Applicable in. H2O Suction Static 0.24 in. H2O Static at Furthest VAV Not Applicable in. H2O Mix Box/Pre-Filter SP Not Listed in. H2O See Note in. H2O Sys. Operational Static Not Applicable in. H2O PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-2*Page 11 of 28 2020-12-30 Photo's NOTES: Test Pressures Mix Box/Pre-Filter SP No where to safely drill a hole to take a static’s inside the unit. Filters and fan are back to back. Numbers provided are before filter, and after discharge. F-2* / Photo's PHOTO'S Unit Photo F-2 IMAGES: PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-2*Page 12 of 28 2020-12-30 F-2* / Traverse Summary PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-2*Page 13 of 28 2020-12-30 TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*F-2 SA Main 20x20 2.780 509 1415 496 1379 0.100 Totals 1415 1379 F-2* / Supply Outlet Summary SUPPLY OUTLET SUMMARY Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design SO-001 115 BR-A 7 0.270 556 150 347 507 137 91 SO-002 115 BR-A 7 0.270 556 150 399 501 135 90 SO-003 116 BR-A 6 0.196 510 100 490 495 97 97 SO-004 117 BR-A 7 0.270 519 140 356 475 128 92 SO-005 134 BR-A 6 0.196 510 100 373 501 98 98 SO-006 133 BR-A 6 0.196 510 100 441 515 101 101 SO-007 132 BR-A 6 0.196 510 100 239 500 98 98 SO-008 102 BR-A 6 0.196 434 85 298 441 86 102 SO-009 102 BR-A 6 0.196 434 85 273 428 84 99 SO-010 101 BR-A 6 0.196 510 100 260 510 100 100 SO-011 130 BR-A 6 0.196 357 70 332 363 71 102 SO-007A 132 BR-2 6 0.196 510 100 257 492 96 96 SO-005A 134 BR-A 6 0.196 510 100 374 496 97 97 Totals 1380 1328 PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-2*Page 14 of 28 2020-12-30 Design Actual %Design Actual % F-3* UNIT DATA Equipment Location Basement Filter Type Pleated Area Served Bight Side Building Filter Quantity 1 Unit Manufacturer York Filter Size 25x16x5 in Unit Model No.CF30BXA1A Performed By RW Unit Serial No.W2F0914816 Pass/Fail F-3* / Test Data* TEST DATA Total Unit CFM 1015 CFM 1033 CFM 102 O/A Damper Position See Note % Outlet CFM 980 CFM 983 CFM 100 R/A Damper Position See Note % Outside Air CFM 103 CFM 103 CFM 100 Discharge Air Temp 120 deg F Return Air CFM 912 CFM 930 CFM 102 Hertz at Design CFM 60 Hz Fan RPM Not Listed RPM Direct Drive RPM Test Date 12/29/2020 NOTES: Test Data Outside Air CFM The O/A intake is connected to a common return plenum all 3 units use. MTI traversed the O/A intake total and divided this by 3 to show the ESTIMATED O/A to each unit. The total flow at the O/A intake is shown under F-1 in the Outside Air traverse info (308 cfm) F-3* / Motor Data* MOTOR DATA Motor Manufacturer EGenteq Ensite Power Factor 0.850 Motor Frame Not Listed Plate Volts 115 Volts PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-3*Page 15 of 28 2020-12-30 Design Actual %Design Actual % Motor RPM Direct Drive RPM Actual Volts 120 Volts Motor Horsepower 1/2 HP Plate Amps 6.4 Amps Motor Phase / Hertz 1/60 Actual Amps 5.70 Amps Service Factor 1 Starter Heater EP Efficiency 0.850 Brake Horsepower 0.662 MOTOR DATA NOTES: Motor Data Efficiency The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP. F-3* / Drive Data* DRIVE DATA Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in Motor Bore Direct Drive in No. of Belts Direct Drive Motor Sheave % Closed Direct Drive %Belt Size Direct Drive Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in F-3* / Test Pressures* TEST PRESSURES Total Static Pressure 0.60 in. H2O 0.5 in. H2O 83 Pre-Filter DP Not Listed in. H2O See Note in. H2O External Static Pressure Not Listed in. H2O 0.5 in. H2O Pre-Heat Coil DP Not Listed in. H2O See Note in. H2O Discharge Static 0.35 in. H2O Cooling Coil DP Not Listed in. H2O See Note in. H2O Suction Static 0. in. H2O Static at Furthest VAV Not Applicable in. H2O Mix Box/Pre-Filter SP Not Listed in. H2O See Note in. H2O Sys. Operational