TAB Report - 365 Bay RoadNortheastern Air Quality, Inc.
P.O. Box 3271
Albany, New York 12203
(518) 857-3641
HVAC SYSTEMS TESTING:
Project:365 Bay Road
Bay Road Liquors
Location:Queensbury, New York
Architect:Rucinski Hall Architecture
Glens Fdalls, New York
Engineer:
Piping:
Sheet Metal:Monahan & Every Plumbing and Heating
Queensbury, New York
Date:1/28/212
Prepared by:R. Kelley
RKelley@NortheasternAirQuality.com
Air Balance Report
CERTIFICATION
PROJECT:
ADDRESS:
TESTING AND BALANCING FIRM:
CERTIFIED BY:DATE:1/28/212
SIGNATURE:
Robert V. Kelley
#REF!
Queensbury, New York
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM
PERFORMANCE AND WAS OBTAINED IN ACCORDANCE WITH NEBB STANDARD
PROCEDURES. ANY VARIANCES FROM DESIGNED QUANTITIES WHICH EXCEEDS NEBB
TOLERANCES ARE NOTED THROUGHOUT THIS REPORT.
THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL
ADJUSTMENTS HAVE BEEN MADE IN ACCORDANCE WITH NEBB ''PROCEDURAL
STANDARDS FOR TESTING AND BALANCING OF ENVIRONMENTAL SYSTEM'' AND THE
PROJECT SPECIFICATIONS.
Northeastern Air Quality, Inc. #3159
Page 2
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641 PROJECT:
THE FOLLOWING IS A LIST OF STANDARD ABBREVIATIONS WHICH MAY APPEAR IN THIS REPORT:
MEANING MEANING
A AMPS or AMPERAGE NL NOT LISTED
ACH AIR CHANGES PER HOUR NOM NOMINAL
AD ACCESS DOOR NOM EFFY NOMINAL EFFICIENCY
ADJ ADJUSTABLE NR NOT REQUIRED
Ak KINETIC (EFFECTIVE FREE) AREA NS NOT SPECIFIED
BG BLAST GATE OBD OPPOSED BLADE DAMPER
BHP BRAKE HORSEPOWER OED OPEN END DUCT
CALC CALCULATED PF POWER FACTOR
CALIBR CALIBRATION or CALIBRATED PH PHASE
CD CEILING DIFFUSER Ps STATIC PRESSURE
CF CUBIC FEET Pt TOTAL PRESSURE
CFM CUBIC FEET PER MINUTE Pv VELOCITY PRESSURE
cL CENTERLINE RG RETURN GRILLE
CLG CEILING RPM REVOLUTIONS PER MINUTE
CR CEILING REGISTER RR RETURN REGISTER
CS CIRCUIT SETTER SBD SINGLE BLADE DAMPER
CSD CEILING SUPPLY DIFFUSER SD SMOKE CONTROL DAMPER
DD DIRECT DRIVE SF SERVICE FACTOR
DDC DIRECT DIGITAL CONTROL SMC SHEET METAL CONTRACTOR
DISC DISCONNECT SWITCH SPS STATIC PRESSURE SENSOR
DISCH DISCHARGE SR SUPPLY REGISTER
DPR DAMPER TC TEMPERATURE CONTROL
DR PRESSURE DIFFERENTIAL TCC TEMPERATURE CONTROL CONTRACTOR
EC END CAP TCD TEMPERATURE CONTROL DAMPER
ER EXHAUST REGISTER TP THERMALLY PROTECTED
FL BHP BRAKE HORSEPOWER @ FULL LOAD AMPS TRAV DUCT TRAVERSE
FLA FULL LOAD AMPS V VOLTS or VOLTAGE
FTR FINNED TUBE RADIATION VAR VARIABLE
GPM GALLONS PER MINUTE VBD V-BELT DRIVE
HP HORSEPOWER VD VOLUME DAMPER
LD LINEAR DIFFUSER VEL VELOCITY
LF LINEAR FEET (NOMINAL)W WATTS or WATTAGE
NA NOT ACCESSIBLE WG WALL GRILLE
ND NO DAMPER WMS WIRE MESH SCREEN
NDRG NON-DUCTED RETURN GRILLE WR WALL REGISTER
NG NO GAUGE ZD ZONE DAMPER
NI NOT INSTALLED
NIC NOT IN CONTRACT
ABBREVIATIONS
#REF!
ABBREVIATION ABBREVIATION
Page 3
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641
1/28/2021
MOTOR
NAME-RPM
PLATE VOLTS HERTZ 115 60 115 60
DATA
EXT.
