FRM-004033-2020 08052020INSPECTION WORKSHEET (FRM-004033-2020)
CC-0227-2020Permit Management
Case Number:Case Module:
08/05/2020Partial Pass
Inspection Date:Inspection Status:
Dave HatinBuilding Framing
Inspector:Inspection Type:
296.7-1-8
Job Address:Parcel Number:
597 Bay Rd
Queensbury, NY 12804
Contact TypeCompany NameName
ApplicantKoock E Jung Revocable TrustDavid Jung
ArchitectRucinski-Hall Architecture
ContractorChristopher Corlew
Granted PermissionKoock E Jung Revocable TrustDavid Jung
Primary OwnerKoock E Jung Revocable TrustDavid Jung
Checklist ItemPassedComments
Building Inspector NotesFalse
7/31/20 Framing Not Approved - Exit Landing and steps.
1) Guards on landing and steps need to be 42" high.
2) Install handrails on both sides with 12" extensions top and
bottom.
3) Existing Landing needs structural blocks installed under deck
beams down to top of concrete piers. The beam was fastened to
posts on both sides which is not a compliant means of
installation.
3) Create a 3'x3' Landing at bottom of steps because of the last
riser height being shorter then the other steps.
8/3/20 Framing Partial Approval - Exterior Landing and Stairs.
Joist hangersFalse
Bracing BridgingFalse
Deck (post beam connections hex head bolts)True
7/31/20 Framing Not Approved - Exit Landing and steps.
1) Guards on landing and steps need to be 42" high.
2) Install handrails on both sides with 12" extensions top and
bottom.
3) Existing Landing needs structural blocks installed under deck
beams down to top of concrete piers. The beam was fastened to
posts on both sides which is not a compliant means of
installation.
3) Create a 3'x3' Landing at bottom of steps because of the last
riser height being shorter then the other steps.
8/3/20 Framing Partial Approval - Exterior Landing and Stairs.
Jack Studs HeadersFalse
Jack Posts Main BeamsTrue
7/31/20 Framing Not Approved - Exit Landing and steps.
1) Guards on landing and steps need to be 42" high.
2) Install handrails on both sides with 12" extensions top and
bottom.
3) Existing Landing needs structural blocks installed under deck
beams down to top of concrete piers. The beam was fastened to
posts on both sides which is not a compliant means of
installation.
3) Create a 3'x3' Landing at bottom of steps because of the last
riser height being shorter then the other steps.
8/3/20 Framing Partial Approval - Exterior Landing and Stairs.
January 06, 2021Page 1 of 2
INSPECTION WORKSHEET (FRM-004033-2020)
Checklist ItemPassedComments
FramingTrue
7/31/20 Framing Not Approved - Exit Landing and steps.
1) Guards on landing and steps need to be 42" high.
2) Install handrails on both sides with 12" extensions top and
bottom.
3) Existing Landing needs structural blocks installed under deck
beams down to top of concrete piers. The beam was fastened to
posts on both sides which is not a compliant means of
installation.
3) Create a 3'x3' Landing at bottom of steps because of the last
riser height being shorter then the other steps.
8/3/20 Framing Partial Approval - Exterior Landing and Stairs.
8/5/20 Blocking installed as requested
Headroom 6 ft. 8 in.False