Static Not Applicable in. H2O PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-3*Page 16 of 28 2020-12-30 Photo's NOTES: Test Pressures Mix Box/Pre-Filter SP No where to safely drill a hole to take a static’s inside the unit. Filters and fan are back to back. Numbers provided are before filter, and after discharge. F-3* / Photo's PHOTO'S Unit Photo F-3 IMAGES: PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-3*Page 17 of 28 2020-12-30 F-3* / Traverse Summary PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-3*Page 18 of 28 2020-12-30 TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*F-1 SA Main 18x10 1.250 812 1015 826 1033 0.350 Totals 1015 1033 F-3* / Supply Outlet Summary SUPPLY OUTLET SUMMARY Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design SO-001 118 BR-A 7 0.270 444 120 412 450 122 101 SO-002 118 BR-A 7 0.270 444 120 453 445 120 100 SO-003 122 BR-A 6 0.196 383 75 313 380 74 99 SO-004 123 BR-A 6 0.196 510 100 522 511 100 100 SO-005 124 BR-A 6 0.196 255 50 410 254 50 100 SO-006 125 BR-A 6 0.196 383 75 510 383 75 100 SO-007 129 BR-A 7 0.270 444 120 506 440 119 99 SO-008 129 BR-A 7 0.270 444 120 515 450 122 101 SO-003A BR2 6 0.196 510 100 592 509 100 100 SO-006A BR2 6 0.196 510 100 496 513 101 101 Totals 980 983 PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 F-3*Page 19 of 28 2020-12-30 Design Actual %Design Actual % Exhaust Fans EF-1 UNIT DATA Equipment Location Roof Unit Serial No.See Notes Area Served General Exhaust Performed By RW Unit Manufacturer See Notes Pass/Fail Pass (See Notes) Unit Model No.See Notes Date of Test 12/30/2020 TEST DATA Total Unit CFM (MAX)555 CFM 536 CFM 97 Fan RPM Not Listed RPM See Notes RPM Outlet CFM 520 CFM 536 CFM 103 Operational Static Press.Not Applicable in. H2O Total Unit CFM (MIN)Not Applicable CFM Not Applicable CFM Hertz at Design CFM 60 HZ MOTOR DATA Motor Manufacturer See Notes Power Factor See Notes Motor Frame See Notes Plate Volts 115 Volts Motor RPM 1550 RPM Actual Volts See Notes Volts Motor Horsepower 1/8 HP Plate Amps See Notes Amps Motor Phase 1 Actual Amps See Notes Amps Motor Hertz 60 Hz Starter Heater CB Service Factor See Notes Brake Horsepower Efficiency See Notes DRIVE DATA Motor Sheave/OD Size See Notes Fan Bore See Notes in Motor Bore See Notes in No. of Belts See Notes Motor Sheave % Closed See Notes %Belt Size See Notes Fan Sheave/OD Size See Notes Center Distance See Notes in PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 EF-1 Page 20 of 28 2020-12-30 Design Actual %Design Actual % TEST PRESSURES Total Static Pressure 0.6 in. H2O See Notes in. H2O Discharge Static See Notes in. H2O Suction Static See Notes in. H2O Filter DP (If Applicable)See Notes in. H2O See Notes in. H2O NOTES: Unit Data Pass/Fail The fan is installed on a pitched roof with surrounding ice, unable to safely access the info at the roof level. MTI set the fan for design flow at the inlets. EF-1 / Photos Unit Photos EF-1 IMAGES: EF-1 / Traverse Summary TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*See Note See Note See Note See Note See Note See Note See Note PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 EF-1 Page 21 of 28 2020-12-30 Totals 0 0 TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure NOTES: Traverse Summary Main Traverse* / System No access to duct, above hard ceiling. EF-1 / Exhaust Inlet Summary EXHAUST INLET SUMMARY Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design EI-001 117 ER-A 8x8 1.100 45 50 154 45 50 99 EI-002 109 ER-A 8x8 1.100 45 50 143 45 50 99 EI-003 108 ER-A 8x8 1.100 91 100 87 87 96 96 EI-004 135 ER-A 8x8 1.100 91 100 146 95 105 105 EI-005 123 ER-A 8x8 1.100 91 100 28 99 109 109 EI-006 124 ER-A 8x8 1.100 45 50 110 48 53 106 EI-007 130 ER-A 8x8 1.100 64 70 70 66 73 104 Totals 520 536 PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 