STATIC
PRESSURE
VOLTS
AMPS
BHP (calc.)0.30
T3 (3 Ph only)
F.L.A.ACTUAL 0.25
T1 6.4 2.7 6.4 3.2
T2 (3 Ph only)
T1 - T3 (3 Ph only)
T1 - T2 115 122 115 122
T2 - T3 (3 Ph only)
SYSTEM:AHU-1 AHU-2
LOCATION:Meh. Closet Meh. Closet
MODEL:TM9E060B12MP12A TM9E080B12MP12A
SERIAL NUMBER:W2H0094978 W2H00132211
SERVICE:North/East Side Soth/West
MANUFACTURER:York York
PROJECT:#REF!
TESTED BY:R. Kelley DATE:
AIR MOVEMENT EQUIPMENT TEST SHEET
STYLE FRAME -DD -DD
DATE TESTED:1/28/2021 1/28/2021
MANUFACTURER Gentech Gentech
1 1
FL AMPS S.F.6.4 -6.4 -
--
Direct Drive Direct Drive
HP 1/2 1050 1/2 1050
PHASE
P.F.NOM EFFY ----
TEST DATA DESIGN ACTUAL DESIGN ACTUAL
Direct Drive
Direct Drive Direct Drive
Direct Drive Direct Drive
CALCULATED (P.F. x NOM EFFY) *
MOTOR SHEAVE
STARTER HEATER ELEMENTS
0.57 0.57
SHEAVE cL DISTANCE
BELTS
FAN SHEAVE
FAN RPM
Direct Drive
NS 851
TOTAL CFM - FAN NS 876 NS 1153
-0.35
TOTAL CFM - OUTLETS NS 862 NS 1121
RETURN AIR CFM NS 841
0.43
NL 0.13
OUTSIDE AIR CFM NS -NS 222
TOTAL -
DISCHARGE NL 0.17 NL 0.22
INLET NL 0.26
REMARKS:
* NOTE: If P.F. or NOM EFFY are NL,
(P.F. x NOM EFFY) = 746Hp/(VAX),
where X = 1 if 1 Ph, and 1.73 if 3 Ph
Page 4
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641
1/28/2021
MOTOR
NAME-RPM
PLATE VOLTS HERTZ 115 60 115 60
DATA
EXT.
STATIC
PRESSURE
VOLTS
AMPS
BHP (calc.)
REMARKS:
Direct Drive
Direct Drive
Direct Drive
Direct Drive
0.06
PROJECT:365 Bay Road
TESTED BY:R. Kelley DATE:
SYSTEM:ERV1
LOCATION:Storage Room
SERVICE:AHU-2
MANUFACTURER:Lifebreath
MODEL:267Max
SERIAL NUMBER:10202008904
DATE TESTED:1/28/2021
FAN DATA SUPPLY RETURN
MANUFACTURER
STYLE FRAME -DD -DD
HP
PHASE 1 1
FL AMPS S.F.4.5 NS 4.5 NS
P.F.NOM EFFY NS NS NS NS
calculated (P.F. x NOM EFFY) *0.72 0.72
STARTER HEATER ELEMENTS -
MOTOR SHEAVE Direct Drive Direct Drive
FAN SHEAVE Direct Drive Direct Drive
BELTS
SHEAVE cL DISTANCE
TEST DATA DESIGN ACTUAL DESIGN ACTUAL
TOTAL CFM - FANS
TOTAL CFM - OUTLETS 180 184 180 178
RETURN AIR CFM
OUTSIDE AIR CFM
DISCHARGE NL NL
INLET NL NL
TOTAL
FAN RPM
T1 - T2 115 122 115 122
T2 - T3 (3 Ph only)
T1 - T3 (3 Ph only)
T1 5 5
T2 (3 Ph only)
T3 (3 Ph only)
F.L.A.ACTUAL 0.06
* NOTE: If P.F. or NOM EFFY are NL,
(P.F. x NOM EFFY) = 746Hp/(VAX),
where X = 1 if 1 Ph, and 1.73 if 3 Ph
ENERGY RECOVERY VENTILATOR TEST SHEET
Page 5
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641
MOTOR
NAME-RPM
PLATE VOLTS HERTZ
DATA
EXT.
STATIC
PRESSURE
VOLTS
AMPS
BHP (calc.)
REMARKS:
SYSTEM:
LOCATION:
SERVICE:
MANUFACTURER:
MODEL:
SERIAL NUMBER:
DATE TESTED:
FAN DATA
MANUFACTURER
STYLE FRAME
HP
PHASE
FL AMPS S.F.
