JB201133.0120.Concrete Compressive Strength Test.2021-02-26.Rpt.0120Rev1Report Number: Service Date: Report Date: Task: Client Queensbury, NY 12804 Bay Road and Blind Rock Road Fowler Square SI and CMTRosetti Acquisitions LLC Attn: Christopher Falvey 427 New Karner Rd Albany, NY 12205 518-266-0310 Albany, NY 12203-5169 30 Corporate Cir Ste 201* Report Contains Deviation(s)JB201133.0120 02/26/21 03/05/21 Revision 1 - input cylinder weights CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: JB201133 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: C40R762 Glens Falls Ready Mix Co. Material Information 0700 487 Plant: Ticket No.: Glens Falls 1835620 Field Test Data Test Air Content (%): Result Specification 8 1/2 6 - 8 1.5 Max 3 59 40 - 95 29 * * = Field Test Results do not meet project specifications. 4,000 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:02/26/21 0735 Christian Makasi Partly-Sunny 10 10 End of truckSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Second floor slab on deckPlacement Location: Laboratory Test Data Set Avg Diam.Area Weight DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By(lbs) 1 1 4.00 12.57 03/01/21 8.80 03/05/21 7 53,970 2 4,290 ADB 1 2 03/01/21 8.70 03/26/21 28 1 3 03/01/21 8.75 03/26/21 28 1 4 03/01/21 8.70 03/26/21 28 1 5 03/01/21 8.70 Hold 1 6 03/01/21 8.75 Hold Initial Cure:Final Cure:Onsite Cooler Moist Room Comments:Not tested for plastic unit weight. 4000R No Air Superplasticizer 2% Non Chloride Accelerator Samples Made By: Dente Group - A Terracon Co. Sample fresh concrete at the placement locations, perform required field tests and cast compressive strength samples.Services: Reported To: Contractor: Report Distribution: (1) Rosetti Acquisitions LLC, Christopher Falvey (1) 260 Structural Engineering, Dan Thomas (1) BBL Construction Services, Bobby Chatterton (1) BBL Construction Services, Eric Weatherwax (1) BBL Construction Services, Ryan Etue (1) D.A. Collins Construction Co Inc, Robin Stothers (1) Galusha & Sons LLC, Drew Stevens (1) Galusha & Sons LLC, James Campagnone Bobby w. BBL ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Dente Group - A Terracon Co. Rep.: Christian Makasi The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Queensbury, NY 12804 Bay Road and Blind Rock Road Fowler Square SI and CMTRosetti Acquisitions LLC Attn: Christopher Falvey 427 New Karner Rd Albany, NY 12205 518-266-0310 Albany, NY 12203-5169 30 Corporate Cir Ste 201* Report Contains Deviation(s)JB201133.0120 02/26/21 03/05/21 Revision 1 - input cylinder weights CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: JB201133 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: C40R762 Glens Falls Ready Mix Co. Material Information 0754 657 Plant: Ticket No.: Glens Falls 1835625 Field Test Data Test Air Content (%): Result Specification 8 3/4 6 - 8 0.6 Max 3 60 40 - 95 30 * * = Field Test Results do not meet project specifications. 4,000 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:02/26/21 0851 Christian Makasi Partly-Sunny 60 10 End of truckSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Second floor slab on deckPlacement Location: Laboratory Test Data Set Avg Diam.Area Weight DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By(lbs) 2 1 4.00 12.57 03/01/21 8.85 03/05/21 7 61,540 2 4,900 ADB 2 2 03/01/21 8.95 03/26/21 28 2 3 03/01/21 8.90 03/26/21 28 2 4 03/01/21 8.95 03/26/21 28 2 5 03/01/21 8.90 Hold 2 6 03/01/21 8.90 Hold Initial Cure:Final Cure:Onsite Cooler Moist Room Comments:Not tested for plastic unit weight. 4000R No Air Superplasticizer 2% Non Chloride Accelerator Samples Made By: Dente Group - A Terracon Co. Sample fresh concrete at the placement locations, perform required field tests and cast compressive strength samples.Services: Reported To: Contractor: Report Distribution: (1) Rosetti Acquisitions LLC, Christopher Falvey (1) 260 Structural Engineering, Dan Thomas (1) BBL Construction Services, Bobby Chatterton (1) BBL Construction Services, Eric Weatherwax (1) BBL Construction Services, Ryan Etue (1) D.A. Collins Construction Co Inc, Robin Stothers (1) Galusha & Sons LLC, Drew Stevens (1) Galusha & Sons LLC, James Campagnone Bobby w. BBL ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Dente