EF-1 Page 22 of 28 2020-12-30 Design Actual %Design Actual % DEF-1* UNIT DATA Equipment Location Basement Unit Serial No.Not Listed Area Served Dryer Performed By RW Unit Manufacturer S&P Pass/Fail Pass Unit Model No.PV-100xps Date of Test 12/30/2020 TEST DATA Total Unit CFM (MAX)110 CFM 112 CFM 102 Fan RPM 2500 RPM 2500 RPM 100 Outlet CFM 110 CFM 112 CFM 102 Operational Static Press.Not Applicable in. H2O Total Unit CFM (MIN) Not Applicable CFM Not Applicable CFM Hertz at Design CFM 60 HZ MOTOR DATA Motor Manufacturer S&P Power Factor 0.850 Motor Frame Inline Plate Volts 115 Volts Motor RPM 2880 RPM Actual Volts 120 Volts Motor Horsepower 1/8 HP Plate Amps 0.8 Amps Motor Phase 1 Actual Amps 0.70 Amps Motor Hertz 60 Hz Starter Heater TP Service Factor 1 Brake Horsepower 0.081 Efficiency 0.850 DRIVE DATA Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in Motor Bore Direct Drive in No. of Belts Direct Drive Motor Sheave % Closed Direct Drive %Belt Size Direct Drive Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 DEF-1*Page 23 of 28 2020-12-30 Design Actual %Design Actual % TEST PRESSURES Total Static Pressure 0.5 in. H2O 0.76 in. H2O 152 Discharge Static 0.56 in. H2O Suction Static 0.2 in. H2O Filter DP (If Applicable) Not Applicable in. H2O Not Applicable in. H2O NOTES: Motor Data Efficiency The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP. DEF-1* / Photos Unit Photos DEF-1 IMAGES: PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 DEF-1*Page 24 of 28 2020-12-30 DEF-1* / Exhaust Inlet Summary EXHAUST INLET SUMMARY Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design EI-001 Base EA 4"O 0.087 1264 110 1290 1290 112 102 Totals 110 112 PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 DEF-1*Page 25 of 28 2020-12-30 Design Actual %Design Actual % DEF-2* UNIT DATA Equipment Location Basement Unit Serial No.Not Listed Area Served Dryer Performed By RW Unit Manufacturer S&P USA Ventilators Pass/Fail Pass Unit Model No.PV-100xps Date of Test 12/30/2020 TEST DATA Total Unit CFM (MAX)110 CFM 113 CFM 103 Fan RPM Not Listed RPM 2500 RPM Outlet CFM 110 CFM 113 CFM 103 Operational Static Press.Not Applicable in. H2O Total Unit CFM (MIN) Not Applicable CFM Not Applicable CFM Hertz at Design CFM 60 HZ MOTOR DATA Motor Manufacturer S&P Power Factor 0.850 Motor Frame Inline Plate Volts 115 Volts Motor RPM 2500 RPM Actual Volts 120 Volts Motor Horsepower See Note HP Plate Amps 0.8 Amps Motor Phase 1 Actual Amps 0.70 Amps Motor Hertz 60 Hz Starter Heater TP Service Factor 1 Brake Horsepower 0.081 Efficiency 0.850 DRIVE DATA Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in Motor Bore Direct Drive in No. of Belts Direct Drive Motor Sheave % Closed Direct Drive %Belt Size Direct Drive Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 DEF-2*Page 26 of 28 2020-12-30 Design Actual %Design Actual % TEST PRESSURES Total Static Pressure 0.5 in. H2O 078 in. H2O 15600 Discharge Static 0.58 in. H2O Suction Static 0.2 in. H2O Filter DP (If Applicable) Not Applicable in. H2O Not Applicable in. H2O NOTES: Motor Data Efficiency The Power Factor and Efficiency is not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP. DEF-2* / Photos* Unit Photos DEF-2 IMAGES: PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 DEF-2*Page 27 of 28 2020-12-30 DEF-2* / Traverse Summary TRAVERSE SUMMARY Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure Main Traverse*DEF-2 Main 4 0.087 1264 110 1298 113 0.200 Totals 110 113 DEF-2* / Exhaust Inlet Summary EXHAUST INLET SUMMARY Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design EI-001 Base EA 4'O 0.087 1264 110 See Note 1298 113 103 Totals 110 113 PROJECT NUMBER: 20-250 CONTACT: Rich Wyckoff LOCATION: United Cerebral Palsy Association-New Respite Care Facility 160 Aviation Road Queensbury NY 12804 DEF-2*Page 28 of 28 2020-12-30