P.F.NOM EFFY
calculated (P.F. x NOM EFFY) *
STARTER HEATER ELEMENTS
MOTOR SHEAVE
FAN SHEAVE
BELTS
SHEAVE cL DISTANCE
TEST DATA
TOTAL CFM - FANS
TOTAL CFM - OUTLETS
RETURN AIR CFM
OUTSIDE AIR CFM
DISCHARGE
INLET
TOTAL
FAN RPM
T1 - T2
T2 - T3 (3 Ph only)
T1 - T3 (3 Ph only)
T1
T2 (3 Ph only)
T3 (3 Ph only)
F.L.A.ACTUAL
* NOTE: If P.F. or NOM EFFY are NL,
(P.F. x NOM EFFY) = 746Hp/(VAX),
where X = 1 if 1 Ph, and 1.73 if 3 Ph
1/28/2021
PROJECT:365 Bay Road
TESTED BY:DATE:
SUPPLY RETURN
DESIGN ACTUAL DESIGN ACTUAL
NLNL
NL NL
ENERGY RECOVERY VENTILATOR TEST SHEET
Page 6
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641
MOTOR
NAME-RPM
PLATE VOLTS HERTZ
DATA
EXT.
STATIC
PRESSURE
VOLTS
AMPS
BHP (calc.)
REMARKS:
SYSTEM:
LOCATION:
SERVICE:
MANUFACTURER:
MODEL:
SERIAL NUMBER:
DATE TESTED:
FAN DATA
MANUFACTURER
STYLE FRAME
HP
PHASE
FL AMPS S.F.
P.F.NOM EFFY
calculated (P.F. x NOM EFFY) *
STARTER HEATER ELEMENTS
MOTOR SHEAVE
FAN SHEAVE
BELTS
SHEAVE cL DISTANCE
TEST DATA
TOTAL CFM - FANS
TOTAL CFM - OUTLETS
RETURN AIR CFM
OUTSIDE AIR CFM
DISCHARGE
INLET
TOTAL
FAN RPM
T1 - T2
T2 - T3 (3 Ph only)
T1 - T3 (3 Ph only)
T1
T2 (3 Ph only)
T3 (3 Ph only)
F.L.A.ACTUAL
* NOTE: If P.F. or NOM EFFY are NL,
(P.F. x NOM EFFY) = 746Hp/(VAX),
where X = 1 if 1 Ph, and 1.73 if 3 Ph
1/28/2021
PROJECT:365 Bay Road
TESTED BY:DATE:
SUPPLY RETURN
DESIGN ACTUAL DESIGN ACTUAL
NL NL
NL NL
ENERGY RECOVERY VENTILATOR TEST SHEET
Page 7
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641
MOTOR
NAME-RPM
PLATE VOLTS HERTZ
DATA
EXT.
STATIC
PRESSURE
VOLTS
AMPS
BHP (calc.)
REMARKS:
SYSTEM:
LOCATION:
SERVICE:
MANUFACTURER:
MODEL:
SERIAL NUMBER:
DATE TESTED:
FAN DATA
MANUFACTURER
STYLE FRAME
HP
PHASE
FL AMPS S.F.
P.F.NOM EFFY
calculated (P.F. x NOM EFFY) *
STARTER HEATER ELEMENTS
MOTOR SHEAVE
FAN SHEAVE
BELTS
SHEAVE cL DISTANCE
TEST DATA
TOTAL CFM - FANS
TOTAL CFM - OUTLETS
RETURN AIR CFM
OUTSIDE AIR CFM
DISCHARGE
INLET
TOTAL
FAN RPM
T1 - T2
T2 - T3 (3 Ph only)
T1 - T3 (3 Ph only)
T1
T2 (3 Ph only)
T3 (3 Ph only)
F.L.A.ACTUAL
* NOTE: If P.F. or NOM EFFY are NL,
(P.F. x NOM EFFY) = 746Hp/(VAX),
where X = 1 if 1 Ph, and 1.73 if 3 Ph
1/28/2021
PROJECT:365 Bay Road
TESTED BY:DATE:
SUPPLY RETURN
DESIGN ACTUAL DESIGN ACTUAL
NL NL
NL NL
ENERGY RECOVERY VENTILATOR TEST SHEET
Page 8
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641
MOTOR
NAME-RPM
PLATE VOLTS HERTZ
DATA
EXT.
STATIC
PRESSURE
VOLTS
AMPS
BHP (calc.)
REMARKS:
SYSTEM:
LOCATION:
SERVICE:
MANUFACTURER:
MODEL:
SERIAL NUMBER:
DATE TESTED:
FAN DATA
MANUFACTURER
STYLE FRAME
HP
PHASE
FL AMPS S.F.