Group - A Terracon Co. Rep.: Christian Makasi The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Queensbury, NY 12804 Bay Road and Blind Rock Road Fowler Square SI and CMTRosetti Acquisitions LLC Attn: Christopher Falvey 427 New Karner Rd Albany, NY 12205 518-266-0310 Albany, NY 12203-5169 30 Corporate Cir Ste 201 JB201133.0120 02/26/21 03/05/21 Revision 1 - input cylinder weights CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: JB201133 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: C40R762 Glens Falls Ready Mix Co. Material Information 0919 652 Plant: Ticket No.: Glens Falls 1835630 Field Test Data Test Air Content (%): Result Specification 7 3/4 6 - 8 0.9 Max 3 62 40 - 95 35 4,000 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:02/26/21 0945 Christian Makasi Partly-Sunny 110 10 End of truckSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Second floor slab on deckPlacement Location: Laboratory Test Data Set Avg Diam.Area Weight DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By(lbs) 3 1 4.00 12.57 03/01/21 8.85 03/05/21 7 53,230 2 4,240 ADB 3 2 03/01/21 8.85 03/26/21 28 3 3 03/01/21 8.85 03/26/21 28 3 4 03/01/21 8.85 03/26/21 28 3 5 03/01/21 8.85 Hold 3 6 03/01/21 8.80 Hold Initial Cure:Final Cure:Onsite Cooler Moist Room Comments:Not tested for plastic unit weight. 4000R No Air Superplasticizer 2% Non Chloride Accelerator Samples Made By: Dente Group - A Terracon Co. Sample fresh concrete at the placement locations, perform required field tests and cast compressive strength samples.Services: Reported To: Contractor: Report Distribution: (1) Rosetti Acquisitions LLC, Christopher Falvey (1) 260 Structural Engineering, Dan Thomas (1) BBL Construction Services, Bobby Chatterton (1) BBL Construction Services, Eric Weatherwax (1) BBL Construction Services, Ryan Etue (1) D.A. Collins Construction Co Inc, Robin Stothers (1) Galusha & Sons LLC, Drew Stevens (1) Galusha & Sons LLC, James Campagnone Bobby w. BBL ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Dente Group - A Terracon Co. Rep.: Christian Makasi The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Queensbury, NY 12804 Bay Road and Blind Rock Road Fowler Square SI and CMTRosetti Acquisitions LLC Attn: Christopher Falvey 427 New Karner Rd Albany, NY 12205 518-266-0310 Albany, NY 12203-5169 30 Corporate Cir Ste 201 JB201133.0120 02/26/21 03/05/21 Revision 1 - input cylinder weights CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: JB201133 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: C40R762 Glens Falls Ready Mix Co. Material Information 1028 644 Plant: Ticket No.: Glens Falls 1835635 Field Test Data Test Air Content (%): Result Specification 7 3/4 6 - 8 0.8 Max 3 65 40 - 95 35 4,000 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:02/26/21 1055 Christian Makasi Partly-Sunny 160 10 End of truckSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Second floor slab on deckPlacement Location: Laboratory Test Data Set Avg Diam.Area Weight DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By(lbs) 4 1 4.00 12.57 03/01/21 8.80 03/05/21 7 62,290 3 4,960 ADB 4 2 03/01/21 8.80 03/26/21 28 4 3 03/01/21 8.80 03/26/21 28 4 4 03/01/21 8.75 03/26/21 28 4 5 03/01/21 8.80 Hold 4 6 03/01/21 8.75 Hold Initial Cure:Final Cure:Onsite Cooler Moist Room Comments:Not tested for plastic unit weight. 4000R No Air Superplasticizer 2% Non Chloride Accelerator Samples Made By: Dente Group - A Terracon Co. Sample fresh concrete at the placement locations, perform required field tests and cast compressive strength samples.Services: Reported To: Contractor: Report Distribution: (1) Rosetti Acquisitions LLC, Christopher Falvey (1) 260 Structural Engineering, Dan Thomas (1) BBL Construction Services, Bobby Chatterton (1) BBL Construction Services, Eric Weatherwax (1) BBL Construction Services, Ryan Etue (1) D.A. Collins Construction Co Inc, Robin Stothers (1) Galusha & Sons LLC, Drew Stevens (1) Galusha & Sons LLC, James Campagnone Bobby w. BBL ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Dente Group - A Terracon Co. Rep.: Christian Makasi The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Queensbury, NY 12804 Bay Road and Blind Rock