Signed Inspection Report (Fri Mar 5, 2021 at 159 PM)INSPECTION WORKSHEET (FRM-008707-2021)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0789-2020 Case Module:Permit
Inspection Date:Fri Mar 5, 2021 Inspection Status:Failed
Inspector:O'Brien, John Inspection Type:Building Framing
Job Address:Parcel Number:88 MAIN ST
Queensbury, NY, 12804
309.14-1-19
Contact Type Company Name Name
Contractor Burke, Corey
Granted Permission RAIMO, JUSTIN
Applicant RAIMO, JUSTIN
Primary Owner RAIMO, JUSTIN
Checklist Item Status
Building Inspector Notes Failed
3/5/21 Building Framing Not Approved
- 3 Existing 2nd floor 2"x6" floor joists have existing 3" holes in them from existing plumbing removed. These
holes will have to be gussetted with a minimum of 5/8" plywood 24" passed the hole at each side of hole on both
sides of floor joist. The plywood must be be glued and screwed every 3" oc.
Framing Failed
3/5/21 Building Framing Not Approved
- 3 Existing 2nd floor 2"x6" floor joists have existing 3" holes in them from existing plumbing removed. These
holes will have to be gussetted with a minimum of 5/8" plywood 24" passed the hole at each side of hole on both
sides of floor joist. The plywood must be be glued and screwed every 3" oc.
Mar 05, 2021 Page (1)
O'Brien, John