P.F.NOM EFFY
calculated (P.F. x NOM EFFY) *
STARTER HEATER ELEMENTS
MOTOR SHEAVE
FAN SHEAVE
BELTS
SHEAVE cL DISTANCE
TEST DATA
TOTAL CFM - FANS
TOTAL CFM - OUTLETS
RETURN AIR CFM
OUTSIDE AIR CFM
DISCHARGE
INLET
TOTAL
FAN RPM
T1 - T2
T2 - T3 (3 Ph only)
T1 - T3 (3 Ph only)
T1
T2 (3 Ph only)
T3 (3 Ph only)
F.L.A.ACTUAL
* NOTE: If P.F. or NOM EFFY are NL,
(P.F. x NOM EFFY) = 746Hp/(VAX),
where X = 1 if 1 Ph, and 1.73 if 3 Ph
1/28/2021
PROJECT:365 Bay Road
TESTED BY:DATE:
SUPPLY RETURN
DESIGN ACTUAL DESIGN ACTUAL
NL NL
NL NL
ENERGY RECOVERY VENTILATOR TEST SHEET
Page 9
Northeastern Air Quality, Inc.GRILLE, REGISTER & DIFFUSER REPORT
P.O. Box 3271, Albany, NY 12203-0271 PROJECT:
(518) 857-3641 TESTED BY:DATE:
REMARKS:
DESIGN INITIAL INTERMEDIATE FINAL % OF
NO.LOCATION SIZE MODEL Ak VEL CFM VEL CFM VEL CFM VEL CFM DES DATE REMARKS
AHU-1
1 Retail 14" x 6"Hood 48 Hood 48 1/28/21
2 Retail 14" x 6"Hood 75 Hood 75 1/28/21
3 Retail 14" x 6"Hood 96 Hood 96 1/28/21
4 Retail 14" x 6"Hood 101 Hood 101 1/28/21
5 Retail 14" x 6"Hood 48 Hood 48 1/28/21
6 Retail 14" x 6"Hood 101 Hood 101 1/28/21
7 Retail 14" x 6"Hood 112 Hood 112 1/28/21
8 Retail 14" x 6"Hood 88 Hood 88 1/28/21
9 Retail 14" x 6"Hood 128 Hood 128 1/28/21
10 Retail 14" x 6"Hood 65 Hood 65 1/28/21
Total 862 862 1/28/21
Return
11 Floor 30" x 8"Hood 419 Hood 419 1/28/21
12 Wall 30" x 8"Hood 422 Hood 422 1/28/21
Total 841 841 1/28/21
AHU-2
13 Retail 12" x 8"Hood 134 Hood 134 1/28/21
14 Retail 12" x 8"Hood 133 Hood 133 1/28/21
15 Retail 12" x 8"Hood 118 Hood 118 1/28/21
16 Rear Entrance 12" x 8"Hood 122 Hood 122 1/28/21
17 Retail 12" x 8"Hood 115 Hood 115 1/28/21
18 Office 12" x 8"Hood 154 Hood 154 1/28/21
19 Storage 12" x 8"Hood 135 Hood 135 1/28/21
20 Bathroom 12" x 8"Hood 87 Hood 87 1/28/21
21 Storage 12" x 8"Hood 123 Hood 123 1/28/21
Total 1,121 1,121 1/28/21
R. Kelley 1/28/212
365 Bay Road
Page 10
Northeastern Air Quality, Inc.GRILLE, REGISTER & DIFFUSER REPORT
P.O. Box 3271, Albany, NY 12203-0271 PROJECT:
(518) 857-3641 TESTED BY:DATE:
REMARKS:
DESIGN INITIAL INTERMEDIATE FINAL % OF
NO.LOCATION SIZE MODEL Ak VEL CFM VEL CFM VEL CFM VEL CFM DES DATE REMARKS
R. Kelley 1/28/212
365 Bay Road
Return
22 Retail Sales 26" x 8"Hood 368 Hood 368 1/28/21
23 Retail Sales 26" x 8"Hood 265 Hood 265 1/28/21
24 Retail Sales 26" x 8"Hood 218 Hood 218 1/28/21
Total 851 851 1/28/21
ERV
25 Supply 6" R 0.2 NS 921 184 921 181 1/28/21
26 Exhaust 6" R 0.2 NS 942 178 942 185 1/28/21
Page 11
Northeastern Air Quality, Inc.Duct Traverse Totals
P.O. Box 3271, Albany, NY 12203-0271 PROJECT:
(518) 857-3641 DATE:
System Area % OF
NO.Zone or Branch Sq. Ft.VEL CFM VEL CFM SP VEL CFM SP DES DATE
T-1 AHU-1
Supply 8''x 20''1.11 NS 788 876 788 876 0.17 1/28/21
T-2 AHU-2
Supply 8''x 20''1.11 NS 1,038 1,153 1,038 1,153 0.22 1/28/21
ERV
T-3 Supply 6''Rnd 0.20 1,121 220 936 184 1,106 217 0.10 99%1/28/21
T-4 Return 6''Rnd 0.20 1,121 220 908 178 1,131 222 0.11 101%1/28/21
Duct Size
Low Speed High Speed
#REF!
1/28/2021
DESIGN REQUIRMENT INITIAL FINAL