Road Fowler Square SI and CMTRosetti Acquisitions LLC Attn: Christopher Falvey 427 New Karner Rd Albany, NY 12205 518-266-0310 Albany, NY 12203-5169 30 Corporate Cir Ste 201 JB201133.0120 02/26/21 03/05/21 Revision 1 - input cylinder weights CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: JB201133 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: C40R762 Glens Falls Ready Mix Co. Material Information 1115 634 Plant: Ticket No.: Glens Falls 1835640 Field Test Data Test Air Content (%): Result Specification 8 6 - 8 1.1 Max 3 61 40 - 95 37 4,000 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:02/26/21 1216 Christian Makasi Partly-Sunny 210 10 End of truckSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Second floor slab on deckPlacement Location: Laboratory Test Data Set Avg Diam.Area Weight DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By(lbs) 5 1 4.00 12.57 03/01/21 8.90 03/05/21 7 61,150 3 4,870 ADB 5 2 03/01/21 8.90 03/26/21 28 5 3 03/01/21 8.85 03/26/21 28 5 4 03/01/21 8.90 03/26/21 28 5 5 03/01/21 8.80 Hold 5 6 03/01/21 8.85 Hold Initial Cure:Final Cure:Onsite Cooler Moist Room Comments:Not tested for plastic unit weight. 4000R No Air Superplasticizer 2% Non Chloride Accelerator Samples Made By: Dente Group - A Terracon Co. Sample fresh concrete at the placement locations, perform required field tests and cast compressive strength samples.Services: Reported To: Contractor: Report Distribution: (1) Rosetti Acquisitions LLC, Christopher Falvey (1) 260 Structural Engineering, Dan Thomas (1) BBL Construction Services, Bobby Chatterton (1) BBL Construction Services, Eric Weatherwax (1) BBL Construction Services, Ryan Etue (1) D.A. Collins Construction Co Inc, Robin Stothers (1) Galusha & Sons LLC, Drew Stevens (1) Galusha & Sons LLC, James Campagnone Bobby w. BBL ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Dente Group - A Terracon Co. Rep.: Christian Makasi The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 5 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Queensbury, NY 12804 Bay Road and Blind Rock Road Fowler Square SI and CMTRosetti Acquisitions LLC Attn: Christopher Falvey 427 New Karner Rd Albany, NY 12205 518-266-0310 Albany, NY 12203-5169 30 Corporate Cir Ste 201* Report Contains Deviation(s)JB201133.0120 02/26/21 03/05/21 Revision 1 - input cylinder weights CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: JB201133 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: C40R762 Glens Falls Ready Mix Co. Material Information 1305 628 Plant: Ticket No.: Glens Falls 1835645 Field Test Data Test Air Content (%): Result Specification 9 6 - 8 0.7 Max 3 55 40 - 95 40 * * = Field Test Results do not meet project specifications. 4,000 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:02/26/21 1330 Christian Makasi Partly-Sunny 260 10 End of truckSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Second floor slab on deckPlacement Location: Laboratory Test Data Set Avg Diam.Area Weight DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By(lbs) 6 1 4.00 12.57 03/01/21 8.85 03/05/21 7 62,420 2 4,970 ADB 6 2 03/01/21 8.75 03/26/21 28 6 3 03/01/21 8.75 03/26/21 28 6 4 03/01/21 8.85 03/26/21 28 6 5 03/01/21 8.85 Hold 6 6 03/01/21 8.85 Hold Initial Cure:Final Cure:Onsite Cooler Moist Room Comments:Not tested for plastic unit weight. 4000R No Air Superplasticizer 2% Non Chloride Accelerator Samples Made By: Dente Group - A Terracon Co. Sample fresh concrete at the placement locations, perform required field tests and cast compressive strength samples.Services: Reported To: Contractor: Report Distribution: (1) Rosetti Acquisitions LLC, Christopher Falvey (1) 260 Structural Engineering, Dan Thomas (1) BBL Construction Services, Bobby Chatterton (1) BBL Construction Services, Eric Weatherwax (1) BBL Construction Services, Ryan Etue (1) D.A. Collins Construction Co Inc, Robin Stothers (1) Galusha & Sons LLC, Drew Stevens (1) Galusha & Sons LLC, James Campagnone M. McHenry Materials Department Manager Bobby w. BBL Reviewed By: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Dente Group - A Terracon Co. Rep.: Christian Makasi The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 6 of 6CR0001, 11-16-12, Rev.6